Elkay ENOB2-8RAC Installation Manual

ENOB2-8C, ENOB2-8RAC
INSTALLATION, CARE & USE MANUAL
TM
SWIRLFLO Refrigerated fountains with FLEXI-GUARD
ENOB2-8C ENOB2-8RAC
TM
INSTALLER
Review these instructions before beginning installation. Be sure that installation conforms to all plumbing, electrical and other applicable codes.
for future reference.
Service to be performed by authorized service personnel only .
NOTE: It is common practice to ground electrical hardware such as telephones, computers and other devices to
available water lines. This can, however , cause electrical feedback in the plumbing circuit, which results in an “electrolysis” effect occurring in the fountain. This may result in water which has a metallic taste to it or has a noticeable increase in the metallic content of the water.
When inspecting plumbing circuit, remember the line may be grounded some distance from the installation, and may occur outside the building or area in which the unit is being installed.
This condition can be avoided (in most cases) by using recommended materials during installation. Any drain fittings provided by the installer should be made of plastic which will electronically isolate the fountain from the remainder of the building’s plumbing circuits.
1
98005C (REV. B - 3/05)
1 1/8"
29mm
11"
279mm
8"
203mm
4 1/2"
114mm
28 3/4"
730mm
12"
305mm
5/8"
16mm
41 11/16"
1060mm
33 15/16"
863mm
1 5/8"
41mm
1 5/8"
41mm
C
D
36 1/2"
926mm
FINISHED FLOOR
MINIMUM DEPTH
18 3/4"
476mm
9 3/8"
238mm
8 1/8"
206mm
A
B
1 1/8"
29mm
3 1/8"
79mm
18 3/8"
467mm
27"
686mm
ADA
REQUIREMENT
BACK WALL LINE
ENOB2-8C, ENOB2-8RAC
36 1/2"
927mm
28 3/4"
730mm
18 3/4"
476mm
3 1/8"
80mm
1 1/8"
29mm
A
B
Model ENOB2-8C Model ENOB2-8RAC
98005C (REV. B - 3/05)
9 3/8"
238mm
8 1/8"
206mm
BACK WALL LINE
C
5/8"
16mm
12"
305mm
MINIMUM DEPTH
18 3/8"
467mm
1 5/8"
41mm
1 5/8"
41mm
33 15/16"
863mm
41 11/16"
1059mm
8"
203mm
4 1/2"
114mm
1 1/8"
29mm
11"
D
FINISHED FLOOR
27"
686mm
ADA
REQUIREMENT
LEGEND
2
Figure 1 - Rough-in Dimensions
279mm
A = 1/4” O.D. Tube - Water Outlet Connection
B = 3/8” O.D. Tube - Water Inlet Connection
C = 1-1/4” Waste Tube
D = ELECTRICAL INLET
Figure 2 - Chiller Installation
ENOB2-8C, ENOB2-8RAC
REQUIRED TOOLS AND MA TERIALS
These tables show special tools and/or additional materials (not provided) which are necessary to complete installation of these units:
Special Tools
Item Description Quantity
NONE
Additional Materials
Item Description Quantity
1 Unplated copper inlet pipe 2 Service Stop
1. Install chiller: Remove front panel of chiller. Slide chiller onto the shelf and position it to the left as per dimensions in Figure 1.
Note: Building construction must allow for adequate air flow on both sides, top and back of chiller. A minimum of 4” (102mm) on both sides and top is required. See chiller installation for additional instructions.
21
22
CHILLER OUTLET
TO BUBBLER
21
23
CHILLER INLET
2. Attach solenoid valve assembly to the underside of
cross member of mounting frame on electronic sensor unit. (See Fig. 7).
3. Make water supply connections. Inlet port is marked on the chiller (1/4” O.D. copper tube). Bend the copper tube (provided) at an appropriate length from the chiller to opening in frame. Install the in-line strainer (provided with chiller) by pushing it in until it reaches a positive stop, approximately 3/4” (19mm) on the marked chiller inlet port (See Figs. 3) (Refer to Fig. 13 on page 7 for details on assembling quick connect fittings). Attach an unplated and deburred copper water inlet line and a service stop (not provided) to the chiller. Turn on the water supply and flush the line thoroughly.
Caution: DO NOT SOLDER tubes inserted
into the strainer as damage to o-rings may result.
4. Make connection between remote chiller outlet tube and solenoid valve assembly. Outlet port is marked on the chiller (1/4” O.D. copper tube). Install a 1/4” tee (provided) on the marked chiller outlet port. Insert one end of 1/4” poly tubing into the tee and the other end into the straight fitting on the solenoid valve assy. (See Fig. 3)
5. Hang the upper panel on the mounting frame hanger. Be
sure that the panel is engaged with hanger at the top of frame before releasing it. Align holes in the panel with holes in the mounting frame. Install two (2) #10-24 x 5/8” (16mm) screws (Item 27 - Figure 4) in holes and tighten securely.
