2 Intended Use .......................................................................................................................................7
3 Technical Data ....................................................................................................................................8
3.1 Mechanical data ........................................................................................................................8
Replication, distribution and / or editing of this document and the use and distribution of its content is
prohibited unless explicitly permitted. Violation obligates compensation for damages.
All rights reserved in case of the issue of a patent, utility patent or design patent.
1 Safety
1.1 Definitions
To point out dangers and important information,
the following signal words and symbols are used
in these operating instructions:
1.1.1 Safety alert symbol
The safety alert symbol is located in the
safety precautions in the highlighted heading field
on the left next to the signal word (DANGER,
WARNING, CAUTION).
Safety precautions with a safety alert symbol
indicate a danger of injuries.
Be sure to follow these safety precautions to
protect against injuries or death!
Safety precautions without a safety alert symbol
indicate a danger of damage.
1.1.2 Signal words
DANGER
WARNING
CAUTION
NOTICE
NOTE
Danger of injuries.
Indicates an imminently hazardous situation,
that will result in death or serious injury if the
corresponding measures are not taken.
Danger of injuries.
Indicates a potentially hazardous situation, that
could result in death or serious injury if the
corresponding measures are not taken.
Danger of injuries.
Indicates a potentially hazardous situation, that
may result in minor or moderate injury if the
corresponding measures are not taken.
The signal words are located in
the safety precautions in the
highlighted heading field.
They follow a certain hierarchy and
indicate (in conjunction with the
safety alert symbol, see
Chapter 1.1.1) the seriousness of
the danger and the type of
warning.
See the following explanations:
DANGER
WARNING
CAUTION
Safety
CAUTION
Danger of damage.
Indicates a potentially hazardous situation that
may result in property damage if the
corresponding measures are not taken.
NOTICE
Indicates a possible disadvantage, i.e.
undesirable conditions or consequences can
occur if the corresponding measures are not
taken.
NOTE
Indicates a possible advantage if the
corresponding measures are taken; tip.
1.2 General safety precautions
WARNING
Improper use of the unit can result in
serious or even fatal injuries!
These operating instructions
must have been read completely and
understood before beginning any work with
or at the pump-motor unit,
must be strictly observed,
must be available at the operating location of
the pump-motor unit.
WARNING
Improper use of the unit can result in
serious or even fatal injuries!
Only operate the pump-motor unit
for the purposes indicated under "Intended
Use"!
with the fluids indicated under 'Intended Use'!
with the values indicated under 'Technical
Data'!
WARNING
Improper use of the unit can result in
serious or even fatal injuries!
All work on and with the pump-motor unit
(transport, installation, operation, shut-down,
maintenance, disposal) may only be carried out
by trained, reliable expert personnel!
Hair and clothing can be pulled into the unit
or caught and wound up moving parts!
Do not wear long, loose hair or wide, loose
clothes! Wear a hair net!
DANGER
Electrical danger!
Work on electrical installations may be carried
out by trained and authorized electricians only!
DANGER
Electrical danger!
Before beginning work on the unit or system, the
following measures must be carried out:
Deenergize.
Secure against being switched on again.
Determine whether deenergized.
Ground and short-circuit.
Cover or block off adjacent energized parts.
DANGER
Electrical danger!
Do not open the motor terminal box until
absence of electricity has been ensured!
WARNING
Danger due to vacuum and gauge pressure:
sudden escape of fluids (skin and eye
injuries),
sudden drawing in of hair and clothing!
Danger due to escaping fluid:
Burns!
Use mounting elements, connections, lines,
fittings and containers with sufficient freedom
from leaks and strength for the pressures which
occur.
Check the mounting elements, connections,
lines, fittings and containers for strength, leaks
and firm seating at regular intervals!
WARNING
Danger from rotating parts (external fan,
impeller, shaft):
Cutting/cutting off of extremities,
Grasping/winding up of hair and clothing!
Danger due to vacuum and gauge pressure:
sudden escape of fluids (skin and eye
injuries),
sudden drawing in of hair and clothing!
Danger due to escaping fluid:
Burns!
Start-up
and operation only under the following
conditions:
The pump-motor unit must be completely
assembled. When doing so, pay particular
attention to the following components:
– the vacuum pump/compressor cover,
– the muffler on inlet and discharge
connections,
– the fan guard.
The pipes/hoses must be connected to inlet
and discharge connections.
Inlet and discharge connections and the
connected pipes/hoses may not be closed,
clogged or soiled.
Check the mounting elements, connections
of the pipe/hose connections, lines, fittings
and containers for strength, leaks and firm
seating at regular intervals.
Danger from rotating parts (external fan,
impeller, shaft):
Cutting/cutting off of extremities,
Grasping/winding up of hair and clothing!
Danger due to vacuum and gauge pressure:
sudden escape of fluids (skin and eye
injuries),
sudden drawing in of hair and clothing!
Danger due to escaping fluid:
Burns!
Before beginning work on the pump-motor unit
,
take the following measures:
Shut down pump-motor unit and secure
against being switched on again.
