
ECDFPW314FP
Installation/Care/Use Manual
Soft Sides™ Freeze Resistant Fount ain
Installer
T o assure you install this model easily and correctly , PLEASE READ THESE SIMPLE
INSTRUCTIONS BEFORE ST ARTING THE INST ALLA TION. CHECK YOUR
INST ALLATION FOR COMPLIANCE WITH PLUMBING, ELECTRICAL AND OTHER
APPLICABLE CODES. After installation, leave these instructions inside the fountain for
future reference. This Freeze Resistant Fountain is shipped in two separate cartons.
The second carton contains the Freeze Resistant Package LKFRB1 that is installed on
an interior heated wall. The interior space must maintain a minimum temperature of 50°
F (10° C). Refer to the Freeze Resistant Package for the rough-in dimensions for installation.
IMPORTANT
ALL SERVICE TO BE PERFORMED BY AN AUTHORIZED SER VICE PERSON
IMPORTANT! INSTALLER PLEASE NOTE.
THE GROUNDING OF ELECTRICAL EQUIPMENT SUCH AS TELEPHONE, COMPUTERS, ETC. T O
WA TER LINES IS A COMMON PROCEDURE. THIS GROUNDING MA Y BE IN THE BUILDING OR MA Y
OCCUR A WA Y FROM THE BUILDING . THIS GROUNDING CAN CAUSE ELECTRICAL FEEDBACK
INTO A FOUNT AIN, CREATING AN ELECTROLYSIS WHICH CAUSES A METALLIC TASTE OR AN
INCREASE IN THE MET AL CONTENT OF THE WA TER. THIS CONDITION IS A VOIDABLE BY USING
THE PROPER MA TERIALS AS INDICA TED. ANY DRAIN FITTINGS PROVIDED BY THE INST ALLER
SHOULD BE MADE OF PLASTIC TO ELECTRICALL Y ISOLA TE THE FOUNT AIN FROM THE BUILDING
PLUMBING SYSTEM.
Page 1
98011C (Rev. J - 1/08)

ECDFPW314FP
FIG . 1
ECDFPW314FPC
MOUNTING BOL T AND ACCESS HOLE LAYOUT
98011C (Rev. J - 1/08)
Page 2
LEGEND
A = RECOMMENDED W A TER SUPPL Y LOCA TION. 3/8 O.D. UNPLA TED
COPPER TUBE CONNECT STUBBED 1-1/2" (38mm) FROM WALL.
SHUT OFF BY OTHERS.
B = RECOMMENDED LOCATION FOR W ASTE OUTLET 1-1/4" O.D. DRAIN.
NOTE: REINFORCE THE WALL IN THE SHADED AREAS

ECDFPW314FP
FIG . 2
ECDFPW314FPC
ROUGH-IN DRAWING
Page 3
1. Wall should already be framed for the fountains using dimensions shown in Fig. 1. Shown dimensions pertain to installation location.
These dimensions are required for compliance with ANSI Standard A117.1. and ADA (Framing shown for reference only).
2. Remove bottom covers from fountains and save the screws.
3. Install the fountains using bolts and washers (provided). Tighten securely.
4. Attach drain tubes to fountains and cut to required length using the freeze resistant boxes as guides.
5. Install freeze-resistant boxes - see box instructions.
6. Replace bottom covers.
98011C (Rev. J - 1/08)

ECDFPW314FP
CABLE SHEA TH ADJUSTMENT
T o Increase Free Play
T o Reduce Free Play
FIG . 3
Note: Fountain Style May Vary
FIG . 4
See Fig. 7
See Fig. 3
98011C (Rev. J - 1/08)
FIG . 6
FIG . 5
FIG . 7
Page 4