Figure 3 - ENO Tube Routing
6. Install the fountain. Remove the screw (Item 28) from cover
plate (Item 12) and slide cover plate toward basin. Mount the fountain to the upper panel and frame with (4) 5/16” x 1” (25mm) long bolts (Item 30), bracket (Item 34) and nuts (Item 33) provided. Tighten securely. Brackets (Item 34)
must be installed as shown to properly support fountain. (See Fig. 5)
3
98005C (REV. B - 3/05)
ENOB2-8C, ENOB2-8RAC
7. Attach waste tube (1-1/4” O.D.) to 1-1/4” O.D. slip trap (provided by others).
Figure 4 - Upper Panel Installation
30
11
28
34
33
View From Rear
Figure 5 - Fountain Installation
24, 25
27
27
8. Connect the fountain drain waste tube to the building sanitary sewer system. Connection should be made in compliance with local plumbing code requirements. (Note: Plumbing trap is not included with the fountain).
9. Make connection between solenoid valve assembly and fountain(s). Insert the 1/4” poly tubing coming from the fountain with sensor into the solenoid valve. Insert the 1/4” poly tubing coming from the fountain with push button into the tee (See Fig. 3).
10. Connect power cord of sensor to solenoid valve
assembly by running it through the back panel and connecting it to terminal as shown in Fig. 8.
11. Turn on water supply and check for leaks. Release air from tank by interrupting infrared beam; a steady stream of water assures all air is removed. The sensor has a 30 second maximum ON time. It may be necessary to step away from beam a few times to allow chiller tank to fill.
DO NOT SOLDER tubes while
inserted into the strainer as damage to o-rings may result.
12. These products are designed to operate on 20-105 PSIG supply line pressure. If inlet pressure is above 105
PSIG, a pressure regulator must be installed in the supply line.
Any damage caused byconnecting these products to a supply line with pressure lower than 20 PSIG or higher than 105 PSIG
IS NOT covered
under warranty.
13. Make electrical connections to the chiller. See chiller instructions.
14. Check stream height from bubbler. Stream height is
factory set at 35-40 PSI. If supply pressure varies greatly from this, please do the following. For Push Button units only, remove push button (Item 14 - Figure 12) and adjust the screw on the regulator (Item 16 - Figure 12). To remove push button, remove set screw from bottom of sleeve (Item 31). Insert a small punch in screw hole and push up while grasping the push button and pull forward removing the push button. Clockwise adjustment will raise stream height and counterclockwise movement will lower stream height. For best adjustment stream should hit basin approximately 6-1/2” from the bubbler. Reassemble push button by pushing in on button until the push button catches in the sleeve. Reinstall the set screw (Item 31) in the sleeve (Item 12). For Electronic sensor units only, remove lower panel (Item 26 - Fig. 4) and turn adjustment screw on the regulator (Item 16 - Fig. 8). Clockwise adjustment will raise stream height and counterclockwise movement will lower stream height. For best adjustment stream should hit basin approximately 6-1/2” from the bubbler.
Figure 6 - Lower Panel Installation
98005C (REV. B - 3/05)
26
15. Mount lower panel. Loosen the three (3) #10-24 x 5/8”
(16mm) screws (Item 27 - Figure 5) at frame bottom lip. Slide upper tongue of lower panel (Item 26 - Figure 6) under lower edge of already installed upper panel. Tighten previously loosened screws securely. (See Figure 6)
4
29
ENOB2-8C, ENOB2-8RAC
34
34
29
7
ENOB2-8C
ENOB2-8RAC
Figure 7 - Solenoid Assembly
CONNECT TO FOUNT AIN
SENSOR WIRING CONNECTOR
38
45, 46, 47
48
15
40
39
16
41
Figure 8 - Regulator Assembly
5
98005C (REV. B - 3/05)
See Fig. 10
ENOB2-8C, ENOB2-8RAC
20
8
44
27
42
36
19
32
18
6
11
9
10
35
37
43
Figure 9 - Exploded View
BUBBLER DETAIL
NOTE:
When installing replacement bubbler and pedestal, tighten nut (Item 5) only to hold parts snug in position. Do Not Overtighten.
98005C (REV. B - 3/05)
1
2
Figure 10 - Bubbler Assembly
6
3
4
Basin
5
T
1
ENOB2-8C, ENOB2-8RAC
See Fig. 10
19
9
29
See Fig. 10
8
18
Figure 11 - Fountain Body Assembly
10
27
20
11
21
32
32
12
49
13
14
15
16
17
31
Figure 12 - Push Button Assembly
Actuation of Quick Connect Water Fittings: Cooler is provided with lead-free connectors which utilize an o-ring water seal. T o remove tubing from the fitting, relieve water pressure, push in on the gray collar while pulling on the tubing. (See Figure 13) T o insert tubing, push tube straight into fitting until it reaches a positive stop (approximately 3/4”).
