Transmittal, reproduction, dissemination and/or editing of this document as well as utilization of its
contents and communication thereof to others without express authorization are prohibited. Offenders
will be held liable for payment of damages. All rights created by patent grant or registration of a utility
model or design patent are reserved.
Page 3
Design of side channel blowers in conjunction with frequency inverters
Declaration of conformity.................................................................................................................. 50
Form for statement on safety ........................................................................................................... 51
Design of side channel blowers in conjunction with frequency inverters
1
7
6
10
11
2
4
9
8
Position Description
1 Frequency inverter
2 Inlet connection with muffler and arrow indicating delivery direction
3 Discharge connection with muffler and arrow indicating delivery direction
4 Base
5 Arrow indicating direction of rotation
6 Blower cover
7 blower housing
8 Drive motor
9 Fan guard above the motor fan with rating plate, warning notices and arrow
indicating direction of rotation
10 Status display with 2 light-emitting diodes (red, green)
11 Communication interface for connecting the hand-held keypad
Fig. 1: Design of side channel blowers in conjunction with frequency inverters
Side channel blowers are pre-configured for four
operating modes. It only takes a few steps and
they are ready for operation:
ACHTUNG
The drive motor is protected against
overheating by a thermal detector.
– If the drive motor gets too hot, the
frequency inverter will switch off the
pump-motor unit.
– Please contact the manufacturer if the
hydraulic process does not allow
immediate switch-off.
A minimum wiring is required for
commissioning! ( 22)
1 Read the safety instructions.
The safety instructions start on page 5.
2 Install the pump-motor unit and attach it.
Listing of the mounting steps starts on
3 Wire the pump-motor unit.
4 Put the pump-motor unit into operation.
5 Adapt important process parameters.
page 16.
Please observe that a minimum wiring is
required!
Otherwise commissioning of the pump-
motor unit is not possible.
Important notes concerning the wiring
start on page 22.
Description of the commissioning steps
starts on page 34.
Adapt acceleration and deceleration time to
the hydraulic process via C0012 and
C0013.
Description of parameter changing
starts on page 35.
6 Adjust the speed.
A) Speed adjustment using a potentiometer
The speed is adjusted via the analog input.
The speed can be adjusted between
aminimum and a maximum
value.Description of potentiometer wiring
starts on page 30.
B) Operation with several adjustable fixed
speeds
The speed of the pump−motor unit can be
adjusted in steps of 1000/min via the digital
inputs E3 and E4.
Description of the wiring of E3 and E4
starts on page30.
C) Operation with one fixed speed
Connect hand−held keypad.
Set required fixed speed under C0140.
Disconnect hand−held keypad.
The pump−motor unit will be operated with
this speed when switched on.
Description of hand−held keypad
connection and parameter changing
starts on page35.
D) Speed adjustment using the keypad
Connect hand−held keypad.
Select C0140.
Set the required speed during the
process using the keys _..
The pump−motor unit will be operated with
the last set speed when switched on.
Description of hand−held keypad
connection and parameter changing
starts on page35.
To point out dangers and important information,
the following signal words and symbols are used
in these Operating Instructions:
1.1.1 Safety alert symbols and signal words
The safety alert symbol is located in the safety
instructions in the highlighted heading field on the
left next to the signal word (DANGER,
WARNING, CAUTION).
Safety instructions with a safety alert symbol
indicate a danger of injuries.
Be sure to follow these safety instructions to
protect against injuries or death!
Safety instructions without a safety alert symbol
indicate a danger of damage. – Be sure to follow
these safety instructions to avoid material
damage!
1.1.2 Signal words
DANGER
WARNING
CAUTION
NOTICE
NOTE
Danger of injuries.
Indicates an imminently hazardous situation,
that will result in death or serious injury if the
corresponding measures are not taken.
Danger of injuries.
Indicates a potentially hazardous situation, that
could result in death or serious injury if the
corresponding measures are not taken.
The signal words are located in
the safety precautions in the
highlighted heading field.
They follow a certain hierarchy
and indicate (in conjunction with
the safety alert symbol, see
Chapter 1) the seriousness of
the danger and the type of
warning.
See the following explanations:
DANGER
WARNING
CAUTION
Danger of injuries.
Indicates a potentially hazardous situation, that
may result in minor or moderate injury if the
corresponding measures are not taken.
CAUTION
Danger of damage.
Indicates a potentially hazardous situation that
may result in property damage if the
corresponding measures are not taken.
NOTICE
Indicates a possible disadvantage, i.e.
undesirable conditions or consequences can
occur if the corresponding measures are not
taken.
NOTE
Indicates a possible advantage if the
corresponding measures are taken; tip.
1.1.3 Abbreviations used
Product designation
For side channel blower in conjunction with
frequency inverters the term pump−motor unit is
used in these Instructions.