Attach a sign on the system controller and on
the control elements for the pump-motor unit:
"DANGER! Maintenance work on vacuum
pump/compressor! Do not switch on!"
Wait for pump-motor unit to come to a
complete stop. Observe run-on time!
Allow pump-motor unit to cool!
Shut-off lines. Release pressure.
Make sure that no vacuum or gauge pressure
is present in the lines/tanks to be opened.
Make sure that no fluids can escape.
WARNING
Danger from rotating impeller:
Cutting/cutting off of extremities!
The rotating impeller is accessible with the inlet
and discharge connections open!
Do not reach into the unit through open
connections!
Do not insert objects into the unit through the
openings!
WARNING
Danger from rotating impeller:
Cutting/cutting off of extremities!
The rotating impeller is accessible with the inlet
and discharge connections open!
With free entry and exit of gases, i.e. with direct
intake out of or direct feeding into the
atmosphere without piping, the following
therefore applies:
Provide the inlet and discharge connections of
the pump-motor unit either with additional
mufflers or with additional piping of a sufficient
length to prevent access to the impeller!
WARNING
Danger of burns from hot surfaces of the
pump-motor unit and from hot fluids!
High temperatures of up to approx. +160°C
[+320°F] can occur on the surface of the pumpmotor unit.
Cover the pump-motor unit with a suitable touch
protection (e.g. perforated plate cover or wire
cover).
Do not touch during operation!
Allow to cool after shut-down!
Increased pressure differences can be
achieved with the two-impeller and threeimpeller pump-motor units.
, see
Intended Use
are primarily intended for higher pressure
conditions;
are designed for continuous operation.
With increased switch-on frequency (at equal
intervals of approx. 5x per hour) or increased
gas entry and ambient temperature, the over
temperature of the winding and the bearings
can be exceeded.
Consultation with the Service Department is
required for operating conditions of this kind.
When operating the G-BH7, the limits listed in
Chapter 3, "Technical Data", Pg. 8 ff. must
always be complied with.
Foreseeable Misuse
It is prohibited
to use the G-BH7 in applications other than
industrial applications unless the necessary
protection is provided on the system, e.g.
guards suitable for children's fingers;
to use the device in rooms in which explosive
gases can occur if the G-BH7 is not expressly
intended for this purpose;
to extract, to deliver and to compress
explosive, flammable, corrosive or toxic fluids,
unless the G-BH7 is specifically designed for
this purpose;
to operate the G-BH7 with values other than
those specified in Chapter 3, "Technical
Data", Pg. 8 ff.
Any unauthorized modifications of the G-BH7 are
prohibited for safety reasons.
The operator is only permitted to perform the
maintenance and service work described in these
operating instructions.
Any maintenance and service work which goes
beyond this many only be performed by
companies authorized by the manufacturer
(inquire with the Service Department).
Measuring-surface sound-pressure level as per
EN ISO 3744, measured at a distance of 1 m
[3.28 ft] at an operating point of approximately
2/3 of the permissible total pressure difference
with the lines connected without a vacuum or
pressure relief valve, tolerance ±3 dB (A).
The information listed in the following tables
corresponds to the heating of vacuum
pump/compressor housings and the air exiting
compared to the ambient temperature during
operation with a permissible total pressure
difference and an air pressure of 1,013 mbar
[14.7 psi]. At lower air pressures these values
Pump-motor units for higher fluid
temperatures on request.
Ambient
temperature
(standard
design)
1
:
max. permissible temperature:
+40°C
min. permissible temperature:
-15°C
Nominal value:
+25°C
Ambient temperatures between
25°C [+77°F] and 40°C [+104°F]
affect the permissible total
pressure difference (see Section
"Permissible total pressure
difference").
At higher temperatures the
winding may be damaged and
the grease change interval may
be shortened.
[+104°F]
[+59°F]
[+104°F]
[+5°F]
[+77°F]
Min. inlet
See rating plate.
pressure:
Max. discharge
See rating plate.
pressure during
compressor
operation:
Max. permissible
pressure in
pump-motor unit:
2.5 bar abs. [36.2 psia]
At this pressure the operation of
the pump-motor unit may be
considerably impaired.
Provide a corresponding
protective device (e.g. pressure
relief valve) if necessary.
Permissible total
pressure
difference:
The total pressure difference
specified on the rating plate only
applies under the following
conditions:
Ambient temperature:
Inlet temperature
Pressure:
At an ambient temperature of
40°C [104°F] the total pressure
difference specified on the rating
plate must be reduced by 10%.
If the ambient temperature is
between 25°C [77°F] and 40°C
[104°F], then the total pressure
difference specified on the rating
plate must be reduced linearly to
the temperature by between 0
and 10 %.
Installation altitude
25°C [77°F].
(temperature of pumped
gases at inlet connection):
15°C [59°F].
during vacuum-pump
operation:
1,013 mbar [14.7 psia] at
discharge connection;
during compressor
operation:
1,013 mbar [14.7 psia] at
inlet connection;
Max. of 1,000 m [3,280 ft] above sea level.
