M1 includes the SIA CP-01 Standards for False Alarm Reduction †
L520 Rev. J 11/11/10Current with Firmware 5.2.x
TM
Introduction
LIMITATION
The ELK-M1G Control is designed to warn against unauthorized entry and other situations. However, it is not a guarantee of protection against
the occurrence of burglary, fire, or other emergency. Any alarm system is subject to compromise or failure to warn for various reasons. For
example:
- Unauthorized access can be gained through unprotected points or by disarming or bypassing protected points.
- Sensing devices are power driven and do not operate without electrical power. Battery-operated devices will not work without batteries, with
dead batteries, or if the batteries are not put in properly. Devices powered solely by AC will not work if their AC power supply is cut off for any
reason, however briefly.
- Telephone lines over which alarm signals are transmitted may be out of service or rendered inoperable by an intruder.
- Even if the system responds to the emergency as intended, occupants may have insufficient time to protect themselves from the emergency
situation. In the case of a monitored alarm system, authorities may not respond appropriately.
- Smoke detectors have limitations and cannot detect all types of fires. According to data published by the Federal Emergency Management
Agency, while smoke detectors have played a key role in reducing residential fire deaths in the United States, they may not activate or provide
early warning for a variety of reasons in as many as 35% of all fires, . Some of the reasons some detectors used in conjunction with this
System may not work are as follows. Smoke detectors may have been improperly installed and positioned. Smoke detectors may not sense
fires that start where smoke cannot reach the detectors, such as in chimneys, in walls, or roofs, or on the other side of closed doors. Smoke
detectors also may not sense a fire on another level of a residence or building. A second floor detector, for example, may not sense a first floor
or basement fire. Finally, smoke detectors have sensing limitations. No smoke detector can sense every kind of fire every time. In general,
detectors may not always warn about fires caused by carelessness and safety hazards like smoking in bed, violent explosions, escaping gas,
improper storage of flammable materials, overloaded electrical circuits, children playing with matches, or arson. Depending an the nature of the
fire, and/or location of the smoke detectors, the detector, even if it operates as anticipated, may not provide sufficient warning to allow all
occupants to escape in time to prevent injury or death..
- Signals sent by wireless transmitters may be blocked or reflected by metal before they reach the alarm receiver. Even if the signal path
has been recently checked during a weekly test, blockage can occur if a metal object is moved into the path.
- Wireless transmitters (used in some systems) are designed to provide long battery life under normal operating conditions. Longevity of
batteries may be as much as 4 to 7 years, depending on the environment, usage, and the specific wireless device being used. External
factors such as humidity, high or low temperatures, as well as large swings in temperature, may all reduce the actual battery life in a given
installation. This wireless system, however, can identify a true low battery situation, thus allowing time to arrange a change of battery to
maintain protection for that given point within the system.
- Installing an alarm system may make the owner eligible for a lower insurance rate, but an alarm system is not a substitute for insurance.
Homeowner, property owners and renters should continue to act prudently in protecting themselves and continue to insure their lives and
property.
- A user may not be able to reach a panic or emergency button quickly enough.
- Passive Infrared Motion Detectors can only detect intrusion within the designed ranges as diagrammed in their installation manual. Passive
Infrared Detectors do not provide volumetric area protection. They do create multiple beams of protection, and intrusion can only be detected
in unobstructed areas covered by those beams. They cannot detect motion or intrusion that takes place behind walls, ceilings, floors, closed
doors, glass partitions, glass doors, or windows. Mechanical tampering, masking, painting or spraying of any material on the mirrors, windows
or any part of the optical system can reduce their detection ability. Passive Infrared Detectors sense changes in temperature; however, as the
ambient temperature of the protected area approaches the temperature range of 90 to 105F (32 to 40C), the detection performance can
decrease.
- Alarm warning devices such as sirens, bells or horns may not alert people or wake up sleepers if they are located on the other side of
closed or partly open doors. If warning devices are located on a different level of the residence from the bedrooms, they are less likely to
waken or alert people inside the bedrooms. Even persons who are awake may not hear the warning if the alarm is muffled by noise from a
stereo, radio, air conditioner or other appliance, or by passing traffic. Finally, alarm warning devices, however loud, may not warn hearingimpaired people.
- This equipment, like other electrical devices, is subject to component failure. Even though this equipment is designed to last as long as 20
years, the electronic components could fail at any time.
- The most common cause of an alarm system not functioning when an intrusion or fire occurs is inadequate maintenance. This alarm
system should be tested weekly to make sure all sensors and transmitters are working properly.
ALL RIGHTS RESERVED
No part of this publication may be reproduced, stored in a retrieval system, or transmitted in any form or by any means, electronic, mechanical,
photocopying, recording, or otherwise without the prior written permission of the manufacturer. The material in this publication is for information
purposes and subject to change without notice. The manufacturer assumes no responsibility for any errors which may appear in this publication.
Printed in U.S.A.
Use of this control for fire detection and/or annunciation may not be permitted by certain states, counties, municipalities or local jurisdiction. It is
the responsibility of the installing alarm company to check with the local A.H.J. (Authority Having Jurisdiction) or State Fire Marshal’s office prior
to using this control for fire detection.
Page 2
M1G Installation and Programming
Table of Contents
Specifications, Features, and Benefits ..................................................................................................... 5
Section 1 - Installation and Wiring ............................................................................................................. 8
1.1 Planning the Installation ...................................................................................................................... 8
1.2 Parts Diagram & Descriptions ........................................................................................................... 8
1.3 Mounting and Wiring Preparation ....................................................................................................... 8
1.4 Control Wiring .................................................................................................................................... 9
Data Bus E.O.L. Termination - VERY IMPORTANT! .............................................................................. 12
Section 2 - Operating the System ............................................................................................................ 14
3.2 Local Keypad Programming ............................................................................................................. 21
3.3 Local or Remote Computer Programming (ELK-RP) and Anti-Takeover ......................................... 21
3.4 Area Partitioning ................................................................................................................................ 21
4.2 Update/Verify Firmware in the Control and Peripherals ................................................................... 50
4.3 Automation Rules and Attributes ...................................................................................................... 51
Appendix A - Event Codes ........................................................................................................................ 58
Appendix B - Telephone Remote Control ............................................................................................... 60
Appendix C - Voice Message Vocabulary *RP only * ............................................................................. 62
Appendix D - Two Way “Listen-in/Talk” Interface ................................................................................... 64
Appendix E - SIA CP-01 Compliance ........................................................................................................ 65
Appendix F - Regulatory Agency Statements .......................................................................................... 66
Appendix G - Additional ELK-M1KP Keypad Information ...................................................................... 69
Index ............................................................................................................................. 71
M1G Installation and Programming
Page 3
2200
Ohm
EOL
2200
Ohm
EOL
2200
Ohm
EOL
2200
Ohm
EOL
2200
Ohm
EOL
2200
Ohm
EOL
2200
Ohm
EOL
2200
Ohm
EOL
2200
Ohm
EOL
2200
Ohm
EOL
2200
Ohm
EOL
2200
Ohm
EOL
2200
Ohm
EOL
2200
Ohm
EOL
2200
Ohm
EOL
2200
Ohm
EOL
1.1 Amp PTC protected
UL Listed Transformer,
Class 2, 16.5VAC, 45VA
Bat Leads
ZONE
N.C.
1
ZONE
N.C.
2
ZONE
N.C.
3
ZONE
N.C.
4
ZONE
N.C.
5
ZONE
N.C.
6
ZONE
N.C.
7
ZONE
N.C.
8
ZONE
N.C.
9
ZONE
N.C.
10
ZONE
N.C.
11
ZONE
N.C.
12
ZONE
N.C.
13
ZONE
N.C.
14
ZONE
N.C.
15
ZONE
N.C.
16
ZONE 16
NORMAL
TELCO SEIZED
DIALER ACTIVE
+SAUX
+12VDC Switched
Smoke Power
See Note 1.
+VAUX
+12VDC Auxiliary
Power (3)
1.25 Amp PTC
protected
Do not connect to a
switched outlet.
ELK-TRG1640
Power
ON
Status
Reverse
Jumper to start with
no AC - See Note 4.
SW1
N.O.
N.O.
N.O.
N.O.
N.O.
N.O.
N.O.
N.O.
N.O.
N.O.
N.O.
N.O.
N.O.
N.O.
N.O.
N.O.
JP1
BATTERY
12V Battery
7 to 18 Ah
Z1
NEG
Z2
Z3
NEG
Z4
Z5
NEG
Z6
Z7
NEG
Z8
Z9
NEG
Z10
Z11
NEG
Z12
Z13
NEG
Z14
Z15
NEG
Z16
2WIRE
SMOKE
+SAUX
NEG
+VAUX
NEG
+VAUX
NEG
+VAUX
NEG
AC
16.5 V
AC
-
+
ELK-M1
Cross Platform Control
16 Zones expandable to 208
Control specifications subject to change without
notice. All circuits are power limited except for
Battery leads.
