Emerson 1057 Instruction Manual

Page 1
THREE-INPUT INTELLIGENT ANALYZER
Instruction Manual
PN 51-1057/rev.C January 2010
Model 1057
Page 2
ESSENTIAL INSTRUCTIONS
READ THIS PAGE BEFORE PROCEEDING!
• Failure to follow the proper instructions may cause any one of the following situations to occur: Loss of life; personal injury; property dam­age; damage to this instrument; and warranty invalidation.
• Ensure that you have received the correct model and options from your purchase order. Verify that this manual covers your model and options. If not, call 1-800-854-8257 or 949-757-8500 to request correct manual.
• For clarification of instructions, contact your Rosemount representative.
• Follow all warnings, cautions, and instructions marked on and supplied with the product.
• Use only qualified personnel to install, operate, update, program and maintain the product.
• Educate your personnel in the proper installation, operation, and maintenance of the product.
• Install equipment as specified in the Installation section of this manual. Follow appropriate local and national codes. Only connect the product to electrical and pressure sources specified in this manual.
• Use only factory documented components for repair. Tampering or unauthorized substitution of parts and procedures can affect the performance and cause unsafe operation of your process.
• All equipment doors must be closed and protec­tive covers must be in place unless qualified per­sonnel are performing maintenance.
Equipment protected throughout by double insulation.
• Installation and servicing of this product may expose personel to dangerous voltages.
• Main power wired to separate power source must be disconnected before servicing.
• Do not operate or energize instrument with case open!
• Signal wiring connected in this box must be rated at least 240 V.
• Non-metallic cable strain reliefs do not provide grounding between conduit connections! Use grounding type bushings and jumper wires.
• Unused cable conduit entries must be securely sealed by non-flammable closures to provide enclosure integrity in compliance with personal safety and environmental protection requirements. Unused conduit openings must be sealed with NEMA 4X or IP65 conduit plugs to maintain the ingress protection rating (NEMA 4X).
• Electrical installation must be in accordance with the National Electrical Code (ANSI/NFPA-70) and/or any other applicable national or local codes.
• Operate only with front panel fastened and in place.
Proper use and configuration is the responsibility of the
user.
This product generates, uses, and can radiate radio frequency energy and thus can cause radio communication interference. Improper installation, or operation, may increase such interfer­ence. As temporarily permitted by regulation, this unit has not been tested for compliance within the limits of Class A comput­ing devices, pursuant to Subpart J of Part 15, of FCC Rules, which are designed to provide reasonable protection against such interference. Operation of this equipment in a residential area may cause interference, in which case the user at his own expense, will be required to take whatever measures may be required to correct the interference.
This product is not intended for use in the light industrial, residential or commercial environments per the instru­ment’s certification to EN50081-2 (EN61000-6-2).
Emerson Process Management
Liquid Division
2400 Barranca Parkway Irvine, CA 92606 USA Tel: (949) 757-8500 Fax: (949) 474-7250
http://www.raihome.com
© Rosemount Analytical Inc. 2009
CAUTION
CAUTION
WARNING
RISK OF ELECTRICAL SHOCK
Page 3
QUICK START GUIDE
Model 1057 Three Input Analyzer
1. Refer to Section 2.0 for mechanical installation instructions.
2. Wire sensor(s) to the signal boards. See Section 3.0 for wiring instructions. Refer to the sensor instruction sheet for additional details. Make current output, alarm relay and power connections.
3. Once connections are secured and verified, close panel and apply power to the analyzer.
4. When the analyzer is powered up for the first time, Quick Start screens appear. Quick Start operating tips are as follows:
a. A backlit field shows the position of the cursor.
b. To move the cursor left or right, use the keys to the left or right of the ENTER key. To scroll up or down
or to increase or decrease the value of a digit use the keys above and below the ENTER key . Use the left or right keys to move the decimal point.
c. Press ENTER to store a setting. Press EXIT to leave without storing changes. Pressing EXIT during Quick
Start returns the display to the initial start-up screen (select language).
5. Complete the steps as shown in the Quick Start Guide flow diagram, Fig. A on the following page.
6. After the last step, the main display appears. The outputs are assigned to default values.
7. To change output, and temperature-related settings, go to the main menu and choose Program. Follow the prompts. For a general guide to the Program menu, see the Quick Reference Guide, Fig.B.
8. To return the analyzer to the default settings, choose Reset Analyzer under the Program menu.
WARNING
Electrical installation must be in accordance with the National Electrical Code (ANSI/NFPA-70) and/or any other applicable national or local codes.
WARNING
RISK OF ELECTRICAL SHOCK
Page 4
D
QUICK START GUIDE – MODEL 1057
Figure A. QUICK START GUIDE
Page 5
E
QUICK REFERENCE GUIDE
Figure B. MODEL 1057 MENU TREE
Page 6
F
This manual contains instructions for installation and operation of the Model 1057 Three-Input Intelligent Analyzer. The following list provides notes concerning all revisions of this document.
Rev. Level Date Notes
A 01/09 This is the initial release of the product manual. The manual has been reformatted
to reflect the Emerson documentation style and updated to reflect any changes
in the product offering. B 10/09 Russian language added. UL Approval added. C 01/10 CSA Class I, Div 2 Non-incendive harardous area approval added.
About This Document
Page 7
MODEL 1057 TABLE OF CONTENTS
MODEL 1057
THREE INPUT INTELLIGENT ANALYZER
TABLE OF CONTENTS
QUICK START GUIDE QUICK REFERENCE GUIDE TABLE OF CONTENTS
Section Title Page
1.0 DESCRIPTION AND SPECIFICATIONS ................................................................ 1
2.0 INSTALLATION ....................................................................................................... 5
2.1 Unpacking and Inspection........................................................................................ 5
2.2 Installation................................................................................................................ 5
3.0 WIRING.................................................................................................................... 9
3.1 General .................................................................................................................... 9
3.2 Preparing Conduit Openings.................................................................................... 10
3.3 Preparing Sensor Cable .......................................................................................... 10
3.4 Power, Output, Alarms and Sensor Connections..................................................... 10
4.0 DISPLAY AND OPERATION................................................................................... 15
4.1 User Interface .......................................................................................................... 15
4.2 Instrument Keypad................................................................................................... 15
4.3 Main Display ............................................................................................................ 16
4.4 Menu System ........................................................................................................... 17
5.0 PROGRAMMING THE ANALYZER – BASICS ....................................................... 19
5.1 General .................................................................................................................... 19
5.2 Changing StartUp Settings ...................................................................................... 19
5.3 Choosing Temperature Units and Automatic/Manual Temperature Compensation . 20
5.4 Configuring and Ranging the Current Outputs......................................................... 20
5.5 Setting a Security Code ........................................................................................... 22
5.6 Security Access........................................................................................................ 23
5.7 Using Hold ............................................................................................................... 23
5.8 Resetting Factory Default Settings ........................................................................ 24
5.9 Programming Alarm Relays ..................................................................................... 25
6.0 PROGRAMMING - MEASUREMENTS ................................................................... 29
6.1 Programming Measurements – Introduction ........................................................... 29
6.2 pH ............................................................................................................................ 30
6.3 ORP ......................................................................................................................... 31
6.4 Contacting Conductivity .......................................................................................... 33
7.0 CALIBRATION ...................................................................................................... 39
7.1 Calibration – Introduction ......................................................................................... 39
7.2 pH Calibration .......................................................................................................... 39
7.3 ORP Calibration ....................................................................................................... 42
7.4 Contacting Conductivity Calibration ......................................................................... 43
7.5 Calibrating Temperature .......................................................................................... 46
8.0 RETURN OF MATERIAL ........................................................................................ 51
Warranty................................................................................................................... 51
Ordering Information ................................................................................................ 53
i
Page 8
LIST OF TABLES
Number Section Table Title Page
5-1 SEC 5.2.1 Measurements and Measurement Units ........................................... 19
6-1 SEC 6.2.1 pH Measurement Programming......................................................... 30
6-2 SEC 6.3.1 ORP Measurement Programming...................................................... 31
6-3 SEC 6.4.1 Contacting Conductivity Measurement Programming........................ 33
7-1 SEC 7.2 pH Calibration Routines ....................................................................... 39
7-2 SEC 7.3 ORP Calibration Routine................................................................... 42
7-3 SEC 7.4 Contacting Conductivity Calibration Routines...................................... 43
7-11 SEC 7.5 Temperature Calibration Routines........................................................ 46
MODEL 1057 TABLE OF CONTENTS
TABLE OF CONTENTS CONT’D
LIST OF FIGURES
Fig# Section Figure Title Page
A PREFACE Quick Start Guide
B PREFACE Quick Reference Guide
2-1 SEC 2.0 Panel Mounting Dimensions .............................................................. 6
2-2 SEC 2.0 Pipe and Wall Mounting Dimensions ................................................. 7
3-1 SEC 3.1 Connectors and Signal Input boards ................................................. 9
3-2 SEC 3.4 24VDC Power Supply ........................................................................ 10
3-3 SEC 3.4 Switching AC Power Supply............................................................... 10
3-4 SEC 3.4 Alarm Relay Wiring ............................................................................ 11
3-5 SEC 3.4 Contacting Conductivity board and sensor cable leads ..................... 12
3-6 SEC 3.4 pH/ORP/ISE signal board and sensor cable leads ............................ 12
3-7 SEC 3.4 Power Wiring for Model 1057 85-265 VAC ........................................ 13
3-8 SEC 3.4 Output Wiring for Model 1057 Main PCB........................................... 13
3-9 SEC 3.4 Power Wiring for Model 1057 24VDC ................................................ 14
4-1 SEC 4.3 Formatting the Main Display ............................................................. 18
5-1 SEC 5.3.2 Choosing Temp Units and Manual Auto Temp Compensation........... 20
5-2 SEC 5.4.5 Configuring and Ranging the Current Outputs................................... 21
5-3 SEC 5.5.2 Setting A Security Code .................................................................... 22
5-4 SEC 5.7.2 Using Hold ......................................................................................... 23
5-5 SEC 5.8.2 Resetting Factory Default Settings .................................................... 24
6-1 SEC 6.4 Configuring pH/ORP Measurements ................................................. 36
6-2 SEC 6.4 Configure Contacting Measurements ............................................... 37
7-1 SEC 7.2 Calibrate pH ....................................................................................... 47
7-2 SEC 7.3 Calibrate ORP.................................................................................... 48
7-3 SEC 7.4 Calibrate Contacting Conductivity...................................................... 49
7-4 SEC 7.9 Calibrate Temperature ....................................................................... 50
ii
Page 9
SECTION 1.0.
DESCRIPTION AND SPECIFICATIONS
1
MODEL 1057 SECTION 1.0
DESCRIPTION AND SPECIFICATIONS
• MULTI-PARAMETER INSTRUMENT – up to three inputs. Choose pH/ORP/ISE or Contacting Conductivity/Resistivity in any combination.
• LARGE DISPLAY – large easy-to-read process measurements.
• EASY TO INSTALL – modular boards, removable connectors, easy to wire power, sensors, and out­puts.
• INTUITIVE MENU SCREENS with advanced diagnostics and help screens.
• SMART -Enabled - compatible with SMART pH sensors.
• EIGHT Menu Languages.
• FOUR ANALOG OUTPUTS.
• UL and CSA APPROVED.
FEATURES AND APPLICATIONS
The Model 1057 analyzer offers three sensor inputs and four current outputs thus reducing the cost per loop and saving panel space. The pH signal input board supports pH, ORP, and Ion-Selective Electrode meas­urements. The Conductivity signal input board supports contacting conductivity, resistivity, Total Dissolved Solids, salinity and percent concentration curves for special applications. The modular design allows signal input boards to be field replaced making configuration changes easy. Conveniently, live process values are always displayed during programming and calibration routines. Standard features include isolated inputs, 8embedded local languages, four 4-20mA current outputs, 4 alarm relays and removable connectors for power and current outputs.
QUICK START PROGRAMMING: Exclusive Quick Start screens appear the first time the Model 1057 is powered. The instrument auto-recognizes each measurement board and prompts the user to configure each sensor loop in a few quick steps for immediate deployment.
MENUS: Menu screens for calibrating and programming are simple and intuitive. Plain language prompts and help screens guide the user through these procedures.
4-ELECTRODE CONDUCTIVITY: For applications requiring wide range conductivity measurements, use Rosemount Analytical’s Model 410VP
PUR-SENSE
4-electrode sensor. It is not affected by fouling and is supported by the same contacting conductivity signal board as traditional 2-electrode sensors.
THREE SENSOR INPUTS: The Model 1057 accepts one, two or three isolated inputs. Inputs are isolat­ed from other signal sources and earth ground.
FOUR CURRENT OUTPUTS: Four 0/4-20 mA cur­rent outputs are electrically isolated. Outputs are fully scalable and can be programmed to linear or logrithmic modes. Output dampening can be enabled with time constants from 0 to 999 seconds.
ENCLOSURE: The instrument fits standard ½ DIN panel cutouts. The versatile enclosure design supports panel-mount, pipe-mount, and surface/wall-mount installations.
