Elmo Rletschle G-BH7e User Manual

Page 1
Edition: 12.2009 · 610.44520.40.000 Original operating instructions · English
2BH72..-..N 2BH73..-..N 2BH74..-..N 2BH75..-..N 2BH76..-..N
G-Serie
G-Series
Seitenkanal
Side Channel
Page 2
Contents
Contents
Design of side channel blowers in conjunction with frequency inverters ........................................... 3
Quick start guide ................................................................................................................................ 4
1 Safety instructions ...............................................................................................................................5
1.1 Definitions .................................................................................................................................5
1.1.1 Safety alert symbols and signal words.........................................................................5
1.1.2 Signal words.................................................................................................................5
1.1.3 Abbreviations used.......................................................................................................5
1.2 General safety and application notes........................................................................................5
1.3 Residual risks............................................................................................................................7
1.4 Application as directed..............................................................................................................9
1.5 Foreseeable Misuse................................................................................................................10
2 Technical data ...................................................................................................................................11
2.1 Mechanical data ......................................................................................................................11
2.1.1 Weights ......................................................................................................................11
2.1.2 Noise level..................................................................................................................11
2.1.3 Temperature increase ................................................................................................12
2.2 Electrical data..........................................................................................................................12
2.3 General data/operating conditions..........................................................................................13
3 Transport and handling .....................................................................................................................14
3.1 Transport devices....................................................................................................................14
3.2 Transport types .......................................................................................................................14
4 Installation .........................................................................................................................................16
4.1 Installation ...............................................................................................................................17
4.1.1 Important notes ..........................................................................................................17
4.1.2 Free spaces................................................................................................................18
4.1.3 Mounting.....................................................................................................................19
4.1.4 Final works .................................................................................................................20
4.2 Mounting of the muffler ...........................................................................................................20
4.3 Connecting the pump-motor unit to the system ......................................................................20
4.3.1 Important notes ..........................................................................................................20
4.3.2 Connecting the inlet line.............................................................................................21
4.3.3 Connecting the pressure line .....................................................................................21
4.4 Electrical installation................................................................................................................22
4.4.1 Important notes ..........................................................................................................22
4.4.2 Preparing works .........................................................................................................23
4.4.3 Connecting frequency inverters 2FC4152-1NE00 and 2FC4222-1NE00..................23
4.4.4 Connecting frequency inverters 2FC4302-1NE00 ... 2FC4752-1NE00.....................26
4.4.5 Wiring of control connections .....................................................................................29
4.4.6 Final works .................................................................................................................32
5 Commissioning..................................................................................................................................34
5.1 Preparation..............................................................................................................................34
5.2 Parameter setting....................................................................................................................35
5.2.1 The hand-held keypad 2FX4506-0NE00....................................................................35
5.2.2 Code table ..................................................................................................................37
5.3 Start-up of the pump-motor unit ..............................................................................................39
5.4 Shut-down of the pump-motor unit..........................................................................................40
6 Operation...........................................................................................................................................41
7 Shut-down and longer standstills ......................................................................................................42
7.1 Preparation..............................................................................................................................42
7.2 Storage conditions ..................................................................................................................42
© 2009 Gardner Denver Deutschland GmbH · Industriestraße 26 · 97616 Bad Neustadt · Germany
Transmittal, reproduction, dissemination and/or editing of this document as well as utilization of its contents and communication thereof to others without express authorization are prohibited. Offenders will be held liable for payment of damages. All rights created by patent grant or registration of a utility model or design patent are reserved.
Page 3
Design of side channel blowers in conjunction with frequency inverters
Servicing............................................................................................................................................43
8
8.1 Repair/ troubleshooting...........................................................................................................43
8.1.1 Malfunctions at side channel blower ..........................................................................43
8.1.2 Frequency inverter status indications.........................................................................44
8.1.3 Fault indication at the keypad ....................................................................................45
8.1.4 Fault indication reset (TRIP-RESET) .........................................................................47
8.2 Service/ after-sales service .....................................................................................................47
8.3 Decontamination and declaration of clearance.......................................................................48
9 Disposal.............................................................................................................................................49
Declaration of conformity.................................................................................................................. 50
Form for statement on safety ........................................................................................................... 51
Design of side channel blowers in conjunction with frequency inverters
1
7
6
10
11
2
4
9
8
Position Description
1 Frequency inverter 2 Inlet connection with muffler and arrow indicating delivery direction 3 Discharge connection with muffler and arrow indicating delivery direction 4 Base 5 Arrow indicating direction of rotation 6 Blower cover 7 blower housing 8 Drive motor 9 Fan guard above the motor fan with rating plate, warning notices and arrow
indicating direction of rotation 10 Status display with 2 light-emitting diodes (red, green) 11 Communication interface for connecting the hand-held keypad
Fig. 1: Design of side channel blowers in conjunction with frequency inverters
5
3
2bhxn402
44 35
© Gardner Denver Deutschland GmbH 3 / 52 610.44520.40.000
Page 4
Quick start guide
Quick start guide
Side channel blowers are pre-configured for four operating modes. It only takes a few steps and they are ready for operation:
ACHTUNG
The drive motor is protected against
overheating by a thermal detector.
If the drive motor gets too hot, the
frequency inverter will switch off the pump-motor unit.
Please contact the manufacturer if the
hydraulic process does not allow immediate switch-off.
A minimum wiring is required for
commissioning! ( 22)
1 Read the safety instructions.
The safety instructions start on page 5.
2 Install the pump-motor unit and attach it.
Listing of the mounting steps starts on
3 Wire the pump-motor unit.
4 Put the pump-motor unit into operation.
5 Adapt important process parameters.
page 16.
Please observe that a minimum wiring is
required!
Otherwise commissioning of the pump-
motor unit is not possible.
Important notes concerning the wiring
start on page 22.
Description of the commissioning steps
starts on page 34.
Adapt acceleration and deceleration time to
the hydraulic process via C0012 and C0013.
Description of parameter changing
starts on page 35.
6 Adjust the speed.
A) Speed adjustment using a potentiometer
The speed is adjusted via the analog input. The speed can be adjusted between
aminimum and a maximum value.Description of potentiometer wiring starts on page 30.
B) Operation with several adjustable fixed speeds
The speed of the pump−motor unit can be
adjusted in steps of 1000/min via the digital inputs E3 and E4.
Description of the wiring of E3 and E4
starts on page30.
C) Operation with one fixed speed
Connect handheld keypad. Set required fixed speed under C0140. Disconnect handheld keypad. The pumpmotor unit will be operated with
this speed when switched on.
Description of hand−held keypad
connection and parameter changing starts on page35.
D) Speed adjustment using the keypad
Connect handheld keypad. Select C0140. Set the required speed during the process using the keys _.. The pumpmotor unit will be operated with
the last set speed when switched on.
Description of hand−held keypad
connection and parameter changing starts on page35.
610.44520.40.000 4 / 52 © Gardner Denver Deutschland GmbH
Page 5
Safety instructions
1 Safety instructions
1.1 Definitions
To point out dangers and important information, the following signal words and symbols are used in these Operating Instructions:
1.1.1 Safety alert symbols and signal words
The safety alert symbol is located in the safety instructions in the highlighted heading field on the left next to the signal word (DANGER, WARNING, CAUTION).
Safety instructions with a safety alert symbol indicate a danger of injuries.
Be sure to follow these safety instructions to protect against injuries or death!
Safety instructions without a safety alert symbol indicate a danger of damage. – Be sure to follow these safety instructions to avoid material damage!
1.1.2 Signal words
DANGER
WARNING
CAUTION
NOTICE
NOTE
Danger of injuries.
Indicates an imminently hazardous situation, that will result in death or serious injury if the corresponding measures are not taken.
Danger of injuries.
Indicates a potentially hazardous situation, that could result in death or serious injury if the corresponding measures are not taken.
The signal words are located in the safety precautions in the highlighted heading field.
They follow a certain hierarchy and indicate (in conjunction with the safety alert symbol, see Chapter 1) the seriousness of
the danger and the type of warning.
See the following explanations:
DANGER
WARNING
CAUTION
Danger of injuries.
Indicates a potentially hazardous situation, that may result in minor or moderate injury if the corresponding measures are not taken.
CAUTION
Danger of damage.
Indicates a potentially hazardous situation that may result in property damage if the corresponding measures are not taken.
NOTICE
Indicates a possible disadvantage, i.e. undesirable conditions or consequences can occur if the corresponding measures are not taken.
NOTE
Indicates a possible advantage if the corresponding measures are taken; tip.
1.1.3 Abbreviations used
Product designation
For side channel blower in conjunction with frequency inverters the term pumpmotor unit is used in these Instructions.
Crossreference
Crossreferences to other parts of these Instructions are marked with a book symbol: ( 9)
1.2 General safety and application notes
WARNING
Improper use of the pumpmotor unit can result in serious or even fatal injuries!
These Operating Instructions
must have been read completely and
understood before beginning any work with or at the pumpmotor unit,
must be strictly observed, must be available at the operating location of
the pumpmotor unit.
© Gardner Denver Deutschland GmbH 5 / 52 610.44520.40.000
Page 6
Safety instructions
WARNING
Improper use of the pumpmotor unit can result in serious or even fatal injuries!
Only operate the pumpmotor unit
for the purposes indicated under "Application
as directed"!
with the media indicated under "Application
as directed"!
with the values indicated under "Technical
data"!
WARNING
Improper use of the pumpmotor unit can result in serious or even fatal injuries!
All work on and with the pumpmotor unit (transport, installation, operation, shut−down, maintenance, disposal) may only be carried out by trained, reliable expert personnel!
WARNING
When working on the pumpmotor unit, there is a danger of injury, e.g. in the form of cuts/cutting off, crushing and burns!
During all work on and with the pump−motor unit (transport, installation, operation, shutdown, maintenance, disposal) wear personal safety equipment (safety helmet, safety gloves, safety shoes)!
WARNING
Hair and clothing can be pulled into the pump−motor unit or caught and wound up by moving parts! Do not wear long, loose hair or wide, loose clothing! Use a hairnet!
DANGER!
Electrical danger!
Work on electrical installations may be carried out by trained and authorized electricians only!
DANGER!
Electrical danger!
Before beginning work on the pumpmotor unit or system, the following measures must be carried out :
Deenergize. Secure against being switched on again. Determine whether deenergized. Ground and shortcircuit. Cover or block off adjacent energized parts.
DANGER!
Electrical danger!
Do not open the frequency inverter until absence of electricity has been ensured!
WARNING
Danger due to vacuum and gauge pressure: sudden escape of media (skin and eye injuries), sudden drawingin of hair and clothing!
Danger due to escaping media: burns!
Use mounting elements, connections, lines, fittings and containers with sufficient freedom from leaks and strength for the pressures which occur.
Check the mounting elements, connections, lines, fittings and containers for strength, leaks and firm seating at regular intervals!
WARNING
Danger from rotating parts (motor fan, impeller, shaft): cutting/cutting off of extremities, grasping/winding up of hair and clothing! Danger due to vacuum and gauge pressure: sudden escape of media (skin and eye injuries), sudden drawingin of hair and clothing! Danger due to escaping media: burns!
Commissioning and operation only under the following conditions:
The pumpmotor unit must be completely
assembled. When doing so, pay particular attention to the following components:
the blower cover, the mufflers on inlet and discharge
connections,
the fan guard.
The pipes and hoses must be connected to
inlet and discharge connections.
Inlet and discharge connections and the
connected pipes/hoses may not be closed, clogged or soiled.
Check the mounting elements, connections
of the pipe/hose connections, lines, fittings and containers for strength, leaks and firm seating at regular intervals.
610.44520.40.000 6 / 52 © Gardner Denver Deutschland GmbH
Page 7
Safety instructions
WARNING
Danger from rotating parts (motor fan, impeller, shaft): cutting/cutting off of extremities, grasping/winding up of hair and clothing!
Danger due to vacuum and gauge pressure: sudden escape of media (skin and eye injuries), sudden drawingin of hair and clothing! Danger due to escaping media: burns!
Before beginning work on the pumpmotor unit, take the following measures :
Shut down pump−motor unit and secure
against being switched on again.
Attach a sign on the system controller and
on the control elements for the pump−motor unit: "DANGER! Maintenance work on the vacuum pump/compressor! Do not switch on!"
Wait for pump−motor unit to come to a
complete stop.
Observe run−on time!
Allow pumpmotor unit to cool! Shutoff lines.
Release pressure.
Make sure that no vacuum or gauge
pressure is present in the lines/tanks to be opened.
Make sure that no media can escape.
WARNING
Danger from rotating impeller: cutting/cutting off of extremities!
The rotating impeller is accessible with the inlet and discharge connections open!
Do not reach into the pumpmotor unit through open connections!
Do not insert objects into the pumpmotor unit through the openings!
WARNING
Danger of burns from hot surface of the pumpmotor unit and from hot media!
High temperatures of up to approx. 160 °C [320 °F] can occur on the surface of the pumpmotor unit:
Cover the pump−motor unit with a suitable
touch protection (e.g. perforated plate cover or wire cover).
Do not touch during operation! Allow to cool after shutdown!
1.3 Residual risks
WARNING
Danger zone:
Hot surface of up to approx.160 °C [320 °F].
Hazard:
Possible burns.
Protective measures:
Cover the pumpmotor unit with a suitable touch protection (e.g. perforated plate cover or wire cover).
WARNING
Danger zone:
Fan guard
Hazard:
Long, loose hair can be drawn into motor fan through the fan guard grate, even with
fan guard mounted!
Protective measures:
Wear hair net!
WARNING
Danger from rotating impeller: cutting/cutting off of extremities!
The rotating impeller is accessible with the inlet and discharge connections open!
With free entry and exit of gases, i.e. with direct intake out of or direct feeding into the atmosphere without piping, the following therefore applies:
Provide the inlet and discharge connections
of the pump−motor unit either with additional mufflers or with additional piping of a sufficient length to prevent access to the impeller!
© Gardner Denver Deutschland GmbH 7 / 52 610.44520.40.000
Page 8
Safety instructions
WARNING
Danger zone:
Missing or defective muffler on inlet or discharge connection.
Hazard:
Possible serious hearing damage due to emitted noise.
Protective measures:
Have missing or defective mufflers replaced. Conduct a noise measurement in the system
after installing the pumpmotor unit. The following measures must be taken by the
operator:
from 85 dB(A):
Hearing protection must be available.
from 90 dB(A):
Mark noise area with a warning sign. Wear hearing protection.
WARNING
Danger zone:
Environment of pumpmotor unit.
Hazard:
Possible serious hearing damage due to emitted noise.
Protective measures:
Conduct a noise measurement in the system during operation after installing the
pumpmotor unit. The following measures must be taken by the
operator:
from 85 dB(A):
Hearing protection must be available.
from 90 dB(A):
Mark noise area with a warning sign. Wear hearing protection. With free entry and exit of gases, i.e. with
direct intake out of or direct feeding into the atmosphere without piping, attach an additional muffler.
CAUTION
Danger zone:
Frequency inverter
Hazard:
Material damage at the frequency inverter caused by switching on the device too
frequently with too short intervals.
Protective measures:
In the case of cyclic mains switching for a longer time period, allow at least 3 minutes between two switchon actions.
CAUTION
Danger zone:
Side channel blower
Hazard:
Material damage at the side channel blower caused by too high speeds.
Protective measures:
Do not set the output frequency at the
frequency inverter higher than the maximum frequency specified in the documentation.
Use special overspeed monitors if
necessary.
610.44520.40.000 8 / 52 © Gardner Denver Deutschland GmbH
Page 9