4-Wire Smoke Detector - Any Zone
N.O. Alarm
Contacts
2200
Ohm
EOL
U.L. Listed EOL Supervision Relay, ESL #204A
or equiv. Use 2,200 Ohm EOL resistor, part #
ELK-ER2200. Set JP1 to 'Normal'.
2-Wire Smoke Detector - Zone 16 ONLY
820
Ohm
EOL
To configure Zone 16 as a 2-wire smoke zone,
set Jumper JP1 to '2WIRE SMOKE' and use 820
Ohm EOL resistor, part # ELK-ER820
Use Only Compatible Detectors
Control Compatibility Identifier: M10001
Refer to the Wiring & Hookup Diagram in the
Installation Manual # L520 Rev. J for the 2-Wire
Smoke Detector Compatibility chart.
1. Refer to Appendix F located in the Installation
Manual #L520 Rev. J for UL limitations on total
continuous 'standby' current drain from terminals
+SAUX, +VAUX, +VKP, and J16.
2. OUT 1 †† for speaker(s) ONLY (4 to 8 Ohms).
If connecting more than 2, use series/parallel
wiring to avoid going below a 4 ohm total load.
OUT 2 Connect ONLY 1 UL Listed Bell or
Siren (self-contained). Current limited to 1 Amp.
Program Global Option 26 to Voltage. Thisoutput supervised. Speaker(s) only permitted
for non-UL installations. Series/parallel wire to
avoid dropping below a 4 ohm total load.
OUT 3 NO/NC dry contact relay rated 4A.
OUT 7 through 16 are +12V switched positive
voltage outputs rated at 50mA max.
3. This terminal (formerly earth gnd) not used.
Do not connect any neg terminals to ground.
4. If AC fails, control will shut down if battery
drops below 10.2 Volts. To start the control with a
good battery and no AC, short the silver pads
momentarily. Replace Battery every 3-5 years.
Test regularly with ELK-BLT Battery Life Tester.
†† Not for use in UL Listed Systems
Complies with FCC Part 68:
Reg. # US: 5K6AL03BELK-M1 REN: 0.3B
Use Standard Jack: USOC RJ-31X.
Serial Number located below on base.
Complies with part 15 of FCC rules.
This Class B digital apparatus complies with
Canadian ICES-003
HA008E
+
-
-
Notes
† Not Evaluated by UL
TEST SYSTEM WEEKLY
ELK
HILDEBRAN, N.C., 28637, USA
PRODUCTS, INC.
+
-
+
To Zone Input
To Zone NEG
TM
StripStrip Wire s to 1/4" Lengt h
+SAUX
NEG
NEG
Z16
Grey
R1
Brown
T1
RING
TIP
J3
1
JP2
J5
Data Bus Term inating Resistor
+VKP
DATA A
DATA B
NEG
Red
Green
Aux Data Bus ††
B
A
for wireless receiver
-
i.e. GE-Caddx
C
+
NX408E, NX416E,
or NX448E
See Manual
Select PLC Mode
1 WAY
(PL513/PSC04)
(TW523/PSC 05)
2 WAY
for Computer/ELKRP
PLC ††
Lighting
Interface
Conn.
OUT 2
OUT 1OUT 3
Audio Network Interface ††
Do Not
Connect to
a Phone
Line!
J-16 Programmable Outputs
See Note 1
1
OUT3 On LED
N/C
COM
N/O
+
Bell (Supervised)
-
See Note 2
+
Voice/Siren † †
-
See Note 2
O - I - B A +
RED
GREEN
WHITE
BLACK
Not Used -See Note 3
Keypad &
Data Bus
HOUSE
PHONES
TELCO
LINE
J4
Serial Port ††
See Manual
PSC05 ††
or
Equivalent
+12V
& Note 2
NEG
OUT 16
OUT 15
OUT 14
OUT 13
OUT 12
OUT 11
OUT 10
OUT 9
OUT 8
OUT 7
Dry Contact Relay
rated 4A @
12 - 24VDC
See Note 2
1
J7
JP3
1.25 Amp PTC
protected
Keypad
Data Bus
See Note 1
J2 J1
NEG
DATA B
DATA A
+12V
RS232 CONN.
Page 4
M1G Installation and Programming
Specifications, Features, and Benefits
General:
• Large zone capacity: 16 on-board zones expandable to 208
• Wireless capability † Up to 144 zones
• Two Way Listen-in interface †
• Flash Memory - Allows field updates to firmware electronically
• RS-232 serial port to interface PCs and peripheral devices
• Time/Date stamped 512 event history log
• Menu driven, text keypad programming - no manual required!
• Voice announcement of alarms, zone descs, status, etc.
- 500+ Word/Phrase Vocabulary
- Link up to 6 words/phrases per announcement
- 10 custom recordable words/phrases
• 13 On-Board Outputs: 1 voice driver/siren, 1 siren driver/
voltage, 1 form “C” Relay, and 10 low current (50 mA) voltage
outputs
• Elk-RP PC programming software with conflict resolution to
easily highlight differences between control and PC
- Dial-up, ethernet, RS-232 port, or local house phone jack
- Automatic answering machine bypass
Keypad
• Backlit, Large Character LCD Display, 16 x 2 lines
• Built-in Temperature Sensor
• Optional Plug-in Prox Access reader (26 bit Weigand format)
• Menu navigation keys and 6 programmable function keys
• Plug-in connector, only 4 wires to the control
• 1 Zone input and 1 Output Programmable per Keypad
• Programmable display of time, date, & temperature
• Displays system diagnostics and settings.
• Maximum Keypads allowed: 16
Automation & Integration
• Create lifestyle enhancing comfort, convenience, and security
• Powerful “Whenever/And/Then” RULES Programming allows
almost any imaginable operation. No need to chain rules
together. Any single “Whenever” event can have one or more
ANDs and THENs (conditions and commands).
• Rules utilize easy to understand text based references
• Control lighting using RS-232 serial or 2-way Power Line
Control (PLC) Commands include On, Off, Dim, All On, All Off †
• Transmit and receive custom serial ASCII strings
• Read Temperature Sensors - Communicate with Thermostats
• Turn on Tasks, Lights, Outputs via Keypad or Telephone
• Sunset/Sunrise calculation and activation built-in
Power Supply
• Heavy duty - 2.5 Amp power supply
• Dynamic battery test
• Master power switch and Low battery disconnect
• PTC (fuseless) resettable overload protection
• Multiple auxiliary power terminals
Part Numbers and Accessories:
ELK-M1GCBM1G Gold Board Only (No Teminals Blocks)
ELK-M1GOLDM1G Gold - Control in 14” metal can
ELK-M1GKM1G Gold Kit - No Metal Can, for use with
structured wiring systems
ELK-M1SYS4M1G Gold Kit - 14” metal can, Ctrl, Encl, Xfmr,
KP, 12V-8Ah, Spkr, RJset
ELK-M1KPKeypad, LCD,16 character x 2 line
ELK-M1KP2Small LCD Keypad, 16 character x 2 line †
(no internal temp sensor and 2 less “F” keys)
ELK-M1KPASKeypad Arming Station †
ELK-M1XIN16 Zone (input) expander
ELK-M1XOVR16 Output expander, 8 Voltage/8 Relays
ELK-M1RBRelay board, 8 form ”C” relays
ELK-M1DBHData bus wiring hub “Passive” †
ELK-M1DBHRData bus wiring hub “Active” for Retrofit †
ELK-M1XEPEthernet Port Exp/Interface †
ELK-M1XRF2GWireless Receiver for GE Crystal Xmtrs †
ELK-M1XRF2HWireless Receiver for Honeywell 5800 Xmtrs †
ELK-M1XSPLighting, Thermostat Interface & Serial exp. †
ELK-M1PRMini prox reader for keypad †
ELK-M1TWITwo Way Listen-in Int. w/3 mic inputs †
ELK-M1TWSSpeaker & Mic for Two Way Listen-in †
ELK-M1ZTSZone Temperature Sensor -50 to 140 F †
ELK-RPPC software - Free upon request with
Control Panel purchase
ELK-RMRemote “User” Management software
NOTE: Use of Two Way Listen-in may be regulated by local or state laws and/or ordinance. It is the responsibility of the
Installer to check before using this feature.
† Not evaluated by UL†† Not for use in UL Listed Systems
M1G Installation and Programming
Page 5
Wiring & Hookup Diagram
This unit provides Residential fire alarm service when installed according to ANSI/NFPA 72. Transmission
of the fire alarm signal to a fire alarm headquarters or central station shall be permitted only with the
approval of the authority having jurisdiction. The burglar alarm signal shall not be transmitted to a police
emergency number, equipment is to be installed in accordance with NFPA (985,55.1.P).