3/8" O.D. UNPLATED
/4" O.D. TUBE
WATER INLET
TO COOLER
COPPER TUBE CONNECT
COLD WATER SUPPLY
BUILDING WATER INLE
SERVICE STOP
(NOT FURNISHED)
98005C (REV. B - 3/05)
Figure 13 – Quick Connect Fittings
NOTE: WATER FLOW DIRECTION
Figure 14 – Water Supply Connections
7
ITEM NO.
1 2 3 4 5 6 7 8
9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49
P ARTS LIST
PAR T NO.
56073C 40322C 56011C 55997C 75580C 15027C 28455C 28474C 28473C 45767C 28343C 45781C 45847C 45848C 50986C 61315C 15005C 56163C 45769C 45768C 56092C 70682C 55996C 28383C 28384C 27026C
111008343890
70432C
38417001
75560C 75632C 70817C 70020C 28395C 36207C 36193C 45813C 31376C 40045C 50203C 56082C 56204C 70022C 70644C 31272C 70817C 75507C 28454C 75671C
ENOB2-8C, ENOB2-8RAC
DESCRIPTION
Bubbler Assy Orifice Assy Housing Assembly Pedestal Bubbler Locknut Brkt - Swirlflow Assy - Brkt Solenoid/Reg/Wire Basin - Swirlflow Lower Shell Fountain Body Cover Plate Sleeve Pin - Push Button Push Button Holder - Regulator Regulator Retaining Nut Gasket - Drain Assy - Drain/Tailpipe Drain - Ferrule Poly Tubing (Cut To Length) Tee - 1/4 Strainer (Provided with Chiller) Back Panel RH ADA Back Panel LH ADA Lower Panel Screw - #10-24 x .62 HHSM Screw - #8-32 x .38 THSM Screw - #8-18 x .37 HHSM Screw - 5/16-18 x 1.00 HHMS Setscrew - #10-32 x .31 Fttng - Elbow 1/4 x 1/4 Nut - Hex 5/16-18 Bracket - Support Wire - Extension Assy - Sensor Eye Sleeve - Swirlflow EE Cord - Power 115v Nut - Hex 1 5/16 Bushing - Strain Relief Nut - Regulator Lens - Swirlflow EE Screw - #6-32 x .31 Set Screw - #6-32 x .50 PHMS Solenoid Valve Fttng-Elbow 1/4 Stem x 1/4x90 Fttng-1/4 NPTF x 1/4OD Brkt -Solenoid/Reg Swirlflo Spring - Push Button
Installation Package
The components for installation are packed in three separate boxes, regardless of the type of unit being installed. The boxes contain the following:
Box No. 1: Wall Frame(s) Box No. 2: Remote Chiller, ECH8 Box No. 3: Fountain Arm and Panels
Additional materials, as noted in the Parts List, are also shipped in these boxes.
TROUBLE SHOOTING AND MAINTENANCE
1. Orifice Assy: Minerals deposits on orifice can cause water flow to spurt or not regulate. Mineral deposits may be removed from the orifice with a small round file not over 1/8" diameter or a small diameter wire. CAUTION: Do not file or cut orifice materials.
2. Stream Regulator: If orifice is free of material deposits regulate water flow according to instructions on page 4.
3. Sensor Control: The sensor has a 2 second delay time. If sensor fails to operate valve mechanism or operates erratically, check the following: a) Ensure there are no obstructions within a 40 inch radius from the front of fountain. b) Check wire connections at the solenoid valve and at the sensor. CAUTION: Make sure unit is unplugged before checking any wiring. c) Ensure proper operation of solenoid valve. If there is an audible clicking sound yet no water flows, look for an obstruction in the valve itself or elsewhere in the water supply line. WARNING: Do not expose sensor to direct sunlight.
4. Sensor Range Adjustment: The electronic sensor used in this fountain is factory pre-set for a "visual" range of 36 inches. If actual range varies greatly from this, or a different setting is desired, follow the range adjustment procedure below: a) Remove front lens. b) Locate range adjustment screw between the lenses of the sensor, then with a small tip screwdriver, rotate the range adjust­ ing screw clockwise to increase range or counter-clockwise to decrease range. 1/4 turn of screw is equal to approximately 12 - 18 inches of range. CAUTION: Complete range of sensor (24 - 46 inches) is only one turn of the adjusting screw. c) Replace lens.
CARE AND CLEANING INSTRUCTIONS
DO NOT use abrasive or chemical cleaners to clean the sensor lens.
They may dull the luster and attack the plastic cover and chrome finish of the fountain. Use ONLY soap and water, then wipe with clean cloth or towel. When cleaning adjacent surfaces, the fountain and the sensor lens should be protected from any splattering of cleaners. Acid and cleaning fluids can discolor and damage chrome plating and plastic sensor lens.
REPAIR SERVICE INFORMATION TOLL FREE NUMBER 1.800.260.6640
FOR PARTS, CONTACT YOUR LOCAL DISTRIBUTOR OR CALL 1.800.323.0620
ELKAY MANUFACTURING COMPANY • 2222 CAMDEN COURT • OAK BROOK, IL 60523 • 630.574.8484
98005C (REV. B - 3/05)
8
Loading...