When installing the pump-motor unit at an
altitude of more than 1,000 m [3,280 ft] above
sea level, first inquire with the Service
department.
The transport must be carried out in different
ways depending on the model:
WARNING
Tipping or falling can lead to crushing,
broken bones etc.!
Sharp edges can cause cuts!
Wear personal safety equipment (gloves, safety
shoes and protective helmet) during transport!
WARNING
Danger from tipping or falling loads!
Prior to transport and handling make sure that
all components are securely assembled and
secure or remove all components the fasteners
of which have been loosened!
Manual handling:
WARNING
Danger from lifting heavy loads!
Manual handling of the unit is only permitted
within the following limits:
max. 30 kg [max. 66 lbs] for men
max. 10 kg [max. 22 lbs] for women
max. 5 kg [max. 11 lbs] for pregnant women
For the weight of the pump-motor unit, see
Chapter 3.1, "Mechanical data",
Section "Weight", Pg. 8.
For weights above the given values use suitable
lifting appliances and handling equipment!
Handling by means of lifting equipment:
WARNING
Danger from tipping or falling loads!
When transporting with lifting equipment,
observe the following basic rules:
The lifting capacity of lifting equipment and
lifting gear must be at least equal to the unit's
weight.
For the weight of the pump-motor unit, see
Chapter 3.1, "Mechanical data",
Section "Weight", Pg. 8.
The pump-motor unit must be secured so
that it cannot tip or fall.
Do not stand or walk under suspended loads!
Models 2BH72., 2BH73., 2BH74. [single-
impeller] and 2BH75. [single-impeller]:
Manual handling
Models 2BH74. [two-impeller], 2BH75. [two-
impeller] and 2BH76.:
Transport with crane, hooked onto eye bolt
(1 attachment point)
For transport with a crane, the pump-motor unit
can be hooked onto the crane hook as follows:
directly on the eye bolt
or possibly
with lifting belts.
Eye bolt:
All models are equipped with an eye bolt. The
eye bolt is mounted on the vacuum
pump/compressor housing.
In case of possible removal and remounting of
the eye bolt, it must be ensured that the eye level
is positioned exactly in the axis direction of the
pump-motor unit. Lay shims under the eye bolt if
necessary.
The eye bolt must be firmly tightened.
Loads laterally to the ring level are not
permissible. Heavy impact loads during transport
must be avoided.
Improper use of the unit can result in
serious or even fatal injuries!
Have you read the safety precautions in Chapter
1, "Safety", pg. 3 f.?
Otherwise you many not carry out any work with
or on the pump-motor unit!
DANGER
Danger from missing view into area of pumpmotor unit!
When operating the control elements without a
view into the area of the pump-motor unit, there
is a danger that the pump-motor unit will be
switched on while other persons are still
performing work on it. Extreme injuries are
possible!
Provide control elements at a location with a
view of the pump-motor unit.
DANGER
Electrical danger!
The pump-motor unit must be installed so that
the electrical device cannot be damaged by
external influences!
In particular, the feed pipes must be securely
routed, e.g. in cable ducts, in the floor etc.
WARNING
Danger from balance damage caused by
vibration!
Vibrating environments can cause balance
damage!
Install the pump-motor unit on a solid foundation
or on a solid mounting surface.
Check screw glands/unions for mounting the
pump-motor unit on the mounting surface
regularly for strength and firm seating.
WARNING
Danger from crushing due to pump-motor
unit tipping over!
Wear personal safety equipment (protective
gloves and safety shoes).
Handle the unit with the appropriate care.
Install the pump-motor unit on a solid foundation
or on a solid mounting surface!
Check screw glands/unions for mounting the
pump-motor unit on the mounting surface
regularly for strength.
Installation
WARNING
Danger of fire from flammable substances!
The pump-motor unit must never come into
contact with flammable substances.
For exact information on the temperature
increase, see Chapter 3.1, "Mechanical data",
Section "Temperature increase", Pg. 9.
WARNING
Danger of burns from hot surfaces of the
pump-motor unit and from hot fluids!
High temperatures of up to approx. +160°C
[+320°F] can occur on the surface of the pumpmotor unit.
The pump-motor unit must be installed so that
accidental touch of its surface is not possible.
Cover the pump-motor unit with a suitable touch
protection (e.g. perforated plate cover or wire
cover).
WARNING
Danger of injuries from flying parts!
Select installation so that parts that are thrown
out through the grate if the external fan breaks
cannot hit persons!
CAUTION
Danger of tripping and falling!
Make sure the unit does not present a danger of
tripping.
Lay cables and pipes so that they cannot be
reached during operation(recessed in floor, in
ducts on the wall etc.).
CAUTION
Danger of overheating due to hot surface of
pump-motor unit!
High temperatures can occur on the surface of
the pump-motor unit.
Temperature sensitive parts, such as lines or
electronic components, may not come into
contact with the surface of the pump-motor unit.
The pump-motor unit is ready to connect on
delivery.
The drive motors of the pump-motor units have
the following design:
However, if the time from delivery to
commissioning of the pump-motor unit exceeds a
certain period, the lubrication of the rolling
bearings must be renewed.