Recommended locations and wiring methods shall be in accordance with CSA C22.1, Canadian Electrical
Code, Part I, Safety Standard for Electrical Installations; CAN/ULC-S302, Installation and Classification of
Burglar Alarm Systems for Financial and Commercial Premises, Safes and Vaults; and CAN/ULC-S301,
Standard for Central and Monitoring Station Burglar Alarm Systems.
Reference NFPA70 (NEC) & Canadian Electrical Code.
All circuits are current limited except for Battery leads. Refer to Appendix F.
For Installation of Residential Fire Warning Systems reference CAN/ULC-S540 Standard.
Testing of this system should be performed regularly with the primary AC power de-energized. Control
panel specifications are subject to change without notice.
Lithium 3V "Clock" battery, Varta #CR2032 located in upper left corner behind cover. Battery has a life
expectancy of approx. 10 years. Replace ONLY with exact model available at most electronics and camera
retailers. "CAUTION: Lithium Battery May Explode If Mistreated. Do Not Recharge, Disassemble, or
Dispose Of In Fire."
(Left Side Terminals)
2200
N.C.
Ohm
EOL
2200
N.C.
Ohm
EOL
2200
N.C.
Ohm
EOL
2200
N.C.
Ohm
EOL
2200
N.C.
Ohm
EOL
2200
N.C.
Ohm
EOL
2200
N.C.
Ohm
EOL
2200
N.C.
Ohm
EOL
NOTE: M1ZTS Temperature Sensors may only be connected to the first 16 zones.
2200
N.C.
Ohm
Color Code for 2200
Ohm EOL Resistor
Part # ELK-ER2200
Red (2)
Red (2)
Red (2 x 0)
Gold (quality)
Color Code for 820
Ohm EOL Resistor
Part # ELK-ER820
Gray (8)
Red (2)
Brown (1 x 0)
Gold (quality)
2-Wire Smoke Detector Compatibility
Name
System Sensor
Sentrol (GE)
To configure Zone 16 as a 2-wire smoke zone, set Jumper JP1 to "2 WIRE SMOKE" and use 820
Ohm EOL resistor, part # ELK-ER820.
Compatibility Identifier: M10001
Maximum Operating Voltage: 13.8 VDC
Max. wire resistance should not exceed 13 Ohms.
Use 18AWG Fire approved wire. Max. wire length = 1000 feet.
Do not mix different models on same circuit as proper operation
may be impaired.
Smoke Detector covers should be kept free
from dust and dirt by use of a dry or damp
(water) cloth as needed. When necessary,
clean the detector interior and/or replace the
optical chamber according to instructions
provided by the Smoke Detector Manufacturer.
Auxiliary +12VDC Power Outputs protected by 1.25A PTC NOTE:
Refer to Appendix F for the UL limitations on total continuous 'standby'
current drain from terminals +SAUX, +VAUX, +VKP, and J16.
16.5VAC, 45VA UL Listed Class 2 Transformer - ELK-TRG1640
DO NOT CONNECT TO A SWITCHED OUTLET
For Canada use cUL Listed Transformer - ATC Frost # FPS-4016
LEDS
Indicators
TELCO
SEIZED
DIALER
ACTIVE
Power
Status
Battery
Reversed
Normal
State
OFF
OFF
ON
Regular 1
sec. Blink
OFF
Descriptions
Phone line is good and house phones are connected. If ON constantly, the phone
line may be bad. During remote mode this LED will be ON since the house phones
are then disconnected from the outside line & are being powered from control.
Dialer/Modem is idle. If ON, Dialer/Modem is in use (communicating).
AC Voltage is present and power switch is turned ON. If OFF, check AC power.
1 blink with equal On and Off times is Normal. 2 fast blinks = Control running on
bootloader only. 4 fast blinks = Control is re-initializing it's EEPROM memory after
a firmware flash. 5 fast blinks = Memory/Operation overflow
Battery is connected correctly. If ON, check battery lead connections.
Control needs AC power to start. Momentarily shorting these two pads allows control to startup on battery only.
Master Power Switch (SW1), disconnects AC and Battery power from control.
Replace Battery every 3-5 years. Use ELK model # ELK1280 (12V - 8 Ah) or ELK12180 (12V - 18 Ah) or equivalent.
ZONE
1
ZONE
2
ZONE
3
ZONE
4
ZONE
5
ZONE
6
ZONE
7
ZONE
8
ZONE
9
ZONE
10
ZONE
11
ZONE
12
ZONE
13
ZONE
14
ZONE
15
ZONE
16
18AWG Min.
N.O.
N.O.
N.O.
N.O.
N.O.
N.O.
N.O.
N.O.
N.O.
N.O.
N.O.
N.O.
N.O.
N.O.
N.O.
N.O.
Z1
NEG
Z2
Z3
NEG
Z4
Z5
NEG
Z6
Z7
NEG
Z8
Z9
NEG
Z10
Z11
NEG
Z12
Z13
NEG
Z14
Z15
NEG
Z16
ZONE 16
NORMAL
TELCO SEIZED
DIALER ACTIVE
+SAUX
NEG
+VAUX
NEG
+VAUX
NEG
+VAUX
NEG
AC
16.5 V
AC
POWER
STATUS
REVERSE
BAT LEADS
JUMPER TO START
WITH NO AC
JP1
SW1
Lead Acid
2WIRE
SMOKE
BATTERY
12 Volt
Sealed
-
+
Page 6
M1G Installation and Programming
R1
T1
RING
TIP
J3J4
B
A
-
NEG
C
+12V
+
PLC
JP2
Mode
1 WAY
2 WAY
Lighting ††
Interface Conn.
J5
J16
+12V (+VAUX)
NEG
16
15
14
13
12
11
10
9
OUTPUTS
8
7
OUT3OUT2
OUT1
J7
AUDIO NETW ORK INTERFACE
RS-485 DATA BUS
+VKP
DATA A
DATA B
NEG
Not Used
J1J2
NEG -
DATA B
DATA A
DATA BUS
JP3
Terminating Jumper (JP3): See
important informat ion about Data
Bus Termination.
+12V
OUT3 LED
N/CCOMN/O
+
-
+
-
RJ31X JACK (ELK-RJSET)
Grey
Brown
Red
Green
Aux Data Bus (J3) ††
For wireless receiver. Presently
works with ITI / Caddx NX408E,
NX416E, or NX448E. See
Programming Menu 14.
Serial Port (J4) ††
for Comput er/ELKRP
RS232
(This connection not
evaluated by UL)
JP2
1 WAY (PL513/PSC04)
2 WAY (TW523/PSC05)
PSC05 or
equiv.
+VAUX
NEG
OUT 16
OUT 15
OUT 14
OUT 13
OUT 12
OUT 11
OUT 10
OUT 9
OUT 8
OUT 7
N/C
COM
N/O
+
Bell (Supervised)
-
+
Voice/Siren †
-
Audio Network Connection (J7) ††
For Two-Way Listen-in and Future Use!
RS-485 Data BusMax. length is 4000 ft. Total
length of 2 homeruns must not exceed that distance.
RED
GREEN
WHITE
BLACK
A UL Listed Supplementary Power Supply may be required to meet t he minimum standby
power supply requirements. Refer to the Chapter containing Regulatory Agency Statements.
R1
1
8
T1
Lighting Interface Conn. (J5) ††
Use Std. 4 conductor modular telephone
cable to connect to a powerline Interface
(PSC05, X-10 PLC or equiv.).
Do not connect to a live phone line!
(This connection not evaluated by UL)
+12V
NEG
Out 3 - Programmable General Purpose Relay
Rated at 4Amps @ 12 - 24VDC
(Dry Contacts)
Out 2 - Connect ONLY 1 UL Listed Bell or Siren (self-contained). For residential Fire the indicating
device shall be W heelock 34T-12 or equiv. Current limited to 1 Amp. Program Global Option 26 to Voltage.
Speaker(s) are only permitted for non-UL installations and they must be series/parallel wired to avoid
dropping below a 4 ohm total load.
Out 1 - Voice/Siren ††
Speaker output only (Interior)
ELK-SP35 or equiv.
Min. wire gauge: 24 AWG
18 to 22 AWG is best for
R
4
5
T
Select PLC Mode (JP2)
Selects single or bi-directional
PLC Transmissions
long distances.
Demark
Black
Yello w
Green
Red
Use 26AWG telco wire
PC
Red
Black
White
Green
Brown
Blue
Orange
Yello w
Viole t
Grey
Pink
Tan
splices
Tip
Ring
* See Auxiliary Current ratings
TELCO
Personal Computer
(Windows Based)
Programmable Outputs (J16)
OUT 7 - 16 are +12V switched
positive general purpose
outputs rated at 50mA.
