Replication, distribution and / or editing of this document and the use and distribution of its content is
prohibited unless explicitly permitted. Violation obligates compensation for damages.
All rights reserved in case of the issue of a patent, utility patent or design patent.
In these instructions the following technical terms with the specified meaning are used:
Designation: Definition:
Vacuum pump
Compressor
Machine
Pump-motor unit
Machine set
Driving side;
D side
Non-driving side;
N side
Inlet pressure
Machine for generating a vacuum.
Machine for generating a gauge pressure.
Here: Vacuum pump or compressor.
Unit for extracting, transporting and compressing gases and/or vapors, as well as
for generating vacuum and gauge pressure. Here the drive is not considered part
of the machine.
Unit consisting of a machine and a drive motor.
Two or more machines that are interconnected with couplings and mounted on a
common base frame.
Side of the machine on which the drive is connected.
Side of the machine on which no drive is connected.
Pressure of the pumped gases/vapors on the inlet connection of the machine.
Discharge pressure;
Compression pressure
Pressure of the pumped gases/vapors at the discharge connection of the machine.
Test pressure
Pressure to which the machine is subjected when testing for leaks.
Qualified personnel Persons who, based on their training, experience and instruction, as well as their
knowledge of the pertinent standards, regulations, accident protection regulations
and operating conditions, are capable of carrying out certain tasks (e.g. start-up,
operation, maintenance, repair) and can recognize and avoid possible dangers in
the process. The required knowledge includes a knowledge of first aid and of the
on-site emergency equipment.
These persons must be authorized by the person responsible for system safety to
perform the required tasks.
To point out dangers and important
information, the following signal words and
symbols are used in these operating
instructions:
2.1.1 Safety alert symbol
The safety alert symbol is
located in the safety precautions
in the highlighted heading field
on the left next to the signal word
(DANGER, WARNING,
CAUTION).
Safety precautions with a safety
alert symbol indicate a danger of
injuries.
Be sure to follow these safety
precautions to protect against
injuries or death!
2.1.2 Signal words
DANGER
WARNING
CAUTION
NOTICE
NOTE
Safety precautions without a
safety alert symbol indicate a
danger of damage.
The signal words are located in
the safety precautions in the
highlighted heading field.
They follow a certain hierarchy
and indicate
(in conjunction with the safety
alert symbol, see Chapter 2.1.1)
the seriousness of the danger
and the type of warning.
See the following explanations:
DANGER
Safety
WARNING
Danger of injuries.
Indicates a potentially hazardous
situation,
that could result in death or serious injury
if the corresponding measures
are not taken.
CAUTION
Danger of injuries.
Indicates a potentially hazardous
situation,
that may result in minor or moderate injury
if the corresponding measures
are not taken.
CAUTION
Danger of damage.
Indicates a potentially hazardous
situation
that may result in property damage
if the corresponding measures
are not taken.
NOTICE
Indicates a possible
disadvantage,
i.e. undesirable conditions or
consequences can occur
if the corresponding measures
are not taken.
NOTE
Danger of injuries.
Indicates an imminently
hazardous situation,
that will result in death or serious injury
if the corresponding measures
Indicates a possible advantage
if the corresponding measures
are taken;
tip.
Improper use of the unit can
result in serious
or even fatal injuries!
These operating instructions
must have been read
completely and understood
before beginning any work
with or at the pump-motor
When working on the unit,
there is a danger of injury,
e.g. in the form of cuts/cutting
off, crushing and burns!
During transport/handling as well
as assembly and disassembly
always wear personal protective
equipment (safety helmet,
protective gloves, safety boots)!
unit,
must be strictly observed,
must be available at the
operating location of the
pump-motor unit.
WARNING
WARNING
Hair and clothing can be pulled
Improper use of the unit can
result in serious
or even fatal injuries!
Only operate the pump-motor
into the unit or caught and
wound up
moving parts!
Do not wear long, loose hair or
wide, loose clothes!
unit
for the purposes indicated
under "Intended Use"!
with the fluids indicated under
Use a hair net!
DANGER
'Intended Use'!
with the values indicated
under 'Technical Data'!
WARNING
Electrical danger!
Before beginning work on the
unit or system, the following
measures must be carried out:
Deenergize.
Improper use of the unit can
result in serious
or even fatal injuries!
Transport and handling as well
as assembly and disassembly of
the unit may be carried out by
trained and responsible
personnel only!
Secure against being
switched on again.
Determine whether
deenergized.
Ground and short-circuit.