SMART pH SENSORS: Avoid buffer calibrations in the field. Use Rosemount Analytical SMART pH sensors to automatically calibrate the measure­ment loop when connected to Model 1057. Choose from a complete range of SMART pH sensors suit­ed to most applications.
Page 10
MODEL 1057 SECTION 1.0
DESCRIPTION AND SPECIFICATIONS
2
SECURITY ACCESS CODES: Two levels of security
access are available. Program one access code for routine calibration and hold of current outputs; program another access code for all menus and functions.
DIAGNOSTICS: The analyzer continuously monitors itself and the sensor(s) for problematic conditions. The display flashes Fault and/or Warning when these conditions occur.
DISPLAY: The high-contrast LCD provides live measurement readouts in large digits and shows up to six additional process variables or diagnostic param­eters. The display is back-lit and the format can be cus­tomized to meet user requirements.
LOCAL LANGUAGES : Rosemount Analytical extends its worldwide reach by offering eight local languages – English, French, German, Italian, Spanish, Portuguese, Chinese and Russian. Every unit includes user programming menus; calibration routines; faults and warnings; and user help screens in all eight lan­guages. The displayed language can be easily set and changed using the menus.
SPECIFICATIONS - General
Enclosure: Polycarbonate. NEMA 4X/CSA 4 (IP65). Dimensions: Overall 155 x 155 x 131mm (6.10 x 6.10 x
5.15 in.). Cutout: 1/2 DIN 139mm x 139mm (5.45 x 5.45 in.) Minimum depth for panel mount insatllations 101.6 mm
(4.0 in). Conduit Openings: Accepts 1/2” or PG13.5 conduit
fittings
Display: Monochromatic graphic liquid crystal display.
128 x 96 pixel display resolution. Backlit. Active display area: 58 x 78mm (2.3 x 3.0 in.).
Ambient Temperature and Humidity: 0 to 55°C
(32 to 131°F). RH 5 to 95% (non-condensing)
Storage Temperature Effect: -20 to 60ºC (-4 to 140°F) Power: Code -02: 20 to 30 VDC. 15 W.
Code -03: 84 to 265 VAC, 47.5 to 65.0 Hz, switching.
15 W.
Equipment protected by double insulation
Approvals:
Hazardous Location Approvals:
Alarms relays: Four alarm relays for process meas-
urement(s) or temperature. Any relay can be config­ured as a fault alarm instead of a process alarm. Each relay can be configured independently and each can be programmed with interval timer settings.
Relays: Form C, SPDT, epoxy sealed
Inductive load: 1/8 HP motor (max.), 40 VAC Inputs: Up to three sensor inputs-electrically isolated
Outputs: Four 4-20 mA or 0-20 mA isolated current
outputs. Fully scalable. Max Load: 550 Ohms.
Current Output Accuracy: ±0.05 mA @25 ºC Terminal Connections Rating: Power connector
(3-leads): 24-12 AWG wire size. Signal board ter­minal blocks: 26-16 AWG wire size. Current output connectors (4-leads): 24-16 AWG wire size. Alarm relay terminal blocks: 24-12 AWG wire size
Weight/Shipping Weight: (rounded up to nearest lb or
nearest 0.5 kg): 3 lbs/4 lbs (1.5 kg/2.0 kg)
Diagnostics Faults Warnings Sensor 1 Sensor 2 Sensor 3 Out 1: 12.05 mA Out 2: 12.05 mA Out 3: 12.05 mA Out 4: 12.05 mA 1057-02-20-30-42 Instr SW VER: 3.12
AC Freq. Used: 60Hz
Information about each condition is quickly accessible by pressing DIAG on the keypad. User help screens are displayed for most fault and warning conditions to assist in troubleshooting.
RFI/EMI: EN-61326 LVD: EN-61010-1
Maximum Relay Current
Resistive
28 VDC 5.0 A 115 VAC 5.0 A 230 VAC 5.0 A
CAUTION
RISK OF ELECTRICAL SHOCK
POLLUTION DEGREE 2: Normally only non-conductive pollution occurs. Occasionally, however, a temporary conductivity caused by condensation must be expected.
Altitude: for use up to 2000 meters (6562 ft.)
Ordinary Locations: (only with -UL ordering option)
Ordering options for CSA: all except UL
Class I, Division 2, Groups A, B, C, & D Class Il, Division 2, Groups E, F, & G Class Ill T4A Tamb= 50
°C
Evaluated to the ANSI/UL Standards. The ‘C’ and ‘US’ indi­cators adjacent to the CSA Mark signify that the product has been evaluated to the applicable CSA and ANSI/UL Standards, for use in Canada and the U.S. respectively.
Page 11
MODEL 1057 SECTION 1.0
DESCRIPTION AND SPECIFICATIONS
3
Cell 0.01μS/cm 0.1μS/cm 1.0μS/cm 10μS/cm 100μS/cm 1000μS/cm 10mS/cm 100mS/cm 1000mS/cm Constant
0.01
0.1
1.0
4-electrode
0.01μS/cm to 200μS/cm
0.1μS/cm to 2000μS/cm
1 μS/cm to 20mS/cm
2 μS/cm to 300mS/cm
200μS/cm to 6000μS/cm
2000μS/cm to 60mS/cm
20mS/cm to 600mS/cm
±0.6% of reading in recommended range
+2 to -10% of reading outside high recommended range
±5% of reading outside low recommended range
±4% of reading in recommended range
Measures conductivity in the range 0 to 600,000 μS/cm (600mS/cm). Measurement choices are conductivity, resistivity, total dissolved solids, salinity, and % concen­tration. The % concentration selection includes the choice of five common solutions (0-12% NaOH, 0-15% HCl, 0-20% NaCl, and 0-25% or 96-99.7% H
2SO4
).
The conductivity concentration algorithms for these solutions are fully temperature compensated. Three temperature compensation options are available: manual slope (X%/°C), high purity water (dilute sodium chloride), and cation conductivity (dilute hydrochloric acid). Temperature compensation can be disabled, allowing the analyzer to display raw conductivity. For more information concerning the use and operation of the contacting conductivity sensors, refer to the product data sheets.
Note: When contacting conductivity sensors are used for sensor 1 and sensor 2, Model 1057 can derive an inferred pH value called pHCalc. pHCalc is calculated pH, not directly measured pH.
Note: Selected 4-electrode, high-range contacting conductivity sensors are compatible with Model 1056.
Input filter: time constant 1 - 999 sec, default 2 sec. Response time: 3 seconds to 100% of final reading Salinity: uses Practical Salinity Scale
Total Dissolved Solids: Calculated by multiplying
conductivity at 25ºC by 0.65
RECOMMENDED SENSORS FOR CONDUCTIVITY:
All Rosemount Analytical ENDURANCE Model 400 series conductivity sensors (Pt 1000 RTD) and Model 410 sensor.
CONTACTING CONDUCTIVITY (Codes -20, -30 and -40)
Temperature range 0-200ºC
Temperature Accuracy,
Pt-1000, 0-50 ºC
± 0.1ºC
Temperature Accuracy,
Pt-1000, Temp. > 50 ºC
± 0.5ºC
PERFORMANCE SPECIFICATIONS
Recommended Range – Contacting Conductivity
Temperature Specifications:
ENDURANCETMseries of
conductivity sensors
Cell Constant Linearity
family
4-electrode sensors
Page 12
MODEL 1057 SECTION 1.0
DESCRIPTION AND SPECIFICATIONS
4
pH/ORP/ISE (Codes -22, -32 and -42)
For use with any standard pH or ORP sensor. Measurement choices are pH, ORP, Redox, ammonia, fluoride or custom ISE. The automatic buffer recognition feature uses stored buffer values and their temperature curves for the most common buffer standards available worldwide. The analyzer will recognize the value of the buffer being measured and perform a self stabilization check on the sensor before completing the calibration. Manual or automatic temperature compensation is menu selectable. Change in pH due to process temper­ature can be compensated using a programmable tem­perature coefficient. For more information concerning the use and operation of the pH or ORP sensors, refer to the product data sheets.
Model 1057 can also derive an inferred pH value called pHCalc (calculated pH). pHCalc can be derived and displayed when two contacting conductivity sensors are used as sensor 1 and sensor 2.
PERFORMANCE SPECIFICATIONS ­ANALYZER (pH INPUT)
Measurement Range [pH]: 0 to 14 pH
Accuracy: ±0.01 pH
Diagnostics: Glass impedance, reference impedance
Temperature coefficient: ±0.002pH/ ºC
Solution temperature correction: Pure water, dilute
base and custom.
Buffer recognition: NIST, DIN 19266, JIS 8802, and BSI.
Input filter: Time constant 1 - 999 seconds, default 4
seconds.
Response time: 5 seconds to 100%
Sensor Compatibility: Model 1057 is also compatible
with SMART pH sensors from Rosemount Analytical. Choose from 14 SMART sensor models for a wide array of applications and process condi­tions.
Temperature Specifications:
PERFORMANCE SPECIFICATIONS ­ANALYZER (ORP INPUT)
Measurement Range [ORP]: -1500 to +1500 mV
Accuracy: ± 1 mV
Temperature coefficient: ±0.12mV / ºC
Input filter: Time constant 1 - 999 seconds, default 4
seconds.
Response time: 5 seconds to 100% of final reading
RECOMMENDED SENSORS FOR ORP:
All standard ORP sensors.
Temperature range 0-150ºC
Temperature Accuracy, Pt-100, 0-50 ºC ± 0.5ºC
Temperature Accuracy, Temp. > 50 ºC ± 1ºC
Fourteen SMART sensor models include PERpH-X, TUpH and
general purpose pH sensor families.
Rosemount Analytical pH Sensors
Page 13
SECTION 2.0.
INSTALLATION
MODEL 1057 SECTION 2.0
INSTALLATION
2.1 UNPACKING AND INSPECTION
2.2 INSTALLATION
Type of Mounting Figure
Panel 2-1
Wall and Pipe 2-2
2.1 UNPACKING AND INSPECTION
Inspect the shipping container. If it is damaged, contact the shipper immediately for instructions. Save the box. If there is no apparent damage, unpack the container. Be sure all items shown on the packing list are present. If items are missing, notify Rosemount Analytical immediately.
2.2 INSTALLATION
2.2.1 General Information
1. Although the analyzer is suitable for outdoor use, do not install it in direct sunlight or in areas of extreme tem­peratures.
2. Install the analyzer in an area where vibration and electromagnetic and radio frequency interference are min­imized or absent.
3. Keep the analyzer and sensor wiring at least one foot from high voltage conductors. Be sure there is easy access to the analyzer.
4. The analyzer is suitable for panel, pipe, or surface mounting. Refer to the table below.
Electrical installation must be in accordance with the National Electrical Code (ANSI/NFPA-70) and/or any other applicable national or local codes.
WARNING
RISK OF ELECTRICAL SHOCK
5
Page 14
Bottom View
Front View
Side View
FIGURE 2-1 PANEL MOUNTING DIMENSIONS
MILLIMETER
INCH
6
The front panel is hinged at the bottom. The panel swings down for easy access to the wiring locations.
Panel mounting seal integrity (4/4X) for outdoor applications is the responsibility of the end user.
Page 15
FIGURE 2-2 PIPE AND WALL MOUNTING DIMENSIONS
(Mounting bracket PN:23820-00)
The front panel is hinged at the bottom. The panel swings down for easy access to the wiring locations.
Bottom View
Front View
Side View
Side View
Wall / Surface Mount
Pipe Mount
MILLIMETER
INCH
154.9
6.1
102
4.0
187
7.4
154.9
6.1
232
9.1
33.5
1.3
130
5.1
165
6.5
232
9.1
130
5.1
33.5
1.3
165
6.5
108.9
4.3
45.21
1.8
80.01
3.2
71.37
2.8
7
Page 16
This page left blank intentionally
MODEL 1057 SECTION 2.0
INSTALLATION
8
Page 17
SECTION 3.0.
WIRING
3.1 GENERAL
3.2 PREPARING CONDUIT OPENINGS
3.3 PREPARING SENSOR CABLE
3.4 POWER, OUTPUT, AND SENSOR CONNECTIONS
MODEL 1057 SECTION 3.0
WIRING
3.1 GENERAL
The Model 1057 is easy to wire. It includes removable connectors and slide-out signal input boards.
3.1.1 Removable connectors and signal input boards
Model 1057 uses removable signal input boards and communication boards for ease of wiring and instal­lation. Each of the signal input boards can be partially or completely removed from the enclosure for wiring. The Model 1057 has three slots for placement of up to three signal input boards and one communication
board.
3.1.2 Signal Input boards
Slots 1, 2 and 3 are for signal input measurement boards. Wire the sensor leads to the measurement board following the lead locations marked on the board. After wiring the sensor leads to the signal board, carefully slide the wired board fully into the enclosure slot and take up the excess sensor cable through the cable gland. Tighten the cable gland nut to secure the cable and ensure a sealed enclosure. Note: that signal input board 3 is inserted into slot 1. Board 3 is inverted in the slot to allow board components to face to the right. Board 3 uses a long ribbon cable to connect to the main PCB. Boards 1 and 2 use a split ribbon cable to connect both signal boards to a common connector on the main board.
