INSTALLATION
MANUAL
Cross Platform ControlTM
Specifications, Installation and Programming
M1 includes the SIA CP-01 Standards for False Alarm Reduction †
L520 Rev. J 11/11/10 |
Current with Firmware 5.2.x |
Introduction
LIMITATION
The ELK-M1G Control is designed to warn against unauthorized entry and other situations. However, it is not a guarantee of protection against the occurrence of burglary, fire, or other emergency. Any alarm system is subject to compromise or failure to warn for various reasons. For example:
-Unauthorized access can be gained through unprotected points or by disarming or bypassing protected points.
-Sensing devices are power driven and do not operate without electrical power. Battery-operated devices will not work without batteries, with dead batteries, or if the batteries are not put in properly. Devices powered solely by AC will not work if their AC power supply is cut off for any reason, however briefly.
-Telephone lines over which alarm signals are transmitted may be out of service or rendered inoperable by an intruder.
-Even if the system responds to the emergency as intended, occupants may have insufficient time to protect themselves from the emergency situation. In the case of a monitored alarm system, authorities may not respond appropriately.
-Smoke detectors have limitations and cannot detect all types of fires. According to data published by the Federal Emergency Management Agency, while smoke detectors have played a key role in reducing residential fire deaths in the United States, they may not activate or provide early warning for a variety of reasons in as many as 35% of all fires, . Some of the reasons some detectors used in conjunction with this System may not work are as follows. Smoke detectors may have been improperly installed and positioned. Smoke detectors may not sense fires that start where smoke cannot reach the detectors, such as in chimneys, in walls, or roofs, or on the other side of closed doors. Smoke detectors also may not sense a fire on another level of a residence or building. A second floor detector, for example, may not sense a first floor or basement fire. Finally, smoke detectors have sensing limitations. No smoke detector can sense every kind of fire every time. In general, detectors may not always warn about fires caused by carelessness and safety hazards like smoking in bed, violent explosions, escaping gas, improper storage of flammable materials, overloaded electrical circuits, children playing with matches, or arson. Depending an the nature of the fire, and/or location of the smoke detectors, the detector, even if it operates as anticipated, may not provide sufficient warning to allow all occupants to escape in time to prevent injury or death..
-Signals sent by wireless transmitters may be blocked or reflected by metal before they reach the alarm receiver. Even if the signal path has been recently checked during a weekly test, blockage can occur if a metal object is moved into the path.
-Wireless transmitters (used in some systems) are designed to provide long battery life under normal operating conditions. Longevity of batteries may be as much as 4 to 7 years, depending on the environment, usage, and the specific wireless device being used. External factors such as humidity, high or low temperatures, as well as large swings in temperature, may all reduce the actual battery life in a given installation. This wireless system, however, can identify a true low battery situation, thus allowing time to arrange a change of battery to maintain protection for that given point within the system.
-Installing an alarm system may make the owner eligible for a lower insurance rate, but an alarm system is not a substitute for insurance. Homeowner, property owners and renters should continue to act prudently in protecting themselves and continue to insure their lives and property.
-A user may not be able to reach a panic or emergency button quickly enough.
-Passive Infrared Motion Detectors can only detect intrusion within the designed ranges as diagrammed in their installation manual. Passive Infrared Detectors do not provide volumetric area protection. They do create multiple beams of protection, and intrusion can only be detected in unobstructed areas covered by those beams. They cannot detect motion or intrusion that takes place behind walls, ceilings, floors, closed doors, glass partitions, glass doors, or windows. Mechanical tampering, masking, painting or spraying of any material on the mirrors, windows or any part of the optical system can reduce their detection ability. Passive Infrared Detectors sense changes in temperature; however, as the ambient temperature of the protected area approaches the temperature range of 90 to 105F (32 to 40C), the detection performance can decrease.
-Alarm warning devices such as sirens, bells or horns may not alert people or wake up sleepers if they are located on the other side of closed or partly open doors. If warning devices are located on a different level of the residence from the bedrooms, they are less likely to waken or alert people inside the bedrooms. Even persons who are awake may not hear the warning if the alarm is muffled by noise from a stereo, radio, air conditioner or other appliance, or by passing traffic. Finally, alarm warning devices, however loud, may not warn hearingimpaired people.
-This equipment, like other electrical devices, is subject to component failure. Even though this equipment is designed to last as long as 20 years, the electronic components could fail at any time.
-The most common cause of an alarm system not functioning when an intrusion or fire occurs is inadequate maintenance. This alarm system should be tested weekly to make sure all sensors and transmitters are working properly.
ALL RIGHTS RESERVED
No part of this publication may be reproduced, stored in a retrieval system, or transmitted in any form or by any means, electronic, mechanical, photocopying, recording, or otherwise without the prior written permission of the manufacturer. The material in this publication is for information purposes and subject to change without notice. The manufacturer assumes no responsibility for any errors which may appear in this publication. Printed in U.S.A.
Use of this control for fire detection and/or annunciation may not be permitted by certain states, counties, municipalities or local jurisdiction. It is the responsibility of the installing alarm company to check with the local A.H.J. (Authority Having Jurisdiction) or State Fire Marshal’s office prior to using this control for fire detection.
Page 2 |
M1G Installation and Programming |
Table of Contents |
|
Specifications, Features, and Benefits ..................................................................................................... |
5 |
Wiring & Hookup Diagram ........................................................................................................................... |
6 |
Section 1 - Installation and Wiring ............................................................................................................. |
8 |
1.1 Planning the Installation ...................................................................................................................... |
8 |
1.2 Parts Diagram & Descriptions ........................................................................................................... |
8 |
1.3 Mounting and Wiring Preparation ....................................................................................................... |
8 |
1.4 Control Wiring .................................................................................................................................... |
9 |
Data Bus E.O.L. Termination - VERY IMPORTANT! .............................................................................. |
12 |
Section 2 - Operating the System ............................................................................................................ |
14 |
2.1 Introduction ....................................................................................................................................... |
14 |
2.2 Powering Up (One Keypad) ............................................................................................................. |
14 |
2.3 User Codes and Authorities .............................................................................................................. |
14 |
2.4 Installer Program Code and Authorities ............................................................................................ |
14 |
2.5 Keypad Overview ............................................................................................................................. |
15 |
Keypad Menus ........................................................................................................................................ |
16 |
Menu 0 - Select Keypad Alternate Area - Multi-area (Partition) Operation .............................................. |
20 |
Section 3 - Programming The Control ..................................................................................................... |
21 |
3.1 Introduction ....................................................................................................................................... |
21 |
3.2 Local Keypad Programming ............................................................................................................. |
21 |
3.3 Local or Remote Computer Programming (ELK-RP) and Anti-Takeover ......................................... |
21 |
3.4 Area Partitioning................................................................................................................................ |
21 |
3.5 Communicator Setup Checklist ....................................................................................................... |
22 |
3.6 Entering Installer Level Programming ............................................................................................... |
22 |
Menu 01 - Bus Module Enrollment .......................................................................................................... |
24 |
Menu 02 - User Code Options ................................................................................................................ |
25 |
Menu 03 - Area Definitions ...................................................................................................................... |
26 |
Menu 04 - Keypad Definitions ................................................................................................................. |
28 |
Menu 05 - Zone Definitions ..................................................................................................................... |
30 |
Menu 06 - Alarm Duration Timers ........................................................................................................... |
33 |
Menu 07 - Global System Definitions ..................................................................................................... |
34 |
Menu 08 - Telephone Account Setup ...................................................................................................... |
38 |
Menu 09 - Area Reporting Codes ........................................................................................................... |
40 |
Menu 10 - Zone Reporting Codes ........................................................................................................... |
42 |
Menu 11 - Keypad F-Key Reporting Codes ............................................................................................ |
43 |
Menu 12 - Sys Report Code Options & Codes ...................................................................................... |
44 |
Menu 13 - User Report Codes................................................................................................................ |
46 |
Menu 14 - Wireless Definitions ............................................................................................................... |
47 |
Section 4 - PC Programming and Automation Capabilities.................................................................... |
49 |
4.1 ELK-RP Software ............................................................................................................................ |
49 |
4.2 Update/Verify Firmware in the Control and Peripherals ................................................................... |
50 |
4.3 Automation Rules and Attributes ...................................................................................................... |
51 |
Appendix A - Event Codes ........................................................................................................................ |
58 |
Appendix B - Telephone Remote Control ............................................................................................... |
60 |
Appendix C - Voice Message Vocabulary *RP only * ............................................................................. |
62 |
Appendix D - Two Way “Listen-in/Talk” Interface................................................................................... |
64 |
Appendix E - SIA CP-01 Compliance ........................................................................................................ |
65 |
Appendix F - Regulatory Agency Statements .......................................................................................... |
66 |
Appendix G - Additional ELK-M1KP Keypad Information ...................................................................... |
69 |
Index ............................................................................................................................. |
71 |
M1G Installation and Programming |
Page 3 |
2200 |
N.C. |
ZONE |
|
Z1 |
|
Ohm |
N.O. |
||||
|
1 |
|
|||
EOL |
|
|
NEG |
||
2200 |
|
ZONE |
|
||
N.C. |
|
|
|||
Ohm |
N.O. |
|
|||
|
2 |
Z2 |
|||
EOL |
|
|
|||
2200 |
N.C. |
ZONE |
|
Z3 |
|
Ohm |
N.O. |
||||
|
3 |
|
|||
EOL |
|
|
NEG |
||
2200 |
|
ZONE |
|
||
N.C. |
|
|
|||
Ohm |
N.O. |
|
|||
|
4 |
Z4 |
|||
EOL |
|
|
|||
2200 |
N.C. |
ZONE |
|
Z5 |
|
Ohm |
N.O. |
||||
|
5 |
|
|||
EOL |
|
|
NEG |
||
2200 |
|
ZONE |
|
||
N.C. |
|
|
|||
Ohm |
N.O. |
|
|||
|
6 |
Z6 |
|||
EOL |
|
|
|||
2200 |
N.C. |
ZONE |
|
Z7 |
|
Ohm |
N.O. |
||||
|
7 |
|
|||
EOL |
|
|
NEG |
||
2200 |
|
ZONE |
|
||
N.C. |
|
|
|||
Ohm |
N.O. |
|
|||
|
8 |
Z8 |
|||
EOL |
|
|
|||
2200 |
N.C. |
ZONE |
|
Z9 |
|
Ohm |
N.O. |
||||
|
9 |
|
|||
EOL |
|
|
NEG |
||
2200 |
|
ZONE |
|
||
N.C. |
|
|
|||
Ohm |
N.O. |
|
|||
|
10 |
Z10 |
|||
EOL |
|
|
|||
2200 |
N.C. |
ZONE |
|
Z11 |
|
Ohm |
N.O. |
||||
|
11 |
|
|||
EOL |
|
|
NEG |
||
2200 |
|
ZONE |
|
||
N.C. |
|
|
|||
Ohm |
N.O. |
|
|||
|
12 |
Z12 |
|||
EOL |
|
|
|||
2200 |
N.C. |
ZONE |
|
Z13 |
|
Ohm |
N.O. |
||||
|
13 |
|
|||
EOL |
|
|
NEG |
||
2200 |
|
ZONE |
|
||
N.C. |
|
|
|||
Ohm |
N.O. |
|
|||
|
14 |
Z14 |
|||
EOL |
|
|
|||
2200 |
N.C. |
ZONE |
|
Z15 |
|
Ohm |
N.O. |
||||
|
15 |
|
|||
EOL |
|
|
NEG |
||
2200 |
|
ZONE |
|
||
N.C. |
|
|
|||
Ohm |
N.O. |
|
|||
|
16 |
Z16 |
|||
EOL |
|
|
|||
|
ZONE 16 |
|
2WIRE |
||
|
NORMAL |
JP1 |
SMOKE |
||
|
|
|
|
||
|
TELCO SEIZED |
|
|||
|
DIALER ACTIVE |
|
|||
|
+SAUX |
|
+SAUX |
||
+12VDC Switched |
|||||
|
|||||
|
Smoke Power |
|
NEG |
||
1.1 Amp PTC protected |
|||||
|
|||||
|
|
|
|
+VAUX |
|
|
See Note 1. |
|
NEG |
||
|
+VAUX |
|
|||
|
|
|
|||
+12VDC Auxiliary |
+VAUX |
||||
|
Power (3) |
|
|||
|
|
|
|||
|
1.25 Amp PTC |
|
NEG |
||
|
protected |
|
|||
|
|
|
|||
UL Listed Transformer, |
+VAUX |
||||
Class 2, 16.5VAC, 45VA |
NEG |
||||
Do not connect to a |
|||||
|
switched outlet. |
|
AC
ELK-TRG1640 16.5 V
AC
Power |
ON |
BATTERY |
Status |
|
+ - |
|
|
|
Reverse |
SW1 |
12V Battery |
Bat Leads |
||
Jumper to start with |
7 to 18 Ah |
|
|
||
no AC - See Note 4. |
|
ELK-M1
Cross Platform Control
TM
16 Zones expandable to 208
Control specifications subject to change without notice. All circuits are power limited except for Battery leads.
|
Strip Wires to 1/4" |
Length |
Strip |
|
|
4-Wire Smoke Detector - Any Zone |
|||
N.O. Alarm |
|
|
||
|
Contacts |
|
To Zone Input |
|
2200 |
|
+ |
To Zone NEG |
|
+ |
+SAUX |
|||
Ohm |
- |
|||
NEG |
||||
EOL |
- |
|
||
|
|
|||
|
|
|
U.L. Listed EOL Supervision Relay, ESL #204A or equiv. Use 2,200 Ohm EOL resistor, part # ELK-ER2200. Set JP1 to 'Normal'.
2-Wire Smoke Detector - Zone 16 ONLY
820 |
- |
NEG |
|
Ohm |
+ |
|
|
EOL |
Z16 |
||
|
To configure Zone 16 as a 2-wire smoke zone, set Jumper JP1 to '2WIRE SMOKE' and use 820 Ohm EOL resistor, part # ELK-ER820
Use Only Compatible Detectors
Control Compatibility Identifier: M10001 Refer to the Wiring & Hookup Diagram in the
Installation Manual # L520 Rev. J for the 2-Wire Smoke Detector Compatibility chart.
Notes
1.Refer to Appendix F located in the Installation Manual #L520 Rev. J for UL limitations on total continuous 'standby' current drain from terminals +SAUX, +VAUX, +VKP, and J16.
2.OUT 1 †† for speaker(s) ONLY (4 to 8 Ohms). If connecting more than 2, use series/parallel wiring to avoid going below a 4 ohm total load.
OUT 2 Connect ONLY 1 UL Listed Bell or Siren (self-contained). Current limited to 1 Amp. Program Global Option 26 to Voltage. This output supervised. Speaker(s) only permitted for non-UL installations. Series/parallel wire to avoid dropping below a 4 ohm total load.
OUT 3 NO/NC dry contact relay rated 4A. OUT 7 through 16 are +12V switched positive
voltage outputs rated at 50mA max.
3.This terminal (formerly earth gnd) not used. Do not connect any neg terminals to ground.
4.If AC fails, control will shut down if battery drops below 10.2 Volts. To start the control with a good battery and no AC, short the silver pads momentarily. Replace Battery every 3-5 years. Test regularly with ELK-BLT Battery Life Tester.
†Not Evaluated by UL
††Not for use in UL Listed Systems
TEST SYSTEM WEEKLY
Complies with FCC Part 68:
Reg. # US: 5K6AL03BELK-M1 REN: 0.3B Use Standard Jack: USOC RJ-31X.
Serial Number located below on base. Complies with part 15 of FCC rules.