DATA BUS TERMINATION IS VERY IMPO RTANT!!
Diagram shows 2 basic (4-wire) home run cables with daisy chained devices on eac h. Last device on each cable
MUST have a Terminating J umper installed. Jumpers are marked JP2 on keypads, JP1 on Expan ders. Control
Hardware pack has two black jumpers for this purpose. Jumpers engage a 120 Ohm resistor across data A & B lines.
NOTE: If there is only 1 data bus cable, install JP3 Jumper on the Control.
WARNING! The RS485 Data Bus must NEVER have more that two (2) terminating jumpers installed.
NOTE: If you want to home run more than 2 cables, run 6 or 8 conductor cable so that the data lines A & B can have a
return path to series connect back out to the next device. This is best done with a ELK-M1DBH Data Bus Hub which
accepts Cat5 or Cat6 cable with RJ45 plugs. For more information see diagram in keypad instructions.
This term inal (formerly earth gr ound) is no longer used. Do not connect this or any neg. terminals to earth ground.
Temporary Connection "Plug-in" jacks for RS-485 Data Bus (J1 & J2)
Local connection for Data Bus Devices ie: Keypads, etc. for testing purposes only.
† Not evaluated by UL†† Not for use in UL Listed Systems
(Right Side Terminals)
HOUSE
PHONES
LINE
Compiles with FCC Part 68
Reg. Number: US:5K6AL03BELK-M1
Ringer Equivalence REN: 0.3B
Use USOC RJ-31X connector.
Complies with the limits for class B computer
devices in accordance with the specifications of
subpart J of part 15 of FCC rules.
11
Pinout for Serial Port Cable (9 pin male to 9 pin female)
Yellow
Green
Red
Black
Close up view of st d. 4 conductor modular phone cord. When
viewed as shown (back to back), the pin to pin color coding
does not reverse. Cord for PLC must be similar to above.
Out 2 is supervised. If not used, install a 2.2K Ohm
resistor to avoid Output 2 trouble condition.
NOTE: Do Not place a Direct Short Across OUTPUT 2.
Data Bus Devices e.g. Keypads, Expanders
DO NOT Jumper
Terminate these dev ices.
Pin 2 < to > 2
Pin 3 < to > 3
Pin 5 < to > 5
Maximum recommended length = 50 ft.
Yellow
Green
Relay Expansion Module (ELK-M1RB )
Optional module adds 8 general purpose
relays. Plugs into J16 connector.
Red
Black
End
view
Jumper
Terminate
these two
devices.
M1G Installation and Programming
Page 7
Section 1 - Installation and Wiring
1.1 Planning the Installation
The first step in any multi-zone security system installation is planning the job.
1.Read this entire manual to familiarize yourself with all system features and procedures before actually beginning the
installation. Read all the information regarding Underwriters Laboratories (UL) and NFPA requirements.
2.Perform a physical survey of the installation site. Use the diagrams below as a guide in planning the installation.
3.Discuss the installation requirements and applications with the customer.
4.Compare the installation requirements and applications with the factory default settings to determine what customized
programming is needed to meet the specific installation requirements.
5.Bench test the system prior to installation.
TYPICAL BURGLARY INSTALLATION LAYOUT
TYPICAL FIRE INSTALLATION LAYOUT
Bedroom 1Bedroom 2
Living Room
K
Kitchen / Dining
CCCC
C
Legend
M
- Main Control
A
- Audible Alarm
- Smoke Detector
S
- Contact
C
- Keypad
K
M
A
Bedroom 3
C
All perimeter o penings below 18 " should be provi ded with protection.
A Smoke Detec tor shall be located in each slee ping area and be tween
the sleeping areas and the main living area.
Early warning fire detection is best achieved by the installation of fire
detection e quipment in the location shown above.
In homes basements or multiple levels at least one smoke detector
shall be on each level.
1.2 Parts Diagram & Descriptions
See Wiring & Hookup Diagram on pages 6 & 7.
1.3 Mounting and Wiring Preparation
SS
Bedroom 1Bedroom 2
S
Bedroom 3
M
A
S
Living Room
K
First Floor
Basement
Kitchen / Dining
Control Mounting
DO NOT MOUNT THE CONTROL OUTDOORS OR IN A DAMP LOCATION OR WHERE THE ENVIRONMENTAL CONDITIONS
ARE UNSUITABLE FOR ELECTRONIC BASED EQUIPMENT. DO NOT MOUNT IN AN UNCONDITIONED ATTIC. USE
COMMON SENSE AND GOOD INSTALLATION PRACTICES. A suitable location would be inside a secure dry location where
the ambient temperature inside the control box can remain at 32‘ to 120
°
Fahrenheit (0’ to +49' Celsius). Choose a location
that allows easy wiring to an unswitched power outlet and to a grounding conductor for the control. A central location makes
running system wiring easier. Remove control box knockouts that best suit your wiring needs.
After removing all packing materials, compare the system components with those in the figure above to familiarize yourself
with the part names. Mount the control using the upper center slotted hole to level. Install and connect all necessary wiring for
the power transformer, detection loops, keypads and siren outputs.
Keypad Mounting and Wiring
Ideal height is 50-58 inches. Pick a location with an ambient temperature range between 32° and 120° F (0° to +49° C). Avoid
direct sunlight if possible. Fasten backplate to electrical box or wall with flat head screws to prevent shorts to the back of the
circuit board. Keypads have an unpluggable harness for connecting to the M1data bus. Splice the Black, Red, White, and
Green wires from the unpluggable harness to the M1 Data Bus field cabling. Plug the connector into the back of the keypad.
Tuck wires neatly into back plate and install Keypad on mounting plate. The LCD keypads have connections for an optional
programmable output and a programmable zone input. NOTE: Min. field wire gauge is 24 AWG, but 18 to 22 AWG is better for
long distances. CAT5 (8 conductor) cable can be purchased in various wire gauge sizes. Where possible always use the
larger gauge CAT5 cable. The extra conductors in CAT5 wires can be used to provide return path for the data A & B lines.
Page 8
M1G Installation and Programming
Hookup Diagram for Keypad
Splice 6 Pin Keypad Wiring Assembly to the Data Bus cable using ELK-900-2 "B" Connectors.
NOTE: Early production M1KP Keypads provided a switched
negative (pull to ground) output. These units have the letter "E"
at the end of the ID number on the lower back side of the board.
Connect per diagram above. Boards marked PC096 with a letter
"F" or later provide the output as a switched positive.
+
Load (50mA max)
i.e. Relay, LED
-
Keypad
BLACK
WHIT E
GREEN
RED
BLUE
BROWN
To BLACK (Neg ) Wi re
Optional programmable Output from Keypad
To BLUE Wire
To BLACK (Neg) Wire
Optional programmable Zone Input from Keypad
Wiring
Assembly
1
6
To BROWN Wire
ELK-M1KP
Keypad 1
+
Load (50mA max)
-
I.E. LED, Relay
N.O.
N.C.
2200
Ohm
EOL
NOTE: Refer to the section ‘Data Bus E.O.L. Termination’ for information on multiple homerun cables. NEVER SPLICE OR
CONNECT WIRE WITH CONTROL POWER ON. Minimum cabling should be four conductor 22 or 24 gauge. Maximum resistance per wire
is 25 Ohms. Device placement beyond 1000' is not recommended.
1.4 Control Wiring
Zone Inputs (1 thru 16 on main board, 17 thru 208 via expanders)
Zones are arranged in groups of 16, starting with Z1 thru Z16 on the main board. Each 2 zones share a common negative
terminal. A zone may be programming for EOL resistor supervision (Default), or normally closed/normally open without a
resistor. In addition, Burglar and Keyswitch zones may be programmed for EOL with Security Alert on Short, or EOL with
Security Alert on Open/Short, also referred to as a Four (4) State Zone (firmware 4.3.5 or later). If EOL resistors are used, they
should be placed at the furthest most remote end of the detection device wiring. EOL zones permit a combination of N.C.
(normally closed) or N.O. (normally open) devices. Using voltage meter probes across the zone and com terminals, a non-
violated EOL zone will measures approx. 7.0 VDC. An open circuit will be approx. 13.8 VDC. A shorted circuit will be 0
VDC. The Keypad also provides the ability “Menu 8 “System Diagnostics” to view zone voltage.
Traditional Three (3) State Zone Wiring (1 series resistor)
A to D
Value
0 - 72
73 - 170
171 - 255
Zone Input
Neg.
Condition When:
Armed
Alarm
-
Alarm
Disarmed
Not Ready
Ready
Not Ready
N.C. Ta mper
Contacts
N.C. A larm
Contacts
Powered Motion, PIR, Glassbreak, etc.
2200
Ohm
EOL
Resistance
Short ~
2.2k Ohms
Open ~
Zone
N.C.
Alarm
Contact
N.O.