Cross−reference
Cross−references to other parts of these
Instructions are marked with a book symbol:
( 9)
1.2 General safety and application notes
WARNING
Improper use of the pump−motor unit can
result in serious or even fatal injuries!
These Operating Instructions
must have been read completely and
understood before beginning any work with
or at the pump−motor unit,
must be strictly observed,
must be available at the operating location of
Improper use of the pump−motor unit can
result in serious or even fatal injuries!
Only operate the pump−motor unit
for the purposes indicated under "Application
as directed"!
with the media indicated under "Application
as directed"!
with the values indicated under "Technical
data"!
WARNING
Improper use of the pump−motor unit can
result in serious or even fatal injuries!
All work on and with the pump−motor unit
(transport, installation, operation, shut−down,
maintenance, disposal) may only be carried out
by trained, reliable expert personnel!
WARNING
When working on the pump−motor unit,
there is a danger of injury, e.g. in the form
of cuts/cutting off, crushing and burns!
During all work on and with the pump−motor
unit (transport, installation, operation,
shut−down, maintenance, disposal) wear
personal safety equipment (safety helmet,
safety gloves, safety shoes)!
WARNING
Hair and clothing can be pulled into the
pump−motor unit or caught and wound up
by moving parts! Do not wear long, loose
hair or wide, loose clothing! Use a hairnet!
DANGER!
Electrical danger!
Work on electrical installations may be carried
out by trained and authorized electricians only!
DANGER!
Electrical danger!
Before beginning work on the pump−motor unit
or system, the following measures must be
carried out :
Deenergize.
Secure against being switched on again.
Determine whether deenergized.
Ground and short−circuit.
Cover or block off adjacent energized parts.
DANGER!
Electrical danger!
Do not open the frequency inverter until
absence of electricity has been ensured!
WARNING
Danger due to vacuum and gauge pressure:
sudden escape of media (skin and eye
injuries), sudden drawing−in of hair and
clothing!
Danger due to escaping media: burns!
Use mounting elements, connections, lines,
fittings and containers with sufficient freedom
from leaks and strength for the pressures which
occur.
Check the mounting elements, connections,
lines, fittings and containers for strength, leaks
and firm seating at regular intervals!
WARNING
Danger from rotating parts (motor fan,
impeller, shaft): cutting/cutting off of
extremities, grasping/winding up of hair and
clothing!
Danger due to vacuum and gauge pressure:
sudden escape of media (skin and eye
injuries), sudden drawing−in of hair and
clothing!
Danger due to escaping media: burns!
Commissioning and operation only under the
following conditions:
The pump−motor unit must be completely
assembled. When doing so, pay particular
attention to the following components:
– the blower cover,
– the mufflers on inlet and discharge
connections,
– the fan guard.
The pipes and hoses must be connected to
inlet and discharge connections.
Inlet and discharge connections and the
connected pipes/hoses may not be closed,
clogged or soiled.
Check the mounting elements, connections
of the pipe/hose connections, lines, fittings
and containers for strength, leaks and firm
seating at regular intervals.
Danger from rotating parts (motor fan,
impeller, shaft): cutting/cutting off of
extremities, grasping/winding up of hair and
clothing!
Danger due to vacuum and gauge pressure:
sudden escape of media (skin and eye
injuries), sudden drawing−in of hair and
clothing!
Danger due to escaping media: burns!
Before beginning work on the pump−motor unit,
take the following measures :
Shut down pump−motor unit and secure
against being switched on again.
Attach a sign on the system controller and
on the control elements for the pump−motor
unit: "DANGER! Maintenance work on the
vacuum pump/compressor! Do not switch
on!"
Wait for pump−motor unit to come to a
complete stop.
– Observe run−on time!
Allow pump−motor unit to cool!
Shut−off lines.
– Release pressure.
Make sure that no vacuum or gauge
pressure is present in the lines/tanks to be
opened.
Make sure that no media can escape.
WARNING
Danger from rotating impeller:
cutting/cutting off of extremities!
The rotating impeller is accessible with the inlet
and discharge connections open!
Do not reach into the pump−motor unit through
open connections!
Do not insert objects into the pump−motor unit
through the openings!
WARNING
Danger of burns from hot surface of the
pump−motor unit and from hot media!
High temperatures of up to approx. 160 °C
[320 °F] can occur on the surface of the
pump−motor unit:
Cover the pump−motor unit with a suitable
touch protection (e.g. perforated plate cover
or wire cover).
Do not touch during operation!
Allow to cool after shut−down!
1.3 Residual risks
WARNING
Danger zone:
Hot surface of up to approx.160 °C [320 °F].
Hazard:
Possible burns.
Protective measures:
Cover the pump−motor unit with a suitable
touch protection (e.g. perforated plate cover or
wire cover).
WARNING
Danger zone:
Fan guard
Hazard:
Long, loose hair can be drawn into motor fan
through the fan guard grate, even with
fan guard mounted!
Protective measures:
Wear hair net!
WARNING
Danger from rotating impeller:
cutting/cutting off of extremities!