This Class B digital apparatus complies with Canadian ICES-003
ELK PRODUCTS, INC. HA008E HILDEBRAN, N.C., 28637, USA
R1 |
|
Grey |
|
|
HOUSE |
||
|
|
|
|
|
|||
T1 |
|
Brown |
|
|
PHONES |
||
|
|
|
|
|
|
||
RING |
|
Red |
|
|
|
||
|
|
|
|
|
|
||
TIP |
|
Green |
|
|
TELCO |
||
|
|
|
|
|
LINE |
||
|
|
|
|
|
|
||
J3 |
|
Aux Data Bus †† |
|
||||
1 B |
J4 |
||||||
- |
for wireless receiver |
||||||
A |
|
|
|
|
|
||
C |
i.e. GE-Caddx |
|
CONN. |
||||
+ |
NX408E, NX416E, |
||||||
|
|||||||
|
|
or NX448E |
|
|
|||
|
|
See Manual |
|
RS232 |
|||
JP2 |
Select PLC Mode |
|
|||||
|
|
||||||
|
|
|
|||||
1 WAY (PL513/PSC04) |
|
|
|||||
2 WAY (TW523/PSC05) |
|
||||||
|
|
|
|
Serial Port †† |
|||
|
|
|
|
for Computer/ELKRP |
|||
|
|
|
|
See Manual |
|||
PLC †† |
|
|
|
PSC05 †† |
|||
Lighting |
|
|
|
||||
Do Not |
|
or |
|||||
Interface |
|
||||||
Connect to |
Equivalent |
||||||
|
Conn. |
||||||
|
|
|
a Phone |
|
|
||
J5 |
|
|
|
Line! |
|
|
|
|
|
|
|
|
|
||
|
|
J-16 Programmable Outputs |
|||||
|
|
1 |
|
+12V |
See Note 1 |
||
|
|
|
|
NEG |
|
& Note 2 |
|
|
|
|
|
OUT 16 |
|
||
|
|
|
|
OUT 15 |
|
||
|
|
|
|
OUT 14 |
|
||
|
|
|
|
OUT 13 |
|
||
|
|
|
|
OUT 12 |
|
||
|
|
|
|
OUT 11 |
|
||
|
|
|
|
OUT 10 |
|
||
|
|
|
|
OUT |
9 |
|
|
|
|
|
|
OUT |
8 |
|
|
|
|
|
|
OUT |
7 |
|
|
|
|
N/C |
OUT3 On LED |
||||
3 |
|
Dry Contact Relay |
|||||
|
|
|
rated 4A @ |
||||
OUT |
|
COM |
12 - 24VDC |
||||
|
|
||||||
|
|
N/O |
See Note 2 |
||||
|
|
|
|
|
|||
2 |
|
+ |
|
|
|
|
|
OUT |
|
Bell (Supervised) |
|||||
|
|
- |
See Note 2 |
|
|||
1 |
|
+ |
|
|
|
|
|
OUT |
|
Voice/Siren † † |
|
||||
|
|
- |
See Note 2 |
|
|||
Audio Network Interface †† |
|||||||
|
|
O - |
I - |
B A |
+ |
1 |
|
|
|
|
|
|
|
J7 |
|
Data Bus Terminating Resistor |
JP3 |
||||||
|
|
||||||
+VKP |
|
RED |
|
1.25 Amp PTC |
|||
|
|
|
|
protected |
|||
|
|
GREEN |
|||||
DATA A |
|
Keypad |
|||||
|
|
|
|
|
|
||
DATA B |
|
WHITE |
|
|
|||
|
|
|
|
|
|
||
NEG |
|
BLACK |
Data Bus |
||||
|
|
|
|
See Note 1 |
|||
|
|
|
|
|
|||
|
|
Not Used -See Note 3 |
|||||
|
|
|
|
J2 |
J1 NEG |
||
|
|
Keypad & |
|
DATA B |
|||
|
|
Data Bus |
|
DATA A |
|||
|
|
|
|
|
|
+12V |
Page 4 |
M1G Installation and Programming |
Specifications, Features, and Benefits
General:
•Large zone capacity: 16 on-board zones expandable to 208
•Wireless capability † Up to 144 zones
•Two Way Listen-in interface †
•Flash Memory - Allows field updates to firmware electronically
•RS-232 serial port to interface PCs and peripheral devices
•Time/Date stamped 512 event history log
•Menu driven, text keypad programming - no manual required!
•Voice announcement of alarms, zone descs, status, etc.
-500+ Word/Phrase Vocabulary
-Link up to 6 words/phrases per announcement
-10 custom recordable words/phrases
•13 On-Board Outputs: 1 voice driver/siren, 1 siren driver/ voltage, 1 form “C” Relay, and 10 low current (50 mA) voltage outputs
•Supports 4 wire (any zone) and 2 wire (zone 16) smoke detectors
•Includes Fire alarm verification routine
•Can be partitioned into 8 areas and account numbers
•User Codes: 99 (4 or 6 digit) with assignable authority levels
•Arm levels: Away, Stay, Stay Instant, Nite, Nite Instant, Vacation
•Plug-in terminal blocks make service and pre-wires a snap!
•Hardware "watchdog" and nonvolatile EEPROM memory
•Supervised phone line, alarm output, and aux. overcurrent
Communications
•True V.22 bis Modem for fast reliable upload/download
•Optional M1XEP Ethernet Interface † for user operation, alarm reporting, programming, and more
•Built-in Phone Remote Control makes any phone a keypad
•Integrated Voice Dialer uses vocabulary or custom words
•Communicator formats: SIA, Contact ID, 4 + 2, and Pager
•Installer telephone (buttset) test feature
•Elk-RP PC programming software with conflict resolution to easily highlight differences between control and PC
-Dial-up, ethernet, RS-232 port, or local house phone jack
-Automatic answering machine bypass
Keypad
•Backlit, Large Character LCD Display, 16 x 2 lines
•Built-in Temperature Sensor
•Optional Plug-in Prox Access reader (26 bit Weigand format)
•Menu navigation keys and 6 programmable function keys
•Plug-in connector, only 4 wires to the control
•1 Zone input and 1 Output Programmable per Keypad
•Programmable display of time, date, & temperature
•Displays system diagnostics and settings.
•Maximum Keypads allowed: 16
Automation & Integration
•Create lifestyle enhancing comfort, convenience, and security
•Powerful “Whenever/And/Then” RULES Programming allows almost any imaginable operation. No need to chain rules together. Any single “Whenever” event can have one or more ANDs and THENs (conditions and commands).
•Rules utilize easy to understand text based references
•Control lighting using RS-232 serial or 2-way Power Line Control (PLC) Commands include On, Off, Dim, All On, All Off †
•Transmit and receive custom serial ASCII strings
•Read Temperature Sensors - Communicate with Thermostats
•Turn on Tasks, Lights, Outputs via Keypad or Telephone
•Sunset/Sunrise calculation and activation built-in
Power Supply
•Heavy duty - 2.5 Amp power supply
•Dynamic battery test
•Master power switch and Low battery disconnect
•PTC (fuseless) resettable overload protection
•Multiple auxiliary power terminals
Part Numbers and Accessories: |
|
|
ELK-M1GCB |
M1G Gold Board Only (No Teminals Blocks) |
|
ELK-M1GOLD |
M1G Gold - Control in 14” metal can |
|
ELK-M1GK |
M1G Gold Kit - No Metal Can, for use with |
|
|
structured wiring systems |
|
ELK-M1SYS4 |
M1G Gold Kit - 14” metal can, Ctrl, Encl, Xfmr, |
|
|
KP, 12V-8Ah, Spkr, RJset |
|
ELK-M1KP |
Keypad, LCD,16 character x 2 line |
|
ELK-M1KP2 |
Small LCD Keypad, 16 character x 2 line |
† |
|
(no internal temp sensor and 2 less “F” keys) |
|
ELK-M1KPAS |
Keypad Arming Station † |
|
ELK-M1XIN |
16 Zone (input) expander |
|
ELK-M1XOVR |
16 Output expander, 8 Voltage/8 Relays |
|
ELK-M1RB |
Relay board, 8 form ”C” relays |
|
ELK-M1DBH |
Data bus wiring hub “Passive” † |
|
ELK-M1DBHR |
Data bus wiring hub “Active” for Retrofit |
† |
ELK-M1XEP |
Ethernet Port Exp/Interface † |
|
ELK-M1XRF2G |
Wireless Receiver for GE Crystal Xmtrs |
† |
ELK-M1XRF2H |
Wireless Receiver for Honeywell 5800 Xmtrs † |
|
ELK-M1XSP |
Lighting, Thermostat Interface & Serial exp. † |
|
ELK-M1PR |
Mini prox reader for keypad † |
|
ELK-M1TWI |
Two Way Listen-in Int. w/3 mic inputs † |
|
ELK-M1TWS |
Speaker & Mic for Two Way Listen-in † |
|
ELK-M1ZTS |
Zone Temperature Sensor -50 to 140 F |
† |
ELK-RP |
PC software - Free upon request with |
|
|
Control Panel purchase |
|
ELK-RM |
Remote “User” Management software |
|
NOTE: Use of Two Way Listen-in may be regulated by local or state laws and/or ordinance. It is the responsibility of the Installer to check before using this feature.
Highlighted Features of the M1G (Gold)
• |
Automation (“Whenever/And/Then”) Rules Capacity |
528 |
• |
Serial (RS232) Port Supported |
8 w/expanders |
• |
Phone Number Capacity |
8 |
• |
Number of HVAC Thermostats † Supported |
16 |
• |
Total Number of Outputs Supported |
205 |
• |
Advanced Lighting † Options (Pre-set Dim, Extended, Levels, Scenes) Yes |
|
• |
Analog Zone Definitions Supported |
Yes |
|
† Not evaluated by UL |
†† Not for use in UL Listed Systems |
|
|
|
|
|
|
M1G Installation and Programming |
Page 5 |
Wiring & Hookup Diagram |
|
2200 |
N.C. |
ZONE |
|
|
|
|
(Left Side Terminals) |
|
|||||
This unit provides Residential fire alarm service when installed according to ANSI/NFPA 72. Transmission |
Ohm |
|
1 |
N.O. |
Z1 |
||
of the fire alarm signal to a fire alarm headquarters or central station shall be permitted only with the |
EOL |
|
|
NEG |
|||
approval of the authority having jurisdiction. The burglar alarm signal shall not be transmitted to a police |
2200 |
N.C. |
ZONE |
|
|||
emergency number, equipment is to be installed in accordance with NFPA (985,55.1.P). |
|
Ohm |
N.O. |
|
|||
|
|
|
2 |
Z2 |
|||
Recommended locations and wiring methods shall be in accordance with CSA C22.1, Canadian Electrical |
EOL |
|
|
||||
Code, Part I, Safety Standard for Electrical Installations; CAN/ULC-S302, Installation and Classification of |
2200 |
N.C. |
ZONE |
|
Z3 |
||
Burglar Alarm Systems for Financial and Commercial Premises, Safes and Vaults; and CAN/ULC-S301, |
Ohm |
N.O. |
|||||
Standard for Central and Monitoring Station Burglar Alarm Systems. |
|
EOL |
|
3 |
|
NEG |
|
Reference NFPA70 (NEC) & Canadian Electrical Code. |
|
2200 |
N.C. |
ZONE |
N.O. |
||
|
Ohm |
|
|||||
All circuits are current limited except for Battery leads. Refer to Appendix F. |
|
EOL |
|
4 |
|
Z4 |
|
For Installation of Residential Fire Warning Systems reference CAN/ULC-S540 Standard. |
|
2200 |
N.C. |
ZONE |
N.O. |
Z5 |
|
|
Ohm |
||||||
Testing of this system should be performed regularly with the primary AC power de-energized. Control |
EOL |
|
5 |
|
NEG |
||
panel specifications are subject to change without notice. |
|
2200 |
N.C. |
ZONE |
|
||
Lithium 3V "Clock" battery, Varta #CR2032 located in upper left corner behind cover. Battery has a life |
Ohm |
N.O. |
Z6 |
||||
EOL |
|
6 |
|
||||
expectancy of approx. 10 years. Replace ONLY with exact model available at most electronics and camera |
2200 |
|
|
|
Z7 |
||
retailers. "CAUTION: Lithium Battery May Explode If Mistreated. Do Not Recharge, Disassemble, or |
N.C. |
ZONE |
N.O. |
||||
Ohm |
|||||||
Dispose Of In Fire." |
|
EOL |
|
7 |
|
NEG |
|
|
|
2200 |
N.C. |
ZONE |
|
||
|
|
Ohm |
N.O. |
Z8 |
|||
|
|
EOL |
|
8 |
|
NOTE: M1ZTS Temperature Sensors may only be connected to the first 16 zones.
Color Code for 2200 |
|
|
|
Color Code for 820 |
|
|
Gray (8) |
||
|
|
Red (2) |
|
|
Red (2) |
||||
Ohm EOL Resistor |
|
|
|
Ohm EOL Resistor |
|
|
|
||
|
|
|
Red (2) |
|
|
|
Brown (1 x 0) |
||
Part # ELK-ER2200 |
|
|
Part # ELK-ER820 |
|
|
||||
|
|
Red (2 x 0) |
|
|
Gold (quality) |
||||
|
|
|
|
|
|
|
|
Gold (quality)
2-Wire Smoke Detector Compatibility
Name |
Model |
Compatibility ID |
Max # |
Base |
System Sensor |
2W-B, 2WT-B, 1151, 2100, 2100T, 2151 |
A |
20 |
None |
Sentrol (GE) † † |
429AT, 521BXT, 521B |
S09A |
20 |
None |
|
|
|
|
|
To configure Zone 16 as a 2-wire smoke zone, set Jumper JP1 to "2 WIRE SMOKE" and use 820 Ohm EOL resistor, part # ELK-ER820.