See Chapter 8.2, "Storage conditions",
Section "Lubrication of rolling bearings after
longer storage", Pg. 23 for information on this
topic.
Carry out the following work to install the pumpmotor unit:
Installation and securing,
Attachment of the included loose muffler if
necessary,
Attachment of threaded flange or hose flange
(available as accessories)
for the connection of inlet or discharge pipe to
the muffler,
Electrical connection,
Connection of inlet and discharge connection
to the system.
5.1 Installation
WARNING
For an installation that differs from the following
specifications, it is necessary to inquire with the
Service Department!
Ambient conditions:
The pump-motor unit is suitable for installation in
the following environments:
In a dusty or damp environment,
in buildings,
in the open.
When properly installed in the open, the
pump-motor unit must be protected from
exposure to intensive sunlight, e.g. by
attaching a protective roof. Otherwise, no
special protective devices against the effects
of weathering are required.
NOTICE
The maximum permissible loading due to
vibrations may not be exceeded!
See Chapter 3.1, "Mechanical data",
Section "Vibrations", Pg. 8 for information on
this topic.
with degree of protection IP55 (see rating
plate),
with tropicalized insulation.
Installation conditions:
The pump-motor unit must be installed as
follows:
on level surfaces,
at a maximum height of 1000 m [3,280 ft]
above sea level.
When installing at an altitude of more than
1,000 m [3,280 ft]above sea level, first inquire
with the Service Department.
Minimum distance:
To ensure sufficient cooling of the pump-motor
unit, it is absolutely necessary that the required
minimum distances to the fan guard and to the
face of the vacuum pump/compressor cover
be maintained.
See Chapter 3.1, "Mechanical data",
Section "Minimum distances", Pg. 8.
The compliance of the specified minimum
distance to the face of the vacuum
pump/compressor cover is especially important
when installing on the vacuum pump/compressor
cover or near a wall.
CAUTION
To ensure sufficient cooling of the pump-motor
unit, also observe the following:
Ventilation screens and openings must
remain clear.
Discharge air of other units may not be
directly sucked in again!
Noise radiation:
To reduce the noise radiation, the following must
be observed:
Do not mount pump-motor unit on noise-
conducting or noise-radiating parts (e.g. thin
walls or sheet-metal plates).
Provide pump-motor unit with sound-insulating
intermediate layers (e.g. rubber buffers under the
base of the pump-motor unit) if necessary.
Install the pump-motor unit on a stable
foundation or on a rigid mounting surface.
This provides for smooth, low-vibration
running of the pump-motor unit.
Components for reducing noise on the pumpmotor unit:
Mufflers (included as standard equipment):
On delivery the pump-motor units are
equipped with attached mufflers as standard.
The noise radiation is considerably reduced
by the mufflers. See Fig. 2 to Fig. 4, Pg. 18 ff.
Additional mufflers (available as an option):
The additional mufflers enable a further noise
reduction. They may only be used with free
entry and exit of gases, i.e. with direct intake
out of or direct feeding into the atmosphere
without piping.
Noise protection hoods (available as an
option):
Noise protection hoods are suitable for
installation in rooms and in the open. They
reduce both the total sound pressure level
and tonal components that are perceived as
particularly annoying.
Installation variants/axis position:
Basically, when installing the pump-motor unit,
Vertical installation on the vacuum
pump/compressor cover ("cover installation")
With vertical installation of the pump-motor unit
with the vacuum pump/compressor cover facing
downward, rubber feet must be used.
Proceed as follows:
The rubber feet are available as accessories.
They are delivered in a set of 3.
On the upper section they are provided with
stud bolts and on the lower section with a
threaded hole.
Mount the rubber feet on the pump-motor unit:
Screw the stud bolts of the rubber feed into
the holes on the face of the vacuum
pump/compressor cover and tighten them.
Mount the pump-motor unit together with the
rubber feet on the installation surface:
Select suitable mounting elements for the
threaded hole.
Screw the rubber feet to the surface or
foundation via the threaded hole.
Vertical mounting on the wall
the following variants are possible with a different
axis position (horizontal or vertical):
Horizontal installation
Vertical installation on the vacuum
pump/compressor cover ("cover installation")
Vertical mounting on the wall.
Basically, all variants are possible with all
models.
However, a distinction must be made between a
design with and a design without a condensed water opening for the axis position:
The pump-motor units without a condensed
water opening can be installed and secured in
any axis position.
The pump-motor unit with a condensed water
opening may only be installed and secured
horizontally with the base at the bottom.
With vertical mounting of the pump-motor unit on
the wall, the pump-motor unit is mounted via the
holes in the base.
Proceed as follows:
Position the pump-motor unit as close to the
wall as possible on a stable supporting plate
with sufficient load-bearing capacity.
The pump-motor unit must be positioned with
the base toward the wall.
Provide the base of the pump-motor unit with
mounting holes.
Select the suitable screw type.
Screw the base of the pump-motor unit to the
wall with the screws.
When doing so, be sure to provide all
mounting holes with screws!
Remove the supporting plate.