Cover or block off adjacent
pumps/compressors of the L-BV7 series,
types 2BV7 060, 2BV7 061, 2BV7 070 and
2BV7 071,
contains instructions bearing on transport
and handling, installation, commissioning,
operation, shut-down, storage, servicing
and disposal of the L-BV7,
must be completely read and understood by
all operating and servicing personnel before
beginning to work with or on the L-BV7,
must be strictly observed,
must be available at the site of operation of
the L-BV7.
About the operating and servicing personnel of
the L-BV7:
These persons must be trained and
authorized for the work to be carried out.
Work on electrical installations may be
carried out by trained and authorized
electricians only.
If necessary, the training/instruction on
using the L-BV7 can be carried out by the
manufacturer/suppler on order of the
owner.
The L-BV7
are pump-motor units for generating
vacuum or gauge pressure.
are used to extract, transport and compress
the following
pumped gases/vapors:
– all dry and humid gases,
which are not explosive or flammable,
– preferably air or air/vapor mixtures.
– In case of corrosive or toxic
gases/vapors contact service.
are designed for operation with the
following
operating liquids:
– Water
with a pH of 6 to 9,
free of solid materials (such as sand).
– If the pH values or operating liquids
differ, it is necessary to contact service.
are intended for industrial applications.
are designed for continuous operation.
When operating the L-BV7, the limits listed in
Chapter 4, "Technical Data", Pg. 13 ff. must
always be complied with.
Foreseeable Misuse
It is prohibited
to use the L-BV7 in applications other than
industrial applications
unless the necessary protection is provided
on the system,
e.g. guards suitable for children's fingers,
to use the device in rooms in which
explosive gases can occur if the L-BV7 is
not expressly intended for this purpose;
to extract, to deliver and to compress
explosive, flammable, corrosive or toxic
fluids
unless the L-BV7 is specifically designed
for this purpose,
to operate the L-BV7 with values other than
those specified in Chapter 4, "Technical
Data", Pg. 13 ff.
Any unauthorized modifications of the L-BV7
are prohibited for safety reasons.
any maintenance and repair work, such as
replacing worn or defective components, may
only be carried out by companies authorized
by the manufacturer (please contact service).
Measuring-surface sound pressure level as per
EN ISO 3744, measured at distance of 1 m
[3.28 ft] with medium throttling (100 mbar abs.
[1.45 psia]) and connected lines, tolerance 3
dB (A).
Type
2BV7 060 70
2BV7 061 70
2BV7 070 72
2BV7 071
Limit speeds for supply by converter
Type n [rpm]
2BV706 4,800
2BV707 4,000
4.2 Electrical data
See drive motor rating plate.
Minimum distance from
fan guard to adjacent surface
[mm] [inches]
1-m measuring-surface sound
pressure level L [dB (A)]
at 50 Hz: at 60 Hz:
70
76
Pressures
Min. inlet
pressure:
Dependent on the operating
liquid temperature
(see Fig. 2, Pg. 17)
When this temperature is
dropped below, the hose of
the liquid separator
(accessory) must be
connected to the connection
for cavitation protection
(Fig. 7, Pg. 25, Item 4).
Max.
1.1 bar abs. [16.0 psia]
discharge
pressure
during
vacuum-pump
operation:
8 bar abs. [116 psia] Max.
permissible
pressure in
pump-motor
unit:
If higher pressures can occur
in the system, then
corresponding protective
devices must be provided.
Max. discharge pressure p
compressor operation (at inlet pressure p
The minimum permissible inlet pressure of the pump-motor unit is dependent on the temperature of the operating
liquid.
During operation without cavitation protection, the minimum inlet pressure must be set above the shaded area.
Nominal operating-liquid flow rate
(with dry air extraction and with water at 15°C
[59 °F] as operating liquid)
Fig. 3: Design and operation of liquid-ring
vacuum pumps/compressors (cross-section of
operating chamber)
1 Discharge connection
2 Operating-liquid port
3 Inlet connection
4 Impeller
5 Housing
6 Discharge port
7 Inlet port
8 Operating liquid
6
8
7
5.1 Design
The L-BV7 2BV7s are liquid-ring vacuum
pumps compressors. They consist of the
vacuum pump/the compressor itself and an
electric motor. For the detailed design, see
Fig. 3, Pg. 18.
The pumped gases/vapors are sucked via the
inlet connection (3) into the pump-motor unit
and pushed out via the discharge connection
(1).
The impeller (4) with the blades is located in
the cylindrical housing (5). The impeller is
arranged eccentrically relative to the housing.