Compatibility Identifier: M10001 |
2-Wire Smoke Detector |
|
|
Maximum Operating Voltage: 13.8 VDC |
820 |
|
|
Max. wire resistance should not exceed 13 Ohms. |
- |
NEG |
|
Use 18AWG Fire approved wire. Max. wire length = 1000 feet. |
Ohm |
+ |
|
Do not mix different models on same circuit as proper operation |
EOL |
|
Z16 |
may be impaired. |
|
|
|
2200 Ohm EOL
2200 Ohm EOL
2200 Ohm EOL
2200 Ohm EOL
2200 Ohm EOL
2200 Ohm EOL
2200 Ohm EOL
2200 Ohm EOL
N.C. |
ZONE |
|
|
9 |
N.O. |
N.C. |
ZONE |
|
|
10 |
N.O. |
N.C. |
ZONE |
|
|
11 |
N.O. |
N.C. |
ZONE |
|
|
12 |
N.O. |
N.C. |
ZONE |
|
|
13 |
N.O. |
N.C. |
ZONE |
|
|
14 |
N.O. |
N.C. |
ZONE |
|
|
15 |
N.O. |
N.C. |
ZONE |
|
|
16 |
N.O. |
|
|
N.O. Alarm |
4-Wire Smoke Detector |
Switched +12 VDC Output |
||
Smoke Detector covers should be kept free |
|
Contacts |
|
To Zone Input |
||
from dust and dirt by use of a dry or damp |
|
|
|
protected by 1.1A PTC. |
||
|
|
|
To Zone NEG |
|
||
(water) cloth as needed. When necessary, |
2200 |
+ |
+ |
|
||
clean the detector interior and/or replace the |
|
|
||||
Ohm |
- |
|
|
|||
optical chamber according to instructions |
|
|
|
|||
EOL |
- |
|
|
|
||
provided by the Smoke Detector Manufacturer. |
|
|
|
|||
|
|
U.L. Listed EOL Supervision Relay |
|
|||
|
|
|
|
|||
|
|
|
(ESL #204 or Equivalent). |
|
||
M1G "Board only" non-alarm |
Auxiliary +12VDC Power Outputs protected by 1.25A PTC NOTE: |
|||||
Refer to Appendix F for the UL limitations on total continuous 'standby' |
||||||
current draw = 140mA ( .14 Amp ) |
||||||
current drain from terminals +SAUX, +VAUX, +VKP, and J16. |
||||||
|
Z9
NEG
Z10
Z11
NEG
Z12
Z13 |
|
|
NEG |
|
|
Z14 |
|
|
Z15 |
|
|
NEG |
|
|
Z16 |
|
|
ZONE 16 |
|
2WIRE |
NORMAL |
JP1 |
SMOKE |
|
|
TELCO SEIZED
DIALER ACTIVE
+SAUX
NEG +VAUX NEG +VAUX NEG +VAUX
|
|
16.5VAC, 45VA UL Listed Class 2 Transformer - ELK-TRG1640 |
|
NEG |
|
|
|
|
|
DO NOT CONNECT TO A SWITCHED OUTLET |
|
AC |
|
|
|
|
|
For Canada use cUL Listed Transformer - ATC Frost # FPS-4016 |
18AWG Min. |
|
|
||
LEDS |
Normal |
|
|
|
16.5 V |
|
|
Indicators |
State |
|
Descriptions |
|
AC |
|
|
|
|
|
|
|
|||
TELCO |
OFF |
Phone line is good and house phones are connected. If ON constantly, the phone |
|
POWER |
|
|
|
line may be bad. During remote mode this LED will be ON since the house phones |
|
|
|
||||
SEIZED |
|
|
|
|
|||
|
are then disconnected from the outside line & are being powered from control. |
|
STATUS |
|
|
||
DIALER |
|
|
|
|
|||
OFF |
Dialer/Modem is idle. If ON, Dialer/Modem is in use (communicating). |
|
|
|
|
||
ACTIVE |
|
REVERSE |
|
|
|||
|
AC Voltage is present and power switch is turned ON. If OFF, check AC power. |
|
|
|
|||
Power |
ON |
|
BAT LEADS SW1 |
|
|||
Status |
Regular 1 |
1 blink with equal On and Off times is Normal. 2 fast blinks = Control running on |
|
|
|||
bootloader only. |
4 fast blinks = Control is re-initializing it's EEPROM memory after |
|
JUMPER TO START |
BATTERY |
|||
sec. Blink |
|
||||||
|
|
a firmware flash. |
5 fast blinks = Memory/Operation overflow |
|
WITH NO AC |
+ |
- |
Battery |
OFF |
Battery is connected correctly. If ON, check battery lead connections. |
|
|
|
|
|
Reversed |
|
|
|
|
|||
|
|
|
|
|
|
|
|
Control needs AC power to start. Momentarily shorting these two pads allows control to startup on battery only. |
|
|
12 Volt |
|
|||
|
|
|
|
|
|
Sealed |
|
Master Power Switch (SW1), disconnects AC and Battery power from control. |
Lead Acid |
|
Replace Battery every 3-5 years. Use ELK model # ELK1280 (12V - 8 Ah) or ELK12180 (12V - 18 Ah) or equivalent. |
||
|
||
|
|
|
|
|
Page 6 |
M1G Installation and Programming |
|
|
R1 |
|
RJ31X JACK (ELK-RJSET) |
Demark |
splices |
|
(Right Side Terminals) |
|||||
|
|
Grey |
|
R1 |
|
Black |
|
HOUSE |
|
Compiles with FCC Part 68 |
|||
|
|
|
|
|
|
Yellow |
|
|
|||||
|
|
T1 |
Brown |
|
1 |
R |
|
PHONES |
Reg. Number: US:5K6AL03BELK-M1 |
||||
|
|
|
|
4 |
|
Tip |
TELCO |
|
Ringer Equivalence REN: 0.3B |
||||
|
|
|
|
|
|
|
|
|
|||||
|
|
RING |
Red |
|
|
5 |
Green |
|
Use USOC RJ-31X connector. |
||||
|
|
|
8 |
|
LINE |
|
|||||||
|
|
TIP |
|
|
|
T1 |
T |
Ring |
|
|
Complies with the limits for class B computer |
||
|
|
Green |
|
|
|
Red |
|
|
|
devices in accordance with the specifications of |
|||
|
|
|
|
|
|
|
|
|
|||||
J3 |
|
J4 |
|
Aux Data Bus (J3) †† |
|
Use 26AWG telco wire |
|
subpart J of part 15 of FCC rules. |
|||||
B |
For wireless receiver. Presently |
|
|
|
|
|
|
||||||
|
A |
|
works with ITI / Caddx NX408E, |
|
|
|
|
1 |
1 |
||||
|
- NEG |
|
NX416E, or NX448E. See |
PC |
Personal Computer |
Pin 2 < to > 2 |
|||||||
|
C |
|
|
Programming Menu 14. |
|
||||||||
|
|
|
|
|
|
(Windows Based) |
Pin 3 < to > 3 |
||||||
|
+ +12V |
|
|
|
|
|
|
|
|
|
|
||
JP2 |
PLC |
RS232 |
|
|
|
|
|
|
|
|
|
Pin 5 < to > 5 |
|
Mode |
|
Serial Port (J4) †† |
|
|
|
|
|
Pinout for Serial Port Cable |
(9 pin male to 9 pin female) |
||||
|
1 WAY |
|
for Computer/ELKRP |
|
|
|
|
|
Maximum recommended length = 50 ft. |
||||
|
2 WAY |
|
(This connection not |
|
|
|
|
|
|
|
|||
|
|
|
evaluated by UL) |
|
|
|
|
|
|
End |
|||
|
|
|
JP2 |
|
|
|
|
|
|
||||
|
|
|
|
|
|
Select PLC Mode (JP2) |
|
|
view |
||||
|
|
|
|
1 WAY (PL513/PSC04) |
|
|
|||||||
|
|
|
|
Selects single or bi-directional |
|
|
|
||||||
|
|
|
|
2 WAY (TW523/PSC05) |
|
Yellow |
Yellow |
||||||
Lighting †† |
|
|
|
|
|
PLC Transmissions |
|
|
Green |
Green |
|||
|
|
|
|
|
|
|
|
|
|
Black |
Black |
||
|
|
|
|
|
|
|
|
|
|
|
|
Red |
Red |
Interface Conn. |
|
PSC05 or |
Lighting Interface Conn. (J5) †† |
|
|
|
|||||||
|
|
|
equiv. |
|
Use Std. 4 conductor modular telephone |
Close up view of std. 4 conductor modular phone cord. When |
|||||||
|
|
|
|
|
|
cable to connect to a powerline Interface |
|||||||
|
|
|
|
|
|
viewed as shown (back to back), the pin to pin color coding |
|||||||
J5 |
|
|
|
|
|
(PSC05, X-10 PLC or equiv.). |
|||||||
|
|
|
|
|
does not reverse. Cord for PLC must be similar to above. |
||||||||
|
|
|
|
|
Do not connect to a live phone line! |
||||||||
|
|
|
|
|
|
|
|
||||||
|
|
|
|
|
|
(This connection not evaluated by UL) |
|
Relay Expansion Module (ELK-M1RB) |
|||||
|
|
|
|
|
|
|
|
|
|
|
|
||
|
|
|
|
|
|
|
|
|
|
|
|
Optional module adds 8 general purpose |
|
J16 |
+12V (+VAUX) |
+VAUX |
+12V |
|
Red |
|
|
|
relays. Plugs into J16 connector. |
||||
|
* See Auxiliary Current ratings |
|
|||||||||||
|
NEG |
NEG |
|
NEG |
|
Black |
|
|
|
|
|
||
|
16 |
|
OUT 16 |
|
|
White |
|
|
|
|
|
||
|
15 |
OUTPUTS |
OUT 15 |
|
|
Green |
|
|
|
|
|
||
|
9 |
OUT |
9 |
|
|
Grey |
|
|
|
|
|
||
|
14 |
|
OUT 14 |
|
|
Brown |
|
Programmable Outputs (J16) |
|
||||
|
13 |
|
OUT 13 |
|
|
Blue |
|
OUT 7 - 16 are +12V switched |
|
||||
|
12 |
|
OUT 12 |
|
|
Orange |
|
p o s i t i v e g e n e ra l p u rp o s e |
|
||||
|
11 |
|
OUT 11 |
|
|
Yellow |
|
|
|||||
|
10 |
|
OUT 10 |
|
|
Violet |
|
outputs rated at 50mA. |
|
||||
|
8 |
|
OUT |
8 |
|
|
Pink |
|
|
|
|
|
|
|
7 |
OUT3 LED |
OUT |
7 |
|
|
Tan |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
OUT3 |
N/OCOMN/C |
OUT2 |
- + |
OUT1 |
- + |
J7
AUDIO NETWORK INTERFACE
RS-485 DATA BUS
+VKP DATA A DATA B NEG
N/C |
Out 3 - Programmable General Purpose Relay |
|
||
COM |
|
|||
Rated at 4Amps @ 12 - 24VDC |
|
|
||
N/O |
(Dry Contacts) |
|
|
|
|
|
|
||
+ |
Out 2 - Connect ONLY 1 UL Listed Bell or Siren (self-contained). For residential Fire the indicating |
|||
device shall be Wheelock 34T-12 or equiv. Current limited to 1 Amp. Program Global Option 26 to Voltage. |
||||
Bell (Supervised) |
||||
Speaker(s) are only permitted for non-UL installations and they must be series/parallel wired to avoid |
||||
- |
||||
dropping below a 4 ohm total load. |
Out 2 is supervised. If not used, install a 2.2K Ohm |
|||
|
||||
+ |
|
|||
Out 1 - Voice/Siren †† |
resistor to avoid Output 2 trouble condition. |
|
||
Voice/Siren † |
Speaker output only (Interior) |
NOTE: Do Not place a Direct Short Across OUTPUT 2. |
||
- |
|
|
|
|
ELK-SP35 or equiv. |
|
Jumper |
||
Audio Network Connection (J7) †† |
|
Terminate |
||
For Two-Way Listen-in and Future Use! |
Data Bus Devices e.g. Keypads, Expanders |
these two |
||
|
|
|||
RS-485 Data Bus Max. length is 4000 ft. Total |
|
devices. |
||
|
|
|||
length of 2 homeruns must not exceed that distance. |
|
|
||
RED |
|
|
|
|
GREEN |
Min. wire gauge: 24 AWG |
|
|
|
18 to 22 AWG is best for |
DO NOT Jumper |
|
||
|
|
|||
WHITE |
long distances. |
Terminate these devices. |
|
|
BLACK |
|
|
|
|
Not Used |
J2 |
J1 |
|
NEG - |
|
DATA B |
|
DATA A |
DATA BUS |
+12V |
|
JP3
Terminating Jumper (JP3): See
A UL Listed Supplementary Power Supply may be required to meet the minimum standby power supply requirements. Refer to the Chapter containing Regulatory Agency Statements.
DATA BUS TERMINATION IS VERY IMPORTANT!!
Diagram shows 2 basic (4-wire) home run cables with daisy chained devices on each. Last device on each cable MUST have a Terminating Jumper installed. Jumpers are marked JP2 on keypads, JP1 on Expanders. Control Hardware pack has two black jumpers for this purpose. Jumpers engage a 120 Ohm resistor across data A & B lines. NOTE: If there is only 1 data bus cable, install JP3 Jumper on the Control.
WARNING! The RS485 Data Bus must NEVER have more that two (2) terminating jumpers installed.
NOTE: If you want to home run more than 2 cables, run 6 or 8 conductor cable so that the data lines A & B can have a return path to series connect back out to the next device. This is best done with a ELK-M1DBH Data Bus Hub which accepts Cat5 or Cat6 cable with RJ45 plugs. For more information see diagram in keypad instructions.
important information about Data |
This terminal (formerly earth ground) is no longer used. Do not connect this or any neg. terminals to earth ground. |
|
Bus Termination. |
Temporary Connection "Plug-in" jacks for RS-485 Data Bus (J1 & J2) |
|
|
||
|
Local connection for Data Bus Devices ie: Keypads, etc. for testing purposes only. |
|
|
† Not evaluated by UL |
†† Not for use in UL Listed Systems |
M1G Installation and Programming |
Page 7 |
Section 1 - Installation and Wiring
1.1 Planning the Installation
The first step in any multi-zone security system installation is planning the job.
1.Read this entire manual to familiarize yourself with all system features and procedures before actually beginning the installation. Read all the information regarding Underwriters Laboratories (UL) and NFPA requirements.
2.Perform a physical survey of the installation site. Use the diagrams below as a guide in planning the installation.
3.Discuss the installation requirements and applications with the customer.
4.Compare the installation requirements and applications with the factory default settings to determine what customized programming is needed to meet the specific installation requirements.
5.Bench test the system prior to installation.
TYPICAL BURGLARY INSTALLATION LAYOUT
Bedroom 2 |
Bedroom 1 |
|
|
|
|
|
|
M |
|
Kitchen / Dining |
|
|
|
|
|
|
|
|
A |
|
|
|
C |
|
|
|
|
|
|
|
Bedroom 3 |
|
|
Living Room |
|
|
|
|
|
|
|
C |
C |
C |
K |
C |
C |
|
|
|
|
TYPICAL FIRE INSTALLATION LAYOUT
Bedroom 2 |
Bedroom 1 |
|
|
S |
|
S |
Kitchen / Dining |
|
|
|
|
|
|
|
M |
|
S |
A |
|
|
|
|
|
|
S |
|
Living Room |
|
Bedroom 3 |
|
|
|
|
|
|
|
|
|
K |
All perimeter openings below 18" should be provided with protection.
A Smoke Detector shall be located in each sleeping area and between the sleeping areas and the main living area.
Early warning fire detection is best achieved by the installation of fire detection equipment in the location shown above.
In homes basements or multiple levels at least one smoke detector shall be on each level.
1.2 Parts Diagram & Descriptions
Legend |
|
M - Main Control |
|
A - Audible Alarm |
|
S - Smoke Detector |
|
C - Contact |
First Floor |
K - Keypad |
|
|
Basement |
See Wiring & Hookup Diagram on pages 6 & 7.
1.3 Mounting and Wiring Preparation
Control Mounting
DO NOT MOUNT THE CONTROL OUTDOORS OR IN A DAMP LOCATION OR WHERE THE ENVIRONMENTAL CONDITIONS ARE UNSUITABLE FOR ELECTRONIC BASED EQUIPMENT. DO NOT MOUNT IN AN UNCONDITIONED ATTIC. USE COMMON SENSE AND GOOD INSTALLATION PRACTICES. A suitable location would be inside a secure dry location where the ambient temperature inside the control box can remain at 32‘ to 120° Fahrenheit (0’ to +49' Celsius). Choose a location that allows easy wiring to an unswitched power outlet and to a grounding conductor for the control. A central location makes running system wiring easier. Remove control box knockouts that best suit your wiring needs.
After removing all packing materials, compare the system components with those in the figure above to familiarize yourself with the part names. Mount the control using the upper center slotted hole to level. Install and connect all necessary wiring for the power transformer, detection loops, keypads and siren outputs.
Keypad Mounting and Wiring
Ideal height is 50-58 inches. Pick a location with an ambient temperature range between 32° and 120° F (0° to +49° C). Avoid direct sunlight if possible. Fasten backplate to electrical box or wall with flat head screws to prevent shorts to the back of the circuit board. Keypads have an unpluggable harness for connecting to the M1data bus. Splice the Black, Red, White, and Green wires from the unpluggable harness to the M1 Data Bus field cabling. Plug the connector into the back of the keypad. Tuck wires neatly into back plate and install Keypad on mounting plate. The LCD keypads have connections for an optional programmable output and a programmable zone input. NOTE: Min. field wire gauge is 24 AWG, but 18 to 22 AWG is better for long distances. CAT5 (8 conductor) cable can be purchased in various wire gauge sizes. Where possible always use the larger gauge CAT5 cable. The extra conductors in CAT5 wires can be used to provide return path for the data A & B lines.
Page 8 |
M1G Installation and Programming |
Hookup Diagram for Keypad
Splice 6 Pin Keypad Wiring Assembly to the Data Bus cable using ELK-900-2 "B" Connectors.
Min. wire gauge: 24 AWG 18 to 22 AWG is best for long distances.
|
|
|
|
|
+ |
|
|
|
To Red (Pos) Wire |
Load (50mA max) |
|||
|
- |
|||||
|
|
|
|
|
||
|
|
|
|
|
i.e. Relay, LED |
|
|
|
|
To Brown Wire |
|
||
|
|
|
|
|
|
NOTE: Early production M1KP Keypads provided a switched negative (pull to ground) output. These units have the letter "E" at the end of the ID number on the lower back side of the board. Connect per diagram above. Boards marked PC096 with a letter "F" or later provide the output as a switched positive.
|
Keypad |
|
ELK-M1KP |
|
|
|
|
|
|
BLACK |
Wiring |
|
Keypad 1 |
|
WHITE |
Assembly |
|
|
|
1 |
|
|
|
|
GREEN |
|
|
|
|
|
|
|
|
|
RED |
6 |
|
|
|
BLUE |
|
|
|
|
|
|
|
|
|
BROWN |
|
|
|
|
To BROWN Wire |
+ |
Load (50mA max) |
||
To BLACK (Neg) Wire |
- |
I.E. LED, Relay |
||
Optional programmable Output from Keypad |
||||
To BLUE Wire |
|
N.C. N.O. |
2200 |
|
|
|
|
Ohm |
|
To BLACK (Neg) Wire |
|
|
EOL |
Optional programmable Zone Input from Keypad
See Note about
Data Bus
Termination
The optional Zone Input # or Output # is determined by the Keypad Address.
KP |
Zone Output |
|
KP |
Zone Output |
||||
Address # |
# |
|
Address # |
# |
||||
|
|
|
|
|
|
|
|
|
1 |
193 |
193 |
9 |
201 |
201 |
|||
2 |
194 |
194 |
10 |
202 |
202 |
|||
3 |
195 |
195 |
11 |
203 |
203 |
|||
4 |
196 |
196 |
12 |
204 |
204 |
|||
5 |
197 |
197 |
13 |
205 |
205 |
|||
6 |
198 |
198 |
14 |
206 |
206 |
|||
7 |
199 |
199 |
15 |
207 |
207 |
|||
8 |
200 |
200 |
16 |
208 |
208 |
NOTE: Refer to the section ‘Data Bus E.O.L. Termination’ for information on multiple homerun cables. NEVER SPLICE OR CONNECT WIRE WITH CONTROL POWER ON. Minimum cabling should be four conductor 22 or 24 gauge. Maximum resistance per wire is 25 Ohms. Device placement beyond 1000' is not recommended.
1.4 Control Wiring
Zone Inputs (1 thru 16 on main board, 17 thru 208 via expanders)
Zones are arranged in groups of 16, starting with Z1 thru Z16 on the main board. Each 2 zones share a common negative terminal. A zone may be programming for EOL resistor supervision (Default), or normally closed/normally open without a resistor. In addition, Burglar and Keyswitch zones may be programmed for EOL with Security Alert on Short, or EOL with Security Alert on Open/Short, also referred to as a Four (4) State Zone (firmware 4.3.5 or later). If EOL resistors are used, they should be placed at the furthest most remote end of the detection device wiring. EOL zones permit a combination of N.C. (normally closed) or N.O. (normally open) devices. Using voltage meter probes across the zone and com terminals, a nonviolated EOL zone will measures approx. 7.0 VDC. An open circuit will be approx. 13.8 VDC. A shorted circuit will be 0 VDC. The Keypad also provides the ability “Menu 8 “System Diagnostics” to view zone voltage.