Safety instructions
1.4 Application as directed
Validity of the Operating Instructions
These Operating Instructions are valid for G-BH7e series side channel blower in conjunction with frequency inverters equipped with the following frequency inverters:

Type
Supply voltage
2FC 4 xxx - 1NE00 1x 35
4 = 400 V/500 V
Power (e.g.152 = 15 ´ 10 (e.g.. 752 = 75 ´ 10
2
W = 1,5 kW)
2
W = 7,5 kW)
1NE00 = integrated inverter
Hardware version
Software version
Fig. 2: Typschild
These Operating Instructions
contain instructions bearing on transport and
handling, installation, commissioning, operation, shutdown, storage, servicing and disposal,
must be completely read and understood by
all operating and servicing personnel before beginning to work,
must be strictly observed, must be available at the site of operation in a
complete and perfectly legible condition.
With differing gases/gas−air mixtures,
inquire with the manufacturer.
are intended for industrial applications. are designed for continuous operation:
With increased switch−on frequency (at
equal intervals of approx. 5 times per hour) or increased gas entry temperature and ambient temperature, the limit overtemperature of the winding and the bearings can be exceeded.
Consultation with the manufacturer is
required for operating conditions of this kind.
Operating and servicing personnel
are equipped with a threephase drive motor
These persons must be trained and
authorized for the work to be carried out.
Work on electrical installations may be carried
out by trained and authorized electricians only.
G-BH1e series side channel blower in conjunction with frequency inverters
with mounted frequency inverter.
are available in the following models:
singleimpeller (singlestage) twoimpeller (twostage) threeimpeller (threestage)
Higher pressure differences can be achieved with the twoimpeller and threeimpeller pump−motor units.
nash_elm o Industries Gmb H Indust riestras se 26 D-97616 Ba d Neustadt
Prod.-ID
Prod.-No. Ser.-No.
Input
Output
Type
Version
2
3
1
ne2bhxn014
are pumpmotor units for generating vacuum
or gauge pressure.
are used to extract, pump and compress the
following gases:
Air, Nonflammable, nonaggressive,
nontoxic and non−explosive gases or gasair mixtures.
are primarily intended for higher pressure
conditions;
During operation the limit values listed under "Technical data" must always be complied with. ( 11)
© Gardner Denver Deutschland GmbH 9 / 52 610.44520.40.000
Page 10
Safety instructions
1.5 Foreseeable Misuse
It is prohibited
to use the pump−motor units in applications
other than industrial applications unless the necessary protection is provided on the system, e.g. touch guards suitable for children’s fingers,
to use the pump−motor units in rooms in
which explosive gases can occur,
to extract, deliver and compress explosive,
flammable, corrosive or toxic media,
to operate the pump−motor units with values
other than those specified in the chapter "Technical data".
Any unauthorized modifications of the pumpmotor units are prohibited for safety reasons.
The operator is only permitted to perform the maintenance and service work described in these Operating Instructions.
Any maintenance and service work which goes beyond this many only be performed by companies authorized by the manufacturer (inquire with the manufacturer).
610.44520.40.000 10 / 52 © Gardner Denver Deutschland GmbH
Page 11
Technical data
2 Technical data
2.1 Mechanical data
2.1.1 Weights
Weight Type
approx. [kg] approx. [lbs]
Singleimpeller design 2BH72100.N1 20 44 2BH72100.N5 32 71 2BH73100.N2 20 44 2BH73100.N6 35 77 2BH74100.N1 27 60 2BH74100.N5 42 93 2BH75100.N2 39 86 2BH75100.N6 48 106 2BH76100.N3 45 99 Twoimpeller design 2BH72200.N5 38 84 2BH73200.N5 40 88 2BH73200.N8 46 101 2BH74200.N2 43 95 2BH74200.N5 49 108 2BH75200.N7 61 134 2BH76200.N3 58 128 2BH76200.N4 68 150 Three-impeller design 2BH76300.N6 96 212
2.1.2 Noise level
Measurement conditions
Measuring-surface sound-pressure level as per EN ISO 3744, measured at a distance of 1 m [3.28 ft] at an operating point of approximately 2/3 of the permissible total pressure difference with the lines connected without a vacuum or pressure relief valve, tolerance 3 dB (A).
Type
Singleimpeller design 2BH72100.N1 70 70 74 2BH72100.N5 70 70 74 2BH73100.N2 70 70 76 2BH73100.N6 70 70 76 2BH74100.N1 70 70 76 2BH74100.N5 70 70 76 2BH75100.N2 70 70 78 2BH75100.N6 70 70 78 2BH76100.N3 70 71 77 Twoimpeller design 2BH72200.N5 70 70 74 2BH73200.N5 70 70 76 2BH73200.N8 70 70 76 2BH74200.N2 70 70 76 2BH74200.N5 70 70 76 2BH75200.N7 70 70 78 2BH76200.N3 70 71 80 2BH76200.N4 70 71 80 Three-impeller design 2BH76300.N6 77 80 80
1m measuringsurface
soundpressure level L for
operation with output
frequency [dB(A)]
50 Hz 60 Hz 86 Hz
© Gardner Denver Deutschland GmbH 11 / 52 610.44520.40.000
Page 12
Technical data
2.1.3 Temperature increase
The information listed in the following tables corresponds to the heating of the side channel housing and the air exiting compared to the ambient temperature during operation with a permissible total pressure difference and an air pressure of 1013 mbar [14.7 psi]. At lower air pressures these values increase.
Type
Temperature increase for
operation with output
frequency (approx.)
50 Hz 60 Hz 86 Hz
T
[K]
∆υ
[F]
T
[K]
∆υ
[F]
T
[K]
∆υ
[F]
Singleimpeller design 2BH72100.N1 52 126 61 142 2BH72100.N5 52 126 77 171 2BH73100.N2 81 178 86 187 2BH73100.N6 88 190 112 234 2BH74100.N1 90 194 101 214
120≤ 248
2BH74100.N5 114 237 120 248 2BH75100.N2 120 248 112 243 2BH75100.N6 120 248 120 248 2BH76100.N3 118 244 124 255 Twoimpeller design 2BH72200.N5 55 131 86 186 2BH73200.N5 81 178 124 255 2BH73200.N8 120 248 120 248 2BH74200.N2 89 192 80 176 2BH74200.N5 121 250 117 243
120≤ 248
2BH75200.N7 125 257 110 230 2BH76200.N3 124 255 126 259 2BH76200.N4 124 255 126 259 Three-impeller design 2BH76300.N6 120 248 120 248
120≤ 248
Tightening torques for screw connections
The following values apply if no other data are given. With nonelectrical connections, property classes of 8.8 and 8 or higher as per DIN ISO 898 (DIN EN 20898 / DIN ISO 898) are assumed.
Tightening torques for
nonelectrical connections
Thread [Nm] [lb-in]
M4 2,7 … 3,3 23,9 … 29,2 M5 3,6 … 4,4 31,9 … 38,9 M6 7,2 … 8,8 63,7 … 77,9
M8 21,6 … 26,4 191 … 234 M10 37,8 … 46,2 335 … 409 M12 63,0 … 77,0 558 … 681
Tightening torques for cable
and conduit glands Metal
Thread [Nm] [lb-in]
M12x1,5 4,0 … 6,0 35,4 … 53,1 M16x1,5 5,0 … 7,5 44,3 … 66,4 M20x1,5 6,0 … 9,0 53,1 … 79,7 M32x1,5 M40x1,5
8,0 … 12,0 70,8 … 106
Tightening torques for cable
and conduit glands Plastic
Thread [Nm] [lb-in]
M12x1,5 2,0 … 3,5 17,7 … 31,0 M16x1,5 3,0 … 4,0 26,6 … 35,4 M20x1,5 4,0 … 5,0 35,4 … 44,3 M32x1,5 M40x1,5
5,0 … 7,0 44,3 … 62,0
2.2 Electrical data
See rating plate.
610.44520.40.000 12 / 52 © Gardner Denver Deutschland GmbH
Page 13
Technical data
2.3 General data/operating conditions
Conformity
CE LowVoltage Directive
Vibration resistance
Acceleration resistant up to 2g (Germanischer Lloyd, general conditions)
Vibration velocity
max. v
4 mm/s [0,013 ft/s] Depending on the application case and the
eff
system type it may be necessary to use vibration dampers.
Site altitude
min. 0 m üNN [0 ft amsl] max. 1000 m üNN [3280 ft amsl] For installations above 1000 m amslA [3280 ft
amsl] consultation of the manufacturer is required.
Climatic conditions
Class 3K3 to EN 50178 (without condensation, relative humidity 30 ... 95 %)
Ambient temperatures
Transport min. -25°C [-13°F] max. +70°C [+158°F] Storage min. -25°C [-13°F] max. +60°C [+140°F] Operation min. -20°C [-4°F] max. +40°C [+104°F] rated value +25°C [+77°F]
Between +25 °C [+77 °F] and +40 °C [+104 °F] reduce the total pressure difference indicated on the rating plate by 0.7 %/°C [0.4 %/°F]. Operation at higher temperatures may damage the winding and shorten the grease change interval.
Temperature of pumped gases
max. +40°C [+104°F] rated value +15°C [+59°F]
Pumpmotor units for higher media temperatures Pump on request.
Pressures
Inlet pressure min. See rating plate Discharge pressure
max. See rating plate during compressor operation
Permissible total
pressure difference
max. See rating plate The total pressure difference specified on the
rating plate only applies under the following conditions:
Ambient temperature: 25 °C [77 °F] Temperature of the pumped gas at the inlet
connection: 15 °C [59 °F]
Pressure:
for vacuum−pump operation: 1013 mbar
[14.7 psia] at the discharge connection
for compressor operation:
1013 mbar [14.7 psia] at the inlet connection
zulässiger Druck im
Aggregat
max. 2 bar abs. [29 psia] At this pressure the operation of the
pumpmotor unit may be considerably impaired. Provide a corresponding protective device (e.g. pressure relief valve) if necessary.
© Gardner Denver Deutschland GmbH 13 / 52 610.44520.40.000
Page 14
Transport and handling
3 Transport and handling
WARNING
Tipping or falling can lead to crushing, broken bones etc.!
Sharp edges can cause cuts!
Wear personal safety equipment (safety
gloves, safety shoes and safety helmet) during transport!
WARNING
Danger from lifting heavy loads!
Manual handling of the pumpmotor unit is only permitted within the following limits:
max. 30 kg [max. 66 lbs] for men max. 10 kg [max. 22 lbs] for women max. 5 kg [max. 11 lbs] for pregnant women
For weights above the given values use suitable lifting appliances and handling equipment!
Weight of the pumpmotor units: ( 11)
WARNING
Danger from tipping or falling loads!
Prior to transport and handling make sure
that all components are securely assembled and secure or remove all components the fasteners of which have been loosened!
When transporting with lifting equipment,
observe the following basic rules:
The lifting capacity of lifting equipment
and lifting gear must be at least equal to the unit’s weight. For the weight of the pumpmotor units see:: ( 11)
The pump−motor unit must be secured
so that it cannot tip or fall.
Do not stand or walk under suspended
loads!
3.1 Transport devices
All pumpmotor units with a weight of more than 30 kg are equipped with an eye bolt at the side channel housing.
The crane hook can be hooked directly into the eye bolt.
Alternatively the pumpmotor units can be transported with lifting belts.
WARNING
Danger from tipping or falling loads!
Place the lifting belts under the side channel
housing and under the motor.
Attach the lifting belts in such a way that the
suspending pumpmotor unit is balanced and cannot slip out of the lifting belts.
3.2 Transport types
CAUTION
Pumpmotor unit damage caused by improper manual handling!
Do not carry the pump−motor unit by holding
it at the frequency inverter!
Avoid heavy impact loads during transport.
CAUTION
Pumpmotor unit damage caused by improper transport with lifting appliances!
Do not attach the lifting appliances to the
frequency inverter!
The eye bolt at the side channel housing
must
be screwed tightly. be exactly in axial direction of the
pumpmotor unit. Lay shims under the eye bolt if necessary.
Loads laterally to the ring level are not
permissible.
Avoid heavy impact loads during transport.
610.44520.40.000 14 / 52 © Gardner Denver Deutschland GmbH
Page 15
Transport and handling
Type of transport Type
manually with lifting
appl.
Singleimpeller design 2BH72100.N1 X 2BH72100.N5 X 2BH73100.N2 X 2BH73100.N6 X 2BH74100.N1 X 2BH74100.N5 X 2BH75100.N2 X 2BH75100.N6 X 2BH76100.N3 Twoimpeller design 2BH72200.N5 X 2BH73200.N5 X 2BH73200.N8 X 2BH74200.N2 X 2BH74200.N5 X 2BH75200.N7 X 2BH76200.N3 X 2BH76200.N4 Threeimpeller design 2BH76300.N6 X
X
X
© Gardner Denver Deutschland GmbH 15 / 52 610.44520.40.000
Page 16
Installation
4 Installation
WARNING
Improper use of the pumpmotor unit can result in serious or even fatal injuries!
Have you read the chapter "Safety instructions"? ( 5)
Otherwise you may not carry out any work with or on the pumpmotor unit!
DANGER!
Danger from missing view into area of pumpmotor unit!
When operating the control elements without a view into the area of the pumpmotor unit, there is a danger that the pumpmotor unit will be switched on while other persons are still performing work on it. Severest injuries are possible!
Provide control elements at a location with a view of the pumpmotor unit.
DANGER!
Electrical danger!
The pumpmotor unit must be installed so that the electrical equipment cannot be damaged by external influences!
In particular, the incoming cables must be routed securely, e.g. in cable ducts, in the floor etc.
WARNING
Danger of balance damage caused by vibration!
Vibrating environments can cause balance damage!
Install the pumpmotor unit on a solid foundation or on a solid mounting surface.
Check screw glands/unions for mounting the pumpmotor unit on the mounting surface regularly for strength and firm seating.
WARNING
Danger of crushing due to pumpmotor unit tipping over!
Wear personal safety equipment (safety gloves and safety shoes). Handle the pumpmotor unit with the appropriate care.
Install the pumpmotor unit on a solid foundation or on a solid mounting surface!
Check screw glands/unions for mounting the pumpmotor unit on the mounting surface regularly for strength.
WARNING
Danger of fire from flammable substances!
The pumpmotor unit must never come into contact with flammable substances.
For exact information on the temperature increase see: ( 12).
WARNING
Danger of burns from hot surface of the pumpmotor unit and from hot media!
High temperatures of up to approx. 160 °C [320 °F] can occur on the surface of the pumpmotor unit.
The pumpmotor unit must be installed so that accidental touch of its surface is not possible. Cover the pumpmotor unit with a suitable touch protection (e.g. perforated plate cover or wire cover).
WARNING
Danger of injuries from flying parts!
Select installation so that parts that are thrown out through the grate if the motor fan breaks cannot hit persons!
CAUTION
Danger of tripping and falling!
Make sure the pumpmotor unit does not present a danger of tripping.
Lay cables and pipes so that they cannot be reached during operation (recessed in floor, in ducts on the wall etc.).
610.44520.40.000 16 / 52 © Gardner Denver Deutschland GmbH
Page 17
Installation
CAUTION
Danger of overheating due to hot surface of pumpmotor unit!
High temperatures can occur on the surface of the pumpmotor unit.
Temperaturesensitive parts, such as cables or electronic components, may not come into contact with the surface of the pump−motor unit.
CAUTION
Danger of pumpmotor unit damage caused by penetration of foreign bodies!