In addition, the housing also contains the
operating liquid (8). This liquid is fed in via the
operating-liquid port (2) and output together
with the pumped gases/vapors via the
discharge connection (1).
5.2 Operating method
When the impeller turns, the operating liquid is
put into motion and accelerated. This forms a
liquid ring that also rotates. Due to centrifugal
force, this ring is arranged concentrically to the
housing and eccentrically to the impeller.
During a complete rotation of the impeller, the
following occurs:
The impeller cells are completely filled with
operating liquid at the upper vertex.
During the first half rotation, the liquid ring
lifts off the impeller hub. The space in the
cells increases so that the pumped
gases/vapors are sucked in through the
inlet port (7).
The space in the cells is largest at the lower
vertex, as these are virtually free of
operating liquid.
During the second half rotation, the liquid
ring approaches the hub again. The space
in the cells decreases so that the pumped
gases/vapors are compressed and pushed
out through the discharge port (6).
The pump-motor unit can function in several
different operating modes.
These differ in how the pump-motor unit is
supplied with operating liquid:
Self-priming operation
Operation with operating-liquid feed:
– Non-automatic operation
– Automatic operation
5.3.1 Self-priming operation
In this operating mode the pump-motor unit
automatically sucks in the operating liquid.
The operating-liquid flow rate is automatically
adjusted.
See Fig. 8, Pg. 30.
5.3.2 Operation with operating-liquid feed
In this operating mode the pump-motor unit
DOES NOT automatically suck in the operating
liquid.
A certain volume flow ("nominal operatingliquid flow rate") or pre-pressure must be set
for the operating liquid.
Description of Vacuum Pump/Compressor
Here the following additional distinctions are
made:
Non-automatic operation
In this case the operating liquid feed is
switched on and off manually with a stop valve.
See Fig. 11, Pg. 32.
Automatic operation
In this case the operating liquid feed is
switched on and off by a solenoid valve. The
solenoid valve is dependent on the motor
operating mode:
Motor/pump-motor unit switched on:
Valve open.
Motor/pump-motor unit switched off:
Valve closed.
See Fig. 12, Pg. 32.
NOTICE
The following is dependent on
the operating mode:
when and how the pump-
motor unit must be filled with
operating liquid the first time,
how the pump-motor unit is
put into operation.
The specifications for this are
contained in Chapter 7,
"Installation", Pg. 22ff., and
Chapter 8, "Commissioning",
Pg. 28ff.
Prior to transport and handling
make sure that all components
are securely assembled and
secure or remove all components
the fasteners of which have been
loosened!
CAUTION
Tipping or falling can lead to
crushing, broken bones etc.!
Sharp edges can cause cuts!
Wear personal safety equipment
(protective helmet, protective
gloves, safety shoes) during
transport!
Packing:
On delivery the pump-motor unit is bolted to a
pallet and covered with a cardboard box.
To unpack, remove the cardboard box and
unscrew the securing bolts on the feet of the
pump-motor unit.
Manual handling:
WARNING
Danger from lifting heavy
loads!
Manual handling of the unit is
only permitted within the
following limits:
max. 30 kg [max. 66 lbs]
for men
max. 10 kg [max. 22 lbs]
for women
max. 5 kg [max. 11 lbs]
for pregnant women
For the weight of the pump-motor
unit, see Chapter 4.1,
"Mechanical data",
Section "Weight", Pg. 16.
For weights above the given
values use suitable lifting
appliances and handling
equipment!
Handling by means of lifting equipment:
WARNING
Danger from tipping or falling
loads!
When transporting with lifting
equipment, observe the following
basic rules:
The lifting capacity of lifting
equipment and lifting gear
must be at least equal to the
unit's weight.
For the weight of the pumpmotor unit, see Chapter 4.1,
"Mechanical data",
Section "Weight", Pg. 16.
Transport and handling by means of a crane
and strap belts is advisable.
Transport and Handling
Attach the strap belts as shown in Fig. 4,
Pg. 21:
Use two strap belts, of which one is routed
under the vacuum pump/compressor
housing, and one under the fan guard.
The strap belts should be seated securely
in the undercuts so that the unit cannot slip
out.
The belts must be sufficiently long (spread
angle smaller than 90°).
Make sure that no damage is caused to any
attached fittings.
WARNING
Danger from tipping loads!
Be sure to observe the routing of
the strap belts as shown in
Fig. 4, S. 21, even if the motor is
provided with attachment points
such as transport eyes or eye
bolts.