ECDFPW314FP
The freeze resistant package must be mounted on an interior wall in a heated area. The room temperature of the interior
heated area must be 50° F (10° C) or higher. The freeze resistant package may be surface or recessed mounted. If recess
mounted the surface of the cover must be flush with the interior wall surface. The package is furnished with screws for
mounting the cover to the box. If the box is recess mounted, do not fasten the top and bottom of the cover to the box. Use
the holes on the front only .
1. Assemble the operating cable to the fountain bracket. (Fountain should be mounted to exterior wall) Create a loop in
the cable and thread the free end of the cable through the wall into the freeze resistant box. The adjustment nuts should
be in the middle of threaded area on the operating cable. See Figure 7
2. Connect free end of operating cable to the valve-operating bracket. The end of the cables must be recessed into the
indents on the pivot brackets.
3. Remove cable free play by adjusting the jam nuts on the ends of the operating cable. See Figure 4
4. Connect water line from fountain bubbler into freeze resistant box. The connection to the box uses a quick connect
water fitting. Position the water line, in the fountain, to drain back into interior mounted box. Any water left standing, in
the exterior line, can freeze.
T o insert tubing, push tube straight into fitting until it reaches a positive stop. T o remove tubing from the fittings, relieve
water pressure, push in on dark gray collar while pulling out on the tubing. See Figure 9
5. Connect drain and water supply lines to the freeze resistant fountain. Refer to Figure 1 for component positions. Inline
strainer must be used on the inlet water line.
Start-up
1. Turn on building water supply and check all connections for leaks. Repair as required.
2. Stream height is factory set at 35 PSI. If stream height needs to be changed adjust the regulator in the freeze resist ant
package. Clockwise adjustment raises stream height, counter clockwise adjustment will lower stream.
3. Adjust operating cable as required. Cable system should have a minimal amount of free play to allow for proper valve
operation. If the system is too tight the valve will stay in the on position creating constant water flow . Too much free
play will result in non-operation of the valve with the push-buttons.
4. Note: Water from the drain back tube in the freeze resistant package, will continue to run while the valve is actuated.
5. After cable system is adjusted properly stuff flexible insulation into any openings between the outside wall and the
interior box.
6. Recheck all connections. If all connections are leak free replace cover on the freeze resistant box and fountain.
1/4" O.D. TUBE
WATER INLET
3/8" O.D. UNPLATED
COPPER TUBE CONNECT
COLD WA TER SUPPLY
BUILDING WA TER
INLET
OPERATION OF QUICK CONNECT FITTINGS
SIMPLY PUSH IN
TUBE TO ATTACH
TUBE IS
SECURED
IN POSITION
PUSH IN COLLET
TO RELEASE TUBE
NOTE: WA TER FLOW DIRECTION
FIG . 8
SERVICE STOP
(NOT FURNISHED)
FIG . 9
Page 5
PUSHING TUBE IN BEFORE
PULLING IT OUT HELPS TO
RELEASE TUBE
98011C (Rev. J - 1/08)

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
NS
PAR T NO.ITEM NO.
40575C
28824C
45662C
45737C
27945C
27946C
40206000
50198C
51667C
75672C
75570C
28790C
55000665
28290C
40045C
55919C
100322740560
15009C
98118C
56092C
28286C
45679C
45805C
50074C
70379C
75541C
111577243890
75520C
PAR TS LIST
DESCRIPTION
Drain - Strainer
Bracket-Regulator Mounting
Push Button
Push Button Sleeve
Bracket-Basin
Bracket-Basin Pivot
Retainer
Snap Bushing
Bumper-Reg. Valve Assy
Cap Screw
Screw #10 X .50 Pinned T orx
Fountain Arm - Long
Bottom Cover Plate - Long
Back Panel
Hex Nut
Push Button (Extension)
Gasket
Bubbler - Nipple
Bubbler Assembly
Poly Tubing (Cut To Length)
Mounting Plate Assy
Drain - T ailpipe
Drain Adapter
Gasket - Tail Pipe
Pivot Rod
Washer - Flat .339/.359ID Steel
Screw - Mach. 5/16-18 x 3/4
Bit-Pinned T orx
ECDFPW314FP
FIG . 10
20
19
17
18
14
26, 27
FIG . 1 1
21
11 13
22,23,24
FIG . 12
25
9
12
1
2
15
FIG. 10
5
4
16
3
8
6
8
7
98011C (Rev. J - 1/08)
10
FIG . 13
FOR PARTS, CONT ACT YOUR LOCAL DISTRIBUTOR OR CALL 1.800.323.0620
ELKAY MANUFACTURING COMP AN Y • 2222 CAMDEN COURT • OAK BROOK, IL 60523 • 630.574.8484
Page 6