Traditional Three (3) State Zone Wiring (1 series resistor)
2200 |
N.O. |
Zone Input |
|
||
Ohm |
|
|
|
||
EOL |
Contact |
Neg. |
|
||
N.C. |
|
|
|||
Alarm |
Alarm Contact |
|
|
|
|
Contact |
|
|
|
||
|
Diagostic Table |
|
Condition When: |
||
Zone |
Approx. Range |
A to D |
Armed |
Disarmed |
|
Resistance |
of Zone Voltage |
Value |
|||
|
|
||||
Short ~ |
0 - 3.9 Volts |
0 - 72 |
Alarm |
Not Ready |
|
2.2k Ohms |
4.0 - 8.8 Volts |
73 - 170 |
- |
Ready |
|
Open ~ |
8.9 - 13.8 Volts |
171 - 255 |
Alarm |
Not Ready |
N.C. Tamper |
Wire in Series with zone |
|
Contacts |
input or use another zone. |
|
|
|
|
|
|
Zone |
N.C. Alarm |
2200 Ohm |
Input |
Contacts |
EOL Resistor |
|
|
|
|
|
|
Neg. |
|
|
Pos. |
Neg.
Powered Motion, PIR, Glassbreak, etc.
Optional Four (4) State Zone Wiring (2 series resistors w/ N.C. contacts) Program Zone for EOL Wiring
Type 4 - Supervisory on Open
Tamper Contact
2200 |
N.C. |
Ohm |
|
EOL |
|
N.C.
Alarm
Contact
2200 Ohm
Resistor
Zone Input
N.O.
Contact
Neg.
Fig 1: N.C. Alarm Contact (Unpowered) with N.C. Tamper
This feature requires Firmware 2.3.5 or later.
N.C. Tamper
Contacts
2200 Ohm
EOL Resistor
Zone
Input
|
Diagnostic Table |
|
Condition When: |
N.C. Alarm |
2200 Ohm |
||
|
|
Contacts |
Resistor |
||||
Zone |
Approx. Zone |
A to D |
Armed |
Disarmed |
|
Neg. |
|
Resistance |
Voltage Reading |
Value |
|
|
|||
|
|
|
Pos. |
||||
Short ~ |
0 - 3.9 Volts |
0 - 72 |
Alarm |
Sec. Alert/Tamper |
|
||
|
|
||||||
2.2k Ohms |
4.0 - 7.3 Volts |
73 - 159 |
- |
Ready |
|
Neg. |
|
4.4k Ohms |
7.4 - 11 Volts |
160 - 220 |
Alarm |
Not Ready |
|
||
Fig 2: Powered PIR, Glassbreak, etc. with Tamper |
|||||||
Open ~ |
11.1 - 13.8 Volts |
221 - 255 |
Alarm |
Sec. Alert/Tamper |
M1G Installation and Programming |
Page 9 |
Two-Wire Smoke Zones (Zone 16)
To enable use of two-wire smoke detectors on Zone 16, position Jumper JP1 (located below Zone 16 terminals) so that the two right hand pins are covered. Go to Installer programming mode, Menu 05 - Zone Definitions, and program Zone 16 as a Fire zone (Def=10). Step to next location and program Wire Type=6. NOTE Use only compatible two-wire detectors listed on the front label of the control. Do not mix brands. The maximum number of detectors is also listed on the front label. For two-wire operation, a 820 Ohm EOL resistor part # ER820 must be used instead of the 2,200 Ohm resistor part # ER2200. Use 18AWG Fire approved wire. Max. wire length = 1000 feet. Max. wire resistance should not exceed 13 Ohms.
Switched Power Connection (+SAUX)
Four-wire smoke detector and other devices that require a temporary power disruption in order to reset or unlatch from the alarm state (i.e. smoke detectors, etc.) should be connected to the +SAUX 12 Volt DC switched power terminal. When a smoke reset is performed, the operating voltage to these devices is momentarily interrupted.
Auxiliary Power Connections (+VAUX)
Motion detectors, glass breaks, etc. and other devices requiring unswitched 24-hour power should be connected to one of the auxiliary terminals, +VAUX. All negative terminals on the terminal strip are at the same reference and may be used whenever a common (circuit ground) negative is required. Use caution when wiring the control to distribute the load devices among the supply and the negative terminals evenly. NOTE: Circuit ground refers to any negative terminal connection on this control.
This does not refer to the earth ground terminal or to the common terminals of Relay Output 3. These terminals are not at the same voltage potential and should not be wired so that they are electrically connected to a negative.
PTC (Positive Temperature Coefficient) Circuit Breakers
The +VAUX Auxiliary power and J16 power output terminals are protected against shorts and overloads by a 1.25A PTC. A PTC is a solid state, auto-restoring type of circuit breaker. The +SAUX Switched (Smoke) power output is protected by a 1.1A PTC. The +VKP Keypad power output is protected by a 1.25A PTC. Output 2 is protected by a 1.25A PTC. NOTE: Sometimes it may be necessary to remove power (unplug the outputs) for approx. 20 seconds after a short, to allow the PTC to reset. Even if the short is no longer present, the remaining residual current draw may be so high that the PTC cannot determine that the short is gone. If the PTC re-trips, check the field wiring and repair.
Transformer Primary Power Input (AC)
The control is powered by a 16.5 VAC, 40 min. VA, UL Listed Class 2 transformer (ELK-TRG1640). The specified sized and rated transformer must be used to operate this control. The transformer must be connected to a 120 VAC, 24-hour outlet not controlled by a switch other than an approved overcurrent protection device.
UL Listed Transformer,
Class 2, 16.5VAC, 45VA
ELK-TRG 1640
+ - |
12V Battery |
5 to 18Ah |
Sealed Lead Acid
Connect the transformer to the AC Terminals using 16 to 18 gauge minimun wire. Do not exceed 50 feet between the transformer and the control or run the AC power in a multiconductor with other system circuits. Leave the transformer unplugged as well as the standby battery until all other connections have been made.
Standby Battery Connection
Connect the BLACK wire to the Neg (-) terminal on the battery, the connect the RED wire to the Pos (+) terminal on the battery. The control is designed to operate with and recharge a 12 volt, sealed lead acid battery from 7Ah up to 18 Ah for backup of the primary power supply. The control maintains a float charge for the battery of 13.8 VDC at 100 mA. This is in addition to the continuous output of 1.5 Amps that the power supply maintains (see maximum current drains for UL Listed Systems).
CAUTION: Do not reverse the battery leads! The control has special circuitry which helps protect it from battery reversal damage for short durations. However, prolonged reversal of the battery leads may cause permanent damage. A reverse battery warning LED is located to the left of the power On/Off switch. If this light is ON, turn the power off immediately and correct the battery lead connections.
Page 10 |
M1G Installation and Programming |
AC Failure, Low Battery, and Automatic Low Voltage Shutdown
During an AC power failure the battery automatically takes over and AC Fail trouble annunciates at the keypad. The communicator can be programmed to report AC Fail to the Central Station after a time delay (see Menu 12, System Option 01).
If the battery voltage falls below 11.2 VDC a Low Battery Trouble condition will occur. The communicator can be programmed to report Low Battery to the Central Station. The battery will continue to run the control until its voltage drops below 10.2 VDC, at which time the control will disconnect and shut down to prevent a false alarm and damage to the battery. The AC Fail trouble display will clear if the AC restores. However, the Low Battery Trouble requires a manual or automatic battery load test before it will clear. An automatic battery load test is performed every 24 hours. See Section 2.2 for powering up the control.
Telephone Line Connection (R1,T1,T,R)
The telephone interface is connected by the use of an approved RJ-31X interconnect jack. This device allows the subscriber to disconnect the control/communicator from the public switched telephone network in the event of a malfunction. The control is equipped with line seizure so that the premises telephone service is interrupted during communication to the central station. Connection to the approved jack is done with a RJSET cord which connects the control terminals to the RJ31X jack.
NOTE: The Telco cord can be supervised to the RJ31X or demarc block by installing an EOL resistor across the Orange and Blue wires (RJ31X terminals 2 and 7). In the control, connect the Orange and Blue leads to any 24hr Burglar zone input.
Outputs
There are 13 outputs on the main board. Outputs may be expanded utilizing output expander boards connected to the RS-485 4-wire Keypad data bus. Outputs 1 & 2 trip when any alarm is activated. All others must be enabled through the RP Rules Programming and can be triggered by multiple conditions “events”. Do not exceed the current limits on voltage only outputs.
Output 1 †† is for speakers(s) ONLY (4 to 8 Ohms). If connecting more than 2, use series/parallel wiring to avoid going below a 4 ohm total load. This output is the source for voice announcements such as: Zone 1 not ready, System Armed, Alarm Activated, etc., as well as alarm siren sounds. The initial start volume and the final volume can be adjusted in programming to suit the application.
Output 2 - Connect a UL Listed Bell or Siren (self-contained). Current limited to 1 Amp. Program Global Option 26 to Voltage. This output is supervised. Speaker(s) are only permitted for non-UL installations. Series/parallel wire to avoid dropping below a 4 ohm total load.
Output 3 is a Single Pole Double Throw Relay with form “C” contacts (Com, N/O, and N/C).
Outputs 7, 8, 9, 10, 11, 12, 13, 14, 15, and 16 are low current, positive (+) voltage only, for driving LEDs, relays, etc. Outputs 4, 5, and 6 ARE NOT available from the main board. They can only be accessed with a data bus Output expander set to address 1. This expander will replicate main board outputs 7 thru 16, while also including outputs 4, 5, and 6.
J16 |
+12V |
+VAUX |
+12V Red |
||
|
NEG |
NEG |
|
Black |
|
|
16 |
|
OUT 16 |
White |
|
|
15 |
OUTPUTS |
OUT 15 |
Green |
|
|
9 |
OUT |
9 |
Grey |
|
|
14 |
|
OUT 14 |
Brown |
|
|
13 |
|
OUT 13 |
Blue |
|
|
12 |
|
OUT 12 |
Orange |
|
|
11 |
|
OUT 11 |
Yellow |
|
|
10 |
|
OUT 10 |
Violet |
|
|
8 |
|
OUT |
8 |
Pink |
|
7 |
|
OUT |
7 |
Tan |
Programmable Outputs (J16) |
OUT 7 - 16 are +12V switched |
positive general purpose outputs rated at 50mA.
|
ELK-924 † |
NEG POS |
OPEN 24V |
-T |
|
+T |
|
|
D3 |
N/O COM N/C N/O COM N/C
+ -
24V AC
Transformer
Using Output 7 (low current) with a sensitive relay to switch 24V AC to a Door Strike †
Door
Strike †
Earth Grounding
Tests have determined that the best results against lightning and transients are obtained by isolating the control from ground. Do NOT connect any of the terminals, especially the Neg. terminals to earth ground. Early production boards had an earth ground terminal. This terminal is no longer used on circuit board revision I or later. However, ancilliary devices such as the ELK-950 Surge Protector on the incoming Telephone circuit are still recommended.
Keypad & Expanders on the RS-485 Data Bus (+VKP, Data A, Data B, Neg)
Keypads and data bus expander devices connect to the four terminals marked +VKP, Data A, Data B, and Neg. The keypad plug-in wire harness color code is: Red +VKP, Green Data A, White Data B, and Black (-) Neg. The +VKP power terminal is protected by an auto reset PTC device. In the event of a short circuit or malfunction, power will be removed from all devices until the problem is resolved. Two (2) quick connect header pin plugs (J1 and J2) along the bottom of the board may be used for temporary purposes I.E. bench testing using a four conductor ribbon cable. Do not use for permanent connections.
† Not evaluated by UL |
†† Not for use in UL Listed Systems |
M1G Installation and Programming |
Page 11 |
Data Bus E.O.L. Termination - VERY IMPORTANT!
The M1 data bus comforms to EIA RS-485 standards and operates at 38,400 bits per second. The RS-485 standard stipulates there be no more than 2 home run data bus cables attached to the M1 Main Data terminals, with the end of each cable terminated by a 120 Ohm resistor connected across the data wires. The M1 board and bus devices come with built-in terminating resistors that may be activated via 2 pin jumpers (2 Gold Pins). Placing a shorting cap (included in hardware pack) on the two gold pins activates the 120 Ohm terminating resistor across Data Lines A & B. These jumpers are marked JP2 on the keypads and JP1 on the expanders. From the factory, no terminating resistors are installed. Without proper termination, noise and interference can cause data corruption and missed communications.
WARNING! Do not splice or interconnect the M1 Data Bus using Telephone type 66 or 110 punch down blocks. The RS-485 Data Bus must NEVER have more than 2 terminating resistors header/jumpers installed.
RS-485 DATA BUS
+VKP
DATA A
DATA B
NEG
NOTE: RS-485 Data Bus Max. wire length is 4000 ft. Total |
|
Data Bus Devices |
|
|
|
length of 2 homeruns must not exceed that distance. |
Keypad 1 |
|
|
||
|
|
e.g. Keypads, Expanders |
|
|
|
RED |
|
|
|
|
|
|
|
|
|
|
|
GREEN |
Min. wire gauge: 24 AWG |
|
|
|
Jumper |
18 to 22 AWG is best for |
|
DO NOT Jumper |
|
||
|
|
|
|||
WHITE |
long distances. |
|
Keypad 3 |
Terminate |
|
|
Terminate these devices. |
||||
|
|
|
|
these two |
|
|
|
|
|
|
|
BLACK |
|
|
|
|
devices. |
The last device on each home run cable SHOULD be terminated via the gold 2 pin terminating header/jumper. Placing a shorting cap on the pins will engage a 120 Ohm resistor across data lines A & B. If there is only 1 data bus home run cable then place shorting cap on JP3 of Main Board. See other hookups below.
Diagram of Two (2) Home Run Cables with Devices Daisy Chained along the Data Bus
|
|
NOTE: RS-485 Data Bus Max. wire length is 4000 ft. Total. Each CAT5 homerun from |
||||||||||
|
|
the M1DBH must be calculated as double the running distance since the Data A & B |
||||||||||
Mount M1DBH inside control. |
lines travel out and then back (A1 & B1) where they are used to feed the next homerun. |
|||||||||||
Use 4 conductor cable to connect |
|
|
|
|
|
|
|
|
|
|
Blue pair is |
|
to the M1 Data Bus terminals. |
|
|
|
|
|
8 |
- Brown |
|
|
|
||
|
|
|
|
|
|
|
|
unused |
||||
+ VKP |
ELK-M1DBH Data Bus Hub † |
|
7 - Wht/Brn |
|
|
CAT5 |
|
|||||
DATA A |
J2 |
J4 |
J6 |
|
J8 |
Front view |
6 |
- Orange |
|
|
or |
|
|
|
5 |
- Wht/Blue |
|
|
Blue |
||||||
DATA B |
|
|
|
|
|
|
|
|
Wht/Blue |
|||
|
|
|
|
|
|
4 |
- Blue |
|
|
CAT6 |
|
|
NEG |
J1 |
J3 |
J5 |
J7 |
J9 |
|
|
|
|
|||
|
3 |
- Wht/Org |
|
|
Cable |
|
||||||
|
|
|
|
|
|
|
|
|
|
|||
|
RS-485 DATA BUS |
|
|
|
|
|
2 |
- Green |
|
|
|
|
|
|
|
|
|
|
Pin1 |
1 - Wht/Grn |
Pin1 |
RJ45 Plug |
TO CONTROL |
||
|
|
|
|
|
|
|
|
|
CAT5 Cables |
COLOR CODE EIA 568A for CAT5/6 Data Bus Cable to RJ45 Plugs. |
Keypad |
Keypad |
|
RJ45 Terminating Plug Insert in first unused jack and terminate the control |
|
|
Min. wire gauge: 24 AWG |
||
|
|
18 to 22 AWG is best for |
||
Brown |
+ |
RED +12V |
long distances. |
|
|
||||
Wht/Brn |
- |
BLACK (-) |
|
|
Orange |
A |
GREEN |
Keypad |
|
Green |
A1 |
WHITE |
||
|
||||
Wht/Org |
B |
|
|
|
Wht/Grn |
B1 |
|
|
|
|
To |
BLUE |
|
|
|
|
|
||
Black (-) |
BROWN |
|
||
|
|
+ |
Load (50mA max) |
|
|
|
To BLACK (Neg) - |
I.E. LED, Relay |
Optional programmable Output
at JP3. DO NOT TERMINATE AT ANY OF THE DEVICES!