On delivery all connection openings are closed in order to prevent the penetration of foreign bodies. Remove the seals right before the respective mounting step.
Installation sequence
The pumpmotor unit is ready to connect on delivery.
CAUTION
The pumpmotor unit may be damaged if it is installed and commissioned after longer storage periods without special preparation!
If the pumpmotor unit was stored for a longer period prior to installation, it has to be prepared for installation: ( 42)
Carry out the following steps to install the pumpmotor unit:
1 Set up the pumpmotor unit and attach it. 2 Mount the muffler (supplied loose) if
necessary.
3 Mount the threaded flange or hose flange to
the muffler if necessary.
4 Connect inlet and discharge connections to
the system.
5 Establish electrical connection.
4.1 Installation
CAUTION
Pumpmotor unit damage caused by incorrect mounting or use under impermissible ambient conditions!
Install and connect the pumpmotor unit only according to the instructions given in this chapter.
If the pumpmotor unit is to be used under differing operating conditions, the manufacturer must be consulted.
NOTE
Dimensioned drawings with detailed dimensions, including fastening dimensions, are provided by the manufacturer.
4.1.1 Important notes
Ambient conditions
The pumpmotor unit is suitable for installation
in a dusty or damp environment, in buildings, in the open.
For proper installation in the open, protect
the pump−motor unit from exposure to intensive sunlight, e.g. by attaching a protective roof.
Further special protective devices against
the effects of weathering are not required.
The motors of the units are to enclosure IP55. The insulation is tropic−proof.
Installation conditions
Attach the pump−motor unit only to even
surfaces.
Do not exceed the maximum permissible
vibration velocity veff = 4mm/s [0.013 ft/s].
Installation altitude max. 1000 m amsl [3280 ft
amsl].
When installing at an altitude of more than
1000 m [3280 ft] above sea level, first inquire with the manufacturer.
© Gardner Denver Deutschland GmbH 17 / 52 610.44520.40.000
Page 18
Installation
Noise radiation
In order to reduce the noise radiation,
do not mount pump−motor unit on
noiseconducting or noiseradiating parts (e.g. thin walls or sheetmetal plates).
provide pumpmotor unit with
soundinsulating intermediate layers (e.g. rubber buffers under the base of the pumpmotor unit) if necessary.
install the pump−motor unit on a stable
foundation or on a rigid mounting surface. This will ensure quiet and low−vibration running of the pumpmotor unit.
Components for reducing noise on the pumpmotor unit:
Muffler (included in the scope of supply)
On delivery the pump−motor units are
equipped with attached mufflers as standard.
The mufflers considerably reduce the noise
radiation.
Additional muffler (available as accessories):
The additional mufflers enable a further
noise reduction.
They may only be used in systems without
piping, i.e. with direct intake out of the atmosphere or direct feeding into the atmosphere.
4.1.2 Free spaces
CAUTION
Material damage caused by overheating of the pumpmotor unit!
It is absolutely necessary to observe the
required free spaces in order to cool the pumpmotor unit sufficiently.
Ventilation screens and ventilation openings
must remain clear.
The discharge air of other pump−motor units
may not be directly sucked in again!
> 100 mm
[ > 4 in ]
> 100 m m > 100 m m
[ > 4 in ] [ > 4 in ]
Noise protection hoods (available as
accessories):
Noise protection hoods are suitable for
installation in rooms and in the open.
They reduce the overall sound pressure
level and tonal components that are perceived as particularly annoying.
Installation variants
Units with motors without condensation water openings can be installed in different ways:
horizontally, vertically on the cover of the side channel
housing ("cover installation"),
vertically on a wall.
CAUTION
Danger of rusting due to collection of condensed water in drive motor area!
Install and attach units with motors equipped with condensation water openings only horizontally, base at the bottom.
a
[mm] [in] [mm] [in]
2BH72.. 2BH73.. 2BH74..
> 30 > 1,18 2BH75.. 2BH76..
Fig. 3: Free spaces
b
Ne2bhxn001
a b Type
> 34 > 1,34
> 52 > 2,05
> 53 > 2,09
610.44520.40.000 18 / 52 © Gardner Denver Deutschland GmbH
Page 19
4.1.3 Mounting
NOTE
Dimensioned drawings with detailed dimensions, including fastening dimensions, are provided by the manufacturer.
Horizontal installation
ne2bhxn002d
Fig. 4: Schematic diagram: horizontal installation
Mounting sequence:
1 Select suitable mounting elements. 2 Attach the pumpmotor unit to the surface:
Screw the base of the pump−motor unit to
the surface via the mounting holes.
When doing so, be sure to provide all
mounting holes with screws!
Installation
ne2bhxn002c
Fig. 5: Schematic diagram: installation on the cover
of the side channel housing
Mounting sequence:
1 Attach the rubber feet to the pumpmotor unit:
Screw the stud bolts of the rubber feet into
the bore holes in the cover of the gas ring blower housing.
Tighten the rubber feet.
2 Mount the pumpmotor unit together with the
rubber feet on the installation surface:
Select suitable mounting elements for the
threaded hole.
Screw the rubber feet to the installation
surface via the threaded holes.
Vertical mounting on a wall
Vertical installation on the cover of the gas ring blower (”cover installation”)
NOTE
You need three rubber feet for the "cover installation" of the pumpmotor unit.
The rubber feet are available as accessories. They come with a stud bolt on one side and a threaded hole on the other side.
ne2bhxn002a
WARNING
Danger of crushing caused by pump−motor unit tipping over!
Avoid free−standing installation of the pumpmotor unit!
Always screw the rubber feet to the foundation or to the installation surface!
Check screw connections regularly for tightness.
ne2bhxn002b
Fig. 6: Schematic diagram: vertical mounting on a
Mounting sequence:
© Gardner Denver Deutschland GmbH 19 / 52 610.44520.40.000
wall
Page 20
Installation
1 Select suitable mounting elements. 2 Position the pumpmotor unit as close to the
wall as possible on a stable supporting plate with sufficient load−bearing capacity.
The pump−motor unit must be positioned
with the base towards the wall.
3 Attach the pumpmotor unit to the wall:
Screw the base of the pump−motor unit to
the wall via the mounting holes.
When doing so, be sure to provide all
mounting holes with screws!
4 Remove the supporting plate.
4.1.4 Final works
After installing the pumpmotor unit, the eye bolt must be removed or screwed tightly.
4.2 Mounting of the muffler
The pumpmotor units are supplied with mufflers for inlet and discharge connections as standard. The mufflers are marked by arrows in the following drawings.
2BH721 ...2BH761 (singleimpeller pump−motor units)
ne2bhxn003a
Fig. 7: Mounting of the muffler 2BH721 ...2BH761.
With the following pumpmotor units, the inlet−side muffler is included loose for packagingrelated reasons. It must be mounted by the operator.
2BH732 ... 2BH762 (twoimpeller pump−motor units with twostage design)
ne2bhxn003b
Fig. 8: Mounting of the muffler 2BH732 ... 2BH762
2BH763 (three−impeller pump−motor unit with threestage design)
ne2bhxn003c
Fig. 9: Mounting of the muffler 2BH763
WARNING
Danger from rotating impeller: cutting/cutting off of extremities!
The rotating impeller is accessible with the inlet and discharge connections open!
With free entry and exit of gases, i.e. with direct intake out of the atmosphere or direct feeding into the atmosphere without piping, the following therefore applies:
Provide the inlet and discharge connections of the pumpmotor unit either with additional mufflers or with additional piping of a sufficient length to prevent access to the impeller!
4.3 Connecting the pump-motor unit to the system
4.3.1 Important notes
Delivery direction of the gases
The pumped gases are sucked in via the inlet connection and discharged via the discharge connection.
The delivery direction of the gases is marked by arrows on the connections:
The inlet connection with the corresponding
muffler is marked by an arrow pointing into the pumpmotor unit.
The discharge connection with the
corresponding muffler is marked by an arrow pointing out of the pumpmotor unit.
610.44520.40.000 20 / 52 © Gardner Denver Deutschland GmbH
Page 21
Installation
Rotation direction of the shaft
The rotation direction of the shaft is marked by an arrow on the cover of the side channel housing and by an arrow on the fan guard of the motor.
WARNING
Danger from interchanging inlet and pressure line!
Interchanged inlet and pressure lines can lead to damage to the pumpmotor unit and the system, and as a result of this to serious injuries!
Make sure that the inlet and the pressure line cannot be confused when connecting.
Pay attention to the clear marking with the arrows indicating the delivery direction on the inlet and discharge connections.
WARNING
Danger due to vacuum and gauge pressure!
Danger due to escaping media!
During operation, connected pipes and vessels are vacuumized or pressurized!
Use only mounting elements, connections, lines, fittings and containers with sufficient freedom from leaks and strength for the pressures which occur.
Make sure that the mounting elements and connections are mounted firmly enough and leakfree!
CAUTION
If the pumped gases are passed on the discharge side in a closed pipe system, then it must be ensured that the pipe system is adapted to the maximum discharge pressure.
Connect a pressure relief valve upstream if necessary.
NOTE
Attach pipes/hoses free of mechanical tensions.
Support the weight of the pipes/hoses.
4.3.2 Connecting the inlet line
WARNING
Danger from solid bodies and impurities in the pumpmotor unit!
If solid bodies penetrate into the pump−motor unit, blades of the impellers can break and broken pieces can be thrown out.
Install a filter in the inlet line. Replace filter regularly!
The pumped gases are taken in via the inlet line.
Connect the inlet line to the inlet connection.
The inlet connection with the
corresponding muffler is marked by an arrow pointing into the pumpmotor unit.
A If you use an inlet pipe, you can screw it
directly into the muffler.
B If you use an inlet hose, you need a hose
flange available as accessories:
Screw the hose flange to the muffler. Push the hose onto the hose flange and
secure it with a hose clamp.
Observe tightening torques ( 12)
4.3.3 Connecting the pressure line
The pumped gases are discharged via the pressure line.
Connect the pressure line to the discharge
connection.
The discharge connection with the
corresponding muffler is marked by an arrow pointing out of the pumpmotor unit.
A If you use a pressure pipe, you can screw it
directly into the muffler.
B If you use a pressure hose, you need a hose
flange available as accessories:
Screw the hose flange to the muffler Push the hose onto the hose flange and
secure it with a hose clamp.
Observe tightening torques ( 12)
© Gardner Denver Deutschland GmbH 21 / 52 610.44520.40.000
Page 22
Installation
4.4 Electrical installation
DANGER!
Electrical danger!
Malpractice can result in severe injuries and material damage!
DANGER!
Electrical danger!
The electrical connection may be carried out by trained and authorized electricians only!
DANGER!
Electrical danger!
Before beginning work on the pumpmotor unit or system, the following measures must be carried out:
Deenergize. Secure against being switched on again. Determine whether deenergized. Ground and shortcircuit.
Cover or block off adjacent energized parts.
DANGER!
Electrical danger!
The terminal box of the frequency inverter must be free from
foreign bodies, dirt, humidity.
Frequency inverter and cable entries must be tightly closed so as to make them dustproof and waterproof. Check for tightness at regular intervals.
DANGER!
Electrical danger!
Danger of electrical shock when a defective pumpmotor unit is touched!
Have electrical equipment checked regularly by a qualified electrician.
4.4.1 Important notes
Regulations
The electrical connection must be carried out as follows:
according to the corresponding VDE
regulations and national regulations.
according to the applicable national, regional
and systemdependent regulations and requirements.
according to the regulations of the utility
company applying to the place of installation.
Electrical power supply
Observe the rating plate of the frequency inverter. It is imperative that the operating conditions correspond to the data given on the rating plate.
Electrical connection ( 23), ( 26)
The electrical connection must be
permanently safe.
The electrical connection to the PE conductor
must be permanently safe.
There may be no protruding wire ends.
Control cable connection ( 29)
Use shielded incoming cables. Do not route control cables together with
power cables in order to avoid interference injections.
For optimum shielding use the shield
connections to ensure largesurface contact when connecting the shield in the terminal box.
Control cables
610.44520.40.000 22 / 52 © Gardner Denver Deutschland GmbH
Page 23
Installation
4.4.2 Preparing works
Open frequency inverter
2FC4152-1NE00 ... 2FC4222-1NE00
ne2bhxn222
Fig. 10: Open frequency inverters 2FC4152−1NE00
and 2FC4222−1NE00
2FC4302-1NE00 ... 2FC4752-1NE00
1 2
4.4.3 Connecting frequency inverters
2FC4152-1NE00 and 2FC4222-1NE00
DANGER!
Electrical danger!
Improper connection of the pumpmotor unit
can result in an electric shock. Observe the following basic rules: The leakage current to earth (PE) is
>3.5 mA. The PE connection must meet EN
50178.
Observe national and regional regulations.
CAUTION
Danger of pumpmotor unit damage caused
by improper connection!
Observe the permissible mains voltage. Any
higher mains voltage will destroy the frequency
inverter.
Wiring according to EMC requirements (installation of a CE-typical drive system)
The pumpmotor units meet the EU Directive on "Electromagnetic Compatibility" if they are installed in accordance with the specifications of the CEtypical drive system. The enduser is responsible for maintaining the EU Directive in the overall system.
ne2bhxn422
Fig. 11: Open frequency inverters 2FC43021NE00 ...
2FC47521NE00
NOTE
Requirements for troublefree operation:
Always shield control cables. Provide largesurface contact between
shielding and shield sheet. Ensure good electrical contact.
© Gardner Denver Deutschland GmbH 23 / 52 610.44520.40.000
Page 24
Installation
2FC4152-1NE00 ... 2FC4222-1NE00
B A
C
D
X1
X2
F
Fig. 12: Terminal box 2FC4152-1NE00 ... 2FC4222-
1NE00
Mains cable L1, L2, L3, PE