3.1.3 Alarm relays
Four alarm relays are supplied with the switching power supply (84 to 265VAC, -03 order code) and the 24VDC power supply (20-30VDC, -02 order code). All relays can be used for process measurement(s) or temperature. Any relay can be configured as a fault alarm instead of a process alarm. Each relay can be configured independently and each can be programmed as an interval timer, typically used to activate pumps or control valves. As process alarms, alarm logic (high or low activation or USP*) and deadband are user-programmable. Customer-defined failsafe operation is supported as a programmable menu function to allow all relays to be energized or not-energized as a default condition upon powering the analyzer. The USP alarm can be programmed to activate when the conductivity is within a user-selectable percentage of the limit. USP alarming is available only when a contacting conductivity measurement board is installed.
Note: If the -UL option code has been ordered, a plastic insulator shield surrounds the entire power supply board (AC power supply only). The protective insulator shield does not appear in this photo.
Slot 1 – Left
Signal board 3
Slot 2 – Center
Signal board 2
Slot 3 – Right
Signal board 1
Figure 3-1
9
Page 18
3.3 PREPARING SENSOR CABLE
The Model 1057 is intended for use with all Rosemount Analytical pH/ORP and contacting conductivity sensors. Refer to the sensor installation instructions for details on preparing sensor cables.
3.4 POWER, OUTPUT, AND SENSOR CONNECTIONS
All field wiring must be rated for 75ºC or higher. Each instrument includes a printed label inside the enclosure stating this wiring requirement.
3.4.1 Power wiring
Two Power Supplies are offered for Model 1057:
a. 24VDC (20 – 30V) Power Supply (-02 ordering code)
b. 84 – 265 VAC Switching Power Supply (-03 ordering code)
AC mains (115 or 230V) leads and 24VDC leads are wired to the Power Supply board which is mounted vertically on the left side of the main enclosure cavity. Each lead location is clearly marked on the Power Supply board. Wire the power leads to the Power Supply board using the lead markings on the board.
MODEL 1057 SECTION 3.0
WIRING
This power supply automatically detects DC power and accepts 20VDC to 30VDC inputs. Four programmable alarm relays are included.
24VDC Power Supply (-02 ordering code) is shown below:
Switching AC Power Supply (-03 ordering code) is shown below:
Figure 3-2
This power supply automatically detects AC line conditions and switches to the proper line voltage and line frequency. Four programmable alarm relays are included.
Figure 3-3
10
3.2 PREPARING CONDUIT OPENINGS
There are six conduit openings in all configurations of Model 1057. (Note that four plugs are provided upon ship­ment.)
Conduit openings accept 1/2-inch conduit fittings or PG13.5 cable glands. To keep the case watertight, block unused openings with NEMA 4X or IP65 conduit plugs.
NOTE: Use watertight fittings and hubs that comply with your requirements. Connect the conduit hub to the conduit before attaching the fitting to the analyzer.
Page 19
MODEL 1057 SECTION 3.0
WIRING
Figure 3-4 Alarm Relay Wiring for Model 1057 Switching Power Supply (-03 Order Code)
NO1
RELAY 1COM1
NC1
NO2
RELAY 2COM2
NC2
NO3
RELAY 3COM3
NC3
NO4
RELAY 4COM4
NC4
3.4.4 Sensor wiring to signal boards
Wire the correct sensor leads to the measurement board using the lead locations marked directly on the board. After wiring the sensor leads to the signal board, carefully slide the wired board fully into the enclosure slot and take up the excess sensor cable through the cable gland.
For best EMI/RFI protection use shielded output signal cable enclosed in an earth-grounded metal conduit. Connect the shield to earth ground. AC wiring should be 14 gauge or greater. Provide a switch or breaker to dis­connect the analyzer from the main power supply. Install the switch or breaker near the analyzer and label it as the disconnecting device for the analyzer.
Keep sensor and output signal wiring separate from power wiring. Do not run sensor and power wiring in the same conduit or close together in a cable tray.
3.4.2 Current Output wiring
All instruments are shipped with four 4-20mA current outputs. Wiring locations for the outputs are on the Main board which is mounted on the hinged door of the instrument. Wire the output leads to the correct position on the Main board connectors using the lead markings (+/positive, -/negative) on the board. Male mating connectors are pro­vided with each unit. Use a 3/32”-wide standard blade screwdriver.
3.4.3 Alarm relay wiring
Four alarm relays are supplied with the switching power supply (84 to 265VAC, -03 order code) and the 24VDC power supply (20-30VDC, -02 order code). Wire the relay leads on each of the independent relays to the correct position on the power supply board using the printed lead markings (NO/Normally Open, NC/Normally Closed, or Com/Common) on the board.
11
Electrical installation must be in accordance with the National Electrical Code (ANSI/NFPA-70) and/or any other applicable national or local codes.
WARNING
RISK OF ELECTRICAL SHOCK
Page 20
Figure 3-6 pH/ORP/ISE signal board and Sensor cable leads
MODEL 1057 SECTION 3.0
WIRING
Sec. 3.4 Signal board wiring
Figure 3-5 Contacting Conductivity signal board and Sensor cable leads
12
Page 21
MODEL 1057 SECTION 3.0
WIRING
FIGURE 3-7 Power Wiring for Model 1057 84-265 VAC Power Supply (-03 ordering code)
13
FIGURE 3-8 Output Wiring for Model 1057 Main PCB
Page 22
MODEL 1057 SECTION 3.0
WIRING
FIGURE 3-9 Power Wiring for Model 1057 24VDC Power Supply (-02 ordering code)
14
To Main PCB
Page 23
MODEL 1057 SECTION 4.0
DISPLAY AND OPERATION
SECTION 4.0
DISPLAY AND OPERATION
4.1 USER INTERFACE
The Model 1057 has a large display which shows three live measurement readouts in large digits and up to six additional process variables or diagnostic parameters concurrently. The display is back-lit and the format can be customized to meet user requirements. The intuitive menu system allows access to Calibration, Hold (of current outputs), Programming, and Display functions by pressing the MENU button. In addition, a dedicated DIAGNOSTIC button is available to provide access to useful operational information on installed sensor(s) and any problematic conditions that might occur. The display flashes Fault and/or Warning when these conditions occur. Help screens are displayed for most fault and warning conditions to guide the user in troubleshooting. During calibration and programming, key presses cause different displays to appear. The displays are self­explanatory and guide the user step-by-step through the procedure.
4.2 INSTRUMENT KEYPAD
There are 4 Function keys and 4 Selection keys on the instrument keypad.
Function keys:
The MENU key is used to access menus for program- ming and calibrating the instrument. Four top-level menu items appear when pressing the MENU key:
Calibrate: calibrate attached sensors and
analog outputs.
Hold: Suspend current outputs. Program: Program outputs, measurement,
temperature, security and reset.
Display: Program display format, language,
warnings, and contrast Pressing MENU always causes the main menu screen to appear. Pressing MENU followed by EXIT causes
the main display to appear.
4.1 USER INTERFACE
4.2 KEYPAD
4.3 MAIN DISPLAY
4.4 MENU SYSTEM
15
Page 24
MODEL 1057 SECTION 4.0
DISPLAY AND OPERATION
Selection keys:
Surrounding the ENTER key, four Selection keys – up, down, right and left, move the cursor to all areas of the screen while using the menus. Selection keys are used to:
1. select items on the menu screens
2. scroll up and down the menu lists.
3. enter or edit numeric values.
4. move the cursor to the right or left
5. select measurement units during operations
4.3 MAIN DISPLAY
The Model 1057 displays one, two or three primary meas­urement values, up to six secondary measurement values, a fault and warning banner, alarm relay flags.
Process measurements:
Three process variables are displayed if three signal boards are installed. One process variable and process temperature is displayed if one signal board is installed with one sensor. The Upper display area shows the Sensor 1 process reading. The Center dis­play area shows the Sensor 2 process reading. For dual conductivity, the display areas can be assigned to different process variables as follows:
Process variables for display- examples:
Measure 1
Measure 2
Measure 3 % Reject
% Pass
Ratio
Blank
pH Calc
Secondary values:
Up to six secondary values are shown in six display quadrants at the bottom of the screen. All four secondary value positions can be programmed by the user to any display parameter available. Possible secondary values include:
Displayable Secondary Values
Slope 1, 2, 3 Output 1 mA
Ref Off 1, 2, 3 Output 2 mA
Gl Imp 1, 2, 3 Output 3 mA
Ref Imp 1, 2, 3
Output 4 mA
Raw 1, 2, 3
Output 1 %
mV Input 1, 2, 3 Output 2 %
Temp 1, 2, 3 Output 3 %
Man Temp 1, 2, 3
Output 4 %
Measure 1, 2, 3 Blank
Pressing the DIAG key displays active Faults and Warnings, and provides detailed instrument information and sensor diagnostics including: Faults, Warnings, Sensor 1, 2 and 3 information, Current Outputs live values, model configuration string e.g. 1057-03 -20-30­42-AN, Instrument Software version, and AC frequen­cy. Pressing ENTER on Sensor 1 or Sensor 2 provides useful diagnostics and information (as applicable): Measurement, Sensor Type, Raw signal value, Cell constant, Zero Offset and Temperature. Offset, selected
measurement range, Cable Resistance, Temperature Sensor Resistance, Signal Board software version.
The ENTER key. Pressing ENTER stores numbers and settings and moves the display to the next screen.
The EXIT key. Pressing EXIT returns to the previous screen without storing changes.
16
Page 25
4.4 MENU SYSTEM
Model 1057 uses a scroll and select menu system. Pressing the MENU key at any time opens the top-level menu including Calibrate, Hold, Program and Display functions.
To find a menu item, scroll with the up and down keys until the item is highlighted. Continue to scroll and select menu items until the desired function is chosen. To select the item, press ENTER. To return to a previ­ous menu level or to enable the main live display, press the EXIT key repeatedly. To return immediately to the main display from any menu level, simply press MENU then EXIT.
MODEL 1057 SECTION 4.0
DISPLAY AND OPERATION
Fault and Warning banner:
If the analyzer detects a problem with itself or the sensor the word Fault or Warning will appear at the bottom of the display. A fault requires immediate attention. A warning indicates a problematic condition or an impending fail­ure. For troubleshooting assitance, press Diag.
Formatting the Main Display
The main display screen can be programmed to show primary process variables, secondary process variables and diagnostics.
1. Press MENU
2. Scroll down to Display. Press ENTER.
3. Main Format will be highlighted. Press ENTER.
4. The sensor 1 process value will be highlighted in reverse video. Press the selection keys to navigate down
to the screen sections that you wish to program. Press ENTER.
5. Choose the desired display parameter or diagnostic for each of the four display sections in the lower screen.
6. Continue to navigate and program all desired screen sections. Press MENU and EXIT. The screen will
return to the main display.
For single sensor configurations, the default display shows the live process measurement in the upper display area and temperature in the center display area. The user can elect to disable the display of temperature in the center display area using the Main Format function. See Fig. 4-1 to guide you through programming the main display to select process parameters and diagnostics of your choice.
For dual sensor configurations, the default display shows Sensor 1 live process measurement in the display area 1 and Sensor 2 live process measurement temperature in the display area 2. See Fig. 4-1 to guide you through programming the main display to select process parameters and diagnostics of your choice.
The selection keys have the following functions: The Up key (above ENTER) increments numerical values, moves the decimal place one place to the right,
or selects units of measurement.
The Down key (below ENTER) decrements numerical values, moves the decimal place one place to the
left, or selects units of measurement
The Left key (left of ENTER) moves the cursor to the left. The Right key (right of ENTER) moves the cursor to the right.
To access desired menu functions, use the “Quick Reference” Figure B. During all menu displays (except main display format and Quick Start), the live process measurements and secondary measurement values are displayed in the top two lines of the Upper display area. This conveniently allows display of the live values during important calibration and programming operations.
Menu screens will time out after two minutes and return to the main live display.
17
Page 26
FIGURE 4-1 Formatting the Main Display
MODEL 1057 SECTION 4.0
DISPLAY AND OPERATION
18
Page 27
MODEL 1057 SECTION 5.0
PROGRAMMING THE ANALYZER - BASICS
SECTION 5.0.
PROGRAMMING THE ANALYZER - BASICS
5.1 GENERAL
Section 5.0 describes the following programming functions:
Changing the measurement type, measurement units and temperature units. Choose temperature units and manual or automatic temperature compensation mode Configure and assign values to the current outputs Set a security code for two levels of security access Accessing menu functions using a security code Enabling and disabling Hold mode for current outputs Choosing the frequency of the AC power (needed for optimum noise rejection) Resetting all factory defaults, calibration data only, or current output settings only
5.2 CHANGING STARTUP SETTINGS
5.2.1 Purpose
To change the measurement type, measurement units, or temperature units that were initially entered in Quick Start, choose the Reset analyzer function (Sec. 5.8) or access the Program menus for sensor 1, 2 or 3 (Sec. 6.0). The following choices for specific measurement type, measurement units are available for each sensor measure­ment board.