Fig. 4: Attachment points
These are solely designed for the
separate transport of the motor,
however not for the different
weight distribution that results for
the mounted vacuum
pump/mounted compressor, so
that the unit could tip!
In the unmounted state, the unit
can easily tip due to its weight
distribution!
Wear gloves and safety shoes!
Handle the unit with the
appropriate care!
CAUTION
Danger of damage to the
pump-motor unit due to
overheating!
When installing the unit, make
sure that heat dissipation and
cooling are not obstructed. The
minimum distances specified in
Chapter 4.1, "Mechanical data",
Section "Minimum distances for
heat dissipation", Pg. 16 must be
complied with.
Discharge air of other units may
Danger of tripping and falling!
Make sure the unit does not
present a danger of tripping!
WARNING
For the space requirement and arrangement of
the holes for installing and securing the pumpmotor unit, please see Fig. 1, Pg. 13.
For minimum clearances for heat dissipation
not be directly sucked in again!
and cooling, see Chapter 4.1, "Mechanical
Electrical danger!
The pump-motor unit must be
installed so that the electrical
device cannot be damaged by
external influences!
data", Section "Minimum distances for heat
dissipation", Pg. 16.
The pump-motor unit must be installed as
follows:
In particular, the feed pipes must
be securely routed, e.g. in cable
ducts or in the floor.
CAUTION
Danger of injuries from flying
parts!
Select installation so that parts
that are thrown out through the
grate if the external fan breaks
cannot hit persons!
on level surfaces,
with shaft in horizontal position,
on stationary (fixed) surfaces or structures,
at a maximum height of 1000 m [3280 ft]
above sea level.
Observe the following when installing the
pump-motor unit:
The load bearing capacity of the base
plate or the foundation must be designed
for at least the weight of the unit.
The vibration behavior at the operating
location must be taken into account.
The total vibrations of the unit are
dependent on the following factors:
– the characteristic vibrations of the unit,
– the alignment and installation,
– the condition (vibration behavior) of the
load-bearing surface,
– the influences by vibrations of other
parts and system components (external
vibrations).
The maximum permissible value for
vibrations is v
service life of the unit, this value may not be
exceeded.
Generally, this value can be adhered to
without a special foundation or a special
base plate.
The points on the unit for measuring the
vibration speed are shown in Fig. 5, Pg. 23.
Installation
Bolt the feet of the unit to the supporting
surface with suitable securing elements, as
shown in Fig. 6, Pg. 23.
Fig. 5: Points for measuring the vibration
speed
Different installation, e.g. with the shaft in the
vertical position, requires consultation with
service.
Fig. 6: Securing elements for bolting feet to
supporting surface
Terminal box cover and cable
entries must be tightly closed so
as to make them dustproof and
waterproof.
Check for tightness at regular
intervals.
For motor overload protection:
Use motor circuit breakers.
Set the motor circuit breakers to the
nominal current specified on the rating
plate.
For supply by converter:
High-frequency current and voltage
harmonics in the motor supply cables can
lead to emitted electromagnetic
interference.
Use shielded supply cables,
whereby the shield must be installed on
both sides.
Limit speed:
see Chapter 4.2, "Electrical data", Pg. 16.
CAUTION
If the unit is run dry, the
mechanical seal will be
destroyed in a matter of seconds!
DO NOT switch on as long as the
unit is not filled with operating
liquid!
Fig. 7: Pipe/hose connection of vacuum
pump/compressor
1 Operating-liquid port G ¼"
2 Discharge connection
3 Inlet connection
4 Connection for cavitation protection G ¼"
5 Drain opening G ¼"
To prevent foreign bodies from entering the
unit, all connections are sealed off when
delivered.
Do not remove the sealing plugs until
immediately before connecting the
pipes/hoses.
For the arrangement of the pipe/hose
connection, see Fig. 7, Pg. 25.
The pumped gases/vapors are sucked in via
the inlet connection
(see Chapter 7.3.1,
Pg. 26) and discharged via the discharge
connection (see Chapter 7.3.2, Pg. 26).
For operation the unit must be continuously
supplied with operating liquid.
This is fed in via the operating-liquid port
(see
Chapter 7.3.3, Pg. 26) and discharged
together with the pumped gases/vapors
through the discharge connection
When and how the pump-motor unit must be
filled with operating liquid the first time is
dependent on the operating mode:
For self-priming operation:
During installation.
For operation with operating-liquid feed:
After completing installation.
For self-priming operation you now pour
operating liquid into the working space of the
pump-motor unit before you connect the
pipes/hoses to the unit.