PE connection mains cable and motor cable

Shielded control cable

Shield connection for the control cable::

1 Prepare cable
E
1ne2bhxn101
X1 Terminal strip for mains connection and relay
output connection
X2 Terminal strip for motor connection and motor
temperature monitoring
PES HF shield termination by large−surface
connection to PE
Mains contactor, fuses and cable cross­sections
NOTE
Observe the following when using earth
leakage circuit breakers: Install earth leakage circuit breakers only
between the supply mains and the frequency inverter.
The earth leakage circuit breaker may trip
incorrectly if several drives are simultaneously connected to the mains.
Frequency inverter
Type [kW] [kW] FI
2FC4152­1NE00
2FC4222­1NE00
Required mains
contactor K1
1,5
4
2,2
30 m
A
2)
2 Pass the cable through the eye of the
shield sheet and bend the eye.
3 Screw together eye and shield sheet:
The shielding must have large−surface
contact to the shield sheet.
The shielding must be connected tightly
to the shield sheet.
PES
Potential free terminal

Control terminal module

0.7 Nm 6lb-in
Fuses and cable cross sections Frequency
inverter
Type
2FC4152­1NE00
2FC4222­1NE00
Installation according
to EN 60204−1
M6 A B6 A 1 5 A 18
M10
B10 A 1,5 10 A 16
A
L1, L2, L3, PE
[mm
Installation according to UL 1)
2
]
L1, L2, L3, PE
[AWG]
Fuse Circuitbreaker
1)
Use only ULapproved cables, fuses and fuse
holders. ULfuse: voltage 500 ... 600 V, tripping characteristic "H", "K5" or "CC"
2)
Pulse current sensitive or all current sensitive
e.l.c.b.
610.44520.40.000 24 / 52 © Gardner Denver Deutschland GmbH
Page 25
Installation
Relay data
NOTE
The service life of the relay depends on the type of load (ohmic, inductive or capacitive) and the value of the switching capacity.
Technical data
AC 250 V/3 A
DC 24 V/2 A ... DC 240 V/0.22 A
Connection
X1
0.5...0.6 Nm
4.4...5.3 lb-in
Function Relay
position
switched
X1/K11 Relay output
opened TRIP normallyclose d contact
X1/K12 Relay
midposition contact
X1/K14 Relay output
closed TRIP normallyopen contact
PES HF shield termination by large−surface
connection to PE
3/PE AC, 320 V ... 550 V, 45 ... 65 Hz
Displayed
message
PES
PES
X1 L3 L2 BR2 K14L1 BR1 K12BR0 K11
1.2...1.5 Nm
5.3 mm
10.7...13.3 lb-in
ne2bhxn231
Fig. 13: Frequency inverter 2FC4152-1NE00 ... 2FC4222-1NE00 1 connecting
1 Connecting the mains cable: A Release two screws at terminal X1 and
remove the terminal. B Pass the mains cable through the cable gland. C Attach the ring cable lug ( 5.3 mm) to the PE
conductor. D Screw the PE conductor onto the PE stud for
the mains cable:
observe tightening torque!
E Connect cores L1, L2 and L3 to X1 in correct
phase relation:
observe tightening torque!
2 Wiring the relay output (if necessary): A Pass the cable through the cable gland. B Connect the shield of shielded cables
according to EMC requirements ( 24). C Connect cores to terminal X1:
© Gardner Denver Deutschland GmbH 25 / 52 610.44520.40.000
observe terminal connection diagram and
tightening torque!
3 Reinsert terminal X1 and tighten with 2
screws:
observe tightening torque!
4 Connecting the control cable shield: A Pass the control cable through the cable
gland.
B Connect the shield according to EMC
requirements ( 24). C Control cable connection: ( 29) 5 Tighten all cable glands.
Page 26
Installation
NOTE
Do not remove the jumper between terminals BR1 and BR0!
Otherwise troublefree functioning of the pumpmotor unit cannot be guaranteed.
4.4.4 Connecting frequency inverters 2FC4302-1NE00 ... 2FC4752-1NE00
DANGER!
Electrical danger!
Improper connection of the pumpmotor unit can result in an electric shock.
Observe the following basic rules:
The leakage current to earth (PE) is > 3.5
mA. The PE connection must meet EN
50178.
Observe national and regional regulations.
CAUTION
Danger of pumpmotor unit damage caused by improper connection!
Observe the permissible mains voltage. Any higher mains voltage will destroy the frequency inverter.
Wiring according to EMC requirements (installation of a CE-typical drive system)
The pumpmotor units meet the EU Directive on "Electromagnetic Compatibility" if they are installed in accordance with the specifications of the CEtypical drive system. The enduser is responsible for maintaining the EU Directive in the overall system.
NOTE
Requirements for troublefree operation:
Always shield control cables. Provide largesurface contact between
shielding and shield sheet. Ensure good electrical contact.
610.44520.40.000 26 / 52 © Gardner Denver Deutschland GmbH
Page 27
Realisation
E
Installation
BA
X1
G
H
X2
CD
Fig. 14: Electrical connections 2FC4302-1NE00 … 2FC4752-1NE00
Mains cable L1, L2, L3, PE

PE connection mains cable

Shielded control cable

Shield connection for the control cable: g:

1 Prepare cable..
2 Insert cable tie..
F
ne2bhxn045
ne2bhxn046
3 Insert cable and tighten cable tie:
Potentialfree terminals
PE connection motor
Support for control terminal module
Control terminal module
X1 Terminal strip for mains connection and relay
output connection
X2 Terminal strip for motor connection
PES HF shield termination by largesurface
connection to PE
2ne2bhxn398
The shielding must have large−surface
contact to the shield sheet.
The shielding must be connected
tightly to the shield sheet.
ne2bhxn047
© Gardner Denver Deutschland GmbH 27 / 52 610.44520.40.000
Page 28
Installation
Mains contactor, fuses and cable cross­sections
NOTE
Observe the following when using earthleakage circuit breakers:
Install earth−leakage circuit breakers only
between the supply mains and the frequency inverter.
The earthleakage circuit breaker may trip
incorrectly if several drives are simultaneously connected to the mains.
Frequency inverter
Required mains
contactor K1
Type [kW] [kW] FI
2FC4302­1NE00
2FC4402­1NE00
2FC4552­1NE00
2FC4752­1NE00
3 3
4 4
300 mA
5,5 5,5
7,5 7,5
Fuses and cable cross sections Frequency
inverter
Type
2FC4302­1NE00
2FC4402­1NE00
2FC4552­1NE00
2FC4752­1NE00
Installation according
to EN 60204-1
L1, L2, L3, PE
2
[mm
]
M16
B16 A 2,5 15 A 14
A
M20
B20 A 4 20 A 12
A
M25
B25 A 4 25 A 10
A
M32
B32 A 6 35 A 8
A
Installation according to UL 1)
L1, L2,
L3, PE [AWG]
Fuse Circuitbreaker
1)
Use only ULapproved cables, fuses and fuse
holders. ULfuse: voltage 500 ... 600 V, tripping characteristic "H", "K5" or "CC"
2)
All−current sensitive e.l.c.b.
Relay data
NOTE
The service life of the relay depends on the type of load (ohmic, inductive or capacitive) and the value of the switching capacity.
Technical data
AC 250 V/3 A
DC 24 V/2 A … DC 240 V/0.22 A
Function Relay
position
switched
2)
X1/K11 Relay output
normallyclose
opened TRIP
d contact
X1/K12 Relay
midposition contact
X1/K14 Relay output
closed TRIP normallyopen contact
PES HF shield termination by large−surface
connection to PE
Displayed
message
610.44520.40.000 28 / 52 © Gardner Denver Deutschland GmbH
Page 29
Connection
Installation
3/PEAC, 320 V ... 550V, 45 ... 65 Hz
1.1 Nm
9.7 lb-in
Fig. 15: Connectiing frequency inverter 2FC4302-1NE00 ... 2FC4752-1NE00
4.3 mm
PES
PES
X1 L3 L2 L1K14 K12 K11
1.2...1.5 Nm
10.7...13.3 lb-in
1 Connecting the mains cable: A Pass the mains cable through the cable gland. B Attach the ring cable lug (Ø 4.3 mm) to the
PE conductor.
C Screw the PE conductor onto the PE stud for
the mains cable:
observe tightening torque
4.4.5 Wiring of control connections
The control connections are on the control terminal module 2FX45010NE00 which is included in the scope of supply.
Install the control terminal module in the terminal box of the frequency inverter before starting to wire the control connections.
D Connect cores L1, L2 and L3 to X1 in correct
phase relation:
observe tightening torque!
2 Wiring the relay output (if necessary): A Pass the cable through the cable gland. B Connect the shield of shielded cables
according to EMC requirements (
27).
C Connect cores to terminal X1:
observe terminal connection diagram and
X3
tightening torque!
3 Connecting the control cable shield: A Pass the control cable through the cable
Fig. 16: Control connections 2FX4501-0NE00
gland.
B Connect the shield according to EMC
requirements (
C Control cable connection: ( (
27).
29)
4 Tighten all cable glands.
Mount control terminal module
If the cap is plugged on the socket connector when assembling the frequency inverter, the control terminal module will be damaged!
Remove the cap from the socket connector
at the control terminal module.
Keep the cap.
6 mm
62 7 78 9 20 28 E1E2 E3 E4 39 A1 59
CAUTION
ne2bhxn431
n_e2fx1006
© Gardner Denver Deutschland GmbH 29 / 52 610.44520.40.000
Page 30
Installation
A
2FC4152-1NE00 … 2FC4222-1NE00
1
2
3
C L
CK
Fig. 17: Control terminal module installation in
frequency inverters 2FC41521NE00 and 2FC42221NE00
2FC4302-1NE00 … 2FC4752-1NE00
1
1.1 Nm
9.7 lb-in
2
ne2bhxn147
Screw terminal data
Electrical
Terminal strip with screw connection
connections Possible
connections
rigid: 1,5 mm
2
(AWG 16)
flexible:
without wire end ferrule 1,0 mm
2
(AWG 18)
without wire end ferrule,
without plastic sleeve 0,5 mm
2
(AWG 20)
with wire end ferrule, with
Tightening
plastic sleeve 0,5 mm
0,22 … 0,25 Nm (1,9 … 2,2 lb-in)
2
(AWG 20)
torque Bare end 5 mm
Wiring
NOTE
Always shield control cables in order to avoid interference injections!
GND2
3
4
CLACK
Fig. 18: Control terminal module installation in
frequency inverters 2FC43021NE00 ... 2FC47521NE00
ne2bhxn447
GND1
62 8 9 20 28 E1 E2 E3 E4 39 A1 59
X3