Signal board Available measurements
Measurements units:
pH/ORP (-22, -32, -42)
pH, ORP, Redox, Ammonia, Fluoride, Custom ISE
pH, mV (ORP) %, ppm, mg/L, ppb, μg/L, (ISE)
Contacting conductivity (-20, -30, -40)
Conductivity, Resistivity, TDS, Salinity, NaOH (0-12%), HCl (0-15%), Low H2SO4, High H2SO4, NaCl (0-20%), Custom Curve
μS/cm, mS/cm, S/cm % (concentration)
Temperature (all)
Temperature °C, ºF
5.2.2 Procedure.
Follow the Reset Analyzer procedure (Sec 5.8) to reconfigure the analyzer to display new measurements or measurement units. To change the specific measurement or measurement units for each signal board type, refer to the Program menu for the appropriate measurement (Sec. 6.0).
TABLE 5-1. Measurements and Measurement Units
5.1 GENERAL
5.2 CHANGING START-UP SETTINGS
5.3 PROGRAMMING TEMPERATURE
5.4 CONFIGURING AND RANGING 4-20MA OUTPUTS
5.5 SETTING SECURITY CODES
5.6 SECURITY ACCESS
5.7 USING HOLD
5.8 RESETTING FACTORY DEFAULTS – RESET ANALYZER
5.9 PROGRAMMING ALARM RELAYS
19
Page 28
MODEL 1057 SECTION 5.0
PROGRAMMING THE ANALYZER - BASICS
5.3.1 Purpose
Most liquid analytical measurements (except ORP) require temperature compensation. The Model 1057 performs temperature compensation automatically by applying internal temperature correction algorithms. Temperature correction can also be turned off. If tem­perature correction is off, the Model 1057 uses the tem­perature entered by the user in all temperature correc­tion calculations.
5.3.2 Procedure.
Follow the menu screens in Fig. 5.1 to select automatic or manual temp compensation, set the manual reference temperature, and to program temperature units as °C or °F.
5.4.1 Purpose
The Model 1057 accepts inputs from three sensors and has four analog current outputs. Ranging the outputs means assigning values to the low (0 or 4 mA) and high (20 mA) outputs. This section provides a guide for configuring and ranging the outputs. ALWAYS CONFIGURE THE OUTPUTS FIRST.
5.4.2 Definitions
1. CURRENT OUTPUTS. The analyzer provides a con­tinuous output current (4-20 mA or 0-20 mA) directly proportional to the process variable or temperature.
The low and high current outputs can be set to any value.
2. ASSIGNING OUTPUTS. Assign a measurement to Outputs 1, 2, 3, or 4.
3. DAMPEN. Output dampening smooths out noisy readings. It also increases the response time of the output. Output dampening does not affect the response time of the display.
4. MODE. The current output can be made directly proportional to the displayed value (linear mode) or directly proportional to the common logarithm of the displayed value (log mode).
S1: 1.234µS/cm 123.4ºC S2: 12.34pH 123.4ºC
S3:123.4µS/cm 123.4ºC
Temperature Units: °C S1 Temp Comp: Auto S2 Temp Comp: Auto S3 Temp Comp: Auto
Figure 5-1. Choosing Temp Units and Manual Auto Temp Compensation
5.3 CHOOSING TEMPERATURE UNITS AND AUTOMATIC/MANUAL TEMPERATURE COMPENSATION
5.4 CONFIGURING AND RANGING THE CURRENT OUTPUTS
20
Page 29
MODEL 1057 SECTION 5.0
PROGRAMMING THE ANALYZER - BASICS
5.4.3 Procedure: Configure Outputs.
Under the Program/Outputs menu, the adjacent screen will appear to allow configuration of the outputs. Follow the menu screens in Fig. 5-2 to configure the outputs.
5.4.4 Procedure: Assigning Measurements the Low and High Current Outputs
The adjacent screen will appear when entering the Assign function under Program/Output/Configure. These screens allow you to assign a measurement, process value, or temperature input to each output. Follow the menu screens in Fig. 5-2 to assign measurements to the outputs.
5.4.5 Procedure: Ranging the Current Outputs
The adjacent screen will appear under Program/Output/Range. Enter a value for 4mA and 20mA (or 0mA and 20mA) for each output. Follow the menu screens in Fig. 5-2 to assign values to the out­puts.
S1: 1.234µS/cm 123.4ºC S2: 12.34pH 123.4ºC
S3:123.4µS/cm 123.4ºC
OutputM Configure Assign: S1 Meas Range: 4-20mA Scale: Linear Dampening: 0sec
Fault Mode: Fixed Fault Value: 21.00mA
S1: 1.234µS/cm 123.4ºC S2: 12.34pH 123.4ºC
S3:123.4µS/cm 123.4ºC
OutputM Assign S1 Measurement S1 Temperature S2 Measurement S2 Temperature S3 Measurement S3 Temperature
S1: 1.234µS/cm 123.4ºC S2: 12.34pH 123.4ºC
S3:123.4µS/cm 123.4ºC
Output Range OM SN 4mA: 0.000µS/cm OM SN 20mA: 20.00µS/cm OM SN 4mA: 00.00pH OM SN 20mA: 14.00pH
Figure 5-2. Configuring and Ranging the Current Outputs
21
Page 30
Figure 5-3. Setting a Security Code
MODEL 1057 SECTION 5.0
PROGRAMMING THE ANALYZER - BASICS
5.5 SETTING A SECURITY CODE
5.5.1 Purpose.
The security codes prevent accidental or unwanted changes to program settings, displays, and calibration. Model 1057 has two levels of security code to control access and use of the instrument to different types of users. The two levels of security are:
- All: This is the Supervisory security level. It allows access to all menu functions, including Programming, Calibration, Hold and Display.
- Calibration/Hold: This is the operator or tech­nician level menu. It allows access to only calibration and Hold of the current outputs.
5.5.2 Procedure.
1. Press MENU. The main menu screen appears. Choose Program.
2. Scroll down to Security. Select Security.
3. The security entry screen appears. Enter a three digit security code for each of the desired security levels. The security code takes effect two minutes after the last key stroke. Record the security code(s) for future access and communication to operators or technicians as needed.
4. The display returns to the security menu screen. Press EXIT to return to the previous screen. To return to the main display, press MENU followed by EXIT.
Fig. 5-3 displays the security code screens.
22
S1: 1.234µS/cm 1.234ºC S2: 12.34pH 1.234ºC
S3: 12.34µS/cm 1.234ºC
Security Calibration/Hold: 000 All: 000
S1: 1.234µS/cm 1.234ºC S2: 12.34pH 1.234ºC
S3: 12.34µS/cm 1.234ºC
Program Outputs Measurement Temperature
Diagnostic Setup Rejection Freq: 60Hz Reset Analyzer
MAIN MENU
Program
Security
Page 31
MODEL 1057 SECTION 5.0
PROGRAMMING THE ANALYZER - BASICS
5.6 SECURITY ACCESS
5.6.1 How the Security Code Works
When entering the correct access code for the Calibration/Hold security level, the Calibration and Hold menus are accessible. This allows operators or technicians to perform routine maintenance. This security level does not allow access to the Program or Display menus. When entering the correct access code for All security level, the user has access to all menu functions, includ­ing Programming, Calibration, Hold and Display.
5.6.2 Procedure.
1. If a security code has been programmed, selecting the Calibrate, Hold, Program or Display top menu items causes the security access screen to appear
2. Enter the three-digit security code for the appropriate security level.
3. If the entry is correct, the appropriate menu screen appears. If the entry is incorrect, the Invalid Code screen appears. The Enter Security Code screen reappears after 2 seconds.
5.7 USING HOLD
5.7.1 Purpose
The analyzer output is always proportional to measured value. To prevent improper operation of systems or pumps that are controlled directly by the current output, place the analyzer in hold before removing the sensor for calibration and maintenance. Be sure to remove the analyzer from hold once calibration is complete. During hold, both outputs remain at the last value. Once in hold, all current outputs remain on
Hold indefinitely.
5.7.2 Using the Hold Function
To hold the outputs,
1. Press MENU. The main menu screen appears. Choose Hold.
2. The Hold Outputs and Alarms? screen appears. Choose Yes to place the analyzer in hold. Choose No to take the analyzer out of hold. Note: There are no alarm relays with this con figuration. Current outputs are included with all configurations.
3. The Hold screen will then appear and Hold
will remain on indefinitely until Hold is disabled.
See figure 5-1 below.
S1: 1.234µS/cm 1.234ºC S2: 12.34pH 1.234ºC S3: 12.34µS/cm 1.234ºC
Security Code
000
MAIN MENU
Hold
S1: 1.234µS/cm 1.234ºC S2: 12.34pH 1.234ºC
S3: 12.34µS/cm 1.234ºC
S1 Hold outputs
and alarms? No Yes
S1: 1.234µS/cm 1.234ºC S2: 12.34pH 1.234ºC S3: 12.34µS/cm 1.234ºC
Hold S1 Hold: No S2 Hold: No S3 Hold: No
Figure 5-4. Using Hold
23
Page 32
MODEL 1057 SECTION 5.0
PROGRAMMING THE ANALYZER - BASICS
5.8 RESETTING FACTORY DEFAULT SETTINGS
5.8.1 Purpose.
This section describes how to restore factory calibration and default values. The process also clears all fault messages and returns the display to the first Quick Start screen. The Model 1057 offers three options for resetting factory defaults.
a. reset all settings to factory defaults b. reset sensor calibration data only c. reset output calibration only
5.8.2 Procedure.
To reset to factory defaults, reset calibration data only or reset analog outputs only, follow the Reset Analyzer flow diagram.
Figure 5-5. Resetting Factory Default Settings
24
Page 33
5.9 Programming Alarm Relays
5.9.1 Purpose.
The Model 1057 24VDC (-02 order code) and the AC switching power supply (-03 order code) provide four alarm relays for process measurement or temperature. Each alarm can be configured as a fault alarm instead of a process alarm. Also, each relay can be programmed independently and each can be programmed as an interval timer. This section describes how to configure alarm relays, simulate relay activation, and synchronize timers for the four alarm relays. This section provides details to program the following alarm features:
Under the Program/Alarms menu, this screen will appear to allow configuration of the alarm relays. Follow the menu screens in Fig. XX to configure the outputs.
This screen will appear to allow selection of a specific alarm relay. Select the desired alarm and press ENTER.
This screen will appear next to allow complete pro­gramming of each alarm. Factory defaults are dis­played as they would appear for an installed contact­ing conductivity board. USP Safety only appears if alarm logic is set to “USP”. Interval timer, On Time, Recover Time, and Hold While Active only appear if the alarm is configured as an Interval timer.
MODEL 1057 SECTION 5.0
PROGRAMMING THE ANALYZER - BASICS
S1: 1.234µS/cm 1.234ºC S2: 12.34pH 1.234ºC S3: 12.34µS/cm 1.234ºC
Alarms Configure/Setpoint Simulate Synchronize Timers: Yes
S1: 1.234µS/cm 1.234ºC S2: 12.34pH 1.234ºC S3: 12.34µS/cm 1.234ºC
Configure/Setpoint Alarm 1 Alarm 2 Alarm 3 Alarm 4
S1: 1.234µS/cm 1.234ºC S2: 12.34pH 1.234ºC S3: 12.34µS/cm 1.234ºC
AlarmM Settings Setpoint: 100.0uS/cm Assign: S1 Measure Logic: High Deadband: 0.00uS/cm USP Safety: 0%↓ Interval time: 24.0 hr On Time: 120 sec Recover time: 60 sec Hold while active: Sens1
Sec.
Alarm relay feature: default Description
5.9.2
Enter Setpoint 100.0uS/cm Enter alarm trigger value
5.9.3
Assign measurement S1 Measure Select alarm assignment
5.9.4 Set relay logic High Program relay to activate at High or Low reading
5.9.5 Deadband: 0.00uS/cm
Program the change in process value after the relay deactivates
5.9.6 USP Safety: 0%↓ Program percentage of the limit to activate the alarm
5.9.7
Normal state: Open
Program relay default condition as open or closed for failsafe operation
5.9.8 Interval time: 24.0 hr Time in hours between relay activations
5.9.9
On-Time: 10 min Enter the time in seconds that the relay is activated.
5.9.10
Recover time: 60 sec Enter time after the relay deactivation for process recovery
5.9.11
Hold while active: S1 Holds current outputs during relay activation
5.9.12 Simulate
Manually simulate alarms to confirm relay operation
5.9.13
Synchronize Timers Yes Control the timing of two or more relay timers set as Interval timers
25
Page 34
MODEL 1057 SECTION 5.0
PROGRAMMING THE ANALYZER - BASICS
5.9.2 Procedure – Enter Setpoints
Under the Program/Alarms menu, this screen will appear to allow configuration of the alarm relays. Enter the desired value for the process measurement or temperature at which to activate an alarm event.
5.9.3 Procedure – Assign Measurement
Under the Alarms Settings menu, this screen will appear to allow assignment of the alarm relays. select an alarm assignment. Additional assignment choices are shown in Figure X-X depending on which meas­urement board(s) is installed.