The rotating impeller is accessible with the inlet
and discharge connections open!
With free entry and exit of gases, i.e. with direct
intake out of or direct feeding into the
atmosphere without piping, the following
therefore applies:
Provide the inlet and discharge connections
of the pump−motor unit either with additional
mufflers or with additional piping of a
sufficient length to prevent access to the
impeller!
These Operating Instructions are valid for G-BH7e series side channel blower in conjunction with
frequency inverters equipped with the following frequency inverters:
Type
Supply voltage
2FC 4 xxx - 1NE00 1x 35
4 = 400 V/500 V
Power
(e.g.152 = 15 ´ 10
(e.g.. 752 = 75 ´ 10
2
W = 1,5 kW)
2
W = 7,5 kW)
1NE00 = integrated inverter
Hardware version
Software version
Fig. 2: Typschild
These Operating Instructions
contain instructions bearing on transport and
handling, installation, commissioning,
operation, shut−down, storage, servicing and
disposal,
must be completely read and understood by
all operating and servicing personnel before
beginning to work,
must be strictly observed,
must be available at the site of operation in a
complete and perfectly legible condition.
– With differing gases/gas−air mixtures,
inquire with the manufacturer.
are intended for industrial applications.
are designed for continuous operation:
– With increased switch−on frequency (at
equal intervals of approx. 5 times per hour)
or increased gas entry temperature and
ambient temperature, the limit
overtemperature of the winding and the
bearings can be exceeded.
– Consultation with the manufacturer is
required for operating conditions of this
kind.
Operating and servicing personnel
are equipped with a three−phase drive motor
These persons must be trained and
authorized for the work to be carried out.
Work on electrical installations may be carried
out by trained and authorized electricians
only.
G-BH1e series side channel blower in
conjunction with frequency inverters
other than industrial applications unless the
necessary protection is provided on the
system, e.g. touch guards suitable for
children’s fingers,
to use the pump−motor units in rooms in
which explosive gases can occur,
to extract, deliver and compress explosive,
flammable, corrosive or toxic media,
to operate the pump−motor units with values
other than those specified in the chapter
"Technical data".
Any unauthorized modifications of the
pump−motor units are prohibited for safety
reasons.
The operator is only permitted to perform the
maintenance and service work described in these
Operating Instructions.
Any maintenance and service work which goes
beyond this many only be performed by
companies authorized by the manufacturer
(inquire with the manufacturer).
Measuring-surface sound-pressure level as per
EN ISO 3744, measured at a distance of 1 m
[3.28 ft] at an operating point of approximately
2/3 of the permissible total pressure difference
with the lines connected without a vacuum or
pressure relief valve, tolerance 3 dB (A).
The information listed in the following tables
corresponds to the heating of the side channel
housing and the air exiting compared to the
ambient temperature during operation with a
permissible total pressure difference and an air
pressure of 1013 mbar [14.7 psi]. At lower air
pressures these values increase.
The following values apply if no other data are
given.
With non−electrical connections, property classes
of 8.8 and 8 or higher as per DIN ISO 898 (DIN
EN 20898 / DIN ISO 898) are assumed.
Acceleration resistant up to 2g (Germanischer Lloyd, general conditions)
Vibration velocity
max. v
4 mm/s [0,013 ft/s] Depending on the application case and the
eff
system type it may be necessary to use vibration
dampers.
Site altitude
min. 0 m üNN [0 ft amsl] max. 1000 m üNN [3280 ft amsl] For installations above 1000 m amslA [3280 ft
amsl] consultation of the manufacturer is
required.
Climatic conditions
Class 3K3 to EN 50178 (without condensation, relative humidity 30 ... 95 %)
Ambient temperatures
Transport min. -25°C [-13°F]
max. +70°C [+158°F]
Storage min. -25°C [-13°F]
max. +60°C [+140°F]
Operation min. -20°C [-4°F]
max. +40°C [+104°F]
rated value +25°C [+77°F]
Between +25 °C [+77 °F] and +40 °C [+104 °F]
reduce the total pressure difference indicated on
the rating plate by 0.7 %/°C [0.4 %/°F].
Operation at higher temperatures may damage
the winding and shorten the grease change
interval.
Temperature of pumped gases
max. +40°C [+104°F]
rated value +15°C [+59°F]
Pump−motor units for higher media
temperatures Pump on request.
Pressures
Inlet pressure min. See rating plate
Discharge pressure
max. See rating plate
during compressor
operation
Permissible total
pressure difference
max. See rating plate The total pressure difference specified on the
rating plate only applies under the following
conditions:
Ambient temperature: 25 °C [77 °F]
Temperature of the pumped gas at the inlet
connection: 15 °C [59 °F]
Pressure:
– for vacuum−pump operation: 1013 mbar
[14.7 psia] at the discharge connection
– for compressor operation:
1013 mbar [14.7 psia] at the inlet
connection
zulässiger Druck im
Aggregat
max. 2 bar abs. [29 psia] At this pressure the operation of the
pump−motor unit may be considerably impaired.