Fig. 19: Supply via the internal voltage source (X3/20)
X3
77
AIN1AO UT1 DIGOUT 1
GND1
7
62
AIN1AOU T1
GND1
+5V +20V
897
Required minimum wiring for operation
n_e2fcx072
GND2
GND1
+20V
+5V
8 9 20 28 E1 E2 E3 E4 39 A1 59
7
DIGOUT1
897
_
24 V ext.
(+12 V DC - 0%
...
+30 V DC + 0%
max. 120 mA
Required minimum wiring for operation
n_e2fcx073
+
Fig. 20: Supply via an external voltage source
610.44520.40.000 30 / 52 © Gardner Denver Deutschland GmbH
Page 31
Terminal assignment
Installation
X3/3 Signal
Function Level
type
X3/62 Analog
Output frequency 0 ... + 6 V
output
X3/7 - GND1, reference potential for analog signals ­X3/8 Analog
input
Setpoint input Change setpoint selection range via DIP switch
0 ... +5 V (default setting) 0 ... +10 V 0 ... +20 mA
X3/9 - Internal, stabilised DC voltage source for
+5,2 V (ref.: X3/7)
setpoint potentiometer
X3/20 - Internal DC voltage source to control digital
+20 V ± 10 % (ref.: X3/7)
inputs and digital outputs
Digital inputs
HIGH LOW
X3/E1 Reset fault (TRIPReset) HIGH X3/E2 External fault
HIGH
START X3/28 Controller inhibit
STOP
Reset fault
Switchoff with fault indication "EEr"
No fault Activation of fixed speeds Adjust maximum frequency C0011 in order
to go through the complete speed range. Maximum value of C0011 = 87 Hz (5000/
min)
LOW E3 E4 X3/E3 34 Hz (2000/min) HIGH LOW 67 Hz (4000/min) LOW HIGH X3/E4 50 Hz (3000/min) HIGH HIGH
X3/39 - GND2, reference potential for digital signals ­X3/A1 Digital
"Pulse inhibit active" message HIGH
pulse inhibit active
output
X3/59 - DC supply for X3/A1
+20 V Internal voltage source (jumper to
X3/20)
+24 V External voltage source
ON
OFF
n_e2fcx070
Switch position
Signal at X3/8 1 2 3 4 5
0 ... 5 V (default
OFF OFF ON OFF OFF
setting)
0 ... 10 V OFF OFF ON OFF ON 0 ... 20 mA OFF OFF ON ON OFF
Fig. 21: Switch position control terminal module
© Gardner Denver Deutschland GmbH 31 / 52 610.44520.40.000
Page 32
Installation
Electrical data of the terminals
X3/ X3/62
Resolution 10 bits Linearity error ±0,5 % Temperature
0,3 % (0 … +60°C)
error
X3/8
Load capacity I Resolution 10 bits
= 2 mA
max
Linearity error ±0,5 % Temperature
0,3 % (0 … +60°C)
error Load capacity I
= 2 mA
max
Input resistance Voltage signal: >50 k
Current signal: 250
X3/9 Load capacity I
= 10 mA
max
X3/7 Isolated from terminal X3/39 (GND2)
Load capacity 3,3 kX3/28 HIGH +12 … +30 V, SPS- level,
X3/E1 … X3/E4
LOW 0 … +3 V, SPS- level,
HTL
HTL X3/39 Isolated from terminal X3/7 (GND1) X3/A1 Load capacity For internal supply:
I
= 10 mA
max
For external supply:
= 50 mA
I
max
4.4.6 Final works
CAUTION
Improper closing of the frequency inverter may damage the contacts of the control terminal module.
Observe the following points to avoid damages:
Place the heatsink of the frequency inverter
carefully on the terminal box.
Place the heatsink upright on the terminal
box from above, do not tilt it!
When placing the heatsink upon the terminal
box, pay attention to placing the plug at the heatsink exactly upon the socket connector at the control terminal module.
Never force the heatsink upon the terminal
box.
CAUTION
If the cap is plugged on the socket connector when assembling the frequency inverter, the control terminal module will be damaged!
Remove the cap from the socket connector
at the control terminal module.
Keep the cap..
2FC4152-1NE00 … 2FC4222-1NE00
2.4 Nm 21 lb-in
Close frequency inverter
DANGER!
IP65
Electrical danger!
The terminal box of the frequency inverter must be free from
foreign bodies, dirt, humidity.
Frequency inverter and cable entries must be
Fig. 22: Close frequency inverters 2FC4152−1NE00
and 2FC4222−1NE00
ne2bhxn227
tightly closed so as to make them dustproof and waterproof. Check for tightness at regular intervals.
DANGER!
Electrical danger!
Danger of electrical shock when a defective pumpmotor unit is touched!
Have electrical equipment checked regularly by a qualified electrician.
610.44520.40.000 32 / 52 © Gardner Denver Deutschland GmbH
Page 33
Installation
2FC4302-1NE00 … 2FC4752-1NE00
1.1 Nm
9.7 lb-in
IP65
ne2bhxn459
Fig. 23: Close frequency inverters 2FC4302−1NE00
... 2FC4752−1NE00
© Gardner Denver Deutschland GmbH 33 / 52 610.44520.40.000
Page 34
Commissioning
5 Commissioning
WARNING
Improper use of the pumpmotor unit can result in serious or even fatal injuries!
Have you read the chapter "Safety instructions"? (
5)
Otherwise you may not carry out any work with or on the pumpmotor unit!
WARNING
Danger from rotating parts (motor fan, impeller, shaft): cutting/cutting off of extremities, grasping/winding up of hair and clothing!
Danger due to vacuum and gauge pressure: sudden escape of media (skin and eye injuries), sudden drawingin of hair and clothing!
Danger due to escaping media: burns!
Commissioning and operation only under the following conditions:
The pumpmotor unit must be completely
assembled. When doing so, pay particular attention to the following components:
the cover of the gas ring blower housing, the mufflers on inlet and discharge
connections,
the fan guard.
The pipes/hoses must be connected to inlet
and discharge connections.
Inlet and discharge connections and the
connected pipes/hoses may not be closed, clogged or soiled.
Check the mounting elements, connections
of the pipe/hose connections, lines, fittings and containers for strength, leaks and firm seating at regular intervals.
5.1 Preparation
WARNING
Danger from closed connections!
With closed/soiled inlet or discharge connections vacuum or gauge pressure results in the pumpmotor unit.
This can overheat and damage the drive motor winding.
Before commissioning, make sure that the inlet and discharge connections are not closed, clogged or soiled!
CAUTION
Before starting up again after a longer standstill:
Measure the insulation resistance of the
motor.
With values < 1 k /Volt of rated voltage,
the winding is to dry.
Measures before start-up:
If a shut−off device is installed in the pressure
line: make sure that the pumpmotor unit is NOT operated with the shutoff device being closed.
Observe the values specified on the rating
plate before starting up the pumpmotor unit. Specifications on the rated motor current apply at a gas entry and ambient temperature of +40° C [104 °F].
WARNING
Danger due to rotating parts!
Danger due to vacuum and gauge pressure!
Danger due to escaping media!
Test runs may only be conducted with the pumpmotor unit completely mounted.
DANGER!
Electrical danger!
The electrical connection may be carried out by trained and authorized electricians only!
610.44520.40.000 34 / 52 © Gardner Denver Deutschland GmbH
Page 35
88800
0050
000
a
bcde
j
g fkih PS
mno
p
qr
Hi
Hz
%sh rpm
°C
Ω
m
AV
Lo
0
1
2
Commissioning
DANGER!
Electrical danger!
Before beginning work on the pumpmotor unit or system, the following measures must be carried out:
Deenergize. Secure against being switched on again. Determine whether deenergized. Ground and shortcircuit. Cover or block off adjacent energized parts.
Check operating speeds:
Observe the maximum speed specified on the rating plate.
This speed may not be exceeded, as otherwise the noise radiation, vibration behavior, grease change interval and bearing change interval worsen.
To prevent damage as a result of higher speeds, it may be necessary to inquire with the manufacturer as to the maximum speed.
WARNING
Danger of hearing damage due to noise radiation!
The noise emission of the pumpmotor unit measured by the manufacturer is specified
under "Technical data" ( The actual noise emission during operation,
however, strongly depends on the installation type and on the system conditions.
For this reason conduct a noise measurement in the system during operation after installing the pumpmotor unit.
The following measures must be taken by the operator:
from 85 dB(A):
Hearing protection must be available.
from 90 dB(A):
Mark noise area with a warning sign. Wear hearing protection. With free entry and exit of gases, i.e. with
direct intake out of the atmosphere or direct feeding into the atmosphere without piping, attach an additional muffler.
11).
5.2 Parameter setting
5.2.1 The hand-held keypad 2FX4506-0NE00
Description
The hand−held keypad is available as accessories. A complete description is part of the Instructions supplied with the handheld keypad.
Installation/ commissioning
a
bcde
j
gfkihPS
Fig. 24: Installation/commissioning handheld keypad
mno
qr
Hi Lo
88888
z
wx
y
j
g fkihPS
mno
qr
Hi Lo
88800
z
wx
y
j
g fkihPS
mno
qr
Hi Lo
88800
z
wx
y
Connect handheld keypad to control interface
p
8888
vtu
bcd e
p
0050
t
v
bcd e
p
0050
vtu
888
%sh rpm
000
%sh rpm
000
%sh rpm
m Hz
a
m
Hz
a
m
Hz
8
AV
°C
Ω
s
1
AV
Ω
°C
s
u
1
AV
Ω
°C
s
2FX4511-0LE00
2FX4512-0LE00
a
bcde
j
gfkihPS
8
mno
p
qr
888
8888
m
Hi
AV
Hz
%sh
°C
Ω
Lo
88888
rpm
z
t
s
wx
y
v
u
2FX4506-0NE00
n_e2fcx118
using the connecting cable. The handheld keypad can be connected and disconnected during operation.
As soon as the keypad is supplied with
voltage, it carries out a short selftest. The keypad is ready for operation when it is in
display mode : Current state of the frequency inverter
First code in the menu
Controller load (each graduation mark = 20 %) Press to leave the mode
© Gardner Denver Deutschland GmbH 35 / 52 610.44520.40.000
Page 36
Commissioning
Display elements and function keys
0 1
2 3
j gfkih PS
mno qr
Hi Lo
88888
p
8888
z
t
abcde
8
888
m
Hz
AV
%sh
°C
Ω
rpm
s
wx
y
Fig. 25: Display elements and function keys
Status displays
Meaning Explanation