Eye bolt:
Horizontal installation
Following installation, the eye bolt must be either
Screw the base of the pump-motor unit to the
surface with suitable mounting elements.
Proceed as follows:
Provide the base of the pump-motor unit with
mounting holes.
Select the suitable screw type.
Screw the base of the pump-motor unit to the
surface with the screws.
When doing so, be sure to provide all
mounting holes with screws!
Improper behavior can result in severe injuries
and material damage!
DANGER
Electrical danger!
The electrical connection may be carried out by
trained and authorized electricians only!
DANGER
Electrical danger!
Before beginning work on the unit or system, the
following measures must be carried out:
Deenergize.
Secure against being switched on again.
Determine whether deenergized.
Ground and short-circuit.
Cover or block off adjacent energized parts.
CAUTION
Incorrect connection of the motor can lead to
serious damage to the unit!
Regulations:
Open the required cable entry openings on the
terminal box. Here the following two cases are
differentiated:
The cable entry opening is prefabricated and
provided with a sealing plug.
Screw out sealing plug.
OR
The cable entry opening is closed off with a
casting skin (only on pump-motor units with
drive-motor axis heights of 100 to 160 in
standard design).
Break out casting skin using a suitable tool.
For example, use a metal pin with a
corresponding diameter or a chisel and
hammer.
CAUTION
When pounding out the casting skin on the
cable entry openings in the terminal box, the
terminal box or its parts can be damaged (e.g.
terminal board, cable connections).
Proceed with suitable caution and precision
when doing so!
Prevent flash formation!
Mount cable glands on the terminal box. Proceed
as follows:
Select one cable gland in each case which is
The electrical connection must be carried out as
follows:
according to the applicable national and local
laws and regulations,
according to the applicable system-dependent
prescriptions and requirements,
according to the applicable regulations of the
utility company.
Electrical power supply:
Observe the rating plate.
It is imperative that the operating conditions
correspond to the data given on the rating plate!
Deviations permissible without reduction in
performance:
±5 % voltage deviation
±2 % frequency deviation
suitable for the cable diameter.
Insert this cable gland in the opening of the
terminal box.
Use a reducer if necessary.
Screw on the cable gland so that no moisture,
dirt etc. can penetrate into the terminal box.
Carry out the connection and the arrangement of
the jumpers in accordance with the circuit diagram in the terminal box.
Connect the protective conductor to the terminal
with the following symbol:
.
The electrical connection must be carried out as
follows:
The electrical connection must be
permanently safe.
There may be no protruding wire ends.
Clearance between bare live parts and
between bare live parts and ground: ≥ 5.5 mm
(at a nominal voltage of U
connections (except terminal strips), see
Chapter 3.1, "Mechanical data",
Section "Tightening torques for screw
connections", Pg. 10.
For terminals with clamping straps (e.g. as per
DIN 46282), the conductors must be inserted
so that approximately the same clamping
height results on both sides of the bar.
Individual conductors must therefore be bent
into a U-shape or connected with a cable lug
(DIN 46234).
This also applies to:
the protective conductor,
the outer ground conductor.
Both conductors can be recognized from their
color (green/yellow).
DANGER
Electrical danger!
The terminal box must be free from
foreign bodies,
dirt,
humidity.
Terminal box cover and cable entries must be
tightly closed so as to make them dustproof and
waterproof. Check for tightness at regular
intervals.
DANGER
Electrical danger!
Clearance between bare live parts and between
bare live parts and ground:
at least 5.5 mm (at a nominal voltage of
U
≤ 690V).
N
There may be no protruding wire ends!
For motor overload protection:
Use motor circuit breakers.
This must be adjusted to the specified
nominal current (see rating plate).
DANGER
Electrical danger!
There is danger of an electrical shock when a
defective pump-motor unit is touched!
Mount motor circuit breaker.
Have electrical equipment checked regularly by
an electrician.
Installation
Interference immunity of drive motor:
For drive motors with integrated sensors, the
operator must provide for a sufficient interference
immunity itself. Select a suitable sensor signal
cable (e.g. with screening, connection as for a
motor power-supply cable) and analyzing unit.
Operation with frequency converter:
With a power supply by external frequency
converters, the following must be observed:
High-frequency current and voltage harmonics
in the motor supply cables can lead to emitted
electromagnetic interference. This is
dependent on the converter design (model,
manufacturer, interference suppression
measures).
Be sure to observe the EMC notes of the
converter manufacturer!
Use screened power supply cables if
necessary. For optimal screening, the screen
must be conductively connected over a large
area to the metal terminal box of the drive
motor with a screwed metal gland.
In the case of drive motors with integrated
sensors (e.g. PTC thermistors) interference
voltage can occur on the sensor cable
depending on the converter model.
Limit speed:
see specifications on the rating plate.
WARNING
Pump-motor units with a UL approbation may
not be operated on frequency converters in the
US without testing by a suitable test agency!
The pump-motor units are delivered with mufflers
(indicated with arrows in the following
illustrations) for the inlet and discharge
connections as standard equipment.