Contact
Alarm Contact
Diagostic Table
Approx. Range
of Zone Voltage
0 - 3.9 Volts
4.0 - 8.8 Volts
8.9 - 13.8 Volts
Optional Four (4) State Zone Wiring (2 series resistors w/ N.C. contacts)
Tamper Contac t
2200
Ohm
EOL
Zone
Resistance
Short ~
2.2k Ohms
4.4k Ohms
Open ~
N.C.
N.C.
Alarm
Contact
2200 Ohm
Resistor
Diagnostic Table
Approx. Zone
Voltage Reading
0 - 3.9 Volts
4.0 - 7.3 Volts
7.4 - 11 Volts
11.1 - 13.8 Volts
N.O.
Contact
Zone Input
Neg.
Fig 1: N.C. Alarm Contact
(Unpowered) with N.C. Tamper
Condition W hen:
A to D
Value
0 - 72
73 - 159
160 - 220
221 - 255
Armed
Alarm
Alarm
Alarm
Sec. Alert/Tamper
Sec. Alert/Tamper
This feature
requires Firmware
2.3.5 or later.
Disarmed
Ready
Not Ready
N.C. Tamper
Contacts
N.C. Alarm
Contacts
Fig 2: Powered PIR, Glassbreak, etc. with Tamper
Wire in Series with zone
input or use another zone.
Zone
2200 Ohm
EOL Resi stor
Input
Neg.
Pos.
Neg.
Program Zone for EOL Wiring
Type 4 - Supervisory on Open
Zone
Input
2200 Ohm
EOL Resi stor
2200 Ohm
Resistor
Neg.
Pos.
Neg.
M1G Installation and Programming
Page 9
Two-Wire Smoke Zones (Zone 16)
To enable use of two-wire smoke detectors on Zone 16, position Jumper JP1 (located below Zone 16 terminals) so that the
two right hand pins are covered. Go to Installer programming mode, Menu 05 - Zone Definitions, and program Zone 16 as a
Fire zone (Def=10). Step to next location and program Wire Type=6. NOTE Use only compatible two-wire detectors listed on
the front label of the control. Do not mix brands. The maximum number of detectors is also listed on the front label. For
two-wire operation, a 820 Ohm EOL resistor part # ER820 must be used instead of the 2,200 Ohm resistor part # ER2200.
Use 18AWG Fire approved wire. Max. wire length = 1000 feet. Max. wire resistance should not exceed 13 Ohms.
Switched Power Connection (+SAUX)
Four-wire smoke detector and other devices that require a temporary power disruption in order to reset or unlatch from the
alarm state (i.e. smoke detectors, etc.) should be connected to the +SAUX 12 Volt DC switched power terminal. When a
smoke reset is performed, the operating voltage to these devices is momentarily interrupted.
Auxiliary Power Connections (+VAUX)
Motion detectors, glass breaks, etc. and other devices requiring unswitched 24-hour power should be connected to one of the
auxiliary terminals, +VAUX. All negative terminals on the terminal strip are at the same reference and may be used whenever
a common (circuit ground) negative is required. Use caution when wiring the control to distribute the load devices among the
supply and the negative terminals evenly. NOTE: Circuit ground refers to any negative terminal connection on this control.
This does not refer to the earth ground terminal or to the common terminals of Relay Output 3. These terminals are not at
the same voltage potential and should not be wired so that they are electrically connected to a negative.
PTC (Positive Temperature Coefficient) Circuit Breakers
The +VAUX Auxiliary power and J16 power output terminals are protected against shorts and overloads by a 1.25A PTC. A PTC
is a solid state, auto-restoring type of circuit breaker. The +SAUX Switched (Smoke) power output is protected by a 1.1A PTC.
The +VKP Keypad power output is protected by a 1.25A PTC. Output 2 is protected by a 1.25A PTC. NOTE: Sometimes it may
be necessary to remove power (unplug the outputs) for approx. 20 seconds after a short, to allow the PTC to reset. Even
if the short is no longer present, the remaining residual current draw may be so high that the PTC cannot determine that
the short is gone. If the PTC re-trips, check the field wiring and repair.
Transformer Primary Power Input (AC)
The control is powered by a 16.5 VAC, 40 min. VA, UL Listed Class 2 transformer (ELK-TRG1640). The specified sized and
rated transformer must be used to operate this control. The transformer must be connected to a 120 VAC, 24-hour outlet not
controlled by a switch other than an approved overcurrent protection device.
UL Listed Transformer,
Class 2, 16.5VAC, 45VA
E
L
K
-
T
R
G
1
6
4
0
+VAUX
NEG
AC
16.5 V
AC
POWER
STATUS
REVERSE
BAT LEADS
JUMPER TO START
WITH NO AC
+
-
SW1
BATTERY
RED BLK
12V Battery
5 to 18Ah
Sealed Lead Acid
+
-
Connect the transformer to the AC Terminals using 16 to 18 gauge minimun wire. Do not exceed 50 feet between the
transformer and the control or run the AC power in a multiconductor with other system circuits. Leave the transformer
unplugged as well as the standby battery until all other connections have been made.
Standby Battery Connection
Connect the BLACK wire to the Neg (-) terminal on the battery, the connect the RED wire to the Pos (+) terminal on the battery.
The control is designed to operate with and recharge a 12 volt, sealed lead acid battery from 7Ah up to 18 Ah for backup of the
primary power supply. The control maintains a float charge for the battery of 13.8 VDC at 100 mA. This is in addition to the
continuous output of 1.5 Amps that the power supply maintains (see maximum current drains for UL Listed Systems).
CAUTION: Do not reverse the battery leads! The control has special circuitry which helps protect it from battery reversal
damage for short durations. However, prolonged reversal of the battery leads may cause permanent damage. A reverse
battery warning LED is located to the left of the power On/Off switch. If this light is ON, turn the power off immediately
and correct the battery lead connections.
Page 10
M1G Installation and Programming
AC Failure, Low Battery, and Automatic Low Voltage Shutdown
During an AC power failure the battery automatically takes over and AC Fail trouble annunciates at the keypad. The
communicator can be programmed to report AC Fail to the Central Station after a time delay (see Menu 12, System Option 01).
If the battery voltage falls below 11.2 VDC a Low Battery Trouble condition will occur. The communicator can be programmed
to report Low Battery to the Central Station. The battery will continue to run the control until its voltage drops below 10.2 VDC,
at which time the control will disconnect and shut down to prevent a false alarm and damage to the battery. The AC Fail
trouble display will clear if the AC restores. However, the Low Battery Trouble requires a manual or automatic battery load test
before it will clear. An automatic battery load test is performed every 24 hours. See Section 2.2 for powering up the control.
Telephone Line Connection (R1,T1,T,R)
The telephone interface is connected by the use of an approved RJ-31X interconnect jack. This device allows the subscriber
to disconnect the control/communicator from the public switched telephone network in the event of a malfunction. The control
is equipped with line seizure so that the premises telephone service is interrupted during communication to the central
station. Connection to the approved jack is done with a RJSET cord which connects the control terminals to the RJ31X jack.
NOTE: The Telco cord can be supervised to the RJ31X or demarc block by installing an EOL resistor across the Orange and
Blue wires (RJ31X terminals 2 and 7). In the control, connect the Orange and Blue leads to any 24hr Burglar zone input.
Outputs
There are 13 outputs on the main board. Outputs may be expanded utilizing output expander boards connected to the RS-485
4-wire Keypad data bus. Outputs 1 & 2 trip when any alarm is activated. All others must be enabled through the RP Rules
Programming and can be triggered by multiple conditions “events”. Do not exceed the current limits on voltage only outputs.
Output 1 †† is for speakers(s) ONLY (4 to 8 Ohms). If connecting more than 2, use series/parallel wiring to avoid going
below a 4 ohm total load. This output is the source for voice announcements such as: Zone 1 not ready, System Armed, Alarm
Activated, etc., as well as alarm siren sounds. The initial start volume and the final volume can be adjusted in programming
to suit the application.
Output 2 - Connect a UL Listed Bell or Siren (self-contained). Current limited to 1 Amp. Program Global Option 26 to Voltage.
This output is supervised. Speaker(s) are only permitted for non-UL installations. Series/parallel wire to avoid dropping
below a 4 ohm total load.
Output 3 is a Single Pole Double Throw Relay with form “C” contacts (Com, N/O, and N/C).
Outputs 7, 8, 9, 10, 11, 12, 13, 14, 15, and 16 are low current, positive (+) voltage only, for driving LEDs, relays, etc. Outputs 4,5, and 6 ARE NOT available from the main board. They can only be accessed with a data bus Output expander set to
address 1. This expander will replicate main board outputs 7 thru 16, while also including outputs 4, 5, and 6.