Ready

Pulse inhibit active Power outputs inhibited

Adjusted current limitation is exceeded in motormode or generator mode

Warning active

Fault active
Function bar 1
Meaning Explanation

Without function Display = loc

Display of first code in the menu

Code selection Fourdigit display of the
Without function Is skipped

Change of parameter value of a code

Without function
Function bar 2
Not active
Bar graph display
Controller load Display range: 180 %
Display of code number
Display of parameter value or fault indication
v
C0022 (motor mode) or C0023 (generator mode)
Active after every mains connection
active code number
Fivedigit display of the current value
... +180 % (each graduation mark = 20 %)
u
4
5
6
n_e2fcx002
Function keys
Function Explanation
Enable controller Terminal X3/28 must
additionally be at HIGH level
Inhibit controller
Change function bar 1 function bar 2

To right/left in active function bar

Increase/decrease value
Fast change: Keep respective key pressed
Store parameters when ! is blinking Confirmation by Store in display
Function bar 2 not active
The active function is framed
Only blinking values can be changed
610.44520.40.000 36 / 52 © Gardner Denver Deutschland GmbH
Page 37
Commissioning
Changing and saving parameters
All parameters for parameterization or monitoring of the controller are stored in codes. The codes are numbered and marked with a "C" in the documentation. The available codes are listed in the code table.
Step Keys Result Action
1. Connect keypad
Set parameters
2.
3.
4.
5.
7.
 

 




XX.XX Hz
XXXX
xxxxx
Store
The function is active. C0140 = setpoint is indicated via keypad.
Select mode ".
Select code..
Modus off Ahlen.
Parameter onstellen.
Confirm entry when ! is blinking. 6.
Confirm entry when ! is not blinking; is inactive.
Start "loop" again at 2. for further parameter setting.
Changed parameters are stored in the nonvolatile memory of the controller.
5.2.2 Code table
How to read the Code table
Column Abbreviation Meaning
Code
Cxxxx Code number Cxxxx The parameter value is accepted
immediately (ONLINE)