5.9.4 Procedure – Set Relay Logic
Under the Alarms Settings menu, this screen will appear to set the alarm logic. Select the desired relay logic to activate alarms at a High reading or a Low reading. USP Safety only appears if a contacting con­ductivity board is installed.
5.9.5 Procedure – Deadband
Under the Alarms Settings menu, this screen will appear to program the deadband as a measurement value. Enter the change in the process value needed after the relay deactivates to return to normal (and thereby preventing repeated alarm activation).
5.9.6 Procedure – USP Safety
Under the Alarms Settings menu, this screen will appear to program the USP alarm setting. Enter the percentage below the limit at which to activate the alarm.
5.9.7 Procedure – Normal state
The user can define failsafe condition in software by programming the alarm default state to normally open or normally closed upon power up. To display this alarm configuration item, enter the Expert menus by holding down the EXIT key for 6 seconds while in the main display mode. Select Yes upon seeing the screen prompt: “Enable Expert Menu?” Under the Alarms Settings menu, this screen will appear to set the normal state of the alarms. Select the alarm condition that is desired each time the analyzer is powering up.
S1: 1.234µS/cm 1.234ºC S2: 12.34pH 1.234ºC S3: 12.34µS/cm 1.234ºC
Alarm1 S2 Setpoint
+100.0uS/cm
S1: 1.234µS/cm 1.234ºC S2: 12.34pH 1.234ºC S3: 12.34µS/cm 1.234ºC
AlarmM Logic: High Low USP
S1: 1.234µS/cm 1.234ºC S2: 12.34pH 1.234ºC S3: 12.34µS/cm 1.234ºC
Alarm1 Deadband
+000.5uS/cm
S1: 1.234µS/cm 1.234ºC S2: 12.34pH 1.234ºC S3: 12.34µS/cm 1.234ºC
Alarm1 USP Safety
+0%
S1: 1.234µS/cm 1.234ºC S2: 12.34pH 1.234ºC S3: 12.34µS/cm 1.234ºC
Alarm2 Normal State
Open
Closed
S1: 1.234µS/cm 1.234ºC S2: 12.34pH 1.234ºC S3: 12.34µS/cm 1.234ºC
AlarmM Assign:
S1 Measurement S1 Temperature S2 Measurement S2 Temperature S3 Measurement S3 Temperature Interval Timer Fault Off
26
Page 35
MODEL 1057 SECTION 5.0
PROGRAMMING THE ANALYZER - BASICS
5.9.8 Procedure – Interval time
Under the Alarms Settings menu, this screen will appear to set the interval time. Enter the fixed time in hours between relay activations.
5.9.9 Procedure – On time
Under the Alarms Settings menu, this screen will appear to set the relay on time. Enter the time in sec­onds that the relay is activated.
5.9.10 Procedure – Recovery time
Under the Alarms Settings menu, this screen will appear to set the relay recovery time. Enter time after the relay deactivation for process recovery.
5.9.11 Procedure – Hold while active
Under the Alarms Settings menu, this screen will appear to program the feature that Holds the current outputs while alarms are active. Select to hold the current outputs for Sensor 1, Sensor 2 or both sensors while the relay is activated.
5.9.12 Procedure – Simulate
Alarm relays can be manually set for the purposes of checking devices such as valves or pumps. Under the Alarms Settings menu, this screen will appear to allow manual forced activation of the alarm relays. Select the desired alarm condition to simulate.
5.9.13 Procedure – Synchronize
Under the Alarms Settings menu, this screen will appear to allow Synchronization of alarms that are set to Interval Timers. Select yes or no to Synchronize two or more timers.
S1: 1.234µS/cm 1.234ºC S2: 12.34pH 1.234ºC S3: 12.34µS/cm 1.234ºC
Alarm1 Interval Time
024.0 hrs
S1: 1.234µS/cm 1.234ºC S2: 12.34pH 1.234ºC S3: 12.34µS/cm 1.234ºC
Alarm1 On-Time
00.00sec
S1: 1.234µS/cm 1.234ºC S2: 12.34pH 1.234ºC S3: 12.34µS/cm 1.234ºC
Alarm1 Recovery
060sec
S1: 1.234µS/cm 1.234ºC S2: 12.34pH 1.234ºC S3: 12.34µS/cm 1.234ºC
Synchronize Timers
Yes
No
S1: 1.234µS/cm 1.234ºC S2: 12.34pH 1.234ºC S3: 12.34µS/cm 1.234ºC
Alarm1 Hold while active Sensor 1 Sensor 2 Sensor 3
All
None
S1: 1.234µS/cm 1.234ºC S2: 12.34pH 1.234ºC S3: 12.34µS/cm 1.234ºC
Simulate Alarm M Don’t simulate De-energize Energize
27
Page 36
This page left blank intentionally
MODEL 1057 SECTION 5.0
PROGRAMMING THE ANALYZER - BASICS
28
Page 37
MODEL 1057 SECTION 6.0
PROGRAMMING THE MEASUREMENTS
SECTION 6.0
PROGRAMMING - MEASUREMENTS
6.1 CONFIGURING MEASUREMENTS – INTRODUCTION
6.2 pH
6.3 ORP
6.4 CONTACTING CONDUCTIVITY
6.1 PROGRAMMING MEASUREMENTS – INTRODUCTION
The Model 1057 automatically recognizes each installed measurement board upon first power-up and each time the analyzer is powered. Completion of Quick Start screens upon first power up enable measurements, but addi­tional steps may be required to program the analyzer for the desired measurement application. This section covers the following programming and configuration functions;
1. Selecting measurement type or sensor type (all sections)
2. Identifying the preamp location (pH-see Sec. 6.2)
3. Enabling manual temperature correction and entering a reference temperature (all sections)
4. Enabling sample temperature correction and entering temperature correction slope (selected sections)
5. Defining measurement display resolution (pH)
6. Defining measurement display units (all sections)
7. Adjusting the input filter to control display and output reading variability or noise (all sections)
8. Selecting a measurement range (conductivity – see Sec’s 6.4, 6.5)
9. Entering a cell constant for a contacting sensor (see Sec’s 6.4, 6.5)
10. Entering a temperature element/RTD offset or temperature slope (conductivity-see Sec’s 6.4)
11. Creating an application-specific concentration curve (conductivity-see Sec’s 6.4, 6.5)
To fully configure the analyzer for each installed measurement board, you may use the following:
1. Reset Analyzer function to reset factory defaults and configure the measurement board to the desired measurement. Follow the Reset Analyzer menu (Fig. 5-5) to reconfigure the analyzer to display new measurements or measurement units.
2. Program menus to adjust any of the programmable configuration items. Use the following configuration and programming guidelines for the applicable measurement.
29
Page 38
MODEL 1057 SECTION 6.0
PROGRAMMING THE MEASUREMENTS
6.2 pH MEASUREMENT PROGRAMMING
6.2.1 Description
This section describes how to configure the Model 1057 analyzer for pH measurements. The following programming and configuration functions are covered.
Measure Sec. Menu function: default setting
Description
pH
6.2.2 Measurement type: pH
Select pH, ORP, Redox, Ammonia, Fluoride, Custom ISE
6.2.3 Preamp location: Analyzer
Identify preamp location
6.2.4 Solution temperature correction Off
Select Off, ultra-pure, high pH, custom
6.2.5 Temp coefficient (custom)
Enter the temp coefficient
6.2.6 Resolution: 0.01pH
Select 0.01pH or 0.1pH for pH display resolution
6.2.7
Filter: 4 sec Override the default input filter, enter 0-999 seconds
6.2.8 Reference Z: Low
Select low or high reference impedance
To configure the pH measurement board:
1. Press MENU
2. Scroll down to Program. Press ENTER.
3. Scroll down to Measurement. Press ENTER.
4. Select Sensor 1 or Sensor 2 corresponding to
pH. Press ENTER. The adjacent screen format will appear (factory defaults are shown). To program any function, scroll to the desired item and press ENTER.
6.2.2 Measurement
The display screen for selecting the measurement is shown. The default value is displayed in bold type. Refer to the pH/ORP Programming flow diagram to complete this function.
S1: 1.234µS/cm 1.234ºC S2: 12.34pH 1.234ºC S3: 12.34µS/cm 1.234ºC
SN Measurement
pH
ORP Redox Ammonia
Fluoride Custom ISE
The following sub-sections provide you with the initial display screen that appears for each configuration function. Use the flow diagram for pH programming at the end of Sec. 6 and the Model 1057 live screen prompts for each function to complete configuration and programming.
6.2.3 Preamp
The display screen for identifying the Preamp location is shown. The default value is displayed in bold type. Refer to the pH/ORP Programming flow diagram to complete this function.
S1: 1.234µS/cm 1.234ºC S2: 12.34pH 1.234ºC S3: 12.34µS/cm 1.234ºC
SN Preamp
Analyzer
Sensor/JBox
TABLE 6-1. pH Measurement Programming
A detailed flow diagram for pH programming is provided at the end of Sec. 6 to guide you through all basic programming and configuration functions.
30
S1: 1.234µS/cm 1.234ºC S2: 12.34pH 1.234ºC S3: 12.34µS/cm 1.234ºC
SN Configure Measure: pH Preamp: Analyzer Sol’n Temp Corr: Off T Coeff: -0.029pH/°C
Resolution: 0.01pH Filter: 4 sec Reference Z: Low
Page 39
MODEL 1057 SECTION 6.0
PROGRAMMING THE MEASUREMENTS
6.2.4 Solution Temperature Correction
The display screen for selecting the Solution temperature correction algorithm is shown. The default value is displayed in bold type. Refer to the pH/ORP Programming flow diagram to complete this function.
6.2.5 Temperature Coefficient
The display screen for entering the custom solution tem­perature coefficient is shown. The default value is dis­played in bold type. Refer to the pH/ORP Programming flow diagram to complete this function.
6.2.6 Resolution
The display screen for selecting 0.01pH or 0.1pH for pH display resolution is shown. The default value is displayed in bold type. Refer to the pH/ORP Programming flow diagram to complete this function.
S1: 1.234µS/cm 1.234ºC S2: 12.34pH 1.234ºC S3: 12.34µS/cm 1.234ºC
SN Sol’n Temp Corr.
Off
Ultra Pure Water High pH Custom
S1: 1.234µS/cm 1.234ºC S2: 12.34pH 1.234ºC S3: 12.34µS/cm 1.234ºC
SN Resolution
0.01pH
0.1pH
S1: 1.234µS/cm 1.234ºC S2: 12.34pH 1.234ºC S3: 12.34µS/cm 1.234ºC
SN Sol’n Temp Coeff.
- 0.032pH/ºC
6.2.7 Filter
The display screen for entering the input filter value in seconds is shown. The default value is displayed in bold type. Refer to the pH/ORP Programming flow diagram to complete this function.
6.2.8 Reference Impedence
The display screen for selecting Low or High Reference impedance is shown. The default value is displayed in bold type. Refer to the pH/ORP Programming flow diagram to complete this function.
S1: 1.234µS/cm 1.234ºC S2: 12.34pH 1.234ºC S3: 12.34µS/cm 1.234ºC
SN Reference Z
Low
High
S1: 1.234µS/cm 1.234ºC S2: 12.34pH 1.234ºC S3: 12.34µS/cm 1.234ºC
SN Input filter
04 sec
6.3 ORP MEASUREMENT PROGRAMMING
6.3.1 Description
The section describes how to configure the Model 1057 analyzer for ORP measurements. The following programming and configuration functions are covered:
Measure Sec. Menu function: default
Description
ORP
6.3.2 Measurement type: pH
Select pH, ORP, Redox, Ammonia, Fluoride, Custom ISE
6.3.3 Preamp location: Analyzer
Identify preamp location
6.3.4 Filter: 4 sec
Override the default input filter, enter 0-999 seconds
6.3.5 Reference Z: Low
Select low or high reference impedance
TABLE 6-2. ORP Measurement Programming
31
Page 40
MODEL 1057 SECTION 6.0
PROGRAMMING THE MEASUREMENTS
The following sub-sections provide you with the initial display screen that appears for each configuration function. Use the flow diagram for ORP programming at the end of Sec. 6 and the Model 1057 live screen prompts for each function to complete configuration and programming.
6.3.2 Measurement
The display screen for selecting the measurement is shown. The default value is displayed in bold type. Refer to the pH/ORP Programming flow diagram to complete this function.
6.3.3 Preamp
The display screen for identifying the Preamp location is shown. The default value is displayed in bold type. Refer to the pH/ORP Programming flow diagram to complete this function.
6.3.4 Filter
The display screen for entering the input filter value in seconds is shown. The default value is displayed in bold type. Refer to the pH/ORP Programming flow diagram to complete this function.
A detailed flow diagram for ORP programming is provided at the end of Sec. 6 to guide you through all basic programming and configuration functions.
To configure the ORP measurement board:
1. Press MENU
2. Scroll down to Program. Press ENTER.
3. Scroll down to Measurement. Press ENTER.
4. Select Sensor 1 or Sensor 2 corresponding to ORP. Press ENTER.
The adjacent screen format will appear (factory defaults are shown). To program any displayed function, scroll to the desired item and press ENTER.
