This manual contains important instructions that should be followed during installation and maintenance of the UPS.
• Intended for installation in a temperature-controlled, indoor area free of conductive
contaminants.
• Maximum ambient temperature 104°F (40°C).
Read this manual thoroughly before attempting to install or operate this UPS.
The equipment can be installed and operated by individuals without previous training.
Size of Branch Circuit Overcurrent Protection
CAUTION
!
To reduce the risk of fire, connect PS3000RT3-120XR models only to a circuit provided with
30 amperes maximum branch circuit overcurrent protection in accordance with the National
Electric Code, ANSI/NFPA 70. Other Liebert PSI models must be connected to a circuit with
20 amperes maximum branch circuit overcurrent protection.
WARNING
!
Operate the UPS only from a properly grounded (earthed) 110-127VAC, 50Hz or 60Hz AC
supply.
Some components are live, even when AC power is disconnected. For service, contact a
properly trained and qualified technician. Do not remove the cover; the UPS has no
user-serviceable parts inside except the internal battery pack.
WARNING
!
Although the UPS has been designed and manufactured to ensure personal safety, improper
use can result in electrical shock or fire. To ensure safety, observe the following rules:
• Turn Off and unplug the UPS before cleaning it. Clean the UPS with a dry cloth. Do not use
liquid or aerosol cleaners.
• Do not install or operate the UPS in or near water.
• Never block or insert any objects into the ventilation holes or other openings of the UPS.
Keep all vents free of dust accumulation that could restrict air flow.
• Do not place UPS power cord anywhere it might be damaged.
Battery Handling Precautions
WARNING
!
Batteries should be replaced only by properly trained and qualified personnel knowledgeable
of batteries and required precautions.
A battery can present a risk of electrical shock and high short-circuit current. The following
precautions must be observed when working on batteries:
• Remove watches, rings and other metal objects.
• Use tools with insulated handles.
• Do not dispose of the battery or batteries in a fire. The battery may explode.
• Do not open or mutilate the battery or batteries. Released electrolyte is toxic. It may cause
injury to the skin and eyes.
• When replacing the battery, use the same type of battery as is listed in Table 5.
• Handle, transport and recycle batteries in accordance with local regulations.
1
CONDITIONS OF USE—The input supply outlet must be within 6 ft. (1.8m) of the UPS and be easily accessed.
This UPS provides conditioned power to connected equipment. It is not intended for use with life-support and other designated “critical” devices. Maximum load must not exceed that shown on the UPS
rating label. If uncertain, consult your local dealer, local Emerson Network Power representative or
Channel Support Applications.
When installing the UPS or making input and output connections, comply with all relevant safety
codes and standards (e.g., UL 1778).
Placing magnetic storage media on top of the UPS may result in data corruption.
ELECTROMAGNETIC COMPATIBILITY—The Liebert PSI XR complies with part 15 of the FCC
Rules. Operation is subject to the following two conditions:
• This device may not cause harmful interference, and
• This device must accept any interference received, including interference that may cause undesired operation.
This equipment uses, generates and can radiate radio frequency energy and, if not installed and used
in accordance with the instructions, may cause harmful interference with radio communications.
However, there is no guarantee that interference will not occur in a particular installation. If this
equipment does cause harmful interference to radio or television reception, the user is encouraged to
try to correct the interference by one or more of the following measures:
• Reorient or relocate the receiving antenna.
• Increase the separation between the UPS and the receiver.
• Connect the UPS to an outlet on a circuit different from the one the receiver is connected to.
NOTICE
Do not connect equipment that could overload the UPS or demand half-wave rectification
from the UPS, such as electric drills, vacuum cleaners, laserjet printers and hair dryers.
2
GLOSSARYOF SYMBOLS
Risk of electrical shock
!
Indicates caution followed by important instructions
Indicates the unit contains a valve-regulated, lead-acid battery
Recycle
DC voltage
Equipment grounding conductor
Bonded to ground
AC voltage
ON/Alarm Silence/Manual Self-Diagnostic Test
OFF
Status Change Button
3
1.0INTRODUCTION
The Liebert PSI™ XR is a 2U, line-interactive UPS that may be installed in a rack or used as a tower
UPS.