Provide a corresponding protective device (e.g.
pressure relief valve) if necessary.
Single−impeller design
2BH7210−0.N1 X
2BH7210−0.N5 X
2BH7310−0.N2 X
2BH7310−0.N6 X
2BH7410−0.N1 X
2BH7410−0.N5 X
2BH7510−0.N2 X
2BH7510−0.N6 X
2BH7610−0.N3
Two−impeller design
2BH7220−0.N5 X
2BH7320−0.N5 X
2BH7320−0.N8 X
2BH7420−0.N2 X
2BH7420−0.N5 X
2BH7520−0.N7 X
2BH7620−0.N3 X
2BH7620−0.N4
Three−impeller design
2BH7630−0.N6 X
Improper use of the pump−motor unit can
result in serious or even fatal injuries!
Have you read the chapter "Safety
instructions"? ( 5)
Otherwise you may not carry out any work with
or on the pump−motor unit!
DANGER!
Danger from missing view into area of
pump−motor unit!
When operating the control elements without a
view into the area of the pump−motor unit,
there is a danger that the pump−motor unit will
be switched on while other persons are still
performing work on it. Severest injuries are
possible!
Provide control elements at a location with a
view of the pump−motor unit.
DANGER!
Electrical danger!
The pump−motor unit must be installed so that
the electrical equipment cannot be damaged by
external influences!
In particular, the incoming cables must be
routed securely, e.g. in cable ducts, in the floor
etc.
WARNING
Danger of balance damage caused by
vibration!
Vibrating environments can cause balance
damage!
Install the pump−motor unit on a solid
foundation or on a solid mounting surface.
Check screw glands/unions for mounting the
pump−motor unit on the mounting surface
regularly for strength and firm seating.
WARNING
Danger of crushing due to pump−motor unit
tipping over!
Wear personal safety equipment (safety gloves
and safety shoes).
Handle the pump−motor unit with the
appropriate care.
Install the pump−motor unit on a solid
foundation or on a solid mounting surface!
Check screw glands/unions for mounting the
pump−motor unit on the mounting surface
regularly for strength.
WARNING
Danger of fire from flammable substances!
The pump−motor unit must never come into
contact with flammable substances.
For exact information on the temperature
increase see: ( 12).
WARNING
Danger of burns from hot surface of the
pump−motor unit and from hot media!
High temperatures of up to approx. 160 °C
[320 °F] can occur on the surface of the
pump−motor unit.
The pump−motor unit must be installed so that
accidental touch of its surface is not possible.
Cover the pump−motor unit with a suitable
touch protection (e.g. perforated plate cover or
wire cover).
WARNING
Danger of injuries from flying parts!
Select installation so that parts that are thrown
out through the grate if the motor fan breaks
cannot hit persons!
CAUTION
Danger of tripping and falling!
Make sure the pump−motor unit does not
present a danger of tripping.
Lay cables and pipes so that they cannot be
reached during operation (recessed in floor, in
ducts on the wall etc.).
Danger of overheating due to hot surface of
pump−motor unit!
High temperatures can occur on the surface of
the pump−motor unit.
Temperature−sensitive parts, such as cables or
electronic components, may not come into
contact with the surface of the pump−motor
unit.
CAUTION
Danger of pump−motor unit damage caused
by penetration of foreign bodies!
On delivery all connection openings are closed
in order to prevent the penetration of foreign
bodies. Remove the seals right before the
respective mounting step.
Installation sequence
The pump−motor unit is ready to connect on
delivery.
CAUTION
The pump−motor unit may be damaged if it
is installed and commissioned after longer
storage periods without special preparation!
If the pump−motor unit was stored for a longer
period prior to installation, it has to be prepared
for installation: ( 42)
Carry out the following steps to install the
pump−motor unit:
1 Set up the pump−motor unit and attach it.
2 Mount the muffler (supplied loose) if
necessary.
3 Mount the threaded flange or hose flange to
the muffler if necessary.
4 Connect inlet and discharge connections to
the system.
5 Establish electrical connection.
4.1 Installation
CAUTION
Pump−motor unit damage caused by
incorrect mounting or use under
impermissible ambient conditions!
Install and connect the pump−motor unit only
according to the instructions given in this
chapter.
If the pump−motor unit is to be used under
differing operating conditions, the manufacturer
must be consulted.
NOTE
Dimensioned drawings with detailed
dimensions, including fastening dimensions,
are provided by the manufacturer.
4.1.1 Important notes
Ambient conditions
The pump−motor unit is suitable for installation
in a dusty or damp environment,
in buildings,
in the open.
– For proper installation in the open, protect
the pump−motor unit from exposure to
intensive sunlight, e.g. by attaching a
protective roof.
– Further special protective devices against
the effects of weathering are not required.