S1: 1.234µS/cm 1.234ºC S2: 12.34pH 1.234ºC S3: 12.34µS/cm 1.234ºC
SN Preamp
Analyzer
Sensor/JBox
S1: 1.234µS/cm 1.234ºC S2: 12.34pH 1.234ºC S3: 12.34µS/cm 1.234ºC
SN Input filter
04 sec
6.3.5 Reference Impedence
The display screen for Selecting Low or high Reference impedance is shown. The default value is displayed in bold type. Refer to the pH/ORP Programming flow diagram to complete this function.
S1: 1.234µS/cm 1.234ºC S2: 12.34pH 1.234ºC S3: 12.34µS/cm 1.234ºC
SN Reference Z
Low
High
S1: 1.234µS/cm 1.234ºC S2: 12.34pH 1.234ºC S3: 12.34µS/cm 1.234ºC
SN Configure Measure: pH Preamp: Analyzer Flter: 4 sec Reference Z: Low
S1: 1.234µS/cm 1.234ºC S2: 12.34pH 1.234ºC S3: 12.34µS/cm 1.234ºC
SN Measurement pH ORP Redox Ammonia
Fluoride
Custom ISE
32
Page 41
6.4.2 Sensor Type
The display screen for selecting 2-Electrode or 4-Electrode type sensors is shown. The default value is displayed in bold type. Refer to the contacting conductivity Programming flow diagram to complete this function.
MODEL 1057 SECTION 6.0
PROGRAMMING THE MEASUREMENTS
6.4 CONTACTING CONDUCTIVITY MEASUREMENT PROGRAMMING
6.4.1 Description
The section describes how to configure the Model 1057 analyzer for conductivity measurements using contacting conductivity sensors. The following programming and configuration functions are covered.
The following sub-sections provide you with the initial display screen that appears for each configuration function. Use the flow diagram for contacting conductivity programming at the end of Sec. 6 and the Model 1057 live screen prompts for each function to complete configuration and programming.
To configure the contacting conductivity measurement board:
1. Press MENU
2. Scroll down to Program. Press ENTER.
3. Scroll down to Measurement. Press ENTER.
4. Select Sensor 1 or Sensor 2 corresponding to contacting conductivity. Press ENTER.
The adjacent screen format will appear (factory defaults are shown). To program any displayed function, scroll to the desired item and press ENTER.
Measure Sec. Menu function: default
Description
Contacting Conductivi
ty
6.4.2 Type: 2-Electrode
Select 2-Electrode or 4-Electrode type sensors
6.4.3 Measure: Conductivity
Select Conductivity, Resistivity, TDS. Salinity or % conc
6.4.4 Range: Auto
Select measurement Auto-range or specific range
6.4.5 Cell K: 1.00000/cm
Enter the cell Constant for the sensor
6.4.6 RTD Offset: 0.00ºC
Enter the RTD Offset
6.4.7
RTD Slope: 0 Enter the RTD Slope
6.4.8 Temp Comp: Slope
Select Temp Comp: Slope, Neutral Salt, Cation or Raw
6.4.9 Slope: 2.00%/°C Enter the linear temperature coefficient
6.4.10 Ref Temp: 25.0°C Enter the Reference temp
6.4.11 Filter: 2 sec Override the default input filter, enter 0-999 seconds
6.4.12 Custom Setup Enter 2-5 data points in ppm and µS/cm for custom curves
6.4.13 Cal Factor: 0.95000/cm Enter the Cal Factor for 4-Electrode sensors from the sensor tag
S1: 1.234µS/cm 1.234ºC S2: 12.34pH 1.234ºC S3: 12.34µS/cm 1.234ºC
SN Configure Type: 2-Electrode Measure: Cond Range: Auto Cell K: 1.00000/cm RTD Offset: 0.00ºC RTD Slope: 0 Temp Comp: Slope Slope: 2.00%/°C Ref Temp: 25.0°C Filter: 2 sec Custom Setup
S1: 1.234µS/cm 1.234ºC S2: 12.34pH 1.234ºC S3: 12.34µS/cm 1.234ºC
SN Type
2-Electrode
4-Electrode
TABLE 6-3. Contacting Conductivity Measurement Programming
A detailed flow diagram for contacting conductivity programming is provided at the end of Sec. 6 to guide you through all basic programming and configuration functions.
33
Page 42
MODEL 1057 SECTION 6.0
PROGRAMMING THE MEASUREMENTS
6.4.3 Measure
The display screen for selecting the measurement is shown. The default value is displayed in bold type. Refer to the contacting conductivity Programming flow diagram to complete this function.
6.4.4 Range
The display screen for Selecting Auto-ranging or a specific range is shown. The default value is displayed in bold type. Note: Ranges are shown as conductance, not conductivity. Refer to the contacting conductivity Programming flow diagram to complete this function.
S1: 1.234µS/cm 1.234ºC S2: 12.34pH 1.234ºC S3: 12.34µS/cm 1.234ºC
SN Measurement
Conductivity
Resistivity TDS Salinity
NaOH (0-12%) HCl (0-15%) Low H2SO4 High H2SO4 NaCl (0-20%) Custom Curve
S1: 1.234µS/cm 1.234ºC S2: 12.34pH 1.234ºC S3: 12.34µS/cm 1.234ºC
SN Range
Auto
50 µS 500 µS 2000 µS 20 mS 200 mS 600 mS
6.4.5 Cell Constant
The display screen for entering a cell Constant for the sensor is shown. The default value is displayed in bold type. Refer to the contacting conductivity Programming flow diagram to complete this function.
S1: 1.234µS/cm 1.234ºC S2: 12.34pH 1.234ºC S3: 12.34µS/cm 1.234ºC
SN Cell Constant
1.00000 /cm
6.4.6 RTD Offset
The display screen for Entering the RTD Offset for the sensor is shown. The default value is displayed in bold type. Refer to the contacting conductivity Programming flow diagram to complete this function.
S1: 1.234µS/cm 1.234ºC S2: 12.34pH 1.234ºC S3: 12.34µS/cm 1.234ºC
SN RTD Offset
0.00°C
6.4.7 RTD Slope
The display screen for entering the RTD slope for the sensor is shown. The default value is displayed in bold type. Refer to the contacting conductivity Programming flow diagram to complete this function.
S1: 1.234µS/cm 1.234ºC S2: 12.34pH 1.234ºC S3: 12.34µS/cm 1.234ºC
SN RTD Slope
2.00%/ºC
6.4.8 Temp Comp
The display screen for Selecting Temperature Compensation as Slope, Neutral Salt, Cation or Raw is shown. The default value is displayed in bold type. Refer to the contacting conductivity Programming flow diagram to complete this function.
S1: 1.234µS/cm 1.234ºC S2: 12.34pH 1.234ºC S3: 12.34µS/cm 1.234ºC
SN Temp Comp
Slope
Neutral Salt Cation Raw
34
Page 43
6.4.13 Cal Factor
Upon initial installation and power up, if 4-electrode was selected for the sensor type in the Quick Start menus, the user enters a Cell Constant and a “Cal Factor” using the instrument keypad. The cell constant is needed to convert measured conductance to conductivity as displayed on the analyzer screen. The “Cal Factor” entry is needed increase the accuracy of the live conductivity readings, especially at low conduc­tivity readings below 20uS/cm. Both the Cell Constant and the “Cal Factor” are printed on the tag attached to the 4-electrode sensor/cable.
The display screen for entering Cal Factor is shown. The default value is displayed in bold type. If necessary after initial installation and start-up, enter the “Cal Factor” as printed on the sensor tag.
MODEL 1057 SECTION 6.0
PROGRAMMING THE MEASUREMENTS
6.4.9 Slope
The display screen for Entering the conductivity/temp Slope is shown. The default value is displayed in bold type. Refer to the contacting conductivity Programming flow diagram to complete this function.
S1: 1.234µS/cm 1.234ºC S2: 12.34pH 1.234ºC S3: 12.34µS/cm 1.234ºC
SN Slope
2.00 %/ºC
6.4.10 Reference Temp
The display screen for manually entering the Reference temperature is shown. The default value is displayed in bold type. Refer to the contacting conductivity Programming flow diagram to complete this function.
S1: 1.234µS/cm 1.234ºC S2: 12.34pH 1.234ºC S3: 12.34µS/cm 1.234ºC
SN Ref Temp
(25.0ºC normal)
+25.0ºC
6.4.11 Filter
The display screen for entering the input filter value in seconds is shown. The default value is displayed in bold type. Refer to the contacting conductivity Programming flow diagram to complete this function.
S1: 1.234µS/cm 1.234ºC S2: 12.34pH 1.234ºC S3: 12.34µS/cm 1.234ºC
SN Input filter
02 sec
6.4.12 Custom Setup
The display screens for creating a custom curve for converting conductivity to concentration is shown. Refer to the contacting conductivity Programming flow diagram to complete this function.
S1: 1.234µS/cm 1.234ºC S2: 12.34pH 1.234ºC S3: 12.34µS/cm 1.234ºC
SN Custom Curve Configure Enter Data Points Calculate Curve
S1: 1.234µS/cm 1.234ºC S2: 12.34pH 1.234ºC S3: 12.34µS/cm 1.234ºC
SN Cal Factor
0.95000/cm
When the custom curve data entry is complete, press ENTER. The display will confirm the determination of a custom curve fit to the entered data by displaying this screen:
S1: 1.234µS/cm 1.234ºC S2: 12.34pH 1.234ºC S3: 12.34µS/cm 1.234ºC
SN Calculate Curve Custom curve fit completed. In Process Cal recommended.
If the custom curve fit is not completed or is unsuccessful, the display will read as follows and the screen will return to the beginning custom curve screen.
S1: 1.234µS/cm 1.234ºC S2: 12.34pH 1.234ºC S3: 12.34µS/cm 1.234ºC
SN Calculate Curve Failure
35
Page 44
MODEL 1057 SECTION 6.0
PROGRAMMING THE MEASUREMENTS
FIGURE 6-1 Configuring pH/ORP Measurements
36
Page 45
MODEL 1057 SECTION 6.0
PROGRAMMING THE MEASUREMENTS
FIGURE 6-2 Configure Contacting Measurements
37
Page 46
This page left blank intentionally
38
Page 47
MODEL 1057 SECTION 7.0
CALIBRATION
SECTION 7.0
CALIBRATION
7.1 CALIBRATION – INTRODUCTION
7.2 pH CALIBRATION
7.3 ORP CALIBRATION
7.4 CONTACTING CONDUCTIVITY CALIBRATION
7.5 TEMPERATURE CALIBRATION
7.1 CALIBRATION – INTRODUCTION
Calibration is the process of adjusting or standardizing the analyzer to a lab test or a calibrated laboratory instrument, or standardizing to some known reference (such as a commercial buffer).
The auto-recognition feature of the analyzer will enable the appropriate calibration screens to allow calibration for any single sensor configuration or dual sensor config­uration of the analyzer. Completion of Quick Start upon first power up enables live measurements but does not ensure accurate readings in the lab or in process. Calibration should be performed with each attached sensor to ensure accurate, repeatable readings.
This section covers the following programming and configuration functions:
1. Auto buffer cal for pH (pH Cal - Sec.7.2)
2. Manual buffer cal for pH (pH Cal - Sec.7.2)
3. Set calibration stabilization criteria for pH (pH Cal - Sec.7.2)
4. Standardization calibration (1-point) for pH, ORP and Redox (pH Cal - Sec.7.2 and 7.3)
5. Entering the cell constant of a conductivity sensor (Conductivity Cal - Sec. 7.4 and 7.5)
6. Calibrating the sensor in a conductivity standard Conductivity Cal - Sec. 7.4 and 7.5)
7. Calibrating the analyzer to a laboratory instrument (Contacting Conductivity Cal - Sec.7.4)
8. Enter a manual reference temperature for temperature compensation of the process measurement
39
7.2 pH CALIBRATION
7.2.1 DESCRIPTION
New sensors must be calibrated before use. Regular recalibration is also necessary. Use auto calibration instead of manual calibration. Auto calibration avoids common pitfalls and reduces errors. The analyzer recognizes the buffers and uses temperature-corrected pH values in the calibration. Once the Model 1057 successfully completes the calibration, it calcu­lates and displays the calibration slope and offset. The slope is reported as the slope at 25°C.
THIS SECTION DESCRIBES HOW TO CALIBRATE THE MODEL 1057 WITH A pH SENSOR. THE FOLLOWING CALIBRATION ROUTINES ARE COVERED.
Measure Sec. Menu function: default
Description
pH
7.2.2 Auto Calibration - pH
2 point buffer calibration with auto buffer recognition
7.2.3 Manual Calibration - pH
2 point buffer calibration with manual buffer value entry
7.2.4 Entering A Known Slope Value - pH
Slope calibration with manual entry of known slope value
7.2.5
Standardization - pH 1 point buffer calibration with manual buffer value entry
TABLE 7-1 pH Calibration Routines
A detailed flow diagram is provided at the end of Sec. 7 to guide you through the calibration routines.