To do this, pour operating liquid into the open
inlet connection, discharge connection or
operating-liquid port.
For proper filling quantities, see Chapter 4.3,
"Operating conditions", Section "Operatingliquid filling amount for priming", Pg. 17.
Then attach the pipes/hoses to the unit as
described in the following.
WARNING
Danger due to gauge pressure
and vacuum!
Danger due to escaping fluid!
During operation, connected
pipes and vessels are
pressurized or vacuumized!
Make sure that all connections
are sufficiently tight! Use only
pipes and vessels of sufficient
strength!
NOTICE
Attach pipes/hoses free of
mechanical tensions.
The inlet connection (Fig. 7, Pg. 25, Item 3) is
marked with an arrow pointing downward (↓).
Connect the inlet pipe here. The pumped
gases/vapors are sucked in via this.
CAUTION
The tightening torque for pipe
connections on intake and
discharge connections may not
exceed 100 Nm [73.8 ft lbs]!
7.3.2 Discharge connection
The discharge connection (Fig. 7, Pg. 25,
Item 2) is marked with an arrow pointing
upward (↑).
Connect the discharge pipe here. Both the
pumped gases/vapors and the operating liquid
are discharged via this pipe.
CAUTION
The tightening torque for pipe
connections on intake and
discharge connections may not
exceed 100 Nm [73.8 ft lbs]!
7.3.3 Operating-liquid port
The operating-liquid port (Fig. 7, Pg. 25,
Item 1) is located between the discharge and
inlet connection.
Connect the feed pipe for the operating liquid
here.
In case of operating liquid with a high lime content:
Soften operating liquid
OR
Decalcify pump-motor unit
regularly (see Chapter 11.1,
"Maintenance", Pg. 36).
To prevent installation residues
(e.g. welding spatter) from
entering the unit,
a start-up screen should be
installed in the inlet pipe for the
first 100 operating hours.
7.4 Accessories
NOTICE
NOTICE
NOTICE
The following accessories are available
according to our catalogue:
Liquid separator
Non-return valve
Connecting and counter flange
Gas ejector.
Danger due to escaping fluid!
Danger due to rotating parts!
The pump-motor unit may only
be put into operation when the
following conditions are met:
Fan guard and vacuum
pump/compressor housing
8.1 Preparation and start-up
CAUTION
If the pumped gases/vapors
discharged on the pressure side
are passed on,
then it must be ensured that the
maximum discharge pressure of
1.1 bar abs. [16.0 psia] is not
exceeded!
NOTICE
are mounted.
The lines to the discharge
connection, inlet connection
and operating-liquid port are
attached.
The lines and connections
have been tested for strength
and leaks.
CAUTION
If a shut-off device is installed in the discharge
pipe:
Make sure that the unit CANNOT be operated
Maximum permissible quantity of
water entrained via the inlet
connection:
See Fig. 13, Pg. 32.
with the shut-off device closed.
If the unit is run dry, the
mechanical seal will be
destroyed in a matter of seconds!
DO NOT switch on as long as the
unit is not filled with operating
liquid!
Fill with operating liquid:
When and how the pump-motor unit must be
filled with operating liquid the first time is
dependent on the operating mode:
For self-priming operation:
During installation.
For operation with operating-liquid feed:
After completing installation.
For operation with operating-liquid feed,
you now fill the working area of the unit with
operating liquid.
To do this, open the respective stop valve for
approx. 20 sec.:
For non-automatic operation:
Stop valve (Fig. 11, Pg. 32, Item 4).
For automatic operation:
Stop valve in the bypass pipe (Fig. 12,
Pg. 32, Item 4a).
Then proceed with commissioning as
described in the following.
new pump-motor units,
pump-motor unit that are already installed
in a system and were prepared for a longer
standstill, as described in Chapter 10.2,
"Preparing for longer standstill", Pg. 34.
To prevent standstill damage during storage,
the environment must provide the following
conditions:
dry,
dust-free,
low-vibration (effective value of vibration
speed v
≤ 0.2 mm/s [0.008"/sec]).
eff
Take the following measures for
commissioning following a longer
standstill:
Measure the insulation resistance of the
motor.
In case of values ≤ 1kΩ per volt of nominal
voltage, dry winding.
Drain off preservative, as described in
Chapter 10.1, "Draining", Pg. 34.
Subsequent cleaning of the pump-motor
unit is not required.
Dispose of preservative in accordance with
the manufacturer's specifications.
For new pump-motor units:
Install pump-motor unit as described in
Chapter 7, "Installation", Pg. 22.