The motors of the units are to enclosure IP55.
The insulation is tropic−proof.
Installation conditions
Attach the pump−motor unit only to even
surfaces.
Do not exceed the maximum permissible
vibration velocity veff = 4mm/s [0.013 ft/s].
Installation altitude max. 1000 m amsl [3280 ft
amsl].
– When installing at an altitude of more than
1000 m [3280 ft] above sea level, first
inquire with the manufacturer.
1 Select suitable mounting elements.
2 Position the pump−motor unit as close to the
wall as possible on a stable supporting plate
with sufficient load−bearing capacity.
– The pump−motor unit must be positioned
with the base towards the wall.
3 Attach the pump−motor unit to the wall:
– Screw the base of the pump−motor unit to
the wall via the mounting holes.
– When doing so, be sure to provide all
mounting holes with screws!
4 Remove the supporting plate.
4.1.4 Final works
After installing the pump−motor unit, the eye bolt
must be removed or screwed tightly.
4.2 Mounting of the muffler
The pump−motor units are supplied with mufflers
for inlet and discharge connections as standard.
The mufflers are marked by arrows in the
following drawings.
With the following pump−motor units, the
inlet−side muffler is included loose for
packaging−related reasons. It must be mounted
by the operator.
2BH732 ... 2BH762 (two−impeller pump−motor
units with two−stage design)
ne2bhxn003b
Fig. 8: Mounting of the muffler 2BH732 ... 2BH762
2BH763 (three−impeller pump−motor unit with
three−stage design)
ne2bhxn003c
Fig. 9: Mounting of the muffler 2BH763
WARNING
Danger from rotating impeller:
cutting/cutting off of extremities!
The rotating impeller is accessible with the inlet
and discharge connections open!
With free entry and exit of gases, i.e. with direct
intake out of the atmosphere or direct feeding
into the atmosphere without piping, the
following therefore applies:
Provide the inlet and discharge connections of
the pump−motor unit either with additional
mufflers or with additional piping of a sufficient
length to prevent access to the impeller!
4.3 Connecting the pump-motor unit to the
system
4.3.1 Important notes
Delivery direction of the gases
The pumped gases are sucked in via the inlet
connection and discharged via the discharge
connection.
The delivery direction of the gases is marked by
arrows on the connections:
The inlet connection with the corresponding
muffler is marked by an arrow pointing into the
pump−motor unit.
The discharge connection with the
corresponding muffler is marked by an arrow
pointing out of the pump−motor unit.
The rotation direction of the shaft is marked by an
arrow on the cover of the side channel housing
and by an arrow on the fan guard of the motor.
WARNING
Danger from interchanging inlet and
pressure line!
Interchanged inlet and pressure lines can lead
to damage to the pump−motor unit and the
system, and as a result of this to serious
injuries!
Make sure that the inlet and the pressure line
cannot be confused when connecting.
Pay attention to the clear marking with the
arrows indicating the delivery direction on the
inlet and discharge connections.
WARNING
Danger due to vacuum and gauge pressure!
Danger due to escaping media!
During operation, connected pipes and vessels
are vacuumized or pressurized!
Use only mounting elements, connections,
lines, fittings and containers with sufficient
freedom from leaks and strength for the
pressures which occur.
Make sure that the mounting elements and
connections are mounted firmly enough and
leak−free!
CAUTION
If the pumped gases are passed on the
discharge side in a closed pipe system, then it
must be ensured that the pipe system is
adapted to the maximum discharge pressure.
Connect a pressure relief valve upstream if
necessary.
NOTE
Attach pipes/hoses free of mechanical
tensions.
Support the weight of the pipes/hoses.
4.3.2 Connecting the inlet line
WARNING
Danger from solid bodies and impurities in
the pump−motor unit!
If solid bodies penetrate into the pump−motor
unit, blades of the impellers can break and
broken pieces can be thrown out.
Install a filter in the inlet line. Replace filter
regularly!
The pumped gases are taken in via the inlet line.
Connect the inlet line to the inlet connection.
– The inlet connection with the
corresponding muffler is marked by an
arrow pointing into the pump−motor unit.
A If you use an inlet pipe, you can screw it
directly into the muffler.
B If you use an inlet hose, you need a hose
flange available as accessories:
– Screw the hose flange to the muffler.
– Push the hose onto the hose flange and
secure it with a hose clamp.
– Observe tightening torques ( 12)
4.3.3 Connecting the pressure line
The pumped gases are discharged via the
pressure line.
Connect the pressure line to the discharge
connection.
– The discharge connection with the
corresponding muffler is marked by an
arrow pointing out of the pump−motor unit.
A If you use a pressure pipe, you can screw it
directly into the muffler.
B If you use a pressure hose, you need a hose
flange available as accessories:
– Screw the hose flange to the muffler
– Push the hose onto the hose flange and
can result in an electric shock.
Observe the following basic rules:
The leakage current to earth (PE) is
>3.5 mA. The PE connection must meet EN
50178.