Status indicators on the front of the Liebert PSI XR display load level, battery level, buck/boost, sitewiring fault, overload, battery status and UPS operation. Controls include a combination On/Alarm
Silence/Manual Self-Diagnostic Test button, an Off button and a Status Change button.
The Liebert PSI XR has USB, DB-9 (contact closure) and Liebert IntelliSlot
USB ports provide detailed operating information including voltages, currents, and alarm status to
the host system when used in conjunction with Liebert MultiLink
The Liebert PSI XR is compliant with the Restriction of Hazardous Substances Directive (ROHS),
prohibiting use of six hazardous materials manufacturing of electronics, including lead-free solder.
Figure 1Front view of UPS
Liebert PSI XR
rack-mount configuration
Display rotates for use as tower
™
software.
Introduction
®
ports. The DB-9 and
Figure 21000 and 1500—rear view
Liebert
IntelliSlot
Port
USB
Port
EPO
DB-9 Port
(Contact
Closure)
EPO
FUNCTION
VOLTAGE=110V
VOLTAGE=120V
VOLTAGE=127V
2 1
tower configuration
Display rotates for use in rack
Input Circuit Breaker
(12A for 1000VA;
15A for 1500VA)
Liebert PSI XR
Output Circuit Breaker
(8A for 1000VA;
15A for 1500VA)
OUTPUTINPUT
DC 24V
Receptacles
NEMA 5-15R
Voltage Configuration
DIP Switch
Network Surge
Protection
External Battery
Cabinet Connector
4
Power Cord; 5-15P
(not shown for clarity)
Figure 32200—rear view
Introduction
DB-9 Port
(Contact
Closure)
EPO
Power Cord; 5-20P
(not shown for clarity)
Liebert
IntelliSlot
Port
EPO
FUNCTION
2 1
VOLTAGE=110V
VOLTAGE=120V
VOLTAGE=127V
USB Port
Voltage Configuration
DIP Switch
Network Surge
Protection
15A Output Circuit Breaker
for Receptacles #3 & #4
Receptacles #1 and #2;
30A Input
NEMA 5-20R T-Slot
Circuit Breaker
DC 48V
External Battery
Cabinet Connector
20A Input Circuit Breaker
Receptacles #1 and #2
Receptacles #3 and #4
NEMA 5-15R
Receptacles
#5 and #6
NEMA 5-15R
INPUT
OUTPUT
15A Output Circuit Breaker
for Receptacles #5 & #6
Figure 43000—rear view
Power Cord; L5-30P
(not shown for clarity)
Liebert
IntelliSlot
Port
DB-9 Port
(Contact
Closure)
EPO
FUNCTION
2 1
VOLTAGE=110V
VOLTAGE=120V
VOLTAGE=127V
EPO
USB Port
Voltage Configuration
DIP Switch
NEMA L5-30R
Receptacle
Network Surge
Protection
15A Output Circuit Breaker
for Receptacles #3 & #4
Receptacles #1 and #2;
30A Input
NEMA 5-20R T-Slot
Circuit Breaker
INPUT
DC 48V
External Battery
Cabinet Connector
20A Output Circuit Breaker
Receptacles #1 and #2
Receptacles #3 and #4
NEMA 5-15R
Receptacles
#5 and #6
NEMA 5-15R
OUTPUT
15A Output Circuit Breaker
for Receptacles #5 & #6
5
2.0WHAT’S INCLUDED
The Liebert PSI XR is shipped with the following items:
• Multi-Language User Manual on CD
• Liebert MultiLink Software and User Manual, downloadable at multilink.liebert.com
• Contact Closure (ML9P9S) Cable
• USB Cable
• Tower Stands
• Mounting Hardware
• Rack-Mount Handles
• Fixed Mounting Rails
•EPO Connector
• Battery-UPS Tab
Figure 5Accessories
What’s Included
Tow e r Sta n ds
Contact Closure
(ML9P9S) Cable
6 ft (1.8m)
USB cable
6 ft (1.8m)
Fixed
Mounting Rails
Mounting Hardware
(Screws and Washers)
Battery-UPS Tab
Rack-Mount
Handles
EPO
Connector
6
Loading...
+ 22 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.