With single-impeller pump-motor units, the
mufflers are already mounted on delivery.
WARNING
Danger from rotating impeller:
Cutting/cutting off of extremities!
The rotating impeller is accessible with the inlet
and discharge connections open!
With free entry and exit of gases, i.e. with direct
intake out of or direct feeding into the
atmosphere without piping, the following
therefore applies:
Provide the inlet and discharge connections of
the pump-motor unit either with additional
mufflers or with additional piping of a sufficient
length to prevent access to the impeller!
Connections:
Fig. 2: 2BH721 ... 2BH761 (single-impeller pump-
motor units)
With two-impeller and three-impeller pumpmotor units, the inlet-side muffler is included
loose for packaging-related reasons and must be
mounted by the operator.
Fig. 3: 2BH722 ... 2BH762 (two-impeller pump-
motor units with two-stage design)
Fig. 4: 2BH723 ... 2BH763 (three-impeller pump-
motor units with three-stage design)
To prevent foreign bodies from entering the unit,
all connections are sealed off when delivered. Do
not remove the sealing plugs until immediately
before connecting the pipes/hoses.
The following applies for the arrangement of the
pipe/hose connections:
The pumped gases are sucked in via the inlet
connection (see Chapter 5.3.1, Pg. 19) and
discharged via the discharge connection
(see
Chapter 5.3.2, Pg. 19).
The rotating direction of the shaft is marked
with an arrow on the face of the vacuum
pump/compressor cover and on the fan guard
(Fig. 1, Pg. 2, Item 7).
The flow direction of the gases is marked with
arrows on both connections (Fig. 1, Pg. 2,
Item 6).
WARNING
Danger from interchanging inlet and
pressure line!
Interchanged inlet and pressure lines can lead
to damage to the pump-motor unit and the
system, and as a result of this to serious
injuries!
Make sure that the inlet and pressure line
cannot be confused when connecting.
Look for the clear marking with the flow direction
arrow on the inlet and discharge connections.
During operation, connected pipes and vessels
are vacuumized or pressurized!
Use only mounting elements, connections, lines,
fittings and containers with sufficient freedom
from leaks and strength for the pressures which
occur.
Make sure that the mounting elements and
connections are mounted sufficiently firmly and
leak-free!
CAUTION
If the pumped gases are passed on the
discharge side in a closed pipe system, then it
must be ensured that the pipe system is
adapted to the maximum discharge pressure.
See Chapter 3.3: "Operating conditions",
Section "Pressures", Pg. 11). Connect a
pressure relief valve upstream if necessary.
NOTICE
Attach pipes/hoses free of mechanical tensions.
Support the weight of the pipes/hoses.
Installation
5.3.1 Inlet connection
The inlet connection with the related muffler
(Fig. 1, Pg. 2, Item 3) is marked with an arrow
pointing into the vacuum pump/compressor.
Connect the inlet pipe here. The pumped gases
are sucked in via this.
Procedure: see Chapter 5.3.3.
WARNING
Danger from solid bodies and impurities in
the pump-motor unit!
If solid bodies penetrate into the pump-motor
unit, blades of the impellers can break and
broken pieces can be thrown out.
Install a filter in the inlet pipe.
Replace filter regularly!
5.3.2 Discharge connection
The discharge connection with the related muffler
(Fig. 1, Pg. 2, Item 4) is marked with an arrow
pointing out of the vacuum pump/compressor.
Connect the discharge pipe here. The pumped
gases are discharged via this.
Procedure: see Chapter 5.3.3.
5.3.3 Procedure when connecting
pipes/hoses
Attach the pipes/hoses to the unit as described in
the following.
The pipes/hoses are connected differently to inlet
and discharge connections depending on the
type of line (pipe or hose):
Muffler (with inside threads):
The pipe is screwed directly into the muffler.
Hose connection:
– Screw hose flange (available as an
accessory) onto the muffler.
– Push the hose onto the hose flange and
secure it with a hose clamp. See
Chapter 3.1, "Mechanical data",
Section "Tightening torques for screw
connections", Pg. 10 for information on this
topic.
Improper use of the unit can result in
serious or even fatal injuries!
Have you read the safety precautions in Chapter
1, "Safety", Pg. 3 f.?
Otherwise you many not carry out any work with
or on the pump-motor unit!
WARNING
Danger from rotating parts (external fan,
impeller, shaft):
Cutting/cutting off of extremities,
Grasping/winding up of hair and clothing!
Danger due to vacuum and gauge pressure:
sudden escape of fluids (skin and eye
injuries),
sudden drawing in of hair and clothing!
Danger due to escaping fluid:
Burns!
Start-up
conditions:
The pump-motor unit must be completely
The pipes/hoses must be connected to inlet
Inlet and discharge connections and the
Check the mounting elements, connections
and operation only under the following
assembled. When doing so, pay particular
attention to the following components:
– the vacuum pump/compressor cover,
– the muffler on inlet and discharge
connections,
– the fan guard.
and discharge connections.
connected pipes/hoses may not be closed,
clogged or soiled.
of the pipe/hose connections, lines, fittings
and containers for strength, leaks and firm
seating at regular intervals.