Observe national and regional regulations.
CAUTION
Danger of pump−motor unit damage caused
by improper connection!
Observe the permissible mains voltage. Any
higher mains voltage will destroy the frequency
inverter.
Wiring according to EMC requirements
(installation of a CE-typical drive system)
The pump−motor units meet the EU Directive on
"Electromagnetic Compatibility" if they are
installed in accordance with the specifications of
the CE−typical drive system. The end−user is
responsible for maintaining the EU Directive in
the overall system.
ne2bhxn422
Fig. 11: Open frequency inverters 2FC4302−1NE00 ...
2FC4752−1NE00
NOTE
Requirements for trouble−free operation:
Always shield control cables.
Provide large−surface contact between
shielding and shield sheet. Ensure good
electrical contact.
4 Connecting the control cable shield:
A Pass the control cable through the cable
gland.
B Connect the shield according to EMC
requirements ( 24).
C Control cable connection: ( 29)
5 Tighten all cable glands.
Page 26
Installation
NOTE
Do not remove the jumper between terminals
BR1 and BR0!
Otherwise trouble−free functioning of the
pump−motor unit cannot be guaranteed.
4.4.4 Connecting frequency inverters
2FC4302-1NE00 ... 2FC4752-1NE00
DANGER!
Electrical danger!
Improper connection of the pump−motor unit
can result in an electric shock.
Observe the following basic rules:
The leakage current to earth (PE) is > 3.5
mA. The PE connection must meet EN
50178.
Observe national and regional regulations.
CAUTION
Danger of pump−motor unit damage caused
by improper connection!
Observe the permissible mains voltage. Any
higher mains voltage will destroy the frequency
inverter.
Wiring according to EMC requirements
(installation of a CE-typical drive system)
The pump−motor units meet the EU Directive on
"Electromagnetic Compatibility" if they are
installed in accordance with the specifications of
the CE−typical drive system. The end−user is
responsible for maintaining the EU Directive in
the overall system.
NOTE
Requirements for trouble−free operation:
Always shield control cables.
Provide large−surface contact between
shielding and shield sheet. Ensure good
electrical contact.
Improper use of the pump−motor unit can
result in serious or even fatal injuries!
Have you read the chapter "Safety
instructions"? (
5)
Otherwise you may not carry out any work with
or on the pump−motor unit!
WARNING
Danger from rotating parts (motor fan,
impeller, shaft): cutting/cutting off of
extremities, grasping/winding up of hair and
clothing!
Danger due to vacuum and gauge pressure:
sudden escape of media (skin and eye
injuries), sudden drawing−in of hair and
clothing!
Danger due to escaping media: burns!
Commissioning and operation only under the
following conditions:
The pump−motor unit must be completely
assembled. When doing so, pay particular
attention to the following components:
– the cover of the gas ring blower housing,
– the mufflers on inlet and discharge
connections,
– the fan guard.
The pipes/hoses must be connected to inlet
and discharge connections.
Inlet and discharge connections and the
connected pipes/hoses may not be closed,
clogged or soiled.
Check the mounting elements, connections
of the pipe/hose connections, lines, fittings
and containers for strength, leaks and firm
seating at regular intervals.
5.1 Preparation
WARNING
Danger from closed connections!
With closed/soiled inlet or discharge
connections vacuum or gauge pressure results
in the pump−motor unit.
This can overheat and damage the drive motor
winding.
Before commissioning, make sure that the inlet
and discharge connections are not closed,
clogged or soiled!
CAUTION
Before starting up again after a longer
standstill:
Measure the insulation resistance of the
motor.
With values < 1 k /Volt of rated voltage,
the winding is to dry.
Measures before start-up:
If a shut−off device is installed in the pressure
line: make sure that the pump−motor unit is
NOT operated with the shut−off device being
closed.
Observe the values specified on the rating
plate before starting up the pump−motor unit.
Specifications on the rated motor current
apply at a gas entry and ambient temperature
of +40° C [104 °F].
WARNING
Danger due to rotating parts!
Danger due to vacuum and gauge pressure!
Danger due to escaping media!
Test runs may only be conducted with the
pump−motor unit completely mounted.
DANGER!
Electrical danger!
The electrical connection may be carried out by
trained and authorized electricians only!
Before beginning work on the pump−motor unit
or system, the following measures must be
carried out:
Deenergize.
Secure against being switched on again.
Determine whether deenergized.
Ground and short−circuit.
Cover or block off adjacent energized parts.
Check operating speeds:
Observe the maximum speed specified on the
rating plate.
This speed may not be exceeded, as otherwise
the noise radiation, vibration behavior, grease
change interval and bearing change interval
worsen.
To prevent damage as a result of higher speeds,
it may be necessary to inquire with the
manufacturer as to the maximum speed.
WARNING
Danger of hearing damage due to noise
radiation!