Page 48
MODEL 1057 SECTION 7.0
CALIBRATION
To calibrate pH:
1. Press the MENU button
2. Select Calibrate. Press ENTER.
3. Select Sensor 1 or Sensor 2 corresponding to pH. Press ENTER.
4. Select pH. Press ENTER.
The following screen will appear. To calibrate pH or Temperature scroll to the desired item and press ENTER.
S1: 1.234µS/cm 1.234ºC S2: 12.34pH 1.234ºC S3: 12.34µS/cm 1.234ºC
SN Calibrate? pH Temperature
7.2.2 AUTO CALIBRATION — pH
This screen appears after selecting pH calibration.
Note that pH auto calibration criteria can be changed. The following criteria can be adjusted:
Stabilization time (default 10 sec.)Stabilization pH value (default 0.02 pH) Type of Buffer used for AUTO CALIBRATION
(default is Standard, non-commercial buffers). The following commercial buffer tables are recognized by the analyzer:
Standard (NIST plus pH7)DIN 19267Ingold Merck
The following screen will appear to allow adjustment of these criteria:
S1: 1.234µS/cm 1.234ºC S2: 12.34pH 1.234ºC S3: 12.34µS/cm 1.234ºC
SN pH Cal Buffer Cal Standardize
Slope: 59.16mV/pH Offset: 600 mV
S1: 1.234µS/cm 1.234ºC S2: 12.34pH 1.234ºC S3: 12.34µS/cm 1.234ºC
SN Setup Stable Time: 10 sec Stable Delta: 0.02 pH Buffer: Standard
The following sub-sections show the initial display screen that appears for each calibration routine. Use the flow diagram for pH calibration at the end of Sec. 7 and the live screen prompts to complete calibration.
40
The following screen will appear if the auto cal is successful. The screen will return to the pH Buffer Cal Menu.
S1: 1.234µS/cm 1.234ºC S2: 12.34pH 1.234ºC S3: 12.34µS/cm 1.234ºC
SN pH Auto Cal Slope: 59.16 mV/pH Offset: 60 mV
1. A High Slope Error will generate this screen display:
S1: 1.234µS/cm 1.234ºC S2: 12.34pH 1.234ºC S3: 12.34µS/cm 1.234ºC
SN pH Auto Cal
High Slope Error
Calculated: 62.11 mV/pH
Max: 62.00 mV/pH Press EXIT
The following screens may appear if the auto cal is unsuccessful.
Page 49
MODEL 1057 SECTION 7.0
CALIBRATION
2. A Low Slope Error will generate this screen display:
3. An Offset Error will generate this screen display:
S1: 1.234µS/cm 1.234ºC S2: 12.34pH 1.234ºC S3: 12.34µS/cm 1.234ºC
SN pH Auto Cal Low Slope Error Calculated: 39.11mV/pH Min: 40.00 mV/pH Press EXIT
S1: 1.234µS/cm 1.234ºC S2: 12.34pH 1.234ºC S3: 12.34µS/cm 1.234ºC
SN pH Auto Cal Offset Error Calculated: 61.22mV Max: 60.00mV Press EXIT
7.2.3 MANUAL CALIBRATION — pH
New sensors must be calibrated before use. Regular recalibration is also necessary. Use manual calibration if non-standard buffers are being used; otherwise, use auto calibration. Auto calibration avoids common pitfalls and reduces errors. The adjacent appears after selecting Manual pH calibra-
tion.
S1: 1.234µS/cm 1.234ºC S2: 12.34pH 1.234ºC S3: 12.34µS/cm 1.234ºC
SN pH Manual Cal Buffer 1 Buffer 2
7.2.5 STANDARDIZATION — pH
The pH measured by the Model 1057 analyzer can be changed to match the reading from a second or referee instrument. The process of making the two readings agree is called standardization. During standardization, the difference between the two pH values is converted to the equivalent voltage. The voltage, called the reference offset, is added to all subsequent measured cell voltages before they are converted to pH. If a standardized sensor is placed in a buffer solution, the measured pH will differ from the buffer pH by an amount equivalent to the standardization offset.
S1: 1.234µS/cm 1.234ºC S2: 12.34pH 1.234ºC S3: 12.34µS/cm 1.234ºC
SN Enter Value
07.00pH
7.2.4 ENTERING A KNOWN SLOPE VALUE — pH
If the electrode slope is known from other measure­ments, it can be entered directly in the Model 1057 ana­lyzer. The slope must be entered as the slope at 25°C.
S1: 1.234µS/cm 1.234ºC S2: 12.34pH 1.234ºC S3: 12.34µS/cm 1.234ºC
SN pH Slope@25ºC
59.16 mV/pH
41
The following screen may appear if ORP Cal is unsuccessful.
An Offset Error will generate this screen display:
If the ORP Cal is successful, the screen will return to the Cal sub-menu.
S1: 1.234µS/cm 1.234ºC S2: 12.34pH 1.234ºC S3: 12.34µS/cm 1.234ºC
SN Standardize Offset Error Calculated: 96mV Max: 60mV Press EXIT
Page 50
MODEL 1057 SECTION 7.0
CALIBRATION
7.3 ORP CALIBRATION
7.3.1 DESCRIPTION
For process control, it is often important to make the measured ORP agree with the ORP of a standard solution. During calibration, the measured ORP is made equal to the ORP of a standard solution at a single point.
Measure Sec. Menu function: default
Description
ORP 7.3.2 Standardization — ORP
1 point buffer calibration with manual buffer value entry
To calibrate ORP:
1. Press the MENU button
2. Select Calibrate. Press ENTER.
3. Select Sensor 1 or Sensor 2 corresponding to ORP. Press ENTER.
4. Select ORP. Press ENTER.
The following screen will appear. To calibrate ORP or Temperature, scroll to the desired item and press ENTER.
S1: 1.234µS/cm 1.234ºC S2: 12.34pH 1.234ºC S3: 12.34µS/cm 1.234ºC
SN Calibrate?
ORP
Temperature
7.3.2 STANDARDIZATION — ORP
For process control, it is often important to make the measured ORP agree with the ORP of a standard solution. During calibration, the measured ORP is made equal to the ORP of a standard solution at a single point. This screen appears after selecting ORP calibra­tion:
If the ORP Cal is successful, the screen will return to the
Cal sub-menu.
The following screen may appear if ORP Cal is unsuccessful.
S1: 1.234µS/cm 1.234ºC S2: 12.34pH 1.234ºC S3: 12.34µS/cm 1.234ºC
SN Enter Value
+0600 mV
S1: 1.234µS/cm 1.234ºC S2: 12.34pH 1.234ºC S3: 12.34µS/cm 1.234ºC
SN Standardize Offset Error Calculated: 61.22mV Max: 60.00mV Press EXIT
THIS SECTION DESCRIBES HOW TO CALIBRATE THE MODEL 1057 WITH AN ORP SENSOR. THE FOL­LOWING CALIBRATION ROUTINE IS COVERED.
A detailed flow diagram is provided at the end of Sec. 7 to guide you through the calibration routines.
The following sub-sections show the initial display screen that appears for each calibration routine. Use the flow diagram for ORP calibration at the end of Sec. 7 and the live screen prompts to complete calibration.
TABLE 7-2 ORP Calibration Routine
42
Page 51
The following sub-sections show the initial display screen that appears for each calibration routine. Use the flow diagram for Conductivity calibration at the end of Sec. 7 and the live screen prompts for each rou­tine to complete calibration.
The adjacent screen appears after selecting
Conductivity calibration:
MODEL 1057 SECTION 7.0
CALIBRATION
To calibrate contacting conductivity:
1. Press the MENU button
2. Select Calibrate. Press ENTER.
3. Select Sensor 1 or Sensor 2 corresponding to contacting conductivity. Press ENTER.
4. Select Conductivity. Press ENTER.
The adjacent screen will appear. To calibrate Conductivity or Temperature, scroll to the desired item and press ENTER.
S1: 1.234µS/cm 1.234ºC S2: 12.34pH 1.234ºC S3: 12.34µS/cm 1.234ºC
SN Calibrate?
Conductivity
Temperature
S1: 1.234µS/cm 1.234ºC S2: 12.34pH 1.234ºC S3: 12.34µS/cm 1.234ºC
SN Calibration Zero Cal In Process Cal Meter Cal
Cell K: 1.00000/cm
7.4 CONTACTING CONDUCTIVITY CALIBRATION
7.4.1 DESCRIPTION
PLACING A NEW CONDUCTIVITY SENSOR IN SERVICE New conductivity sensors rarely need calibration. The cell constant printed on the label is sufficiently accurate for most applications. CALIBRATING AN IN-SERVICE CONDUCTIVITY SENSOR
1. After a conductivity sensor has been in service for a period of time, recalibration may be necessary. There are three ways to calibrate a sensor.
a. Use a standard instrument and sensor to measure the conductivity of the process stream. It is not necessary to remove the sensor from the process piping. The temperature correction used by the standard instrument may not exactly match the temperature correction used by the Model 1057. To avoid errors, turn off temperature correction in both the analyzer and the standard instrument.
b. Place the sensor in a solution of known conductivity and make the analyzer reading match the conductivity of the
standard solution. Use this method if the sensor can be easily removed from the process piping and a standard is available. Be careful using standard solutions having conductivity less than 100 µS/cm. Low conductivity standards are highly susceptible to atmospheric contamination. Avoid calibrating sensors with 0.01/cm cell constants against conductivity standards having conductivity greater than 100 µS/cm. The resistance of these solutions may be too low for an accurate measurement. Calibrate sensors with 0.01/cm cell constant using method c.
c. To calibrate a 0.01/cm sensor, check it against a standard instrument and 0.01/cm sensor while both sensors are measuring water having a conductivity between 5 and 10 µS/cm. To avoid drift caused by absorption of atmospheric carbon dioxide, saturate the sample with air before making the measurements. To ensure adequate flow past the sensor during calibration, take the sample downstream from the sensor. For best results, use a flow-through standard cell. If the process temperature is much different from ambient, keep connecting lines short and insulate the flow cell.
THIS SECTION DESCRIBES HOW TO CALIBRATE THE MODEL 1057 WITH AN ATTACHED CONTACTING CONDUCTIVITY SENSOR. THE FOLLOWING CALIBRATION ROUTINES ARE COVERED.
A detailed flow diagram is provided at the end of Sec. 7 to guide you through the calibration routines
Measure Sec. Menu function: default
Description
Contacting
Conductivity
7.4.2 Cell K: 1.00000/cm
Enter the cell Constant for the sensor
7.4.3 Zero Cal
Zero the analyzer with the sensor attached
7.4.4 In Process Cal
Standardize the sensor to a known conductivity
7.4.5
Meter Cal Calibrate the analyzer to a lab conductivity instrument
7.4.6
Cal Factor: 0.95000/cm Enter the Cal Factor for 4-Electrode sensors from the sensor tag
TABLE 7-3 Contacting Conductivity Calibration Routines
43
Page 52
MODEL 1057 SECTION 7.0
CALIBRATION
7.4.2 ENTERING THE CELL CONSTANT
New conductivity sensors rarely need calibration. The cell constant printed on the label is sufficiently accurate for most applications. The cell constant should be entered:
• When the unit is installed for the first time
• When the probe is replaced
The display screen for entering a cell Constant for the sensor is shown. The default value is displayed in bold
type.
7.4.3 ZEROING THE INSTRUMENT
This procedure is used to compensate for small offsets to the conductivity signal that are present even when there is no conductivity to be measured. This procedure is affected by the length of extension cable and should always be repeated if any changes in extension cable or sensor have been made. Electrically connect the
conductivity probe as it will actually be used and place the measuring portion of the probe in air. Be sure the probe is dry.
The adjacent screen will appear after selecting Zero Cal from the Conductivity Calibration screen:
The adjacent screen will appear if zero Cal is successful. The screen will return to the conductivity Cal Menu.
The adjacent screen may appear if zero Cal is unsuccessful.
S1: 1.234µS/cm 1.234ºC S2: 12.34pH 1.234ºC S3: 12.34µS/cm 1.234ºC
SN Cell Constant
1.00000 /cm
S1: 1.234µS/cm 1.234ºC S2: 12.34pH 1.234ºC S3: 12.34µS/cm
1.234ºC
SN Zero Cal In Air In Water
7.4.4 CALIBRATING THE SENSOR IN A CONDUCTIVITY STANDARD (IN PROCESS CAL)
This procedure is used to calibrate the sensor and analyzer against a solution of known conductivity. This is done by submerging the probe in the sample of known conductivity, then adjusting the displayed value, if necessary, to correspond to the conductivity value of the sample. Turn temperature correction off and use the conductivity of the standard. Use a calibrated ther­mometer to measure temperature. The probe must be cleaned before performing this procedure.
The adjacent screen will appear after selecting In Process Cal from the Conductivity Calibration screen:
S1: 1.234µS/cm 1.234ºC S2: 12.34pH 1.234ºC S3: 12.34µS/cm 1.234ºC
SN InProcess Cal Wait for stable reading.