Commission the pump-motor unit as
described in Chapter 8, "Commissioning",
Pg. 28.
For pump-motor unit that are already
installed in a system:
Commission the pump-motor unit as
described in Chapter 8, "Commissioning",
Pg. 28.
Shut-Down and Longer Standstills
DANGER
Electrical danger!
Work on electrical installations
may be carried out by trained
and authorized electricians only!
However, if dirt or solid matter (e.g. sand) or
lime deposits get into the unit through the
operating liquid and/or the pumped
gases/vapors, then it is necessary to clean the
unit at regular intervals to prevent the impeller
from jamming up and to avoid wearing of the
impeller and the vacuum pump/compressor
housing.
WARNING
Refer to the following table:
Danger from rotating impeller
of unit!
Do not remove the vacuum
pump/compressor housing until
after the unit has been shut down
and the impeller has come to a
complete stop!
Fine-grain dirt (e.g. sand) get
into the vacuum
pump/compressor with the
operating liquid or pumped
gases/vapors.
Impeller is jammed.
Clean the motor cooling fins at regular intervals.
Install a liquid separator, filter or screen in the feed pipe.
OR
Regularly dismantle and clean the vacuum pump/compressor housing as
follows:
Shut unit down.
Drain the pump-motor unit as described in Chapter 10.1, "Draining",
Pg. 34.
Unscrew the housing with a 36 mm [
3
/8"] wrench (in direction of arrow
shown on housing) (see Fig. 15, Pg. 38).
Remove the housing.
Dirt has collected in the housing. Rinse out the housing.
Screw on the housing again (opposite direction of arrow shown on
housing) and tighten with a tightening torque of 50 Nm [36.9 ft lbs].
When commissioning the pump-motor unit, proceed as described in
Chapter 8, "Commissioning", Pg. 28.
Shut unit down.
Guide a M6 or M8 bolt (depending on the type) with a sufficient shank
length through the center opening into the fan guard and screw into the
shaft end on the external fan side (see Fig. 16, Pg. 38).
Free the shaft using the bolt.
Remove the bolt again.
Extremely hard water used
as operating liquid
Lime content > 15°dH).
Soften operating liquid.
OR
Decalcify the pump-motor unit at intervals of 3 months as follows (also see
Fig. 16, Pg. 38):
Wear personal protective equipment (protective gloves and safety
goggles),
Shut unit down.
Drain the pump-motor unit as described in Chapter 10.1, "Draining",
Pg. 34.
Remove pipes/hoses.
Fill the unit with decalcifying liquid through one of the connection
openings. Use 10% solution of acetic acid or another commercially
available decalcifying agent.
Allow the decalcifying liquid to soak for at least 30 minutes.
Turn the shaft occasionally during this time. To do this, guide a M6 or M8
bolt (depending on the type) with a sufficient shank length through the
center opening into the fan guard and screw into the shaft end on the
external fan side (see Fig. 16, Pg. 38).
Turn the shaft using the bolt.
Remove the bolt again.
Drain the decalcifying liquid out of the unit. To do this, proceed as
described in Chapter 10.1, "Draining", Pg. 34.
Mount pipes/hoses.
When commissioning the pump-motor unit, proceed as described in
Chapter 8, "Commissioning", Pg. 28.
The decalcifying liquid can be disposed of in the sewer system.
The pump-motor unit must be delivered
When ordering nash_elmo spare parts, always
indicate the following:
Only the original packing should be used for
Type designation ("2BV...", "2BH..." or
A declaration of clearance must be included
"2BL..."), complete with all additions
(as per rating plate)
Serial number ("No E"), 13-digit
(as per rating plate)
Part item number, 4-digit
The original rating plate of the pump-motor
(as per parts list for exploded view,
Chapter 14, "Exploded View with Parts
List", Pg. 50)
Example of an order:
2BV7071-1AH08S(-Z) = Type
designation
No E F2 7 45688 70 010 = Serial number
047 = Part item #
Impeller = Part
designation
All parts of the parts list for the exploded view
are available from the manufacturer under the
corresponding item number.
See Chapter 14, "Exploded View with Parts
List", Pg. 50.
In case of inquiries, the serial number (No E)
of the pump-motor unit must be specified in
accordance with the rating plate.
11.3.2 Ordering standardized parts
Commercially available standardized parts can
be purchased on the open market.
When doing so, observe the information in the
parts list exactly, especially the design,
dimensions, property class etc.