Changed parameter of the code will be accepted after pressing Changed parameter of the code will be accepted after pressing if
the controller is inhibited Designation Name of the code Manufacturer Default setting (value at delivery or after restoring default setting via
C0002) Further information can be obtained from "IMPORTANT" Selection 1 {%} 99 Min. value {unit} max. value IMPORTANT - Brief, important explanations
Code Possible settings IMPORTANT
No. Designation Manu-
Selection
facturer
C0140 Setpoint offset via
keypad
0,00 -650,00 {0,02 Hz} 650,00 Acts additively on
main setpoint. setpoint 2. fixed speeds (JOG).
The set value is stored in case of mains switching or keypad removal.
C0050 Output frequency -650,00 {Hz} 650,00 Display only: Output frequency
without slip compensation C0052 Motor voltage 0 {V} 1000 Display only C0054 Apparent motor
0,0 {A} 2000,0 Display only
current
© Gardner Denver Deutschland GmbH 37 / 52 610.44520.40.000
Page 38
Commissioning
Code Possible settings IMPORTANT
No. Designation Manu-
Selection
facturer
C0010 Minimum output
10,00 0,00 {0,02 Hz} 650,00 C0010 only limits the analog input 1
frequency
C0011 Maximum output
frequency
Only valid for units 2BH.−..N.1.
and 2BH.−..N.3−.with integrated 2FCxxxx1NE00 inverter
86,00 7,50 {0,02 Hz} 650,00
Maximum permissible value: 86
(5000/min)
C0012 Acceleration time
main setpoint
Only valid for units 2BH.−..N.1.
and 2BH.−..N.3−.with integrated 2FCxxxx1NE00 inverter
10,00 Setting for units up to 5.5 kW 25,00
Setting for 7.5 kW unit
0,00 {0,02 s} 1300,00 Reference: frequency change 0 Hz ...
C0011 C0013 Deceleration time
main setpoint
Only valid for units 2BH.−..N.1.
and 2BH.−..N.3−.with integrated 2FCxxxx1NE00 inverter
10,00 Setting for units up to 5.5 kW 20,00
Setting for 7.5 kW unit
0,00 {0,02 s} 1300,00 Reference: frequency change 0 Hz ...
C0011 C0015 U/f−rated
frequency
Only valid for units 2BH.−..N.1.
and 2BH.−..N.3−.with integrated 2FCxxxx1NE00 inverter
52,70 Setting for units 2BH...N.3. 90,90 7,50 {0,02 Hz} 960,00
Setting for units 2BH.−..N.1−.
VU
][
N
HzC
][*
U
N
][0015 Hzf
r
r
VU
][
= mains rated voltage of
inverter
U
= rated voltage of motor
r
depending on connection method acc. to rating plate
f
= rated frequency of motor acc.
r
To rating plate
The setting applies to the entire
mains voltage range in which the
inverter may be operated.
C0016 U
boost (starting
min
voltage
0,00 {0,01 %} 40,00  Depends on the device
Loadindependent rise of motor
voltage at low speeds:
Reference: rated voltage of motor
(C0090).
The setting applies to the entire
mains voltage range in which the inverter may be operated.
610.44520.40.000 38 / 52 © Gardner Denver Deutschland GmbH
Page 39
2
Commissioning
5.3 Start-up of the pump-motor unit
The description of how to change pre-set parameters using the hand-held keypad starts on page 35.
NOTE
When no setpoint has been entered, the drive rotates with the minimum frequency set under
C0010!
The setpoint offset set under C0140 is stored and will be active at each switchon. The setpoint offset set under C0140 has an additive effect on all other setpoints! This effect can be used, for example, to set speeds between fixed speeds:
Fixed speed via terminal = 67 Hz (4000/min) C0140 = -7 Hz Resulting speed = 60 Hz (3600/min)
Switch-on sequence Note
1. Connect keypad.
2. Ensure that controller inhibit is active after
mains connection.
3. Open the shutoff device in the inlet line or in
the pressure line..
4. Switch on the mains.
Terminal X3/28 = LOW
misc00
5. The keypad is in “Disp” mode after approx. 2
s and indicates the setpoint offset (C0140).
6.
Change to the mode with in order to set drive parameters.
7.
Press
.
8. Set the minimum output frequency (C0010).
Default setting: 10.00 Hz (600/min)
9. Set the maximum output frequency (C0011).
Default setting: 86.00 Hz (3000/min)
10. Set acceleration time Tir (C0012).
Default setting: 10 00 s: frequency inverters up to 5 kW
25.00 s: frequency inverter 7.5 kW
11. Set deceleration timeTif on (C0013).
Default setting: 10 00 s: frequency inverters up to 5 5 kW
20.00 s: frequency inverter 7.5 kW
Se t
C0011
C0010
misc00
0I40 is blinking in the display.
Thus, you skip the display codes for output frequency (C0050), motor voltage (C0052) and apparent motor current (C0054).
[f]
After controller enabling, the motor at least rotates with the frequency set under C0010!
0%
100%
tir = desired acceleration time
tif = desired deceleration time
0011
C
*
tT
irir
C
*
tT
irir
2 ff
0011
2 ff
1
1
© Gardner Denver Deutschland GmbH 39 / 52 610.44520.40.000
Page 40
Commissioning
2
The base settings are now completed and the drive can be started:
Start drive Note
Enter the setpoint.
12.
A) Using the keypad Set desired output frequency
under C0140.
The min. frequency under C0010 and the setpoint offset under C0140 are added!
B) Using the potentiometer via terminals 7, 8, 9
C) Enter fixed speed via terminal.
13. Enable controller.
14. The drive now operates with the set
frequency. The current output frequency is indicated under C0050.
5.4 Shut-down of the pump-motor unit
Shut-down:
1 Set controller inhibit (terminal X3/28 = LOW) 2 Switch off power supply. 3 Close shut-off device in inlet/ pressure line.
Terminal E3 E4 34 Hz (2000/min) HIGH LOW 67 Hz (4000/min) LOW HIGH 50 Hz (3000/min) HIGH HIGH
Terminal X3/28 = HIGH
misc00
Set Disp
SubCode Para
If the drive does not start, press
H / L
in addition.
610.44520.40.000 40 / 52 © Gardner Denver Deutschland GmbH
Page 41
Operation
6 Operation
WARNING
Improper use of the pumpmotor unit can result in serious or even fatal injuries!
Have you read the chapter "Safety instructions"? (
5)
Otherwise you may not carry out any work with or on the pumpmotor unit!
Start-up and shut-down
See chapter Commissioning: (
34)
Important notes during operation
WARNING
Danger of burns from hot surface of the pumpmotor unit and from hot media!
High temperatures of up to approx. 160 °C [320 °F] can occur on the surface of the pumpmotor unit.
Do not touch during operation. Allow to cool after shut−down.
CAUTION
Danger of overheating due to hot surface of pumpmotor unit!
High temperatures of up to approx. 160 °C [320 °F] can occur on the surface of the pumpmotor unit.
Temperaturesensitive parts such as cables or electronic components may not come into contact with the surface of the pump−motor unit.
CAUTION
Danger of overheating!
During operation the standstill heating may, if installed, not be switched on!
CAUTION
Danger of rusting due to collection of condensed water in drive motor area!
On drive motors with closed condensed water openings:
Remove closures occasionally to allow any water which has collected to drain off.
CAUTION
Danger of bearing damage!
Heavy mechanical impacts must be avoided during operating and while at a standstill.
© Gardner Denver Deutschland GmbH 41 / 52 610.44520.40.000
Page 42
Shut-down and longer standstills
7 Shut-down and longer standstills
WARNING
Improper use of the pumpmotor unit can result in serious or even fatal injuries!
Have you read the chapter "Safety instructions"? (
Otherwise you may not carry out any work with or on the pumpmotor unit!
7.1 Preparation
Danger of rusting due to collection of condensed water in drive motor area!
On drive motors with closed condensed water openings:
Remove closures occasionally to allow any water which has collected to drain off.
Prior to shutdown or longer standstill, proceed as follows:
1 Switch off the pumpmotor unit. 2 Close shutoff device in inlet and pressure
line (if installed).
3 Disconnect pumpmotor unit from power
supply.
4 Druckentlastung vornehmen.
Dabei Rohrleitungen / Schläuche langsam und vorsichtig öffnen, so dass sich der Unter-
bzw. Überdruck im Aggregat abbauen kann. 5 Disconnect inlet line and pressure line. 6 Provide mufflers on inlet and discharge side
with sealing plugs.
7.2 Storage conditions
Keep to the following storage conditions to avoid damaging the pump-motor unit:
Dry, Dust-free, Low-vibration (max. vibration velocity v
mm/s [0,009 ft/s]). Ambient temperature: max. 40°C [+104°F].
5)
CAUTION
= 2,8
eff
CAUTION
Danger of overheating due to high temperature!
When storing in an environment with a temperature of over 40 °C [104 °F], the winding may be damaged and the grease change interval may be shortened.
Lubrication of the rolling bearings after longer storage
The new pumpmotor unit may at first be stored following delivery.
If the time from delivery to commissioning exceeds the following periods, the lubrication of the rolling bearings must be renewed:
Under advantageous storage conditions (as
specified above):
4 years
Under disadvantageous storage conditions
(e.g. high humidity, salty air, sandy or dusty air):
2 years
In these cases open rolling bearings must be relubricated and closed rolling bearings must be completely replaced.
This absolutely requires consultation of the manufacturer. In particular detailed information regarding the procedure and the grease type is required.
WARNING
Improper use of the pumpmotor unit can result in serious or even fatal injuries!
All maintenance work on the pumpmotor unit must always be performed by the Service Department!
Maintenance work on the pumpmotor unit may only be conducted by the operator when the related maintenance manual is on hand!
Inquire with the manufacturer!
Commissioning after longer standstill or longer storage:
Before recommissioning after longer standstill or longer storage, the following works must be executed:
Measure the insulation resistance of the
motor. With values 1 k per volt of rated voltage, the winding is to dry.
Form the capacitors of the frequency inverter.
Please contact the manufacturer for this purpose.
610.44520.40.000 42 / 52 © Gardner Denver Deutschland GmbH
Page 43
Servicing
8 Servicing
WARNING
Improper use of the pumpmotor unit can result in serious or even fatal injuries!
Have you read the chapter "Safety instructions"? (
Otherwise you may not carry out any work with or on the pumpmotor unit!
5)
Improper use of the pumpmotor unit can result in serious or even fatal injuries!
All maintenance work on the pumpmotor unit must always be performed by the Service Department!
Maintenance work on the pumpmotor unit may only be conducted by the operator when the related maintenance manual is on hand!
Inquire with the manufacturer!
WARNING
8.1 Repair/ troubleshooting
8.1.1 Malfunctions at side channel blower
Malfunction Cause Remedy Carried
out by
Frequency inverter assumes fault mode after controller enable
See also: 45
Side channel blower does not start
blower rotates
unsteadily
Open blower cover, remove foreign body, clean.
Check or correct impeller gap setting if
necessary. Impeller defective. Replace impeller. Service*) Rolling bearing on drive motor
side or blower side defective. Throttling does not match
specification on rating plate.
One power supply lead interrupted.
DCbus voltage too low. (Red LED blinking fast, keypad display: Lu)
Controller inhibited. (Green LED blinking, keypad display:
Setpoint = 0. Enter the setpoint. Operator Active fault Eliminate fault Electrician
Defective motor cable Check motor cable ElectricianSide channel Motor underexcited or
overexcited.
)
Replace motor bearing or blower bearing. Service*)
Reduce throttling. Service*)
Clean filters, mufflers and connection pipes
if necessary.
Eliminate interruption by fuses, terminals or
power supply cables
Check mains voltage Electrician
Remove controller inhibit. Controller inhibit
can be set through several sources.
Check parameter setting
(C0015, C0016).
Service*) Impeller is jammed.
Service*)
Service*)
Electrician
Operator
Operator
© Gardner Denver Deutschland GmbH 43 / 52 610.44520.40.000
Page 44
Servicing
Malfunction Cause Remedy Carried
out by
Sidechannel blower does not reach the required speed / pump−motor unit does not generate pressure difference or generated difference is too low
Leak in system. Seal leak in the system. Operator Shaft seal defective. Replace shaft seal. Service*) Different density of pumped gas. Take account of the conversion of the
Service
pressure values.
Inquire with Service Department. Change in blade profile due to
soiling. Setpoint range wrongly adjusted
at DIP switch. Setting of maximum output
frequency too low.
Clean impeller, check for wear and replace if
necessary.
Adjust setting of DIP switch to the analog
signal
Increase C0011.
Max. permissible value= 87 Hz (5000/min)
Service*)
Electrician
Electrician
Operator for2BH11 ... 2BH18. Max. permissible value= 70 Hz (4200/min) for 2BH19
Side channel blower operates, setpoints”0”
Min. output frequency set > 0 Hz. (Default setting= 10 Hz)
In C0140 a setpoint has been set. (Setting of C0140 stored in
Change drive characteristics only under special circumstances! (Set C0010 = 0 Hz)
Electrician
Operator Set C0140 = 0 Hz if necessary.. Electrician
Operator
nonvolatile memory
Current consumption of
C0016 set too large or too small. Correct setting Electrician
Operator
motor too high
noises
Flow speed too high. Clean pipes. Use pipes with larger
crosssection if necessary.
Muffler soiled. Clean muffler inserts, check condition and
Operator Abnormal flow
Service*) replace if necessary.
Abnormal running noise
Ball bearing lacking grease or
Regrease or replace ball bearing. Service*)
defective. Seals on muffler defective. Check muffler seals and replace if
Service*) Blower leaky necessary.
Seals in motor area defective. Check motor seals and replace if necessary. Service
*) Can only be repaired by the operator if the maintenance manual is on hand!
8.1.2 Frequency inverter status indications
LED
Operating status
red green
off on Frequency inverter enabled on on Mains switched on and automatic start inhibited off slowly blinking Frequency inverter inhibited off fast blinking Motor parameter identification being executed fast blinking off Undervoltage
slowly blinking off Fault active
610.44520.40.000 44 / 52 © Gardner Denver Deutschland GmbH
Page 45
8.1.3 Fault indication at the keypad
Servicing
Keypad
1)
(PC)

