ELK P412 User Manual

Page 1
Power Supply
ELK-P412
Battery Charger with Enclosure
APPLICATION
The ELK-P412 is a general purpose high current power supply and battery charger. It is ideal for alarm, access control, and CCTV applications requiring up to 4 Amps. It distributes 12 Volts D.C. power to three (3) sets of DC power termi­nals, each having a voltage present indicator LED and automatic resetting overload protection. Built-In Low Battery Cut­off circuit protects the battery from deep discharging if AC power is lost for an extended period of time.
FEATURES
Switching Power Supply, no transformer needed.
Regulated 12VDC Output, capable of delivering 4 Amps.
Automatic Resetting Overload Protection.
Three Individually PTC Fused (2.5A) DC Power Outputs.
Master AC and Battery ON / OFF Power Switch.
Visual AC and DC LED Power Indicators.
Built-In Battery Charging Circuit.
Includes (1) Six foot AC Power Cord and cable clamp.
Heavy Duty Enclosure.
Lifetime Limited Warranty, call for details.
Automatic Low Battery Cutoff Circuit Protects Battery
SPECIFICATIONS
from Deep Discharge.
DC Output Voltage: 13.8 Volts D.C. Current Rating: 4 Amps . Auto Resetting "fuseless" circuit breakers (PTC). AC Input Voltage Range: 85~264VAC @ 47~63Hz. Low Battery Cutoff: ~=10 Volts. Ripple & Noise: 100mVp-p. Enclosure Dimensions: 12"H x 12"W x 3.25"D. Features and Specifications subject to change without notice.
4 AMP POW ER SUPPLY
Before plugging
in the power
cord, replace the
snap-on cover
over the AC
terminals for
shock protection
AC
INPUT
LN -V+V
120VAC POWER
CORD (6')
FILE E127738
EARTH
GROUND
OUTPUT
GRDNEUTRLLINE
DC
WARNING
SHOCK
HAZARD
AC POWER ON LED
DO NOT ADJ UST
(FACTORY SET)
BLACK
RED
NEG
OUTPUT 1
LOAD 1
POWER ON LEDS
+12V
NEG +12V
OUTPUT 2
LOAD 2
NEG +12V
OUTPUT 3
LOAD 3
POWER ON
SW1
POWER OFF
+
-
+
-
14.5VDC IN
BATTERY
INSTALLATION / OPERATION
1. Set Master Power Switch (SW1) to Power Off.
2. Mount enclosure in secure location near an AC power outlet that is not controlled by a switch.(supplied power cord is 6 feet long)
3. Connect devices to be powered to the screw terminals for DC output.The power distribution board has three sets of outputs, each set is limited to 2.5 amps. If a device requires more that 2.5 Amps, parallel two sets of terminals. (DO NOT EXCEED 4 AMPS)
4. Connect Battery to the battery wires, observe polarity.
5. Plug in the AC cord. Warning High Voltage is now present at the power supply AC input terminals.
6. Set the Master Power Switch to Power On. The LEDs at the power outputs should be on (if any are off, check for overloaded condition). The connected devices are now powered.
7. If AC power is lost, the Low Battery circuit will disconnect the battery if it's voltage drops below 10 Vdc. This helps to prevent "deep discharging" of the battery.
P.O. Box 100 • Hildebran, NC 28637 USA • 828-397-4200 • 828-397-4415 FAX http://www.elkproducts.com • email: info@elkproducts.com
05/10
12 Volt Battery
(Purchase separately)
Page 2
ELK-P412 Installation & Hookup Examples
APPLICATION: DUAL 2 AMP HOOKUP
For two separate 2 Amp continuous loads. DO NOT EXCEED 4 AMPS TOTAL. The third output can not be used in this configuration.
4 AMP POWER SUPPLY
WARNING
SHOCK
HAZARD
EARTH
GROUND
AC
INPUT
LN -V+V
DC
OUTPUT
GRDNEUTRLLINE
DO NOT ADJUST
(FACTORY SET)
-
RED
BLACK
12 Volt Battery
AC POWER ON LED
2 AMP LOAD
(Sirens,etc)
+
POWER ON LEDS
NEG
+12V
NEG +12V
OUTPUT 1
-
2 AMP LOAD
(Cameras, etc)
NEG +12V
OUTPUT 2
OUTPUT 3
OUTPUT 3
CAN NOT BE
USED IN THIS
CONFIGURATION
+
POWER ON
SW1
POWER OFF
+
-
+
-
APPLICATION: 4 AMP HOOKUP
Parallel any two outputs together for heavy loads up to 4 AMPS continuous. The third output can not be used in this configuration.
4 AMP POWER SUPPLY
WARNING
SHOCK
HAZARD
EARTH
14.5VDC IN
BATTERY
GROUND
AC
INPUT
LN -V+V
GRDNEUTRLLINE
RED
BLACK
12 Volt Battery
DC
OUTPUT
AC POWER ON LED
DO NOT ADJUST
(FACTORY SET)
-
4 AMP LOAD
(CONTINUOUS)
POWER ON LEDS
NEG
+12V
NEG +12V
OUTPUT 1
+
NEG +12V
OUTPUT 2
OUTPUT 3
OUTPUT 3
CAN NOT BE
USED IN THIS
CONFIGURATION
POWER ON
SW1
POWER OFF
+
-
+
-
14.5VDC IN
BATTERY
BLOCK DIAGRAM of DC Output Terminals
Each output can provide up to 2.5 Amps each (fused at
2.5 amps). However, the combined load from all outputs must not exceed 4 Amps continuously.
4 AMP POWER SUPPLY and BATTERY
(CURRENT DRAW OVER 4 AMPS WILL COME FROM THE BATTERY)
2.5 AMP
FUSE (PTC)
OUTPUT 1
UP TO
2.5 AMPS
-
+
2.5 AMP
FUSE (PTC)
OUTPUT 2
UP TO
2.5 AMPS
--
++
CONNECT LOADS TO EACH OUTPUT OR COMBINE
OUTPUTS TO SUPPLY MORE CURRENT
(DO NOT TO EXCEED 4 AMPS TOTAL)
2.5 AMP
FUSE (PTC)
OUTPUT 3
UP TO
2.5 AMPS
APPLICATION: AC Power Failure Indicator
This hookup will activate a 12 volt sounder if AC Power is lost.The ELK-912 relay will be energized while AC Power is ON. If AC Power is lost then the relay will turn off closing the COM and N.C. contacts to activate the sounder. The sounder is powered from the Battery.
4 AMP POWER SUPPLY
WARNING
SHOCK
HAZARD
EARTH
GROUND
AC
INPUT
LN -V+V
BLACK
12 Volt Battery
DC
OUTPUT
GRDNEUTRLLINE
DO NOT ADJU ST
(FACTORY SET)
Voltage is lost here during AC Power
Failure which will cause the relay to
drop out and activate the sounder
RED
AC POWER ON LED
POWER ON LEDS
NEG
+12V
NEG + 12V
OUTPUT 1
ELK-912 RELAY
NO COM NC
+
-
-
+
12 VOLT
SOUNDER
OUTPUT 2
POWER ON
SW1
POWER OFF
NEG + 12V
OUTPUT 3
+
14.5VDC IN
-
+
BATTERY
-