J16
+12V
NEG
16
15
14
13
12
11
10
9
OUTPUTS
8
7
Programmable Outputs (J16) OUT 7 - 16 are +12V switched
positive gene ral purpose outp uts rated at 50mA .
+VAUX
NEG
OUT 16
OUT 15
OUT 14
OUT 13
OUT 12
OUT 11
OUT 10
OUT 9
OUT 8
OUT 7
+12V Red
Black
White
Green
Brown
Blue
Orange
Yellow
Violet
Grey
Pink
Tan
POS
NEG
-T+T
ELK-924 †
24V OPEN
D3
Door
Strike †
N/OCOMN/C
+
-
24V AC
N/OCOMN/C
Transformer
Using Output 7 (low current) with a sensitive relay to switch 24V AC to a Door Strike †
Earth Grounding
Tests have determined that the best results against lightning and transients are obtained by isolating the control from ground.
Do NOT connect any of the terminals, especially the Neg. terminals to earth ground. Early production boards had an earth
ground terminal. This terminal is no longer used on circuit board revision I or later. However, ancilliary devices such as the
ELK-950 Surge Protector on the incoming Telephone circuit are still recommended.
Keypad & Expanders on the RS-485 Data Bus (+VKP, Data A, Data B, Neg)
Keypads and data bus expander devices connect to the four terminals marked +VKP, Data A, Data B, and Neg. The keypad
plug-in wire harness color code is: Red +VKP, Green Data A, White Data B, and Black (-) Neg. The +VKP power terminal is
protected by an auto reset PTC device. In the event of a short circuit or malfunction, power will be removed from all devices
until the problem is resolved. Two (2) quick connect header pin plugs (J1 and J2) along the bottom of the board may be used
for temporary purposes I.E. bench testing using a four conductor ribbon cable. Do not use for permanent connections.
† Not evaluated by UL†† Not for use in UL Listed Systems
M1G Installation and Programming
Page 11
Data Bus E.O.L. Termination - VERY IMPORTANT!
The M1 data bus comforms to EIA RS-485 standards and operates at 38,400 bits per second. The RS-485 standard stipulates there be no
more than 2 home run data bus cables attached to the M1 Main Data terminals, with the end of each cable terminated by a 120 Ohm resistor
connected across the data wires. The M1 board and bus devices come with built-in terminating resistors that may be activated via 2 pin
jumpers (2 Gold Pins). Placing a shorting cap (included in hardware pack) on the two gold pins activates the 120 Ohm terminating resistor
across Data Lines A & B. These jumpers are marked JP2 on the keypads and JP1 on the expanders. From the factory, no terminating
resistors are installed. Without proper termination, noise and interference can cause data corruption and missed communications.
WARNING! Do not splice or interconnect the M1 Data Bus using Telephone type 66 or 110 punch down blocks.
The RS-485 Data Bus must NEVER have more than 2 terminating resistors header/jumpers installed.
NOTE: RS-485 Data Bus Max. wire length is 4000 ft. Total
RS-485 DATA BUS
+VKP
DATA A
DATA B
NEG
The last device on each home run cable SHOULD be terminated via the gold 2 pin terminating header/jumper. Placing a shorting cap on the pins will engage a 120 Ohm
resistor across data lines A & B. If there is only 1 data bus home run cable then place shorting cap on JP3 of Main Board. See other hookups below.
length of 2 homeruns must not exceed that distance.
RED
GREEN
WHITE
BLACK
Min. wire gauge: 24 AW G
18 to 22 AWG is best for
long distances.
Keypad 1
Diagram of Two (2) Home Run Cables with Devices Daisy Chained along the Data Bus
Data Bus Devices
e.g. Keypads, Expanders
DO NOT Jumper
Terminate these devices.
Keypad 3
Jumper
Terminate
these two
devices.
Mount M1DBH inside control.
Use 4 conductor cable to connect
to the M1 Data Bus terminals.
+ VKP
DATA A
DATA B
NEG
RS-485 DATA BUS
CAT5 Cables
Keypad
ELK-M1DBH Data Bus Hub †
The ELK-M1DBH † Data Bus Hub is great for new installations where it is possi ble run multiple CAT5 homerun cables. The RJ45
jacks allow neat and organized connections and a third wire pair is used to return the DATA lines back from each device where they
are used to feed the next adjacent jack. The M1DBH circuitry daisy chains the devi ces by series connecting the DATA lines A & B.
Termination is accomplished with a plug -in RJ45 terminator (supplied).
NOTE: RS-485 Data Bus Max. wire distance is 4000' total. Each homerun 6 conductor
cable must be calculated as double the running distance since the Data A & B lines
travel out and then back (A1 & B1) where they are used to feed the next homerun.
+VKP
DATA A
DATA B
NEG
RS-485 DATA BUS
RED
GREEN
WHITE
BLACK
Min. wire gauge: 24 AWG
18 to 22 AWG is best for
long distances.
NOTE: RS-485 Data Bus Max. wire length is 4000 ft. Total. Each CAT5 homerun from
the M1DBH must be calculated as double the running distance since the Data A & B
lines travel out and then back (A1 & B1) where they are used to feed the next homerun.
J2
J3 J5 J7 J9
J1
J4 J6 J 8
Keypad
8 - Brown
7 - Wht/Brn
6 - Orange
Front
view
5 - Wht/Blue
4 - Blue
3 - Wht/Org
2 - Green
1 - Wht/Grn
Pin1
COLOR CODE EIA 568A f or CAT5/6 Data Bus Cable to RJ45 Plugs.
RJ45 Terminating Plug Insert in first unused jack and terminate the control
at JP3. DO NOT TERMINATE AT ANY OF THE DEVICES !
Pin1
RJ45 Plug
CAT5
or
CAT6
Cable
TO CONTROL
Blue pair is
unused
Wht/Blue
BlueWht/Grn
OPTION A - Using an optional ELK-M1DBH and CAT5 Cables to Daisy Chain Devices
DATA
A1 A
B1 B
To 12VDC
DATA
A1 A
B1 B
Keypad
6 Wire
Cable
TO CONTROL
Install Teminating
Jumper on this last
device AND on the
control JP3.
Connect each device to the 6 conductor cable as shown above
To 12VDC
Keypad
6 conductor cable
Min. wire gauge: 24 AWG
18 to 22 AWG is best for
BLUE
BROWN
long distanc es.
+
Load (50mA max )
-
I.E. LED, Relay
N.O.
N.C.
Keypad
Keypad
Brown
Wht/Brn
Orange
Green
Wht/Org
RED +12V
+
-
BLACK (-)
A
GREEN
A1
WHITE
B
B1
To
Black (-)
To BLACK (Neg)
Optional programmable Output
To BLACK (Neg)
Optional programmable Zone Input
Refer to Keypad Instructions
for more info about Output and Zone Input
RED +12
+
-
BLACK (-)
GREEN
A
WHITE
A1
B
B1
BLUE
BROWN
Optional Output and Zone Input - See Keypad Instructions
2200
Ohm
EOL
Another option for wiring multiple home runs is to use 6 conductor cabling. This allows devices to be daisy chained using an out and back configuration. This involves a 3
way splice of the data A (Green)wire to 2 wires of the 6 conductor cable (designated A and A1). Same is done for data B (W hite) wire. At the control wires A1 and B1 get
spliced to the A and B wires feeding the next device. Terminate the last wired device and the control JP3 ONLY! The POS (+) and Neg (-) power wires should be parallel
wired to the +VKP and Neg terminals or to an auxiliary P ower Supply if the combined current draw exceeds the rated current available from the Control.
OPTION B - Using 6 Conductor Cables and Series Splices to Daisy Chain Connection of Data Bus Devices
††† An Auxiliary Power Supply will be required if the control's Aux. power load for all
combined loads exceeds 1A. (450 mA for UL Commercial). Connect as shown below.
Be sure to connect the negative (-) terminal of the power supply to the negative (-)
terminal (Data Bus NEG) on the control.
U
L Use a UL Listed, battery backed-up Power Supply for UL installations. The battery
will be supplying power to the Keypads/Expanders during a power outage. The Power
Supply and backup Battery should be sized to supply the Keypads/Expanders with the UL
required minimum standby time.