The noise emission of the pump−motor unit
measured by the manufacturer is specified
under "Technical data" (
The actual noise emission during operation,
however, strongly depends on the installation
type and on the system conditions.
For this reason conduct a noise measurement
in the system during operation after installing
the pump−motor unit.
The following measures must be taken by the
operator:
from 85 dB(A):
– Hearing protection must be available.
from 90 dB(A):
– Mark noise area with a warning sign.
– Wear hearing protection.
– With free entry and exit of gases, i.e. with
direct intake out of the atmosphere or
direct feeding into the atmosphere
without piping, attach an additional
muffler.
11).
5.2 Parameter setting
5.2.1 The hand-held keypad 2FX4506-0NE00
Description
The hand−held keypad is available as
accessories. A complete description is part of the
Instructions supplied with the hand−held keypad.
All parameters for parameterization or monitoring of the controller are stored in codes. The codes are
numbered and marked with a "C" in the documentation. The available codes are listed in the code
table.
Step Keys Result Action
1. Connect keypad
Set parameters
2.
3.
4.
5.
7.
XX.XX Hz
XXXX
xxxxx
Store
The function is active.
C0140 = setpoint is indicated via keypad.
Select mode ".
Select code..
Modus off Ahlen.
Parameter onstellen.
Confirm entry when ! is blinking. 6.
Confirm entry when ! is not blinking; is inactive.
Start "loop" again at 2. for further parameter setting.
Changed parameters are stored in the non−volatile memory of the controller.
5.2.2 Code table
How to read the Code table
Column Abbreviation Meaning
Code
Cxxxx Code number Cxxxx The parameter value is accepted
immediately (ONLINE)
Changed parameter of the code will be accepted after pressing
Changed parameter of the code will be accepted after pressing if
the controller is inhibited
Designation Name of the code
Manufacturer Default setting (value at delivery or after restoring default setting via
C0002)
Further information can be obtained from "IMPORTANT"
Selection 1 {%} 99 Min. value {unit} max. value
IMPORTANT - Brief, important explanations
Code Possible settings IMPORTANT
No. Designation Manu-
Selection
facturer
C0140 Setpoint offset via
keypad
0,00 -650,00 {0,02 Hz}650,00 Acts additively on
main setpoint.
setpoint 2.
fixed speeds (JOG).
The set value is stored in case of
mains switching or keypad
removal.
C0050 Output frequency -650,00 {Hz} 650,00 Display only: Output frequency
without slip compensation
C0052 Motor voltage 0 {V} 1000 Display only
C0054 Apparent motor
The description of how to change pre-set parameters using the hand-held keypad starts on page 35.
NOTE
When no setpoint has been entered, the drive rotates with the minimum frequency set under
C0010!
The setpoint offset set under C0140 is stored and will be active at each switch−on.
The setpoint offset set under C0140 has an additive effect on all other setpoints!
This effect can be used, for example, to set speeds between fixed speeds:
Side−channel
blower does not
reach the
required speed
/ pump−motor
unit does not
generate
pressure
difference or
generated
difference is too
low
Leak in system. Seal leak in the system. Operator
Shaft seal defective. Replace shaft seal. Service*)
Different density of pumped gas. Take account of the conversion of the
Service
pressure values.
Inquire with Service Department.
Change in blade profile due to
Min. output frequency set > 0
Hz. (Default setting= 10 Hz)
In C0140 a setpoint has been
set. (Setting of C0140 stored in
Change drive characteristics only under
special circumstances! (Set C0010 = 0 Hz)
Electrician
Operator
Set C0140 = 0 Hz if necessary.. Electrician
Operator
non−volatile memory
Current
consumption of
C0016 set too large or too small. Correct setting Electrician
Operator
motor too high
noises
Flow speed too high. Clean pipes. Use pipes with larger
cross−section if necessary.
Muffler soiled. Clean muffler inserts, check condition and
Operator Abnormal flow
Service*)
replace if necessary.
Abnormal
running noise
Ball bearing lacking grease or
Regrease or replace ball bearing. Service*)
defective.
Seals on muffler defective. Check muffler seals and replace if
Service*) Blower leaky
necessary.
Seals in motor area defective. Check motor seals and replace if necessary. Service
*) Can only be repaired by the operator if the maintenance manual is on hand!
8.1.2 Frequency inverter status indications
LED
Operating status
red green
off on Frequency inverter enabled
on on Mains switched on and automatic start inhibited
off slowly blinking Frequency inverter inhibited
off fast blinking Motor parameter identification being executed
fast blinking off Undervoltage
1 Values in parentheses: error number indicated by the PC parameter setting program (in preparation).
*) Can only be repaired by the operator if the maintenance manual is on hand!
out by
Operator
*)
Service
Operator
Operator
Electrician
8.1.4 Fault indication reset (TRIP-RESET)
1
3
X3
2028
j
mno
qr
Hi
Lo
88888
wx
2
mno
p
qr
a
bcd e
gfkihPS
8
p
888
8888
m
Hz
AV
W
%sh
°C
rpm
z
s
y
vtu
OFF
4
Hi
Lo
01 61
880Hr
5
000
%sh
rpm
6
Hz
m
W
1
AV
°C
ON
ne2bhxn355
a
bcde
j
g fkih PS
Fig. 26: Fault indication reset (TRIP-RESET)
How to reset the frequency inverter if a fault
occurs (TRIP−Reset):
Connect hand−held keypad to the
communication interface during operation.