(71)
ce1

(62)
ce2

(63)
ce3

(64)
ce4

(65)
ce5

(66)
ce6

(67)
ce7

(68)
EEr

(91)
ErP0 … ErP19

H05

(105)
Malfunction Cause Remedy Carried
out by
System fault
Strong interferences on control
Shield control cables ccr
Electrician
cables Ground or earth loops in the
Remove ground or earth loops.
wiring
Communication fault to CAN−IN1 with Sync control
Communication error to CAN−IN2
Communication error to CAN−IN1 with event or time control
BUSOFF (many communication errors occurred)
CANIN1 object receives faulty data or communication is interrupted
CANIN2 object receives faulty data or communication is interrupted
CANIN1 object receives faulty data or communication is interrupted
Frequency inverter has received too many ncorrect telegrams via the system bus and has been disconnected from the bus
Check if the bus module is
correctly plugged on.
Check transmitter Check if the bus module is
correctly plugged on.
Check transmitter Check if the bus module is
correctly plugged on.
Check transmitter
Check if there is a bus
termination.
Check shield contact of the
cables
Check PE connection Check
Service
Service
Service
Service
bus load, if necessary, reduce the baud rate
CAN timeout For remote parameter setting
via system bus (C0370): Slave does not reply. The
Check system bus wiring Check system bus
configuration
Service
communication check time has been exceeded
Function module system bus (CAN) attached to the control interface is set to "Warning" or "BUS−OFF"
CAN controller signals "Warning" or "BUS OFF"
Check if there is a bus
termination.
Check shield contact of the
cables
Check PE connection
Service
Check bus load, if necessary,
reduce the baud rate
Communication fault during remote parameter setting via system bus (C0370)
Bus device does respond or is not available
Check if there is a bus
termination.
Check shield contact of the
cables
Check PE connection
Service
Check bus load, if necessary,
reduce the baud rate
External fault External encoder signals an
error (terminal X3/E2 = LOW)
Remove external error. Then reset error EEr by:
Mains switching
Operator
or X3/E1 = HIGH (TRIP-
Reset)
Communication
Various Contact manufacturer abort between keypad and basic device
Internal fault Contact manufacturer
© Gardner Denver Deutschland GmbH 45 / 52 610.44520.40.000
Page 46
Servicing
Keypad
1)
(PC)
LU

OC1

(11)

(12)
OC3

(13)
OC4

(14)
OC5

(15)
OC6

(16)
OH

(50) OH

Malfunction Cause Remedy Carried
out by
DCbus undervoltage
Shortcircuit
Earth fault
Frequency inverter overload during acceleration
Mains voltage too low Check mains voltage
DCbus voltage too low Check supply module
400 V frequency inverter
connected to 230 V mains
Connect frequency inverter to the correct mains voltage.
Shortcircuit Search for cause of shortcircuit;
check motor cable.
Excessive capacitive charging
current of the motor cable
Use shorter motor cable with
lower charging current.. Grounded motor phase Check motor, check motor cable OC2 Excessive capacitive charging
current of the motor cable Acceleration time too short
(C0012)
U
- boost (C0016) set too
min
Use shorter motor cable with
lower charging current.
Increase acceleration time
Check drive dimensioning
Correct setting large or too small
Only for operation with
Correct setting
Electrician
Operator Electrician Electrician
Electrician
Operator
control cabinet inverter 2FCxxxx2NE00
U/f- rated frequency (C0015) set too small
Differential pressure too high Check differential pressure of the
system. Side channel blower starts at
half throttle
Increase acceleration time
Open valves.
Impeller jammed Repair side channel blower. Service
Shortcircuit
Defective motor cable Check wiring.
Electrician
Interturn fault in the motor Check motor.
Frequency inverter overload during deceleration
Frequency inverter overload
Deceleration time too short (C0013)
Energy backflow in generator mode operation too high
Frequent and too long overload Check dimensioning of side
Increase deceleration time. Operator
Operator
channel blower.
in stationary operation
Motor overload
2
(I
x t - overload)
Motor is thermally overloaded, for instance, because of
Check dimensioning of side
channel blower.
Operator
impermissible continuous
current
frequent or too long
acceleration processes
Heatsink temperature> +85 °C
Heatsink temperature> +80 °C
Ambient temperature too high Allow frequency inverter to cool
down and ensure better
ventilation. Heatsink strongly polluted Clean heatsink Impermissibly high currents or
frequent and too long accelerations
Check dimensioning of side
channel blower..
Check load, if necessary,
Operator
Operator
Service
replace defective bearings
*)
*)
610.44520.40.000 46 / 52 © Gardner Denver Deutschland GmbH
Page 47
Servicing
Keypad
(PC)
OH3

(53)
OH4

(54)
OU

Malfunction Cause Remedy Carried
1)
Temperature monitoring of the motor has been triggered
Overtemperature frequency inverter
DCbus overvoltage
Motor too hot because of excessive currents or frequent and too long accelerations
Impeller jammed Repair side channel blower. Service PTC or thermostat not
connected or defective Frequency inverter too hot
inside
Mains voltage too high Check voltage supply Electrician Braking operation
Check dimensioning of side
channel blower.
Connect or repair PTC or
thermostat.
Reduce frequency inverter
load.
Improve cooling
Increase deceleration times.
Earth leakage at motor side Check motor cable and motor for
earth faults. (Separate motor and
frequency inverter)
Pr5
Internal fault Defective EEPROM Contact manufacturer

(79)
1 Values in parentheses: error number indicated by the PC parameter setting program (in preparation). *) Can only be repaired by the operator if the maintenance manual is on hand!
out by
Operator
*)
Service
Operator
Operator Electrician
8.1.4 Fault indication reset (TRIP-RESET)
1
3
X3
20 28
j
mno qr
Hi Lo
88888
wx
2
mno
p
qr
a
bcd e
gfkihPS
8
p
888
8888
m Hz
AV
W
%sh
°C
rpm
z
s
y
vtu
OFF
4
Hi Lo
01 61
880Hr
5
000
%sh rpm
6
Hz
m
W
1
AV
°C
ON
ne2bhxn355
a
bcd e
j
g fkih PS
Fig. 26: Fault indication reset (TRIP-RESET)
How to reset the frequency inverter if a fault occurs (TRIP−Reset):
Connect handheld keypad to the
communication interface during operation.
Read and take down fault indication on the
keypad display.
Inhibit frequency inverter. Disconnect pumpmotor unit from the mains. Carry out a fault analysis and eliminate the
fault.
Restart the pump−motor unit.
NOTE
The fault indication "EEr" triggered by an external encoder can also be reset via a HIGHLOW signal at terminal E1 if the fault has been eliminated in advance.
8.2 Service/ after-sales service
Our Service is available for work (in particular the installation of spare parts, as well as maintenance and repair work) not described in these Operating Instructions.
Please observe when returning the pumpmotor unit to the manufacturer:
The pumpmotor unit must be delivered
complete, i.e. not dismantled.
The original rating plate of the pump−motor
unit must be fixed properly, intact and legible.All warranty claims are voided for pump−motor units delivered for a damage expertise without the original rating plate or with a destroyed original rating plate.
In case of warranty claims, the manufacturer
must be informed of the operating conditions, operating duration etc. and additional detailed information must be provided on request if necessary.
The pumpmotor unit may not present a
danger to the workshop personnel.
Pumpmotor units with contact to
hazardous substances must be decontaminated.
A declaration of clearance must be
provided (
48).
© Gardner Denver Deutschland GmbH 47 / 52 610.44520.40.000
Page 48
Servicing
8.3 Decontamination and declaration of clearance
WARNING
Danger from flammable, caustic or toxic substances!
To protect the environment and persons, the following applies:
Pumpmotor units which have come into contact with dangerous substances must always be decontaminated before being passed on to a workshop!
To provide proof that the decontamination was carried out, a declaration of clearance must be included with the pumpmotor unit on delivery to the workshop.
The form required for this purpose is available from the manufacturer.
610.44520.40.000 48 / 52 © Gardner Denver Deutschland GmbH
Page 49
9 Disposal
Have the entire pumpmotor unit scrapped by a suitable disposal company:
Ensure recycling of metals and plastics. Assembled PCBs need to be disposed of
professionally.
For additional information on disposing of the pump−motor unit, ask the Service Department.
Disposal
© Gardner Denver Deutschland GmbH 49 / 52 610.44520.40.000
Page 50
Declaration of conformity
Declaration of conformity
EU declaration of conformity
Manufacturer:
Gardner Denver Deutschland GmbH P.O. Box 1510 D-97605 Bad Neustadt / Saale
Responsible for documentation:
Holger Krause P.O. Box 1510 D-97605 Bad Neustadt / Saale
Designation:
G series Side channel blower G-BH1e, G-BH7e Types 2BH1...-..N, 2BH7...-..N,
2BH1...-..L, 2BH7...-..L
The side channel blower described above meets the following applicable Community harmonisation legislation:
2004/108/EC
Directive 2004/108/EC of the European Parliament and of the Council of 15 December 2004 on the approximation of the laws of the Member States relating to electromagnetic compatibility and repealing Directive 89/336/EEC
2006/42/EC
Directive 2006/42/EC of the European Parliament and of the Council of 17 May 2006 on machinery, and amending Directive 95/16/EC
The protection targets of the directive 2006/95/EC have been met
Harmonised standards applied:
EN 1012-1:1996
EN 1012-2:1996
EN 50178:1197
EN 61800-3:2004
Compressors and vacuum pumps — Safety requirements — Part 1: Compressors
Compressors and vacuum pumps — Safety requirements — Part 2: Vacuum pumps
Electronic equipment for use in power installations
Adjustable speed electrical power drive systems — Part 3: EMC requirements and specific test methods
Bad Neustadt/Saale, 29.12.2009
(Place and date of issue)
ppa. Fred Bornschlegl
(Name and function) (Signature)
664.44521.40.000
610.44520.40.000 50 / 52 © Gardner Denver Deutschland GmbH
Page 51
Form for statement on safety
Form for statement on safety
Statement on health safety and on the protection of the environment
For the safety of our employees and to comply with statutory requirements on handling substances harmful to the health and
the environment, this statement must be enclosed, fully completed, with each unit/system sent.
Without the fully completed statement, repair/disposal is not possible and delays are unavoidable! The statement is to be completed and signed by suitably qualified, authorised personnel at the operating organisation. In the case of shipment to Germany, the statement is to be completed in German or English. The statement is to be attached to the outside of the packing on shipment. If necessary, the carrier is to be informed.
1. Product designation (type):
2. Serial number (no. BN):
3. Reason for sending:
4. The unit/system
has not come into contact with hazardous substances. There will be no hazards for personnel or the environment during repair/disposal. Continue with "6. Legally binding statement“
has come into contact with hazardous substances. Continue with "5. Information on the contamination“
5. Information on the contamination
(if necessary provide more information on an additional sheet)
The unit/system was used in the following application:
and has come into contact with the following classifiable substances or substances presenting a hazard to health/environment:
Trade name: Chemical designation:
Hazardous substance class:
Properties (e.g. toxic, inflammable, caustic, radioactive):
The unit/system has been emptied in accordance with the operating instructions, flushed and cleaned externally.
Safety data sheets in accordance with the applicable regulations are enclosed ( sheet).
The following safety precautions are necessary for handling (e.g. personal protective equipment):
6. Legally binding statement
I herewith guarantee that the details specified are true and complete and that I, as signatory, am in a position to judge that this is so. We are aware that we are liable to the contractor for any damages arising from incomplete or incorrect specifications. We are obliged to indemnify the contractor against claims for damages by third parties arising from incomplete or incorrect specifications. We are aware that, irrespective of this statement, we are directly liable to third parties - in particular including the contractor's employees tasked with repair/disposal.
Company/institute:
Name, position: Phone:
Street: Fax:
Post code, city:
Country: Stamp:
Date, signature:
© Gardner Denver Deutschland GmbH 610.00250.40.905 P.O. box 1510 Phone: +49 7622 392 0 E-mail: er.de@gardnerdenver.com 10.2009 97605 Bad Neustadt Fax: +49 7622 392 300 Internet: www.gd-elmorietschle.com English
© Gardner Denver Deutschland GmbH 51 / 52 610.44520.40.000
Page 52
Elmo Rietschle is a brand of Gardner Denver‘s Industrial Products Group and part of Blower Operations.
www.gd-elmorietschle.de
er.de@gardnerdenver.com
Gardner Denver Schopfheim GmbH
Roggenbachstraße 58 79650 Schopfheim · Deutschland Tel. +49 7622 392-0 Fax +49 7622 392-300
Gardner Denver Deutschland GmbH
Industriestraße 26 97616 Bad Neustadt · Deutschland Tel. +49 9771 6888-0 Fax +49 9771 6888-4000
Loading...