The ELK-M1DBH † Data Bus Hub is great for new installations where it is possible run multiple CAT5 homerun cables. The RJ45 jacks allow neat and organized connections and a third wire pair is used to return the DATA lines back from each device where they are used to feed the next adjacent jack. The M1DBH circuitry daisy chains the devices by series connecting the DATA lines A & B. Termination is accomplished with a plug-in RJ45 terminator (supplied).
|
N.C. N.O. |
2200 |
|
|
|
Ohm |
|
To BLACK (Neg) |
|
|
EOL |
Optional programmable Zone Input
Refer to Keypad Instructions
for more info about Output and Zone Input
OPTION A - Using an optional ELK-M1DBH and CAT5 Cables to Daisy Chain Devices
|
NOTE: RS-485 Data Bus Max. wire distance is 4000' total. Each homerun 6 conductor |
|
|
|
||||||
|
cable must be calculated as double the running distance since the Data A & B lines |
+ |
RED +12 |
|
||||||
|
travel out and then back (A1 & B1) where they are used to feed the next homerun. |
|
||||||||
|
- |
BLACK (-) |
|
|||||||
+VKP |
RED |
To 12VDC |
To 12VDC |
|
|
|
A |
GREEN |
Keypad |
|
|
|
|
6 Wire |
A1 |
WHITE |
|||||
|
GREEN |
|
|
|
|
|||||
DATA A |
|
|
|
|
|
|
||||
|
DATA |
DATA |
Cable |
B |
|
|
||||
DATA B |
WHITE |
|
|
|
||||||
|
A1 |
A |
A1 |
A |
TO CONTROL |
B1 |
|
|
||
NEG |
BLACK |
|
|
|
|
|
|
BLUE |
|
|
|
|
|
|
|
|
|
|
|||
RS-485 DATA BUS |
|
B1 |
B |
B1 |
B |
Install Teminating |
|
BROWN |
|
|
|
|
|
|
|
|
|||||
|
|
|
|
|
|
|
Jumper on this last |
Optional Output and Zone Input - See Keypad Instructions |
||
|
|
|
|
|
|
|
device AND on the |
|||
Min. wire gauge: 24 AWG |
|
6 conductor cable |
|
|
|
|
|
|||
Keypad |
|
Keypad |
control JP3. |
|
|
|
||||
18 to 22 AWG is best for |
|
|
|
|
|
|
||||
|
|
|
|
|
|
|
|
|
||
|
long distances. |
|
|
|
|
|
Connect each device to the 6 conductor cable as shown above |
|||
|
|
|
|
|
|
|
Another option for wiring multiple home runs is to use 6 conductor cabling. This allows devices to be daisy chained using an out and back configuration. This involves a 3 way splice of the data A (Green)wire to 2 wires of the 6 conductor cable (designated A and A1). Same is done for data B (White) wire. At the control wires A1 and B1 get spliced to the A and B wires feeding the next device. Terminate the last wired device and the control JP3 ONLY! The POS (+) and Neg (-) power wires should be parallel wired to the +VKP and Neg terminals or to an auxiliary Power Supply if the combined current draw exceeds the rated current available from the Control.
OPTION B - Using 6 Conductor Cables and Series Splices to Daisy Chain Connection of Data Bus Devices
††† An Auxiliary Power Supply will be required if the control's Aux. power load for all combined loads exceeds 1A. (450 mA for UL Commercial). Connect as shown below. Be sure to connect the negative (-) terminal of the power supply to the negative (-) terminal (Data Bus NEG) on the control.
UL Use a UL Listed, battery backed-up Power Supply for UL installations. The battery will be supplying power to the Keypads/Expanders during a power outage. The Power Supply and backup Battery should be sized to supply the Keypads/Expanders with the UL required minimum standby time.
DATA BUS TERMINALS |
|
AUXILIARY POWER |
|
+ A B - |
|||
SUPPLY |
- +
RED |
GREEN |
WHITE |
BLACK |
BLACK |
GREEN |
WHITE |
RED |
To Keypads or Expanders |
To Keypads or Expanders |
||||||||
|
|
|
|
|
|
|
|
|
|
† Not evaluated by UL |
†† Not for use in UL Listed Systems |
|
|
Page 12 |
M1G Installation and Programming |
The ELK-M1DBHR † Data Bus Hub Retrofit is intended for retrofit jobs where existing 4 conductor cables are the only wires available. It creates 4 managed RS-485 BRANCHES from the single M1 main RS-485 Bus. Like the main M1 Bus, each branch can only have 2 home run cables (4 branches x 2 ea. = 8 home runs). DO NOT connect more than 2 M1DBHRs to an M1. DO NOT connect an M1DBHR on a branch of another M1DBHR! The M1DBHR CANNOT be used as an extender or a remote repeater. DO NOT remote M1DBHR(s) away from the M1. Mount close to the main M1 Control. Terminate the last (end of line) device on each home run.
RS-485 DATA BUS |
+VKP is protected with 1.25A PTC |
|
ELK-M1DBHR † |
|
|
Terminating Jumpers (JP1 - JP5) |
|
|
|
Like the Main M1 Bus, the Maximum wire |
||||||||||
+VKP |
RED |
|
|
DATA BUS HUB FOR RETROFIT |
|
JP1 = Terminates Input from Control |
|
USA |
length of any of the 4 branches on the |
|||||||||||
DATA A |
|
|
|
B- A + |
INPUT CONTROLFROM |
|
|
|
|
|
JP2 = Terminates Branch 1 |
|
|
|
M1DBHR is 4000 ft. |
|||||
GREEN |
|
|
|
|
|
|
|
|
|
|
HILDEBRAN,N.C., 28637, |
|||||||||
|
|
|
|
|
|
|
JP3 = Terminates Branch 2 |
|
|
|
the M1DBHR and JP3 of the M1 Control. |
|||||||||
M1DBHR Hubs to a single M1 Control. |
|
|
|
|
|
|
|
|
|
|||||||||||
DATA B |
WHITE |
|
|
|
|
|
|
|
|
|
JP4 = Terminates Branch 3 |
|
|
|
|
Min. wire gauge: 24 AWG |
||||
NEG |
BLACK |
|
|
|
|
|
|
JP1 |
|
|
JP5 = Terminates Branch 4 |
|
|
|
|
18 to 22 AWG is best for long distances. |
||||
|
|
|
|
|
|
|
|
|
|
|
See details about Data Bus Termination. |
|
|
|||||||
DO NOT attach more than two (2) |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Bus Termination: |
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
If using 1 M1DBHR place jumper on JP1 of |
|||
Mount M1DBHR(s) in same enclosure with the |
|
|
|
|
|
JP2 |
|
JP3 |
|
|
JP4 |
|
|
JP5 |
INC. |
With 2 M1DBHR boards place jumper on |
||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
JP1 of both M1DBHR boards and remove |
||||
M1 Main Board. Connect to the M1 Data Bus |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
PRODUCTS, |
jumper JP3 on the M1 Control. |
||
terminals using a short 4 conductor cable. |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
jumpers on any of the 4 branches of the |
|||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
DO NOT EXCEED two (2) terminating |
DO NOT attempt to remotely mount an |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
ELK |
M1DBHR or the main M1 bus. |
||
M1DBHR or use as a remote bus extender! |
|
|
DATA BUS |
|
|
DATA BUS |
|
DATA BUS |
|
|
DATA BUS |
|
|
|||||||
|
|
JumperTerminate |
|
BRANCH 1 |
|
|
BRANCH 2 |
|
BRANCH 3 |
|
|
BRANCH 4 |
|
Example #4 |
||||||
|
|
+ |
|
|
- |
+ |
|
|
- |
+ |
|
|
- |
+ |
|
|
- |
|||
|
|
this device AND JP2 |
A |
B |
A |
B |
A |
B |
A |
B |
Branch 4 empty (not used) |
|||||||||
|
|
on the M1DBHR. |
|
|
|
|
|
GREEN |
WHITE |
BLACK |
RED |
GREEN |
WHITE |
BLACK |
|
|
|
|
Place terminating jumper JP5 of M1DBHR. |
|
Example #1 |
|
Keypad |
RED |
|
|
|
|
RED |
††† An Auxiliary Power Supply will be required if the control's Aux. |
|||||||||||
A single Keypad on Branch 1 |
|
GREEN |
|
|
|
|
|
|
|
|
|
|
|
power load for all combined loads exceeds 1A. (450 mA for UL |
||||||
Place terminating jumper on the |
|
|
|
|
|
|
|
|
|
|
|
|
Commercial). Connect as shown below. Be sure to connect the |
|||||||
|
WHITE |
|
|
|
|
|
|
|
|
|
|
|
||||||||
Keypad/Bus Device AND on JP2 of |
|
BLACK |
|
|
|
|
|
|
|
|
|
|
|
negative (-) terminal of the power supply to the negative (-) terminal |
||||||
the M1DBHR. |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
(Data Bus NEG) on the control. |
Example #2
Two (2) Keypads on Branch 2
Place terminating jumper on BOTH Keypads and remove jumper JP3 on M1DBHR.
Example #3
Three (3) Keypads & 2 Expanders on Branch 3
(Devices must be Daisy chain wired on each homerun so they appear to be in series.)
Place terminating jumper on the LAST device connected to each homerun and remove jumper JP4 on M1DBHR.
|
Jumper |
The max. number of bus devices |
Terminate |
these two |
|
varies based on the types and |
devices. |
models being used or combined. |
|
|
Keypad |
UL Use a UL Listed, battery backed-up Power Supply for UL |
|
Jumper |
|
||
|
installations. The battery will be supplying power to the Keypads/ |
||
Terminate |
|
||
|
Expanders during a power outage. The Power Supply and backup |
||
these two |
DO NOT Jumper JP3. |
||
Battery should be sized to supply the Keypads/Expanders with the |
|||
devices. |
|||
Keypad |
UL required minimum standby time. |
||
|
|
|
DATA BUS TERMINALS |
AUXILIARY POWER |
||
|
+ A B |
- |
- |
SUPPLY |
|
|
|
||
Keypad |
Keypad |
|
+ |
|
|
|
|
|
DO NOT Jumper JP4. |
|
|
|
|
|
|
|
Keypad |
DO NOT Jumper Terminate |
|
|
|
|
|
|
|
these devices. |
GREEN |
WHITE |
BLACK |
BLACK |
GREEN |
WHITE |
|
|
|
RED |
RED |
OPTION C - Using an optional M1DBHR Active Data Bus Hub
To Keypads or Expanders |
To Keypads or Expanders |
Setting the Data Bus Address and Enrolling Device(s) into the System
Keypads and Expanders communicate over the RS-485 data bus. Each device must have a unique address setting (1 to 16) within it's device type. Keypads are TYPE 1, input (zone) expanders TYPE 2, output expanders TYPE 3, etc. Device types permit address numbers to be re-used on different device type. For example: a Keypad, Zone Expander, and Output Expander can each be set to address 2 on the same data bus because each device is a different device type. But duplicate addresses
CANNOT exist within the same device type. I.E. Multiple keypads on the same bus cannot be set to 'like' addresses.
ADDRESS: From the factory all keypads are set to address 1. Valid addresses are 1 to 16. The first keypad on the system (Keypad 1) is automatically enrolled upon power up. Each additional keypad must be assigned a unique address and then manually enrolled from “Menu 1 - Bus Module Enrollment”. (See Menu 01, for complete instructions on Bus Module Enrollment)
1.Enter Keypad setup by one of the following three (3) methods:
a.Press and hold the " * " key for approx. 10-12 seconds (KP1 Keypads with firmware 2.1.48 or later)
b.Press the “ * ” and F5 keys at the same time for approx. 10 seconds. (older KP1 Keypads)
c.Hold ANY key pressed while applying power.
Keypad is in setup mode when the display indicates: Exit when done. F1 Set Addr.
2.Press the F1 key to display the current address setting.
3.Set the desired address by entering a number from 1 to X.
4.Press the Exit key when done.
ENROLLING:
1.Press the ELK key, then 9 (or scroll up) to display 9 - Installation Programming. Press the RIGHT arrow key to select this menu. The Installer Program Code must be entered to access this menu.
2.Enter the Installer Program Code. (The default code is 172839)
3.The first Installer Programming menu display will be “Bus Module Enrollment”
4.Press the RIGHT arrow key to select this menu. “Enrolling Bus Modules” will display.
5.After a few seconds the display will show the total Bus Modules that are enrolled. To view the enrolled devices and /or remove a device press the RIGHT arrow key next to the word Edit.
6.Press the * or Exit keys to exit Installer Programming.
† Not evaluated by UL |
†† Not for use in UL Listed Systems |
1234567890123456789012345
123456789012345678901234 5
123456789012345678901234123456789012345678901234Auth. Required 55
123456789012345678901234 5
123456789012345678901234Enter Valid Pin 5
123456789012345678901234 5
123456789012345678901234 5
1234567890123456789012345
1234567890123456789012345
12345678901234567890123412345678901234567890123401-Bus Module 55
123456789012345678901234 5
123456789012345678901234 5
123456789012345678901234Enrollment 5
123456789012345678901234 5
123456789012345678901234 5
1234567890123456789012345
123456789012345678901234 5
123456789012345678901234123456789012345678901234XX Bus Modules 55
123456789012345678901234123456789012345678901234 55
123456789012345678901234Enrolled, Edit r 5
123456789012345678901234 5
123456789012345678901234 5
M1G Installation and Programming |
Page 13 |
Section 2 - Operating the System
2.1 Introduction
The control has factory default programming which make it easy to bench test prior to installation. Terminate all zones with EOL resistors, then connect a keypad, transformer, and battery. The factory (Master) user code is 3456. This code can operate all user related features of the system. This section gives an overview of powering up and basic keypad functioning.
2.2 Powering Up (One Keypad)
After all other connections have been made and checked thoroughly, the controls AC transformer and battery may be connected. The Master Power Switch located on the lower left corner can then be turned. Upon power up the control will perform self-diagnostics and auto-enroll the first keypad (Keypad Address #1). Any additional keypads or expanders must be manually enrolled using Installer Level Programming. See “Menu 01 - Bus Module Enrollment”.
NOTE: It is very important to make certain that every keypad, input expander, output expander, or any other data bus device be assigned a unique data bus address within its type. See “MENU 01 - Bus Module Enrollment” for instructions on setting keypad and expander addresses.
System Startup on Battery Only (Ordinarily the control will not startup without AC power)
If AC power is not available (new construction site, etc.) the control may be started on battery ONLY by shorting the two silver pads (located in the lower left corner of the circuit board) with a small blade screwdriver. This will temporarily bypass the AC sensing circuit and allow the control to startup. NOTE: The On/Off power switch must be in the On position.
2.3 User Codes and Authorities
The control has 199 user codes plus one installer code. Each user code may be assigned specific authorities as to what it is allowed to do. The authorities are assigned from the Installer level programming, however the code digits and user names are assigned from the keypad user menu 6 - Change User Codes. Only a Master authority level code or the Installer code is allowed to access keypad user menu 6. The User’s Guide contains a description of operations accessible to the user codes. Control operations accessed by the installer passcode are slightly different.
Factory Default for User Code 1 is: 3 4 5 6 (Master Code) (1 2 3 4 5 6 if the six digit code option is enabled)
User code may be used for functions in a specific area or system-wide. Some options may be performed at any time, even while the control is fully or partially armed. The menu system is designed to be next-step-oriented. After a brief explanation of the options, the user should be able to begin operating the system immediately. For purposes of discussion, the installer and the end consumer are both considered users, but have different capabilities.
2.4 Installer Program Code and Authorities
The installer code can access all the keypad user menus and has limited arm/disarm privileges. It may be used to arm any area and disarm any area as long as the area WAS NOT armed by a user code. The Installer code can silence 24hr alarms or a Burglary alarms in an area that was armed by the installer or in an area that is not armed. The installer code can silence a trouble condition in a disarmed area. See User’s Guide for a full description of arming and disarming procedures.
Factory Default for the Installer Program Code is: 1 7 2 8 3 9
WARNING! Do Not use 0 0 0 0 0 0 for the Installer Program Code.
This will cause complete lockout of Keypad Installer Level Programming.
Page 14 |
M1G Installation and Programming |
2.5 Keypad Overview
Ready Light - ON when all burglar zones are secure and the system is OK to arm. If OFF, one or more zones are violated (not secure). For maximum security, secure all zones before arming the system. If FLASHING, one or more force-armable zones are violated. Force arming temporarily excludes violated zone(s) from the system. If a force armed zone becomes secure while system is armed, it will automatically restore to service. This is handy for a garage door as system may be armed with the door up, but will secure when door closes.
Armed Light- ON when the system is armed. The mode of arm will be indicated by the LCD display and the Exit or Stay lighted pushbuttons. This light will be OFF when the system is disarmed.
Exit Key - May be programmed for single or double press arming to the AWAY (not occupied) mode. If ON the system is armed and all perimeter sensors and interior motions are active. The Away key may be pressed during the exit delay time t to convert from Away to Away
Vacation mode. Vacation mode is primarily for use with the Whenever/And/Then Rules programming of Elk-RP for long term energy savings.
Stay Key - May be programmed for single or double press arming to the STAY (occupied) mode. If ON the system is armed and all interior zones are excluded (bypassed). Only perimeter doors and windows are active in the Stay mode. This key may also be programmed to change to other Stay modes such as: Stay Instant, Stay Night, and Stay Night Instant. Since interior zones are automatically excluded once the Stay mode is activated, the M1 allows this key to Stay arm even while one or more interior zones are violated, provided they are programmed for “force arming”. The Stay Night mode re-activates any interior night zones. To prevent a false alarm the control will not allow change to the Stay Night mode when a interior night zone is violated unless it is programmed for “Force arm”.