6.1 Preparation
WARNING
Danger from closed connections!
With closed/soiled intake or discharge
connections vacuum or gauge pressure results
in the pump-motor unit.
This can overheat and damage the drive motor
winding.
Before start-up, make sure that the inlet and
discharge connections are not closed, clogged
or soiled!
CAUTION
Before starting up again after a longer standstill:
Measure the insulation resistance of the motor.
With values ≤ 1 kΩ per volt of nominal voltage,
the winding must be dried.
Measures before start-up:
If a shut-off device is installed in the discharge
pipe:
Make sure that the unit is NOT operated with
the shut-off device closed.
Before starting up the pump-motor unit,
observe the values specified on the rating
plate. Specifications on the drive-motor
nominal current apply at a gas entry and
ambient temperature of +40 C [+104°F].
Adjust the motor circuit breaker to the drive-
motor nominal current.
Check direction of rotation:
The intended rotating direction of the shaft is
marked with an arrow on the face of the
vacuum pump/compressor cover and on the
fan guard (Fig. 1, Pg. 2, Item 7).
The flow direction is marked with arrows on
the inlet and discharge connections (Fig. 1,
Pg. 2, Item 6).
Make sure the pipes/hoses on the inlet and
discharge connections are properly
connected.
Switch the pump-motor unit on briefly and
then off again.
Compare the actual rotating direction of the
external fan with the intended shaft rotating
direction indicated with the arrows shortly
before the pump-motor unit comes to a
standstill.
Danger due to rotating parts!
Danger due to vacuum and gauge pressure!
Danger due to escaping fluid!
Test runs may also only be conducted with the
pump-motor unit completely mounted.
DANGER
Electrical danger!
The electrical connection may be carried out by
trained and authorized electricians only!
DANGER
Electrical danger!
Before beginning work on the unit or system, the
following measures must be carried out:
Deenergize.
Secure against being switched on again.
Determine whether deenergized.
Ground and short-circuit.
Cover or block off adjacent energized parts.
Check operating speeds:
Observe the operating speed specified on the
rating plate. This may not be exceeded, as
otherwise the noise radiation, vibration behavior,
grease consumption duration and bearing
change interval worsen. To prevent damage as a
result of higher speeds, it may be necessary to
inquire with the Service Department as to the
maximum speed.
WARNING
Danger of hearing damage due to noise
radiation!
For the noise emission of the pump-motor unit
measured by the manufacturer, see Chapter 3.1,
"Mechanical data", Section "Noise level", Pg. 9.
However, the actual noise emission during
operation is highly dependent on the installation
and system conditions.
Conduct a noise measurement in the system
during operation after installing the pump-motor
unit.
The following measures must be taken by the
operator:
from 85 dB(A):
– Hearing protection must be provided.
from 90 dB(A):
– Mark noise area with a warning sign.
– Wear hearing protection.
– With free entry and exit of gases, i.e. with
direct intake out of or direct feeding into
the atmosphere without piping, attach an
additional muffle
To prevent standstill damage during storage, the
environment must provide the following
conditions:
dry,
dust-free,
low-vibration (effective value of vibration speed
≤ 2.8 mm/s).
v
eff
Ambient temperature: max. +40°C [+104°F].
CAUTION
Danger of overheating due to high
temperature!
When storing in an environment with a
temperature of over +40°C [+104°F] the winding
may be damaged and the grease change
interval may be shortened.
Lubrication of rolling bearings after longer
storage:
The new pump-motor unit may at first be stored
following delivery.
If the time from deliver to commissioning exceeds
the following periods, the lubrication of the rolling
bearings must be renewed:
Under advantageous storage conditions
(as specified above): 4 years.
Under disadvantageous storage conditions
(e.g. high humidity, salty air, sandy or dusty
air): 2 years.
In these cases open rolling bearings must be
relubricated and closed rolling bearings must be
completely replaced. In this case be sure to
inquire with the Service Department. In particular,
exact information with regard to the procedure
and grease type are required.
Servicing
WARNING
Improper use of the unit can result in
serious or even fatal injuries!
All maintenance work on the pump-motor unit
must always be performed by the Service
Department!
Maintenance work on the pump-motor unit may
only be conducted by the operator itself when
the related maintenance manual on hand!
Inquire with the Service Department!
Commissioning after longer standstill:
Before recommissioning after a longer standstill,
measure the insulation resistance of the drive
motor. With values ≤ 1 kΩ per volt of nominal
voltage, the winding must be dried.
9 Servicing
WARNING
Improper use of the unit can result in
serious or even fatal injuries!
Have you read the safety precautions in Chapter
1, "Safety", Pg. 3 f.?
Otherwise you many not carry out any work with
or on the pump-motor unit!
WARNING
Improper use of the unit can result in
serious or even fatal injuries!
All maintenance work on the pump-motor unit
must always be performed by the Service
Department!
Maintenance work on the pump-motor unit may
only be conducted by the operator itself when
the related maintenance manual on hand!