Read and take down fault indication on the
keypad display.
Inhibit frequency inverter.
Disconnect pump−motor unit from the mains.
Carry out a fault analysis and eliminate the
fault.
Restart the pump−motor unit.
NOTE
The fault indication "EEr" triggered by an
external encoder can also be reset via a
HIGH−LOW signal at terminal E1 if the fault
has been eliminated in advance.
8.2 Service/ after-sales service
Our Service is available for work (in particular the
installation of spare parts, as well as
maintenance and repair work) not described in
these Operating Instructions.
Please observe when returning the
pump−motor unit to the manufacturer:
The pump−motor unit must be delivered
complete, i.e. not dismantled.
The original rating plate of the pump−motor
unit must be fixed properly, intact and
legible.All warranty claims are voided for
pump−motor units delivered for a damage
expertise without the original rating plate or
with a destroyed original rating plate.
In case of warranty claims, the manufacturer
must be informed of the operating conditions,
operating duration etc. and additional detailed
information must be provided on request if
necessary.
Danger from flammable, caustic or toxic
substances!
To protect the environment and persons, the
following applies:
Pump−motor units which have come into
contact with dangerous substances must
always be decontaminated before being
passed on to a workshop!
To provide proof that the decontamination was
carried out, a declaration of clearance must be
included with the pump−motor unit on delivery to
the workshop.
The form required for this purpose is available
from the manufacturer.
Gardner Denver Deutschland GmbH
P.O. Box 1510
D-97605 Bad Neustadt / Saale
Responsible for documentation:
Holger Krause
P.O. Box 1510
D-97605 Bad Neustadt / Saale
Designation:
G series Side channel blower
G-BH1e, G-BH7e
Types 2BH1...-..N, 2BH7...-..N,
2BH1...-..L, 2BH7...-..L
The side channel blower described above meets the following applicable Community harmonisation legislation:
2004/108/EC
Directive 2004/108/EC of the European Parliament and of the Council of 15 December 2004 on the
approximation of the laws of the Member States relating to electromagnetic compatibility and
repealing Directive 89/336/EEC
2006/42/EC
Directive 2006/42/EC of the European Parliament and of the Council of 17 May 2006 on machinery,
and amending Directive 95/16/EC
The protection targets of the directive 2006/95/EC have been met
Harmonised standards applied:
EN 1012-1:1996
EN 1012-2:1996
EN 50178:1197
EN 61800-3:2004
Compressors and vacuum pumps — Safety requirements — Part 1: Compressors
Compressors and vacuum pumps — Safety requirements — Part 2: Vacuum pumps
Electronic equipment for use in power installations
Adjustable speed electrical power drive systems —
Part 3: EMC requirements and specific test methods
Statement on health safety and on the protection of the environment
For the safety of our employees and to comply with statutory requirements on handling substances harmful to the health and
the environment, this statement must be enclosed, fully completed, with each unit/system sent.
Without the fully completed statement, repair/disposal is not possible and delays are unavoidable!
The statement is to be completed and signed by suitably qualified, authorised personnel at the operating organisation.
In the case of shipment to Germany, the statement is to be completed in German or English.
The statement is to be attached to the outside of the packing on shipment.
If necessary, the carrier is to be informed.
1. Product designation (type):
2. Serial number (no. BN):
3. Reason for sending:
4. The unit/system
has not come into contact with hazardous substances. There will be no hazards for personnel or the environment during
repair/disposal. Continue with "6. Legally binding statement“
has come into contact with hazardous substances. Continue with "5. Information on the contamination“
5. Information on the contamination
(if necessary provide more information on an additional sheet)
The unit/system was used in the following application:
and has come into contact with the following classifiable substances or substances presenting a hazard to health/environment:
The unit/system has been emptied in accordance with the operating instructions, flushed and cleaned externally.
Safety data sheets in accordance with the applicable regulations are enclosed ( sheet).
The following safety precautions are necessary for handling (e.g. personal protective equipment):
6. Legally binding statement
I herewith guarantee that the details specified are true and complete and that I, as signatory, am in a position to judge that this is
so.
We are aware that we are liable to the contractor for any damages arising from incomplete or incorrect specifications. We are
obliged to indemnify the contractor against claims for damages by third parties arising from incomplete or incorrect specifications.
We are aware that, irrespective of this statement, we are directly liable to third parties - in particular including the contractor's
employees tasked with repair/disposal.