Available Keypads Styles
|
ELK-M1KPAS Arming Station |
ELK-M1KP2 LCD Keypad |
Fits a single gang electrical box. |
Smaller than M1KP. |
|
Features and/or operational characteristics will vary by keypad style.
ELK-M1KP LCD Keypad
Keypad Models and Feature Comparison
PART |
PHYSICAL |
DOOR |
ZONE |
PROG. |
OPT. 26 BIT |
TEMP |
FUNCTION |
BACKLIGHTING |
MOUNTING |
||
NUMBER |
DIMENSIONS |
COVER |
INPUT |
OUTPUT |
PROX READER |
SENSOR |
KEYS |
LCD |
|
KEYS |
OPTIONS |
|
|||||||||||
ELKM1KP |
6.87" W x 5.25" H x 1.32" D |
Yes |
Yes (1) |
Yes (1) |
Yes - Int. or Ext. |
Yes |
(6) F1 thru F6 |
Green |
|
Amber |
Surface Only |
ELKM1KP2 |
4.65" W x 5.5" H x .95" D |
No |
Yes (1) |
Yes (1) |
Yes - Ext. Only |
No |
(4) F1 thru F4 |
Blue |
|
Blue |
Surface Std. |
|
|
|
|
|
|
|
|
|
|
|
(Flush w/opt. BBK2) |
ELKM1KPAS |
1.3" W x 2.62" H x .3" D |
No |
No |
No |
No |
No |
(6) F then 1- 6 |
N/A |
|
Blue |
Flush Std. |
|
(keypad area not incl. elect. plate) |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Chime Key - Will be lighted when the Chime mose is On. A tone or announcement will be heard when certain zone(s) are opened. If OFF the chime mode is off. There are four different selections: Tone only, Voice, Tone/Voice, and Off. In the programming mode this key also functions as an insert character key for text programming. The key will be lighted when Chime is On.
Bypass Key - Pressing this key followed by a zone number and the bypass key again will exclude or bypass the selected zone. This key may also be used to delete a character during text programming. When the Bypass key is lit, one or more zones are bypassed.
* Key - Serves as a clear or reset key. If an error is made while entering digits, press this key to clear the error. Master clear is 3 presses.
# Key - This key is currently a duplicate of the Bypass key.
Numerical Keys - Used for entry of passcodes, programming, etc. Keys 2 - 9 also have an assigned alpha character for entering text.
ELK and Arrow Keys - The ELK and arrow keys have powerful functionality for both normal operation and programming. Pressing the
ELK key displays relative information according to each application. The arrow keys allow scrolling through all available options. The user can activate or select the displayed option by pressing the right arrow key. Once an option has been selected, the user may be prompted for a passcode. Additional sub-menu options may appear to assist. The user may return to the status screen by pressing the * key.
M1G Installation and Programming |
Page 15 |
Keypad Menus
123456789012345678901234567890
1123456789012345678901234567892345678901234567890123456789READY TO ARM 00
12345678901234567890123456789 0
123456789012345679:00AM 08/01/039 123456789 0
12345678901234567 9 123456789 0
12345678901234567890123456789 0
12345678901234567890123456789 0
The control offers extended Menu Options via the center navigation “ELK” key. Some menus may require a valid code to authorize. The Factory Default Code for USER Code 1 is: 3 4 5 6 (1 2 3 4 5 6 if the six digit code option is enabled)
Access to menus 1 to 5 can be restricted via programming to only Users that have “User Code Option 8” set. Menus 6 & 8 required a Master or Installer Code. Menu 9 requires the Installer Code. Press ELK to begin, then press the UP or DOWN arrow key to select a menu. Enter a code if prompted. To select a menu press the RIGHT arrow key.
123456789012345678901234567890
12345678901234567890123456789 0
12345678901234567890123456789123456789012345678901234567891-View/Control r 00
12345678901234567890123456789 0
12345678901234567890123456789Automation Fncts 0
12345678901234567890123456789 0
12345678901234567890123456789 0
12345678901234567890123456789 0
123456789012345678901234567890
Allows viewing or controlling of the automation functions such as Tasks, Lighting, Outputs, Temperature Sensor, Keypad Temperature, and Thermostats. Press the RIGHT arrow key to select, then choose the desired function using the UP or DOWN arrow keys.
NOTE: The automation functions must be assigned and named using the ELK-RP software. In most cases they cannot do anything unless they have been written into one of the “Whenever/And/Then” automation rules.
|
|
|
|
|
|
|
|
|
† Tasks are like 1 button macros, performing multiple jobs with one push. To activate a task |
|
|
|
123456789012345678901234567890 |
|
|
|
|
||||
|
|
123456789012345678901234567891234567890123456789012345678912345678901234567890123456789 |
r |
|
|
|
|
|||
|
|
|
|
|
|
|
||||
|
|
123456789012345678901234567891-Tasks |
|
|
|
|
|
press the RIGHT arrow key and press UP or DOWN to scroll through the list of available tasks. |
||
|
|
|
|
|
|
|
||||
|
|
12345678901234567890123456789 |
|
|
|
|
|
|||
|
|
12345678901234567890123456789 |
|
|
|
|
|
To jump directly to a particular task, enter it’s two digit number. Once the task is displayed, all |
||
|
|
12345678901234567890123456789 |
|
|
|
|
|
|||
|
|
|
23456789012345678901234567890 |
|
|
|
|
|||
|
|
|
123456789012345678901234567890 |
|
|
it takes to activate it is to press the # key. A rule to use the “Water the Lawn” task might be: |
||||
|
|
|
|
12345678901234567890123456789 |
|
0 |
||||
|
|
|
1234567890123456789012345678912345678901234567890123456789 |
|
00 |
|||||
|
|
|
12345678901234567890123456789 |
|
0 |
|
||||
|
|
|
|
Water The Lawn |
|
|
WHENEVER “Water the Lawn” IS ACTIVATED THEN TURN ON Valve 19 FOR 5 MINUTES, etc. |
|||
|
|
|
|
12345678901234567890123456789 |
|
0 |
||||
|
|
|
12345678901234567890123456789 |
|
0 |
|||||
|
|
|
12345678901234567890123456789 |
|
0 |
|
||||
|
|
|
|
01: # Activates |
|
|
|
|||
|
|
|
|
123456789012345678901234567890 |
|
|
† Lighting allows the individual control of lights and/or appliances which have been assigned |
|||
|
|
|
|
|
|
|
|
|
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
123456789012345678901234567890 |
|
|
|
|
||||
|
|
1234567890123456789012345678912345678901234567890123456789 r |
00 |
|
|
|
||||
|
|
|
|
|
||||||
|
|
12345678901234567890123456789 |
|
0 |
|
|
|
|
||
|
|
|
2-Lighting |
|
|
|
|
|
through the ELK-RP software. Press the RIGHT arrow key to select Lighting, then press the |
|
|
|
12345678901234567890123456789 |
|
0 |
|
|
|
|||
|
|
12345678901234567890123456789 |
|
0 |
|
|
|
|||
|
|
12345678901234567890123456789 |
|
0 |
|
|
|
UP or DOWN arrow keys to scroll through the list. If you know the three digit number, you may |
||
|
|
|
12345678901234567890123456789 |
|
0 |
|
|
|
||
|
|
|
|
23456789012345678901234567890 |
|
|
enter it to jump directly to that Lighting/Appliance. The current state of the unit will be |
|||
|
|
|
|
234567890123456789012345678923456789012345678901234567892345678901234567890123456789 |
|
|
||||
|
|
|
|
2345678901234567890123456789Kitchen Lights |
|
|
displayed. Press the # key to toggle (change) the unit from on > off or from off > on. |
|||
|
|
|
|
|
|
|||||
|
|
|
|
2345678901234567890123456789 |
|
|
||||
|
|
|
|
2345678901234567890123456789 |
|
|
|
|||
|
|
|
|
001:=Off, # to Chg |
|
|
|
|||
|
|
|
|
2345678901234567890123456789 |
|
|
|
|||
|
|
|
23456789012345678901234567890 |
|
|
Outputs might be relays or voltages used to actuate something like a motor, fan, pump, etc. |
||||
|
|
23456789012345678901234567890 |
|
|
|
|
||||
|
|
|
|
|
|
|||||
|
|
|
|
|
|
|||||
|
122211 456789012345678901234567894567890123456789012345678945678901234567890123456789 |
r |
|
|
|
|
||||
|
|
|
|
|
|
|||||
|
123456789012345678901234567893-Outputs |
|
|
|
|
|
Outputs can be turned on or turned off from this menu. Press the RIGHT arrow key to select |
|||
|
12345678901234567890123456789 |
|
|
|
|
|
||||
|
12345678901234567890123456789 |
|
|
|
|
|
Outputs, then press the UP or DOWN arrow keys to scroll through the list. If you know the |
|||
|
|
12345678901234567890123456789 |
|
|
|
|
|
|||
|
|
|
23456789012345678901234567890 |
|
|
|
|
|||
|
|
|
|
|
|
|
|
|
|
three digit number, you may enter it to jump directly to that Output. The current state of the |
|
|
|
|
2345678901234567890123456789 |
|
|
||||
|
|
|
|
23456789012345678901234567892345678901234567890123456789 |
|
|
||||
|
|
|
|
|
|
|||||
|
|
|
|
2345678901234567890123456789 |
|
|
|
|||
|
|
|
|
Pump Motor Cntrl |
|
|
output will display. Press the # key to toggle (change) the output from on > off or from off > on. |
|||
|
|
|
|
2345678901234567890123456789 |
|
|
||||
|
|
|
|
2345678901234567890123456789 |
|
|
||||
|
|
|
|
2345678901234567890123456789 |
|
|
|
|||
|
|
|
|
001:=Off, # to Chg |
|
|
|
|||
|
|
|
|
23456789012345678901234567890 |
|
|
Remote “Zone” Temperature Sensors can be read from this menu. Press the RIGHT arrow |
|||
|
|
|
|
|
|
|
|
|||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
12345678901234567890123456789 |
|
0 |
|
|
|
|||
|
123123 56789012345678901234567895678901234567890123456789 |
r |
00 |
|
|
|
||||
|
12345678901234567890123456789 |
|
0 |
|
|
|
|
|||
|
|
|
4-Temperature |
|
|
|
|
|
key to select this menu, then press the UP or DOWN arrow keys to scroll through the list of |
|
|
12345678901234567890123456789 |
|
0 |
|
|
|
||||
|
12345678901234567890123456789 |
|
0 |
|
|
|
||||
|
12345678901234567890123456789 |
|
0 |
|
|
|
|
|||
|
|
|
Sensor |
|
|
|
|
|
available sensors. To jump directly to a particular sensor enter it’s two digit number. The |
|
|
|
|
12345678901234567890123456789 |
|
0 |
|
|
|
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
123456789012345678901234567890 |
|
|
current temperature will be displayed. Press the * key to exit. |
|||
|
|
|
1234567890123456789012345678912345678901234567890123456789 |
00 |
|
|||||
|
|
|
12345678901234567890123456789 |
0 |
|
|
||||
|
|
|
|
Outside |
|
|
|
|
|
|
|
|
|
|
12345678901234567890123456789 |
0 |
|
|
|||
|
|
|
12345678901234567890123456789 |
0 |
|
|
||||
|
|
|
12345678901234567890123456789 |
0 |
|
|
||||
|
|
|
|
S01:=032 Degrees |
|
|
|
|||
|
|
|
|
12345678901234567890123456789 |
0 |
|
Keypad Temperature Sensors can be read from this menu. Press the RIGHT arrow key to |
|||
|
|
123456789012345678901234567890 |
|
|
|
|
||||
|
|
|
|
|
|
|||||
|
|
123456789012345678901234567891234567890123456789012345678912345678901234567890123456789 |
r |
000 |
|
|
||||
|
|
|
|
|
||||||
|
|
123456789012345678901234567895-Keypad |
|
0 |
|
|
select this menu, then press the UP or DOWN arrow keys to scroll through the list of available |
|||
|
|
12345678901234567890123456789 |
|
0 |
|
|
||||
|
|
12345678901234567890123456789 |
|
0 |
|
|
|
|||
|
|
12345678901234567890123456789Temperature |
|
0 |
|
|
keypads. To jump directly to a particular keypad enter it’s two digit number. The current |
|||
|
|
123456789012345678901234567890 |
|
|
|
|
||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
temperature at the keypad will be displayed. Press the * key to exit. |
||||||
|
|
|
|
12345678901234567890123456789 |
0 |
|
||||
|
|
|
|
|
||||||
|
|
1234567890123456789012345678912345678901234567890123456789 |
00 |
|
||||||
|
|
|
|
|
||||||
|
|
12345678901234567890123456789 |
0 |
|
|
|||||
|
|
|
|
Keypad 01 |
|
|
|
|
|
|
|
|
|
|
12345678901234567890123456789 |
0 |
|
|
|||
|
12345678901234567890123456789 |
0 |
|
|
||||||
|
12345678901234567890123456789 |
0 |
|
|
||||||
|
|
|
|
K01:=073 Degrees |
|
|
|
|||
|
23456789012345678901234567890 |
|
|
|
||||||
|
|
|
|
|
|
|
|
|
|
|
123456789012345678901234567890 |
|
123456789012345678901234567891234567890123456789012345678912345678901234567890123456789 |
r 000 |
12345678901234567890123456789 |
0 |
6-Thermostat |
|
12345678901234567890123456789 |
0 |
12345678901234567890123456789 |
0 |
12345678901234567890123456789 |
0 |
Temperature |
|
123456789012345678901234567890 |
12345678901234567890123456789
1234567890123456789012345678912345678901234567890123456789Hallway
12345678901234567890123456789
12345678901234567890123456789
12345678901234567890123456789T01:=072 Degrees
12345678901234567890123456789
123456789012345678901234567890
† Thermostats can be read from this menu. Press the RIGHT arrow key to select this menu, then press the UP or DOWN arrow keys to scroll through the list of available thermostats. To jump directly to a particular thermostat enter it’s two digit number. The current temperature at
000 the thermostat will be displayed. Press the * key to exit.
0
0
0
0
2345678901234567890123456789 0
234567890123456789012345678923456789012345678901234567892-Reset r 00
2345678901234567890123456789 0
2345678901234567890123456789Smoke Detectors 0
2345678901234567890123456789 0
2345678901234567890123456789 0
23456789012345678901234567890
12345678901234567890123456789 0
12345678901234567890123456789123456789012345678901234567895 Seconds Smoke 00
12345678901234567890123456789 0
12345678901234567890123456789Output Reset r 0
12345678901234567890123456789 0
12345678901234567890123456789 0
123456789012345678901234567890
Used for resetting latched smoke detectors after a fire alarm activation..
Press the RIGHT arrow key to actuate the Reset Smoke Detector feature. This causes the power to smoke detectors to be removed for 5 seconds. During this time all fire zones will be ignored to keep an accidental alarm from occurring.