11.4 Service/After-sales service
Our Service is available for work (in particular
the installation of spare parts, as well as
maintenance and repair work), not described in
these operating instructions (see front page of
these operating instructions).
Observe the following when returning pumpmotor unit:
Before shipping:
– Drain the pump-motor unit so that it is
residue-free,
as described in Chapter 10.1, "Draining",
Pg. 34.
Servicing
– Clean the unit on the inside and outside,
as described in Chapter 11.1,
"Maintenance", Pg. 36.
complete, i.e. not dismantled.
shipment.
with the shipment,
as described in Chapter 11.5,
"Decontamination and Declaration of
Clearance", Pg. 42.
unit must be properly mounted, intact and
legible.
All warranty claims are voided for pumpmotor units delivered for a damage
expertise without the original rating plate or
with a destroyed original rating plate.
The pipes on the intake and discharge side are
connected to intake and discharge connections
via the flanges.
See Fig. 17, Pg. 44.
2BV7 06: G1
2BV7 07: G1½
2BV7 06: 30 Nm (22.13 ft lb)
2BV7 07: 50 Nm (36.88 ft lb)
13.2 Non-return valve
The non-return valve is basically a valve with a
plate seat. Its function is to prevent the
pumped gases/vapors as well as the operating
liquid from flowing back out of the pump in
case the operation of the pump-motor unit is
interrupted. It is mounted on the inlet
connection of the unit for this purpose.
See Fig. 18, Pg. 44.
2BV7 06: G1
2BV7 07: G1½
Fig. 17: Flanges
Mounting
The flanges are mounted when connecting the
pipes/hoses, as described in Chapter 7.3,
"Connecting pipes/hoses (vacuum
pump/compressor)", Pg. 25.
Proceed as follows:
Screwing flanges onto intake and discharge
connections.
Use commercially available liquid sealant
(e.g. Loctite) when doing so.
Tightening torque: dependent on the
sealant.
Screw intake and discharge connections
onto flanges.
Use commercially available liquid sealant
(e.g. Loctite) when doing so.
Tightening torque: dependent on the
sealant.
Fig. 18: Non-return valve
Mounting
The non-return valve is mounted when
connecting the pipes/hoses, as described in
Chapter 7.3, "Connecting pipes/hoses
(vacuum pump/compressor)", Pg. 25.
Proceed as follows:
Screw on the non-return valve with the
arrow pointing downward on the inlet
connection.
Use commercially available liquid sealant
(e.g. Loctite) when doing so.
Tightening torque: dependent on the
sealant.
Screw the inlet pipe onto the non-return
valve.
Use commercially available liquid sealant
(e.g. Loctite) when doing so.
Tightening torque: dependent on the
sealant.
pressure of the unit in the range from
40 mbar [0.580 psi] to 10 mbar [0.145 psi] is
to be achieved.
The gas ejector compresses the pumped
gases/vapors sucked in to the inlet pressure of
the pump-motor unit.
Ambient air at 20°C [68 °F] and 1013 mbar
[14.7 psi] is used as a propellant. This air may
not contain any liquid droplets.
See Fig. 19, Pg. 45.
Fig. 19: Gas ejector
The gas ejector is mounted when connecting
the pipes/hoses, as described in Chapter 7.3,
"Connecting pipes/hoses (vacuum
pump/compressor)", Pg. 25.
Proceed as follows:
Screw the gas ejector onto the inlet
connection.
Use commercially available liquid sealant
(e.g. Loctite) when doing so.
Tightening torque: dependent on the
sealant.
Screw the inlet pipe onto the gas ejector.
Use commercially available liquid sealant
(e.g. Loctite) when doing so.
Tightening torque: dependent on the
sealant.
With soiled ambient air:
Screw a propellant line onto the gas ejector.
When evacuating containers, the gas ejector
operates as a throttle in the range from
1000 mbar [14.5 psi] to approx. 100 mbar
[1.45 psi]. To achieve fast venting times here,
the gas ejector can be bypassed with a bypass
pipe. The bypass pipe must be closed if the
gas ejector is to be effective. The best point for
switching over to operation with the gas ejector
is at approx. 40 mbar [0.580 psi].
The liquid separator is mounted on the
discharge connection. Its functions consists of
separating the discharged operating liquid form
the pumped gases/vapors. Part of this
separated operating liquid can be fed back to
the pump-motor unit via the operating-liquid
port. The rest is drained off and replaced with
fresh operating liquid.
Operation with a liquid separator and operating
water return is the operating mode
recommended for the pump-motor unit.