Our Service is available for work (in particular the
installation of spare parts, as well as
maintenance and repair work), not described in
these operating instruction.
A list of spare parts with an exploded drawing is
available on the Internet at
www.gd-elmorietschle.com.
Observe the following when returning pumpmotor unit:
The pump-motor unit must be delivered
complete, i.e. not dismantled.
The pump-motor unit may not present a
danger to the workshop personnel.
If the pump-motor unit has come into contact
with dangerous substances, then the
procedure described in Chapter 9.3,
"Decontamination and Declaration of
Clearance", Pg. 25, must be used.
The original rating plate of the pump-motor
unit must be properly mounted, intact and
legible.
All warranty claims are voided for pump-motor
units delivered for a damage expertise without
the original rating plate or with a destroyed
original rating plate.
In case of warranty claims, the manufacturer
must be informed of the operating conditions,
operating duration etc. and additional detailed
information provided on request if necessary.
9.3 Decontamination and Declaration of
Clearance
Disposal
10 Disposal
Have the entire pump-motor unit scrapped by a
suitable disposal company. No special measures
are required when doing so.
For additional information on disposing of the
unit, ask the Service Department.
11 Explosion-Protected Design
An additional set of operating instructions with
supplementary or specific information is provided
with these pump-motor units.
WARNING
Danger from flammable, caustic or toxic
substances!
To protect the environment and persons, the
following applies:
Pump-motor unit which have come into contact
with dangerous substances must always be
decontaminated before being passed on to a
workshop!
To provide proof that the decontamination was
carried out, a so-called declaration of clearance
must be included with the pump-motor unit on
delivery to the workshop.
The form required for this purpose is available
from the Service Department.
Gardner Denver Deutschland GmbH
Industriestraße 26
97616 Bad Neustadt • Germany
Representative for the compilation of technical documents:
Description and identification
of the machine:
Holger Krause
Industriestraße 26
97616 Bad Neustadt • Germany
Vacuum pumps/Compressors (Side channel blower)
Series G-BH7
Types 2BH72..-.....-. 2BH73..-.....-.
2BH74..-.....-. 2BH75..-.....-.
2BH76..-.....-.
The machine described above meets the following applicable Community harmonisation legislation:
2006/42/EC
European Parliament and Council Directive 2006/42/EC from 17th May 2006 on machinery
and amending Directive 95/16/EC.
2004/108/EC*)
Directive 2004/108/EC of the European Parliament and Council from 15th December 2004
for the application of the legal regulations of the EU member states concerning electrical
devices and repealing Directive 89/336/EEC
Harmonised standards applied:
EN 1012-1:2010
EN 1012-2:1996
Compressors and vacuum pumps - Safety requirements - Part 1: Compressors
Compressors and vacuum pumps - Safety requirements - Part 2: Vacuum pumps
+A1:2009
EN ISO 12100:2010
Safety of machinery - General principles for design -
Risk assessment and risk reduction (ISO 12100:2010)
EN 60204-1:2006
Safety of machinery - Electrical equipment of machines Part 1:
General requirements IEC 60204-1:2005 (amended)
EN 60034-1:2010/
AC:2010
Rotating electrical machines - Part 1:
Rating and performance IEC 60034-1:2010 (amended)
Bad Neustadt, 18.04.2012
(Place and date of issue)
Andreas Bernklau, product management/attorney Dr. Rudi Dittmar, development
(Name and function)
Only applicable for version with frequency converter 2FC
For the safety of our employees and to comply with statutory requirements on handling substances harmful to the health and
Statement on health safety and on the protection of the environment
the environment, this statement must be enclosed, fully completed, with each unit/system sent.
Without the fully completed statement, repair/disposal is not possible and delays are unavoidable!
The statement is to be completed and signed by suitably qualified, authorised personnel at the operating organisation.
In the case of shipment to Germany, the statement is to be completed in German or English.
The statement is to be attached to the outside of the packing on shipment.
If necessary, the carrier is to be informed.
1. Product designation (type):
2. Serial number (no. BN):
3. Reason for sending:
4. The unit/system
has not come into contact with hazardous substances. There will be no hazards for personnel or the environment during
repair/disposal. Continue with "6. Legally binding statement“
has come into contact with hazardous substances. Continue with "5. Information on the contamination“
5. Information on the contamination
(if necessary provide more information on an additional sheet)
The unit/system was used in the following application:
and has come into contact with the following classifiable substances or substances presenting a hazard to health/environment:
The unit/system has been emptied in accordance with the operating instructions, flushed and cleaned externally.
Safety data sheets in accordance with the applicable regulations are enclosed ( sheet).
The following safety precautions are necessary for handling (e.g. personal protective equipment):
6. Legally binding statement
I herewith guarantee that the details specified are true and complete and that I, as signatory, am in a position to judge that this is
so.
We are aware that we are liable to the contractor for any damages arising from incomplete or incorrect specifications. We are
obliged to indemnify the contractor against claims for damages by third parties arising from incomplete or incorrect specifications.
We are aware that, irrespective of this statement, we are directly liable to third parties - in particular including the contractor's
employees tasked with repair/disposal.