Continued on next page.. |
† Not evaluated by UL |
|
|
|
|
Page 16 |
M1G Installation and Programming |
123456789012345678901234567890
12345678901234567890123456789 0 121234567890123456789012345678945678901234567890123456789-Walk Test Area r 00 12345678901234567890123456789 0 12345678901234567890123456789< Area? Name > 0 12345678901234567890123456789 0 12345678901234567890123456789 0 123456789012345678901234567890
23456789012345678901234567890
12345678901234567890123456789 0
123456789012345123456789012345000of01678901234567897890123456789Tested r 00
12345678901234567890123456789 0
12345678901234567890123456789A?-Violate Zones 0
12345678901234567890123456789 0
12345678901234567890123456789 0
123456789012345678901234567890
123456789012345678901234567890
1234567890123456789012345678923456789012345678901234567891123456789012345678901234567894-View History r 000
12345678901234567890123456789Log 0
12345678901234567890123456789 0
12345678901234567890123456789 0
12345678901234567890123456789 0
123456789012345678901234567890
1123456789012345678901234567892345678901234567890123456789L001:01/01b08:00 00
12345678901234567890123456789 0
12345678901234567890123456789AreaArmed 103A1 0
12345678901234567890123456789 0
12345678901234567890123456789 0
12345678901234567890123456789 0
23456789012345678901234567890
12345678901234567890123456789 0
12345678901234567890123456789123456789012345678901234567895-View Status r 00
12345678901234567890123456789 0
12345678901234567890123456789of all zones 0
12345678901234567890123456789 0
12345678901234567890123456789 0
12345678901234567890123456789 0
123456789012345678901234567890
11234567890123456789012345678923456789012345678901234567896-Change r 00
12345678901234567890123456789 0
12345678901234567890123456789User Codes 0
12345678901234567890123456789 0
12345678901234567890123456789 0
12345678901234567890123456789 0
Requires Master or
Installer Code
23456789012345678901234567890
123456789012345678901234567891234567890123456789012345678912345678901234567890123456789001:Selb Prgr 000 12345678901234567890123456789 0 12345678901234567890123456789< User Name > 0 12345678901234567890123456789 0 12345678901234567890123456789 0
123456789012345678901234567890
123456789012345678901234567890
12345678901234567890123456789 0
12345678901234567890123456789123456789012345678901234567897--Automation r 00
12345678901234567890123456789 0
12345678901234567890123456789Custom Settings 0
12345678901234567890123456789 0
12345678901234567890123456789 0
123456789012345678901234567890
Requires Master or Installer Code
123456789012345678901234567890 12345678901234567891234567890123456789CS01:b00:00Time123456789123456789 r 00 12345678901234567890123456789 0 12345678901234567890123456789Sprklr On 0 12345678901234567890123456789 0 12345678901234567890123456789 0 12345678901234567890123456789 0
123456789012345678901234567890 1234567890123456789012345678912345678901234567890123456789123456789012345678901234567898-System r 000
12345678901234567890123456789Settings 0
12345678901234567890123456789 0
12345678901234567890123456789 0
12345678901234567890123456789 0
123456789012345678901234567890
Requires Master or Installer Code
23456789012345678901234567890 2345678901234567890123456789234567890123456789012345678981-Set Sys Clock r 00 2345678901234567890123456789 0 234567890123456789012345678924hr format 0 2345678901234567890123456789 0 2345678901234567890123456789 0 2345678901234567890123456789 0
2345678901234567890123456789 0
2345678901234567890123456789234567890123456789012345678982-Out1 Voice 00
2345678901234567890123456789 0
2345678901234567890123456789Adjust Volume r 0
2345678901234567890123456789 0
2345678901234567890123456789 0
23456789012345678901234567890
2345678901234567890123456789 0
2345678901234567890123456789234567890123456789012345678983-Keypad r 00
2345678901234567890123456789 0
2345678901234567890123456789Adjustments 0
2345678901234567890123456789 0
2345678901234567890123456789 0
23456789012345678901234567890
234567890123456789012345678901
23456789012345678901234567890234567890123456789012345678901:Set Keypad r
23456789012345678901234567890
23456789012345678901234567890Beep Tone
23456789012345678901234567890
23456789012345678901234567890
23456789012345678901234567890
23456789012345678901234567890
23456789012345678901234567890234567890123456789012345678902:Set Keypress r
23456789012345678901234567890
23456789012345678901234567890Beep Volume
23456789012345678901234567890
23456789012345678901234567890
234567890123456789012345678901
23456789012345678901234567890
23456789012345678901234567890234567890123456789012345678903:Set Backlight r
23456789012345678901234567890
23456789012345678901234567890Dim Level
23456789012345678901234567890
23456789012345678901234567890
234567890123456789012345678901
Menu 3 permits a local walk test of all zones assigned to this keypad’s area. The siren(s) and communicator are disabled during a walk test. Press the RIGHT arrow key to begin a Walk Test. The keypad displays the total tested zones adjacent to the total number of zones involved. When a zone is activated, it’s name is displayed across the bottom and can be audible if the Chime mode is on.
Allows viewing of the past 512 activities stored in the history log. Press the RIGHT arrow key to view. History activities include: Arm, Disarm, Alarm, Trouble, etc. The top line displays the Log number, Mth/Day, Time, and event description. The log can ONLY be cleared from ElkRP.
L001 is always the most recent event. Press the UP or DOWN arrow keys to move forward and back. Event 512 will be the oldest event. The bottom line displays the event description, the extended data (zone, user, etc.) and the area number (A1-A8).
Allows viewing of the current status of all zones. Press the RIGHT arrow key to select. Press UP or DOWN to scroll through the zones or enter a three digit number to jump directly to a particular zone. I.E. for zone 16 enter 016. Press the * key to exit.
For changing a user code and/or name for codes which have been previously enabled by the Installer. Only a Master code OR the installer code can access this menu. Press the RIGHT arrow key to begin. Press UP or DOWN keys to locate a user, or enter 3 digits to jump. Press RIGHT arrow key to view the existing code. To change, enter the new code digits and listen for 3 beeps to confirm. To edit the name, press the RIGHT arrow key once, then press the DOWN arrow key. Enter the text using the letters on the keys. I.E. For “K” press the 5 key twice. Move RIGHT or LEFT with the arrow keys. Press Chime to insert a space. Press Bypass to erases a letter. The UP and DOWN arrow keys shift from upper to lower case letters. Press the ELK key to save and exit.
.
Allows an end user to change up to 20 settings incorporated into an automation rule. These settings can be: time of day, time duration (seconds), or a numeric value. Each custom setting has a reference number (CS) and a text description: I.E. CS01: Sprkl On 00:00 [Time] implying a time of day setting. Press the RIGHT arrow key to begin.
Press the UP or DOWN arrow keys to locate a setting, then press the RIGHT arrow key to select. Enter the new value and press the ELK key to save and exit.
Menu 8 consists of 8 sub-menus used for advanced system settings. Press the right arrow key and enter a valid user code. Press the UP or DOWN arrow keys to select a sub-menu or enter the one digit number to jump directly to any sub-menu. I.E. enter 6 to jump to 86.
To set the system clock press the RIGHT arrow key, then press the UP or DOWN arrow key to select the day. Next, press the RIGHT arrow key to move to Date/Time setting. Enter two digits for month, date, year, hour, and min. To exit press the * key.
To set the volume for output 1 voice messages (non-alarm) press the RIGHT arrow key and set desired volume with the UP or DOWN keys. There are 8 settings (0-7). WARNING: PROTECT EARS! Each adjustment broadcasts a test message through Output 1. To exit press the * key.
To set keypad adjustments press the RIGHT arrow key. Then press the UP or DOWN keys to select one of the three options.
To set keypad beep tones press the RIGHT arrow key, then select the desired tone using the UP or DOWN keys. There are 9 settings (0-8). When done, exit by pressing the * key.
To set key-press beep volume press the RIGHT arrow key, then select the desired volume using the UP or DOWN keys. There are 7 volume levels (1-7) plus Off (0). To exit press the * key.
To set backlight dim level press the RIGHT arrow key, then select the desired level using the UP or DOWN keys. There are 9 backlight levels (1-9) plus Off (0). The keypad automatically dims to this setting after 30 seconds of no activity in order to save energy. To exit press the * key.
M1G Installation and Programming |
Page 17 |
123456789012345678901234567890
12345678901234567890123456789123456789012345678901234567891234567890123456789012345678984-System r 000
12345678901234567890123456789 0
12345678901234567890123456789Tests 0
12345678901234567890123456789 0
12345678901234567890123456789 0
23456789012345678901234567890
12345678901234567890123456789 0
12345678901234567890123456789123456789012345678901234567891:Battery Test r 00
12345678901234567890123456789 0
123456789for 301234567890123456789Seconds 0
123456789 1234567890123456789 0
12345678901234567890123456789 0
12345678901234567890123456789 0
123456789012345678901234567890
1234567890123456789012345678912345678901234567890123456789123456789012345678901234567892:LCD Test r 000
12345678901234567890123456789 0
12345678901234567890123456789 0
12345678901234567890123456789 0
12345678901234567890123456789 0
123456789012345678901234567890
To perform system tests press the right arrow key. Then press the up or down arrow keys to select one of the three tests.
The control’s standby battery is load tested automatically every 24hrs. However, it can also be manually load tested anytime using this option. Press the right arrow key to start the test. The battery is placed under load for 30 seconds and the battery voltage and system current is displayed. If the battery falls below a set level, a Low Battery trouble will occur. If it’s necessary to replace the battery, this test should be used to test and clear a Low Battery Trouble condition.
To test the keypad’s LCD screen press the RIGHT arrow key. The entire screen should appear black indicating all pixels are working. To exit press the * key.
123456789012345678901234567890
1211223:Communicator456789012345678901234567894567890123456789012345678945678901234567890123456789 r 000 12345678901234567890123456789 0 12345678901234567890123456789Manual Test 0 12345678901234567890123456789 0 12345678901234567890123456789 0
123456789012345678901234567890
To manually test the communicator (dialer) press the RIGHT arrow key. Testing is done using the first phone number that is programmed to send a test code. If there is no phone number programmed to send a test code, the test will end. To exit this menu press the * key.
1234567890123456789012345678912345678901234567890123456789 r 00 |
There are two types of test, silent and monitored. To silently send a test press the right |
||||
|
123456789012345678901234567890 |
|
|
|
|
|
|
12345678901234567890123456789 |
0 |
|
|
|
|
Send Test |
0 |
arrow key from this display. To hear the test using the inside speakers (OUT1) press the up |
|
|
|
||||
|
|
12345678901234567890123456789 |
|||
|
|
12345678901234567890123456789 |
0 |
|
|
|
|
Silently |
|
|
|
|
|
12345678901234567890123456789 |
0 |
or down arrow key to bring up the following display. |
|
|
|
123456789012345678901234567890 |
0 |
||
|
|
12345678901234567890123456789 |
|
||
|
|
|
|
|
|
123456789012345678901234567890
123456789012345678901234567892345678901234567890123456789112345678901234567890123456789Send Test w/ r 000 12345678901234567890123456789 0 12345678901234567890123456789speaker monitor 0 12345678901234567890123456789 0 12345678901234567890123456789 0
123456789012345678901234567890
This unique feature permits you to hear or “monitor” a single communicator test using the inside speakers (OUT1) eliminating the need for a telephone “Butt” set. Simply press the right arrow key from this display to begin.
|
123456789012345678901234567890 |
000 |
Similar to above, this works for multiple communicator tests. Press the right arrow key to |
|
|
123456789012345678901234567891234567890123456789012345678912345678901234567890123456789 r |
|
||
|
|
|||
|
12345678901234567890123456789Turn Butt Set |
0 |
enable. Each communicator transmission will be monitored until mode is cancelled. Press |
|
|
12345678901234567890123456789 |
0 |
||
|
12345678901234567890123456789Monitor Mode On |
0 |
|
|
|
12345678901234567890123456789 |
0 |
the star (*) key three times to cancel. Cancelled automatically after 24hr daily battery test. |
|
|
123456789012345678901234567890 |
|
|
|
|
123456789012345678901234567890 |
|
000 |
This special option allows any pending (not reported) dialer communications to be cleared |
|
123456789012345678901234567891234567890123456789012345678912345678901234567890123456789 r |
|
|
|
|
12345678901234567890123456789Clear Pending |
|
0 |
or cancelled. Typically this will be used only for initial installation and testing. |
|
12345678901234567890123456789 |
|
0 |
|
|
12345678901234567890123456789Dialer Reports |
|
0 |
|
|
12345678901234567890123456789 |
|
0 |
|
|
123456789012345678901234567890 |
|
|
|
NOTE: ALWAYS NOTIFY THE MONITORING STATION BEFORE TESTING THE DIALER! If the test should fail, a Comm Fail trouble will occur. To clear a Comm Fail the dialer must be able to complete a good communication.
123456789012345678901234567890 |
|
12345678901234567890123456789 |
0 |
12341234 678901234567890123456789678901234567890123456789 r 00 |
|
12345678901234567890123456789 |
0 |
85-Connect ‘RP’ |
|
12345678901234567890123456789 |
0 |
12345678901234567890123456789 |
0 |
12345678901234567890123456789 |
0 |
Remote Program |
|
123456789012345678901234567890 |
|
To connect ELK’s Remote Program PC software (RP) via the user assisted method, press the RIGHT arrow key and then select the connection mode with the UP or DOWN arrow keys.
12345678901234567890123456789 0
12345678901234567890123456789123456789012345678901234567891:Seize Line r 00
12345678901234567890123456789 0
12345678901234567890123456789Attended Mode 0
12345678901234567890123456789 0
12345678901234567890123456789 0
123456789012345678901234567890
23456789012345678901234567890
1234567890123456789012345678912345678901234567890123456789123456789012345678901234567892:Seize Line r 000
12345678901234567890123456789 0
12345678901234567890123456789UnAttended Mode 0
12345678901234567890123456789 0
12345678901234567890123456789 0
123456789012345678901234567890
1:Seize Line Attended Mode - 1) Allows RP connection to begin on an already established voice connection between the control phone line and the RP Computer. 2) Also useful for manually answering an incoming call from the RP Computer with programming Rings to Auto Answer.
2:Seize Line Unattended Mode - Pressing the RIGHT arrow key causes the control to dial the programmed RP telephone number. The RP Computer must be in the “wait for call” mode.
234567890123456789012345678901
2345234586789012345678901234567890789012345678901234567890-System r
23456789012345678901234567890
23456789012345678901234567890Diagnostics
23456789012345678901234567890
23456789012345678901234567890
23456789012345678901234567890
234567890123456789012345678901
123456789012345678901234567890
12345678901234567890123456789 0
12345678901234567890123456789123456789012345678901234567891:DataBusErrors b 00
12345678901234567890123456789 0
12345678901234567890123456789T2A1 Retry 00000 0
12345678901234567890123456789 0
12345678901234567890123456789 0
123456789012345678901234567890
123456789012345678901234567890
1234567890123456789012345678912345678901234567890123456789123456789012345678901234567892:Sys Volt/Curr b
1234567 90123456789 123456789
123456713.8V901234567890.440Amps123456789
1234567 90123456789 123456789
12345678901234567890123456789
123456789012345678901234567890
NOTE: UL requires that a Technician be On-Site when doing Remote Programming.
This is a collection of tools for diagnosing system problems. Press the RIGHT arrow key and enter a valid user code to begin. Press the UP or DOWN keys to select one of the four tools:
This tool is for use in conjunction with Tech Support to diagnose data bus retries and errors. It displays the device type and number of retries accumulated since the last power-up. T=Device type, A=The Address within the device type
This tool displays the control’s voltage and average current being drawn from the power supply.
123456789012345678901234567890
1212123:Zone=001456789012345678901234567894567890123456789012345678945678901234567890123456789Volts
12345678901234567890123456789
12345678901234567890123456789Display Level r
12345678901234567890123456789
12345678901234567890123456789
123456789012345678901234567890
This tool allows the voltage on each zone to be displayed in real time. It changes as contacts or devices are violated. Press the RIGHT arrow key to begin.
|
|
00 |
Use the UP or DOWN keys to scroll through each zone. The displayed information consists of: |
|
|
123456789123456789 12345678901234567891234567890123456789 |
|||
|
123456789012345678901234567890 |
|
|
|
|
Zn=001 Volt=07.2 |
0 |
the present zone voltage, the L low and H high alarm thresholds, and the analog (A to D) |
|
|
1234567890123456789 123456789 |
|||
|
12345678901234567890123456789 |
0 |
|
|
|
L04.6 H09.0 |
A132 |
|
|
|
1234567890123456789 |
123456789 |
0 |
equivalent of the zone voltage.. |
|
12345678901234567890123456789 |
0 |
||
|
12345678901234567890123456789 |
0 |
|
|
|
|
|
|
|
123456789012345678901234567890
1234567890123456789012345678912345678901234567890123456789123456789012345678901234567894:LastOnHookTele
12345678901234Line V=57,+6 8901-20%3456789
12345678901234 6 8901 3456789
12345678901234 6 8901 3456789
12345678901234567890123456789
123456789012345678901234567890
This is a read only screen displaying the telephone line voltage during the last on-hook condition. It is an approximate measurement accurate to only +-20%.
Page 18 |
M1G Installation and Programming |
123456789012345678901234567890
123456789012345678901234567891234567890123456789012345678987-Custom 00
12345678901234567890123456789 0
12345678901234567890123456789Message Record r 0
12345678901234567890123456789 0
12345678901234567890123456789 0
12345678901234567890123456789 0
† This option is used in conjuction with a house telephone (microphone) to record up to 10 custom voice messages. Each message occupies a 6 second block. Two or more consecutive blocks may be linked together for longer times. Total record time cannot exceed 60 seconds. These messages require the Elk-RP software, which utilize these messages together with the built-in 500+ word vocabulary to construct voice phrases for many uses, including the voice dialer. Press the RIGHT arrow key to begin custom message record.
123456789012345678901234567890
12345678901234567890123456789 0 12345678902345678901 VM01b2345678901234567892345678901234567891 Block(s) 00 12345678901234567890123456789 0 12345678901234567890123456789Record< Play> 0 12345678901234567890123456789 0 12345678901234567890123456789 0 123456789012345678901234567890
23456789012345678901234567890
234567890123456789012345678923456789012345678901234567896 Sec Blocks=01b 00
2345678901234567890123456789 0
2345678901234567890123456789Record< PlayAll> 0
2345678901234567890123456789 0
2345678901234567890123456789 0
2345678901234567890123456789 0
Selects any one of the custom messages (VM01-VM10) for playback or recording. Press the UP or DOWN arrow keys to select. To Play the selected message press the RIGHT arrow key. The message will play through Output 1 speakers. To record a new message press the LEFT arrow key. To exit press the * key.