† Not evaluated by UL†† Not for use in UL Listed Systems
Page 12
DATA BUS TERMINALS
A+B
-
RED
GREEN
WHITE
BLACK
AUXILIARY POWER
SUPPLY
-
BLACK
+
WHITE
GREEN
To Keypads or ExpandersTo Keypads or Expanders
M1G Installation and Programming
RED
1234567890123456789012345
1
5
1
5
1
5
1
5
1
5
1
5
1
5
1234567890123456789012345
1234567890123456789012345
1
5
1
5
1
5
1
5
1
5
1
5
1
5
1234567890123456789012345
1234567890123456789012345
1
5
1
5
1
5
1
5
1
5
1
5
1
5
1
5
1234567890123456789012345
The ELK-M1DBHR † Data Bus Hub Retrofit is intended for retrofit jobs where existing 4 conductor cables are the only wires available. It creates 4 managed RS-485
BRANCHES from the single M1 main RS-485 Bus. Like the main M1 Bus, each branch can only have 2 home run cables (4 branches x 2 ea. = 8 home runs). DO
NOT connect more than 2 M1DBHRs to an M1. DO NOT connect an M1DBHR on a branch of another M1DBHR! The M1DBHR CANNOT be used as an extender or
a remote repeater. DO NOT remote M1DBHR(s) away from the M1. Mount close to the main M1 Control. Terminate the last (end of line) device on each home run.
RS-485 DATA BUS
+VKP is protected with 1.25A PTC
+VKP
DATA A
DATA B
NEG
RED
GREEN
WHITE
BLACK
DO NOT attach more than two (2)
M1DBHR Hubs to a single M1 Control.
Mount M1DBHR(s) in same enclosure with the
M1 Main Board. Connect to the M1 Data Bus
terminals using a short 4 conductor cable.
DO NOT attempt to remotely mount an
M1DBHR or use as a remote bus extender!
Jumper Terminate
this device AND JP2
on the M1DBHR .
Example #1
A single Keypad on Branch 1
Place t erminat ing jumpe r on the
Keypad/Bus Device AND on JP2 of
the M1DBHR.
Example #2
Two (2) Ke ypads on Bran ch 2
Place t erminat ing jumpe r on BOTH Ke ypads
and remove jumper JP3 on M1DBHR.
Example #3
Three (3) Keypads & 2 Expanders on Branch 3
(Devices must be Daisy chain wired on each
homerun so they appear to be in series.)
Place t erminat ing jumpe r on the LA ST
device connected to each homerun and
remove jumper JP4 on M1DBHR.
The max. number of bus devices
varies based on the types and
models being used or combined.
Jumper
Terminate
these two
devices.
Keypad
Jumper
Terminate
these two
devices.
Keypad
RED
GREEN
WHITE
BLACK
OPTION C - Using an optional M1DBHR Active Data Bus Hub
ELK-M1DBHR †
DATA BUS HUB FOR RETROFIT
FROM CONTROL
+
INPUT
A
B
JP1
-
JP2JP3
DATA BUS
BRANCH 1
A
B
+
Keypad
Keypad
DO NOT Jumper Terminate
these devices.
+
-
RED
DO NOT Jumper JP3.
Terminati ng Jumpe rs (JP1 - JP 5)
JP1 = Terminates Input from Control
JP2 = Terminates Branch 1
JP3 = Terminates Branch 2
JP4 = Terminates Branch 3
JP5 = Terminates Branch 4
See details about Data Bus Termination.
DATA BUS
BRANCH 2
A
B
GREEN
KeypadKeypad
WHITE
-
BLACK
DATA BUS
BRANCH 3
+
RED
A
GREEN
DO NOT Jumper JP4.
Like the Main M1 Bus, the Maximum wire
length o f any of the 4 branches on the
M1DBHR is 4000 f t.
Min. wire ga uge: 24 AWG
18 to 22 AWG is best for long distances.
If using 1 M1DBHR place jumper on JP1 of
JP4
JP5
the M1DBHR and JP3 of the M1 Control.
With 2 M1DBHR b oards place jumper o n
JP1 of both M1DBHR b oards and remove
jumper JP3 on the M1 Control.
jumpers on any of the 4 branches of the
DATA BUS
BRANCH 4
B
-
WHITE
A
+
††† An Auxiliary Power Supply will be required if the control's Aux.
BLACK
power load for all combined loads exceeds 1A. (450 mA for UL
Commercial). Connect as shown below. Be sure to connect the
negative (-) termin al of the power supply t o the negative (-) term inal
(Data Bus NEG) on the control.
U
L Use a UL Lis ted, ba ttery back ed-up Power Supply fo r UL
installations. The battery will be supplying power to the Keypads/
Expanders during a power outage. The Power Supply and backup
Battery should be sized to supply the Keypads/Expanders with the
UL required minimum standby time.
ELK PRODUCTS, INC. HILDEBRAN, N.C., 28 637, USA
Example #4
B
Branch 4 empty (not used)
-
Place terminating jumper JP5 of M1DBHR
DATA BUS TERMINALS
A
B
+
RED
GREEN
-
BLACK
WHITE
Bus Termin ation:
DO NOT EXCEED two (2) terminating
M1DBHR or the mai n M1 bus.
AUXILIARY POWER
SUPPLY
-
BLACK
+
RED
WHITE
GREEN
To Keypads or ExpandersTo Keypads or Expanders
.
Setting the Data Bus Address and Enrolling Device(s) into the System
Keypads and Expanders communicate over the RS-485 data bus. Each device must have a unique address setting (1 to 16)
within it's device type. Keypads are TYPE 1, input (zone) expanders TYPE 2, output expanders TYPE 3, etc. Device types permit
address numbers to be re-used on different device type. For example: a Keypad, Zone Expander, and Output Expander can
each be set to address 2 on the same data bus because each device is a different device type. But duplicate addresses
CANNOT exist within the same device type. I.E. Multiple keypads on the same bus cannot be set to 'like' addresses.
ADDRESS: From the factory all keypads are set to address 1. Valid addresses are 1 to 16. The first keypad on the system
(Keypad 1) is automatically enrolled upon power up. Each additional keypad must be assigned a unique address and then
manually enrolled from “Menu 1 - Bus Module Enrollment”. (See Menu 01, for complete instructions on Bus Module Enrollment)
1. Enter Keypad setup by one of the following three (3) methods:
a. Press and hold the " * " key for approx. 10-12 seconds (KP1 Keypads with firmware 2.1.48 or later)
b. Press the “ * ” and F5 keys at the same time for approx. 10 seconds. (older KP1 Keypads)
c. Hold ANY key pressed while applying power.
2. Press the F1 key to display the current address setting.
3. Set the desired address by entering a number from 1 to X.
4. Press the Exit key when done.
ENROLLING:
1.Press the
arrow key to select this menu. The Installer Program Code must be entered to access this menu.
2.Enter the Installer Program Code. (The default code is 172839)
3.The first Installer Programming menu display will be “Bus Module Enrollment”
4.Press the RIGHT arrow key to select this menu. “Enrolling Bus Modules” will display.
5.After a few seconds the display will show the total Bus Modules that are enrolled. To view the
enrolled devices and /or remove a device press the RIGHT arrow key next to the word Edit.
6.Press the * or Exit keys to exit Installer Programming.
M1G Installation and Programming
Keypad is in setup mode when the display indicates: Exit when done. F1 Set Addr.
23456789012345678901234
23456789012345678901234
23456789012345678901234
Auth. Required
ELK key, then 9 (or scroll up) to display 9 - Installation Programming. Press the RIGHT
† Not evaluated by UL†† Not for use in UL Listed Systems
23456789012345678901234
23456789012345678901234
23456789012345678901234
23456789012345678901234
Enter Valid Pin
23456789012345678901234
23456789012345678901234
23456789012345678901234
01-Bus Module
23456789012345678901234
23456789012345678901234
23456789012345678901234
Enrollment
23456789012345678901234
23456789012345678901234
23456789012345678901234
23456789012345678901234
XX Bus Modules
23456789012345678901234
23456789012345678901234
23456789012345678901234
23456789012345678901234
Enrolled, Edit
23456789012345678901234
rr
r
rr
Page 13
Section 2 - Operating the System
2.1 Introduction
The control has factory default programming which make it easy to bench test prior to installation. Terminate all zones with
EOL resistors, then connect a keypad, transformer, and battery. The factory (Master) user code is 3456. This code can
operate all user related features of the system. This section gives an overview of powering up and basic keypad functioning.
2.2 Powering Up (One Keypad)
After all other connections have been made and checked thoroughly, the controls AC transformer and battery may be
connected. The Master Power Switch located on the lower left corner can then be turned. Upon power up the control will
perform self-diagnostics and auto-enroll the first keypad (Keypad Address #1). Any additional keypads or expanders must be
manually enrolled using Installer Level Programming. See “Menu 01 - Bus Module Enrollment”.
NOTE: It is very important to make certain that every keypad, input expander, output expander, or any other data bus
device be assigned a unique data bus address within its type. See “MENU 01 - Bus Module Enrollment” for instructions
on setting keypad and expander addresses.
System Startup on Battery Only (Ordinarily the control will not startup without AC power)
If AC power is not available (new construction site, etc.) the control may be started on battery ONLY by shorting the two silver
pads (located in the lower left corner of the circuit board) with a small blade screwdriver. This will temporarily bypass the AC
sensing circuit and allow the control to startup. NOTE: The On/Off power switch must be in the On position.