The procedure for mounting the liquid
separator on the pump-motor unit is shown in
Fig. 20, Pg. 47, and Fig. 21, Pg. 48. Here the
following applies:
1) Remove the plug at the top and bottom
on the liquid separator.
2) Screw the hose nipple into the holes on
the liquid separator. Use commercially
available liquid sealant (e.g. Loctite)
when doing so.
Top hole:
Angled hose nipple.
Bottom hole:
Straight hose nipple.
For L-BV7 2BV7 060 and 2BV7 061:
The premounted reducer on the liquid
separator is required. Therefore:
Remove the reducer from the liquid
separator.
Seal off thread. Use commercially
available liquid sealant (e.g. Loctite)
when doing so.
Screw the reducer into the liquid
separator again.
For L-BV7 2BV7 070 and 2BV7 071:
The premounted reducer on the liquid
separator is not required. Therefore:
Remove the reducer from the liquid
separator and dispose of it.
3) Screw the hose nipple into the hole
provided on the pump-motor unit. Use
commercially available liquid sealant
(e.g. Loctite) when doing so.
Operating-liquid port:
Angled hose nipple, directed toward
the front.
Connection for cavitation protection:
Angled hose nipple, directed upward.
4) Mount the "T" hose nipple on the angled
hose nipple on the operating-liquid port
with the hose clamp.
5) Place the liquid separator on the
discharge connection and tighten it by
hand. Use commercially available liquid
sealant (e.g. Loctite) when doing so.
6) Mount the hose for returning the
operating liquid (see arrow) with hose
clamps.
On the liquid separator:
Mount the hose on the lower hose
nipple.
On the pump-motor unit:
Mount the hose on the side
connection of the "T" hose nipple
(operating-liquid port).
7) Mount the cavitation-protection hose
(see arrow) with hose clamps.
On the liquid separator:
Mount the hose on the upper hose
nipple.
On the pump-motor unit:
Mount the hose on the hose nipple of
the cavitation protection connection.
8) Side view of the mounted liquid
separator.
A = Connection for feed pipe for fresh
operating liquid.
B = Connection for draining off
separated operating liquid.
13.5 Cavitation protection
Cavitation is understood to be the production
and sudden implosion of gas bubbles in the
liquid being fed. If the pressure in the vacuum
pump/compressor drops below the evaporation
pressure of the liquid (on the intake side or in
constricted areas), gas bubbles form. When
the pressure increases above the evaporation
pressure again (on the discharge side or at
points with a larger cross-section), these gas
bubbles collapse while forming high pressure
peaks, which may lead to particles being torn
out of the housing wall and impeller. Noise is
radiated. Material destruction of the pumpmotor unit is possible. To prevent this,
measures should be taken for cavitation protection.
To protect the unit from cavitation, connect the
cavitation-protection hose of the liquid
separator to the connection for cavitation
protection (Fig. 7, Pg. 25, Item 4).
For the safety of our employees and to comply with statutory requirements on handling substances harmful to the health and
the environment, this statement must be enclosed, fully completed, with each unit/system sent.
Without the fully completed statement, repair/disposal is not possible and delays are unavoidable!
The statement is to be completed and signed by suitably qualified, authorised personnel at the operating organisation.
In the case of shipment to Germany, the statement is to be completed in German or English.
The statement is to be attached to the outside of the packing on shipment.
If necessary, the carrier is to be informed.
1. Product designation (type):
2. Serial number (no. BN):
3. Reason for sending:
4. The unit/system
has not come into contact with hazardous substances. There will be no hazards for personnel or the environment during
repair/disposal. Continue with "6. Legally binding statement“
has come into contact with hazardous substances. Continue with "5. Information on the contamination“
5. Information on the contamination
The unit/system was used in the following application:
and has come into contact with the following classifiable substances or substances presenting a hazard to health/environment:
Trade name: Chemical designation:
The unit/system has been emptied in accordance with the operating instructions, flushed and cleaned externally.
Safety data sheets in accordance with the applicable regulations are enclosed ( sheet).
The following safety precautions are necessary for handling (e.g. personal protective equipment):
6. Legally binding statement
I herewith guarantee that the details specified are true and complete and that I, as signatory, am in a position to judge that this is
so.
We are aware that we are liable to the contractor for any damages arising from incomplete or incorrect specifications. We are
obliged to indemnify the contractor against claims for damages by third parties arising from incomplete or incorrect specifications.
We are aware that, irrespective of this statement, we are directly liable to third parties - in particular including the contractor's
employees tasked with repair/disposal.