This sets the number of consecutive 6 sec. record blocks. The default is 01 blocks which is normally long enough for most applications. However, to create a longer message press the RIGHT arrow key and enter the number 01 to 02, etc. NOTE: Creating longer messages reduces the total number of custom messages. This screen also allows all messages to be played “PlayAll” by pressing the RIGHT arrow key. When ready to record press the LEFT arrow key.
23456789012345678901234567890
1234567890123456789012345678911234567890123456789012345678923456789012345678901234567896 Sec Blocks=01b 000
12345678901234567890123456789 0
12345678901234567890123456789Rec< LiftPhone! 0
12345678901234567890123456789 0
12345678901234567890123456789 0
23456789012345678901234567890
This is the prerecord screen. To begin recording: 1) lift the house phone (off hook), 2) press the LEFT arrow key, 3) start speaking. To stop recording press the “0” key. If stop is not pressed, recording will automatically end after 6 sec. (or the total number of blocks times 6 seconds).
NOTE: A local house phone is used as the microphone. Installer programming menu 07, option 1, must be set to a 1 in order for the local phone to be recognized by the control.
12345678901234567890123456789 0 11234567890234567890VM01b2345678901234567892345678901234567891 Block(s) 00 12345678901234567890123456789 0 12345678901234567890123456789Record< Play> 0 12345678901234567890123456789 0 12345678901234567890123456789 0 123456789012345678901234567890
This will display as soon as recording has stopped. To play the new message press the RIGHT arrow key. To record the message again press the LEFT arrow key and follow the same procedures again. To exit press the * key.
Step by step summary of procedures for recording a custom message:
1)Verify that a house telephone is connected to the control’s T1 and R1 terminals and that Installer menu 07, option 1 is set to a 1. This allows the control to recognize the telephone and allow it to be used as a microphone.
2)Go to the user menu 8-System Settings by pressing the ELK key and entering 8. Press the r key and enter a valid user code. Press 87 to reach the custom message record screen.
3)Using the Up/Down arrow keys, select the voice message to record VM01 to VM10. There are 10 custom messages.
4)Press the l key and select the number of 6 second blocks for your message. Hint-rehearse and time the message, if it is greater than 6 seconds then increase the number of consecutive blocks as required.
5)Lift the telephone handset and press the l key to begin the recording. The recording will not start until the handset is off-hook and the l key is pressed.
6)Record your message by speaking into the handset. If the message is shorter than the amount of time selected then press 0 to stop recording. Otherwise, recording will stop when the number of blocks is reached.
7)Press the Right arrow key to play the message. The message will be heard through the telephone handset if it is still off-hook. Otherwise the message will be directed to the amplifier connected to output 1.
123456789012345678901234567890 1234567890123456789012345678912345678901234567890123456789123456789012345678901234567899-Installation r 000 Requires 12345678901234567890123456789Programming (0) 0 Installer 12345678901234567890123456789 0 Code 12345678901234567890123456789 0 12345678901234567890123456789 0 123456789012345678901234567890
From this menu you may press the RIGHT arrow to enter Installation Level Programming. If the Installer Programming Code has not already been entered it will be required at this time.
REFER TO PAGE 22 FOR PROGRAMMING INSTRUCTIONS
NOTE: The Remote Programming RP software can be used to lockout certain local program capabilities for “antitakeover” purposes. The number in the lower right corner of this menu will indicate the level of lockout as follows:
(0) = No lockout,
(1)=Lockout Telephone number programming - view everything, (2)=Lockout ALL programming - view everything,
(3)=Lockout ALL Programming and Viewing. This can only be set or removed from the ELK-RP Software.
† Not evaluated by UL
M1G Installation and Programming |
Page 19 |
Menu 0 - Select Keypad Alternate Area - Multi-area (Partition) Operation
This menu allows the keypad to be mapped temporarily to any other area, allowing multi-area (partitioned) operation. An individually mapped area can be armed, disarmed, and controlled just as if the keypad were permanently assigned to that area. It may also be used to access a consolidated display of all areas at once, showing the status of each area.
To reach the keypad menus press the center navigation key labeled “ELK”. A user code may be required depending on how the control is programmed. The four arrow keys around the Elk key are used to scroll, backup, etc. Pressing the RIGHT arrow key will select the displayed menu.
1.Press the ELK key. Enter a user code if prompted.
2.Use the UP or DOWN arrow keys to find menu “0-Select Keypad Alternate Area”.
1234567890123456789012345678
123456789012345678901234567 8
1234567890123456789012345671234567890123456789012345670-Select Keypad 88
123456789012345678901234567 8
123456789012345678901234567Alternate Area r 8
123456789012345678901234567 8
123456789012345678901234567 8
123456789012345678901234567 8
1234567890123456789012345678
1234567890123456789012345678
123456789012345678901234567 8
123456789012345678901234567123456789012345678901234567Auth. Required 88
123456789012345678901234567 8
123456789012345678901234567Enter Valid PIN 8
123456789012345678901234567 8
123456789012345678901234567 8
123456789012345678901234567 8
1234567890123456789012345678
Press the RIGHT arrow key to select this menu and display the following:
Enter a valid user code. The control does not allow (restricts) mapping or viewing of areas that are not authorized for the user code.
12345678901234567890123456789 0
1234567890123456789012345678923456789012345678901234567891 ChangeKPArea-1 r 00
12345678901234567890123456789 0
12345678901234567890123456789[Area Name] A1 0
12345678901234567890123456789 0
12345678901234567890123456789 0
12345678901234567890123456789 0
123456789012345678901234567890
MAPPING TO AN INDIVIDUAL AREA
Enter an area number from 1 to 8 OR scroll UP and DOWN with the arrow keys.
Press the Right Arrow key to map the Keypad to the area shown. The LCD display and the Ready / Armed LEDs will show the status for the mapped area for 1 minute. During this minute, it is possible to arm, disarm, bypass, etc. the mapped area from this keypad. Each time a key is pressed the 1 minute is restarted. However, after 1 minute of no keypress activity, the keypad will return to its original primary assigned area.
123456789012345678901234567890 |
|
12345678901234567890123456789 |
0 |
123456789012345678901234567891234567890123456789012345678912345678901234567890123456789 |
r 000 |
12345678901234567890123456789ChangeKPArea-0 |
0 |
12345678901234567890123456789 |
0 |
12345678901234567890123456789 |
0 |
123456789012345678901234567890=All Areas |
0 |
123456789012345678901234567890 |
1234567890123456789012345678 9 12345678901234567890123451234567890123456789012345Area# 1 2 3 4 5 677878 8 99 1234567890123456789012345678 9 1234567890123456789012345678Status X r r r r r r r 9 1234567890123456789012345678 9 1234567890123456789012345678 9 1234567890123456789012345678 9
12345678901234567890123456789
ACCESSING A CONSOLIDATED DISPLAY OF ALL VALID AREAS Entering “0” for the area number immediately maps the Keypad to a consolidated ‘snapshot’ of all authorized areas. This permits quick arming and disarming only. If an area is not ready to arm it will be necessary to map individually to that area to view the violated zone(s) and either secure or bypass them prior to arming.
This example shows all 8 areas, meaning that the User Code was valid for all 8.
The display only shows the areas for which the user code is authorized.
Note the letter beneath each area number.
The single upper case “X” indicates the primary area. This area is controlled exclusively from the regular operation screens.
A lower case “r” below an area indicates the area is Ready to Arm. A lower case “n” below an area indicates the area is Not Ready.
A upper case “A” below an area indicates the area is Armed.
|
123456789012345678901234123456789012345678901234 678901678901 |
|
22 |
This example shows the user code was only authorized for areas 1, 2, and 3. The |
||
|
|
12345678901234567890123456789012 |
|
|
|
|
|
|
1234567890123456789012345678901 |
|
|
2 |
|
|
|
Area# 1 2 3 4 5 6 7 8 |
|
2 |
unauthorized area(s) have a “-” below them. |
|
|
|
1234567890123456789012345678901 |
|
|
||
|
|
1234567890123456789012345678901 |
r |
|
2 |
|
|
|
Status X r r - - - - - |
|
|
|
|
|
|
1234567890123456789012345678901 |
|
|
2 |
|
|
|
1234567890123456789012345678901 |
|
|
2 |
|
|
|
1234567890123456789012345678901 |
|
|
2 |
To change or ‘toggle’ the arm status of an area, press the number key representing |
|
|
12345678901234567890123456789012 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
the area number. IMPORTANT: The area status is not “real time”. It is a snapshot |
|
|
|
|
|
|
taken when the RIGHT arrow key was pressed. If a zone has since become violated |
|
|
|
|
|
|
the area will still be displaying “r”, however the letter will immediately change to “n” |
|
|
|
|
|
|
and the keypad will emit an error tone when an attempt is made to arm by pressing |
|
|
|
|
|
|
the area number. |
|
|
|
|
|
|
When finished, press the “*” key to exit. |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Page 20 |
|
|
|
M1G Installation and Programming |
Section 3 - Programming The Control
3.1 Introduction
The Security functionality of the M1 Control can be programmed either from an ELK-M1KP LCD Keypad OR from the ELK-RP PC Software. The keypad features a menu-driven “Text” based interface with simple Yes/No answers for most options. After just a short amount of experience the average installer will not even require an instruction manual to keypad program the control.
For the Automation functionality the ELK-RP PC Software is a requirement. The options and capabilities available for automation are so unique and powerful that it takes a PC to make use of all the benefits. The M1 features a powerful “Whenever/And/Then” RULES based programming that allows almost any imaginable operation.
3.2 Local Keypad Programming
There are two levels of operation for programming the control locally, user level and installer level.
-User level programming provides the ability to add, change, or delete user passcodes and names. It also allows custom automation settings to be viewed and changed. A master user code is required to access the user code and custom settings screens. User programming is explained in the User’s Guide.
-Installer level programming allows total customizing of the Security operating features. Only the installer code may access this level. If the installer code is lost or forgotten, it is impossible to program the control locally. Anyone attempting installer level programming should be familiar with the contents of this publication prior to programming the control panel. If remote programming is used, it is possible to “lock out” or prevent takeover of a control by another installation company by selecting “Lockout Local Prog.” This prevents the installer passcode from gaining access to programming via an LCD keypad. The installer passcode may still be used for the non-programming functions described in Chapter 2. Lockout Local Prog does not affect remote programming.
3.3 Local or Remote Computer Programming (ELK-RP) and Anti-Takeover
ELK-RP programming utilizes extensive error checking and security safeguards, including data encryption, password log-on, serial number, and dealer assigned RP access code. The serial # identifies the control to RP while the RP access code identifies the computer to the control prior to a programming session. RP loads the access code during the first connection. It cannot be viewed or changed from local keypad programming. In addition to these safeguards, you can set an anti-takeover option from RP which prevents certain keypad programming. Even a total default of the panel programming cannot reset the anti-takeover option once it is set..
The Factory Default Elk-RP Access Code is: 2 4 6 8 0 1
NOTE: UL requires that a Technician be On-Site when doing Remote Programming.
3.4 Area Partitioning
The control may be divided into 1 to 8 independent areas (partitions). Each area appears as a full-featured system, allowing one control to be shared by multiple, independent departments within a common structure. Zones, User Codes, and Keypads may be assigned to any 1 area up to the maximum number available. An example is a single building divided into room(s) to be armed/disarmed separately. Mount the control in a secure area (common utility closet) with dedicated and uninterrupted AC power and telephone service. Then assign zones, codes, and keypads to each department.
Output 1 siren/voice activates on all alarms, regardless of the area. The RP Software Rules can be used create additional (separate) outputs. When reporting to the central station events like AC Power Failure, Automatic tests, Low Battery, etc., are considered system reports and are transmitted using the Area 1 account number. If area partitioning is not desired, simply designate all zones to a single area (Area 1) which is the factory default setting for zones 1-16.
COMMON AREA - Another popular feature is the ability to have one or more areas made “common” to Area 1. This is often referred to as a “Vestibule Feature”. Any of the Areas 2 thru 8 may be made common to Area 1. The result is: Area 1 cannot be armed until all its common areas are armed. Once armed, Area 1 will disarm if any common area becomes disarmed. This is good for lobbies or vestibules shared by two or more people. Each area must have its own keypad. NOTE: If you want
Area 1 to automatically arm when all its common areas become armed, use a Whenever/And/Then rule from the RP software to do this.
M1G Installation and Programming |
Page 21 |
3.5 Communicator Setup Checklist
The Communicator (Dialer) can dial up to 8 phone numbers plus RP. Digital reporting formats include: Pulse 4+2, SIA, Contact ID, and Pager. There is also a Voice † format which can be commanded from the RP Rules Programming to call a persons home or cellphone and deliver a voice message. Use the following checklist for each required telephone number.
1.Under Menu 08 - Telephone Account Setup, select one of the telephone numbers and program the following: Option 01: Select the desired reporting format - 0=Disable, 1=Contact ID, 2=SIA, 3=Pulse 4+2, 4=Pager, 5=Voice †
Note: The Voice format (5) cannot be enabled from keypad programming. It can only be programmed from the Elk-RP Software using the Whenever/And/Then Rules.
Option 02: Set the priority for the first (primary number) to 0 = Always Report.
Option 03: Program the telephone number digits to be dialed. No special start or ending characters are required. Option 04: Set the dial attempts to greater than 0. For Digital reports 8 is suggested. For Voice the max. is 2. Option 05 Program the digits for the account number to report. Each area (partition) has its own Acct. Number. Option 13: Select Yes to have Area info, Zone Alarms, Zone Restores, and Zone Unbypasses reported to this Tel #. Option 14: Select Yes if you wish to have Zone Bypasses reported to this Tel #.
Option 15: Select Yes if you wish to have Zone Troubles reported to this Tel #.
Option 16: Select Yes if you wish to have User (Open/Close) Reports reported to this Tel #.
Option 17: Select Yes if you wish to have Global System Events (AC Fail, Low Battery, etc.) reported to this Tel #. Option 18: Although not required, you may program a text name for each telephone number.
2.Under Menu 09 - Area Reporting Codes, select the area (partition) and program the desired options such as: Dialer Delay, Alarm Abort, Auto Open/Closings, etc. then .
3.Under Menu 10 - Zone Reporting Codes, select the zone number and program the desired options such as: Zone Alarms, Restores, Bypasses, or Trouble.
Option A: For Zone Alarm program a two digit code. To have the automatic SIA or Contact ID report codes transmitted simply program a nonzero value. I.E. Program a 1 (01).
Option R: For Zone Restore program a two digit code. For automatic SIA or Contact ID codes program a 1 (01). Option B: For Zone Bypass program a two digit code. For automatic SIA or Contact ID codes program a 1 (01). Option T: For Zone Trouble program a two digit code. For automatic SIA or Contact ID codes program a 1 (01).
4.Under Menu 11 - F Key Reporting Codes, select and program the alarm code for each desired Keypad Panic Key. NOTE: Keypad Panics only have Alarm report codes, they do not have restore codes. For automatic SIA or Contact ID codes program a 1 (01).
5.Under Menu 12 - Sys Report Code Options & Codes, select and program each desired option such as: AC Fail, Low Battery, Automatic Test, and other system wide options, including the time values for certain options. For automatic SIA or Contact ID report codes program a 1 (01).
6.Under Menu 13 - User Report Codes, select and and program an Open or Close report code for any User(s) that you wish to track arm/disarm events, including arm/disarm by the Installer Code or Elk-RP computer.
3.6 Entering Installer Level Programming
1.Press the center ‘ELK’ key once followed by the DOWN arrow key until display reads “9-Installation Programming”. NOTE: The keypad may beep and display the following:
2.Enter the Installer Program Code when required.
Press the right arrow key to select the “Installation Programming” option. |
|
|
|
|
|
|
12345678901234567890123456789012123 |
|
|
|
|
123456789012345678901234567890121231234567890123456789012345678901212312345678901234567890123456789012123 |
|
|
|
|
Auth. |
Required |
|
|
|
12345678901234567890123456789012123 |
|
|
|
|
12345678901234567890123456789012123 |
|
|
|
|
Enter |
Valid Pin |
|
|
|
12345678901234567890123456789012123 |
|
|
|
|
12345678901234567890123456789012123 |
|
|
The Factory Default Installer Program Code is: 1 7 2 8 3 9 |
|
12345678901234567890123456789012123 |
|
|
|
|
|
|
|
|
12345678901234567890123456789012123 |
|
||
|
|
|
|
For security against unauthorized programming changes, the installer code should be changed from its factory default setting. This can be done from Menu 07 - Globals System Definitions, Option 42.
Once the Installer Code has been entered, the first programming menu will display and a 4 minute timer will be started. If there is no key-press activity during this time period the control will automatically exit from the programming mode. It is easy to navigate around and between the programming menus and options using the up and down arrow keys. When the correct menu or option is located, press the right arrow key to proceed into that menu.
Refer to the Quick Reference Guide on the following page to locate a particular menu or to see what options appear under each menu. Refer to the individual menus and their option descriptions for details about each of the programmable items.
† Not evaluated by UL
Page 22 |
M1G Installation and Programming |