S1: 1.234µS/cm 1.234ºC S2: 12.34pH 1.234ºC S3: 12.34µS/cm 1.234ºC
SN Zero Cal Sensor Zero Fail Offset too high
Press EXIT
S1: 1.234µS/cm 1.234ºC S2: 12.34pH 1.234ºC S3: 12.34µS/cm 1.234ºC
SN Zero Cal Sensor Zero Done
44
Page 53
MODEL 1057 SECTION 7.0
CALIBRATION
7.4.5 CALIBRATING THE SENSOR TO A LABORATORY INSTRUMENT (METER CAL)
This procedure is used to check and correct the conductivity reading of the Model 1057 using a laboratory conductivity instrument. This is done by submerging the conductivity probe in a bath and measuring the conduc­tivity of a grab sample of the same bath water with a separate laboratory instrument. The Model 1057 reading is then adjusted to match the conductivity reading of the lab instrument.
The adjacent screen will appear after selecting Meter Cal from the Conductivity Calibration screen:
S1: 1.234µS/cm 1.234ºC S2: 12.34pH 1.234ºC S3: 12.34µS/cm 1.234ºC
SN Meter Cal Use precision resistors only
The adjacent screen will appear if In Process Cal is suc­cessful. The screen will return to the conductivity Cal Menu.
The adjacent screen may appear if In Process Cal is unsuccessful. The screen will return to the conductivity Cal Men
S1: 1.234µS/cm 1.234ºC S2: 12.34pH 1.234ºC S3: 12.34µS/cm 1.234ºC
SN InProcess Cal Calibration Error
Press EXIT
S1: 1.234µS/cm 1.234ºC S2: 12.34pH 1.234ºC S3: 12.34µS/cm 1.234ºC
SN InProcess Cal Updated cell constant:
1.00135/cm
After pressing ENTER, the display shows the live value measured by the sensor
If the meter cal is successful the screen will return to the conductivity Cal Menu.
The adjacent screen will appear if Meter Cal is unsuccessful.
The screen will return to the conductivity Cal Menu.
S1: 1.234µS/cm 1.234ºC S2: 12.34pH 1.234ºC S3: 12.34µS/cm 1.234ºC
SN Meter Cal Calibration Error
Press EXIT
S1: 1.234µS/cm 1.234ºC S2: 12.34pH 1.234ºC S3: 12.34µS/cm 1.234ºC
SN Enter Value
xx.xx kΩ
7.4.6 Cal Factor
Upon initial installation and power up, if 4-electrode was selected for the sensor type in the Quick Start menus, the user enters a Cell Constant and a “Cal Factor” using the instrument keypad. The cell constant is needed to convert measured conductance to conduc­tivity as displayed on the analyzer screen. The “Cal Factor” entry is needed increase the accuracy of the live conductivity readings, especially at low conductivity readings below 20uS/cm. Both the Cell Constant and the “Cal Factor” are printed on the tag attached to the 4-electrode sensor/cable.
The display screen for entering Cal Factor is shown. The default value is displayed in bold type. If neces­sary after initial installation and start-up, enter the “Cal Factor” as printed on the sensor tag.
S1: 1.234µS/cm 1.234ºC S2: 12.34pH 1.234ºC S3: 12.34µS/cm 1.234ºC
SN Cal Factor
0.95000 /cm
45
Page 54
To calibrate temperature:
1. Press the MENU button
2. Select Calibrate. Press ENTER.
3. Select Sensor 1 or Sensor 2 corresponding to the desired measurement. Press ENTER.
4. Select Temperature. Press ENTER.
The adjacent screen will appear.
Measure Sec. Calibration function: default value
Description
Temperature 7.5.2 Calibrate
Enter a manual reference temperature for temperature compensation of the process measurement
A detailed flow diagram is provided at the end of Sec. 7 to guide you through the calibration routines.
S1: 1.234µS/cm 1.234ºC S2: 12.34pH 1.234ºC S3: 12.34µS/cm 1.234ºC
SN Calibrate
+025.0°C
The following sub-section provides you with the initial display screen that appears for temperature calibration. Use the flow diagram for Temp calibration at the end of Sec. 7 to complete calibration.
7.5.2 CALIBRATION
The adjacent screen will appear during Temperature Cal.
If the sensor Temperature offset is greater than 5 ºC from the default value, the following screen will appear:
You may continue by selecting Yes or suspend this operation by selecting No.
If the Temp Cal is successful, the screen will return to the Cal Menu.
Note: To select automatic or manual temp compensation or to program temperature units as °C or °F, refer to Sec. 5.3 – Programming Temperature in this manual
S1: 1.234µS/cm 1.234ºC S2: 12.34pH 1.234ºC S3: 12.34µS/cm 1.234ºC
SN Temp Offset > 5°C
Continue?
No
Yes
S1: 1.234µS/cm 1.234ºC S2: 12.34pH 1.234ºC S3: 12.34µS/cm 1.234ºC
SN Calibrate Cal in progress. Please wait.
TABLE 7- 11 Temperature Calibration Routine
MODEL 1057 SECTION 7.0
CALIBRATION
7.5 CALIBRATING TEMPERATURE
7.5.1 DESCRIPTION
Most liquid analytical measurements require temperature compensation (except ORP). The Model 1057 performs temperature compensation automatically by applying internal temperature correction algorithms. Temperature cor­rection can also be turned off. If temperature correction is off, the Model 1057 uses the manual temperature entered by the user in all temperature correction calculations.
THIS SECTION DESCRIBES HOW TO CALIBRATE TEMPERATURE IN THE MODEL 1057 ANALYZER. THE FOLLOWING CALIBRATION ROUTINE IS COVERED.
46
Page 55
47
MODEL 1057 SECTION 7.0
CALIBRATION
FIGURE 7-1 Calibrate pH
Page 56
MODEL 1057 SECTION 7.0
CALIBRATION
FIGURE 7-2 Calibrate ORP
48
Page 57
MODEL 1057 SECTION 7.0
CALIBRATION
FIGURE 7-3 Calibrate Contacting Conductivity
49
Page 58
FIGURE 7-4 Calibrate Temperature
MODEL 1057 SECTION 7.0
CALIBRATION
50
Page 59
SECTION 8.0
RETURN OF MATERIAL
8.1 GENERAL
To expedite the repair and return of instruments, proper communication between the customer and the factory is important. Before returning a product for repair, call 1-949-757-8500 for a Return Materials Authorization (RMA) number.
8.2 WARRANTY REPAIR
The following is the procedure for returning instruments still under warranty:
1. Call Rosemount Analytical for authorization.
2. To verify warranty, supply the factory sales order number or the original purchase order number. In the case of individual parts or sub-assemblies, the serial number on the unit must be supplied.
3. Carefully package the materials and enclose your “Letter of Transmittal” (see Warranty). If possible, pack the materials in the same manner as they were received.
4. Send the package prepaid to:
Rosemount Analytical Liquid Division 2400 Barranca Parkway Irvine, CA 92606
Attn: Factory Repair
RMA No. ____________
Mark the package: Returned for Repair
Model No. ____
8.3 NON-WARRANTY REPAIR
The following is the procedure for returning for repair instruments that are no longer under warranty:
1. Call Rosemount Analytical for authorization.
2. Supply the purchase order number, and make sure to provide the name and telephone number of the individ­ual to be contacted should additional information be needed.
3. Do Steps 3 and 4 of Section 17.2.
NOTE
Consult the factory for additional information regarding service or repair.
IMPORTANT
Please see second section of “Return of Materials Request” form. Compliance with the OSHA requirements is mandatory for the safety of all personnel. MSDS forms and a certification that the instruments have been disinfected or detoxified are required.
MODEL 1057 SECTION 8.0
RETURN OF MATERIAL
51
Page 60
WARRANTY
Seller warrants that the firmware will execute the programming instructions provided by Seller, and that the Goods manufactured or Services provided by Seller will be free from defects in materials or workmanship under normal use and care until the expiration of the applicable warranty period. Goods are warranted for twelve (12) months from the date of initial installation or eighteen (18) months from the date of shipment by Seller, whichever period expires first. Consumables, such as glass electrodes, mem-
branes, liquid junctions, electrolyte, o-rings, catalytic beads, etc., and Services are warranted for a period of 90 days from the date of shipment or provision.
Products purchased by Seller from a third party for resale to Buyer ("Resale Products") shall carry only the warranty extended by the original manufacturer. Buyer agrees that Seller has no liability for Resale Products beyond making a reasonable commercial effort to arrange for procurement and shipping of the Resale Products.
If Buyer discovers any warranty defects and notifies Seller thereof in writing during the applicable warranty period, Seller shall, at its option, promptly correct any errors that are found by Seller in the firmware or Services, or repair or replace F.O.B. point of man­ufacture that portion of the Goods or firmware found by Seller to be defective, or refund the purchase price of the defective portion of the Goods/Services.
All replacements or repairs necessitated by inadequate maintenance, normal wear and usage, unsuitable power sources, unsuit­able environmental conditions, accident, misuse, improper installation, modification, repair, storage or handling, or any other cause not the fault of Seller are not covered by this limited warranty, and shall be at Buyer's expense. Seller shall not be obligated to pay any costs or charges incurred by Buyer or any other party except as may be agreed upon in writing in advance by an authorized Seller representative. All costs of dismantling, reinstallation and freight and the time and expenses of Seller's person­nel for site travel and diagnosis under this warranty clause shall be borne by Buyer unless accepted in writing by Seller.
Goods repaired and parts replaced during the warranty period shall be in warranty for the remainder of the original warranty period or ninety (90) days, whichever is longer. This limited warranty is the only warranty made by Seller and can be amended only in a writing signed by an authorized representative of Seller. Except as otherwise expressly provided in the Agreement, THERE ARE NO REPRESENTATIONS OR WARRANTIES OF ANY KIND, EXPRESS OR IMPLIED, AS TO MERCHANTABILITY, FITNESS FOR PARTICULAR PURPOSE, OR ANY OTHER MATTER WITH RESPECT TO ANY OF THE GOODS OR SERVICES.
RETURN OF MATERIAL
Material returned for repair, whether in or out of warranty, should be shipped prepaid to:
Emerson Process Management
Liquid Division
2400 Barranca Parkway
Irvine, CA 92606
The shipping container should be marked:
Return for Repair Model
_______________________________
The returned material should be accompanied by a letter of transmittal which should include the following information (make a copy of the "Return of Materials Request" found on the last page of the Manual and provide the following thereon):
1. Location type of service, and length of time of service of the device.
2. Description of the faulty operation of the device and the circumstances of the failure.
3. Name and telephone number of the person to contact if there are questions about the returned material.
4. Statement as to whether warranty or non-warranty service is requested.
5. Complete shipping instructions for return of the material.
Adherence to these procedures will expedite handling of the returned material and will prevent unnecessary additional charges for inspection and testing to determine the problem with the device.
If the material is returned for out-of-warranty repairs, a purchase order for repairs should be enclosed.
Page 61
53
ORDERING INFORMATION
The Model 1057 multi-parameter analyzer supports up to three sensor inputs of pH/ORP and contacting conduc­tivity measurements in any combination thus reducing the cost per loop and saving panel space. All configura­tions of the analyzer include four 4-20mA current outputs and four fully programmable alarm relays with interval timers. The instrument supports most industrial, commercial, and municipal applications and is ideal for OEMs, systems integrators and customers requiring multiple inputs and outputs. All Model 1057 units also include­electrically isolated inputs, 8 local languages, removable connectors for easy wiring, 4 solid plugs for closure of openings, and panel mount hardware. All configurations of Model 1057 can be ordered to meet UL approval requirements. Model 1057 is Class I, Div 2 approved for hazardous area installations by CSA.
ACCESSORIES
PART # DESCRIPTION
23554-00
Cable Gland Kit - Qty 5 per pack
23820-00
2" Pipe Mounting Bracket includes U-bolts, mounting bracket, nuts, washers, and screws (complete). Also accommodates wall / surface mounting.
23820-01
2" Pipe Mounting Bracket, Stainless Steel
9240048-00 S.S. Tag (specify marking)
Model 1057 Three-Input Intelligent Analyzer
CODE Power
02 24 VDC with four alarm relays 03 84-265 VAC switching, 50/60 Hz with four alarm relays
CODE MEASUREMENT 1
20 Contacting Conductivity 22 pH/ORP/ISE
CODE MEASUREMENT 2
30 Contacting Conductivity 32 pH/ORP/ISE 38 None (not available if -40 or -42 are selected)
CODE MEASUREMENT 3
40 Contacting Conductivity 42 pH/ORP/ISE 48 None
CODE UL OPTION
No Selection
UL UL Approval
Page 62
Credit Cards for U.S. Purchases Only.
The right people, the right answers, right now.
ON-LINE ORDERING NOW AVAILABLE ON OUR WEB SITE
http://www.raihome.com
Emerson Process Management
Rosemount Analytical Inc.
2400 Barranca Parkway Irvine, CA 92606 USA Tel: (949) 757-8500 Fax: (949) 474-7250
http://www.raihome.com
© Rosemount Analytical Inc. 2009
Loading...