2.3 User Codes and Authorities
The control has 199 user codes plus one installer code. Each user code may be assigned specific authorities as to what it is
allowed to do. The authorities are assigned from the Installer level programming, however the code digits and user names
are assigned from the keypad user menu 6 - Change User Codes. Only a Master authority level code or the Installer code is
allowed to access keypad user menu 6. The User’s Guide contains a description of operations accessible to the user codes.
Control operations accessed by the installer passcode are slightly different.
Factory Default for User Code 1 is: 3 4 5 6 (Master Code)(1 2 3 4 5 6 if the six digit code option is enabled)
User code may be used for functions in a specific area or system-wide. Some options may be performed at any time, even
while the control is fully or partially armed. The menu system is designed to be next-step-oriented. After a brief explanation of
the options, the user should be able to begin operating the system immediately. For purposes of discussion, the installer and
the end consumer are both considered users, but have different capabilities.
2.4 Installer Program Code and Authorities
The installer code can access all the keypad user menus and has limited arm/disarm privileges. It may be used to arm any
area and disarm any area as long as the area WAS NOT armed by a user code. The Installer code can silence 24hr alarms
or a Burglary alarms in an area that was armed by the installer or in an area that is not armed. The installer code can silence
a trouble condition in a disarmed area. See User’s Guide for a full description of arming and disarming procedures.
Factory Default for the Installer Program Code is: 1 7 2 8 3 9
WARNING! Do Not use 0 0 0 0 0 0 for the Installer Program Code.
This will cause complete lockout of Keypad Installer Level Programming.
Page 14
M1G Installation and Programming
2.5 Keypad Overview
Ready Light - ON when all burglar zones are secure and the system is OK to arm. If OFF, one or more zones are violated (not secure). For
maximum security, secure all zones before arming the system. If FLASHING, one or more force-armable zones are violated. Force arming
temporarily excludes violated zone(s) from the system. If a force armed zone becomes secure while system is armed, it will automatically
restore to service. This is handy for a garage door as system may be armed with the door up, but will secure when door closes.
Armed Light- ON when the system is armed. The mode of arm will be indicated by the LCD display and the Exit or Stay lighted pushbuttons.
This light will be OFF when the system is disarmed.
Exit Key - May be programmed for single or double press arming to the AWAY (not occupied) mode. If ON the system is armed and all
perimeter sensors and interior motions are active. The Away key may be pressed during the exit delay time t to convert from Away to Away
Vacation mode. Vacation mode is primarily for use with the Whenever/And/Then Rules programming of Elk-RP for long term energy savings.
Stay Key - May be programmed for single or double press arming to the STAY (occupied) mode. If ON the system is armed and all interior
zones are excluded (bypassed). Only perimeter doors and windows are active in the Stay mode. This key may also be programmed to
change to other Stay modes such as: Stay Instant, Stay Night, and Stay Night Instant. Since interior zones are automatically excluded once
the Stay mode is activated, the M1 allows this key to Stay arm even while one or more interior zones are violated, provided they are programmed for “force arming”. The Stay Night mode re-activates any interior night zones. To prevent a false alarm the control will not allow
change to the Stay Night mode when a interior night zone is violated unless it is programmed for “Force arm”.
Available Keypads Styles
ELK-M1KPAS Arming Station
ELK-M1KP2 LCD Keypad
Smaller than M1KP.
Features and/or operational characteristics will vary by keypad style.
Fits a single gang electrical box.
ELK-M1KP LCD Keypad
Keypad Models and Feature Comparison
PART
NUMBER
ELKM1KP
ELKM1KP2
ELKM1KPAS
PHYSICAL
DIMENSIONS
6.87" W x 5.25" H x 1.32" D
4.65" W x 5.5" H x .95" D
1.3" W x 2.62" H x .3" D
(keypad area not incl. elect. plate)
DOOR
COVER
Yes
No
No
ZONE
INPUT
Yes (1)
Yes (1)
No
PROG.
OUTPUT
Yes (1)
Yes (1)
No
OPT. 26 BIT
PROX READER
Yes - Int. or Ext.
Yes - Ext. Only
No
TEMP
SENSOR
Yes
No
No
Chime Key - Will be lighted when the Chime mose is On. A tone or announcement will be heard when certain zone(s) are opened. If OFF
the chime mode is off. There are four different selections: Tone only, Voice, Tone/Voice, and Off. In the programming mode this key also
functions as an insert character key for text programming. The key will be lighted when Chime is On.
Bypass Key - Pressing this key followed by a zone number and the bypass key again will exclude or bypass the selected zone. This
key may also be used to delete a character during text programming. When the Bypass key is lit, one or more zones are bypassed.
* Key - Serves as a clear or reset key. If an error is made while entering digits, press this key to clear the error. Master clear is 3 presses.
# Key - This key is currently a duplicate of the Bypass key.
FUNCTION
KEYS
(6) F1 thru F6
(4) F1 thru F4
(6) F then 1- 6
BACKLIGHTING
LCDKEYS
GreenAmber
BlueBlue
N/ABlue
MOUNTING
OPTIONS
Surface Only
Surface Std.
Flush w/opt. BBK2)
(
Flush Std.
Numerical Keys - Used for entry of passcodes, programming, etc. Keys 2 - 9 also have an assigned alpha character for entering text.
ELK and Arrow Keys - The ELK and arrow keys have powerful functionality for both normal operation and programming. Pressing the
ELK key displays relative information according to each application. The arrow keys allow scrolling through all available options. The user
can activate or select the displayed option by pressing the right arrow key. Once an option has been selected, the user may be prompted
for a passcode. Additional sub-menu options may appear to assist. The user may return to the status screen by pressing the * key.
M1G Installation and Programming
Page 15
Keypad Menus
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
123456789012345678901234567890
0
0
0
0
0
0
0
123456789012345678901234567890
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
2345678901234567890123456789
2345678901234567890123456789
2345678901234567890123456789
READY TO ARM
2345678901234567890123456789
2345678901234567890123456789
2345678901234567890123456789
9:00AM 08/01/03
2345678901234567890123456789
Access to menus 1 to 5 can be restricted via programming to only Users that have “User Code Option 8” set. Menus 6 & 8
required a Master or Installer Code. Menu 9 requires the Installer Code. Press ELK to begin, then press the UP or DOWN
arrow key to select a menu. Enter a code if prompted. To select a menu press the RIGHT arrow key.
2345678901234567890123456789
2345678901234567890123456789
2345678901234567890123456789
2345678901234567890123456789
1-View/Controlr
2345678901234567890123456789
2345678901234567890123456789
2345678901234567890123456789
Automation Fncts
2345678901234567890123456789
2345678901234567890123456789
2345678901234567890123456789
2345678901234567890123456789
1-Tasksr
2345678901234567890123456789
2345678901234567890123456789
2345678901234567890123456789
2345678901234567890123456789
12345678901234567890123456789
12345678901234567890123456789
12345678901234567890123456789
12345678901234567890123456789
Water The Lawn
12345678901234567890123456789
12345678901234567890123456789
12345678901234567890123456789
01: # Activates
The control offers extended Menu Options via the center navigation “ELK” key. Some menus
may require a valid code to authorize. The Factory Default Code for USER Code 1 is: 3 4 5 6
(1 2 3 4 5 6 if the six digit code option is enabled)
Allows viewing or controlling of the automation functions such as Tasks, Lighting, Outputs,
Temperature Sensor, Keypad Temperature, and Thermostats. Press the RIGHT arrow key to
select, then choose the desired function using the UP or DOWN arrow keys.
NOTE: The automation functions must be assigned and named using the ELK-RP software.
In most cases they cannot do anything unless they have been written into one of the
“Whenever/And/Then” automation rules.
† Tasks are like 1 button macros, performing multiple jobs with one push. To activate a task
press the RIGHT arrow key and press UP or DOWN to scroll through the list of available tasks.
To jump directly to a particular task, enter it’s two digit number. Once the task is displayed, all
it takes to activate it is to press the # key. A rule to use the “Water the Lawn” task might be:
WHENEVER “Water the Lawn” IS ACTIVATED THEN TURN ON Valve 19 FOR 5 MINUTES, etc.
2345678901234567890123456789
2345678901234567890123456789
2345678901234567890123456789
2-Lightingr
2345678901234567890123456789
2345678901234567890123456789
2345678901234567890123456789
2345678901234567890123456789
2345678901234567890123456789
2345678901234567890123456789
2345678901234567890123456789
Kitchen Lights
2345678901234567890123456789
2345678901234567890123456789
2345678901234567890123456789
001:=Off, # to Chg
2345678901234567890123456789
2345678901234567890123456789
2345678901234567890123456789
2345678901234567890123456789
3-Outputsr
2345678901234567890123456789
2345678901234567890123456789
2345678901234567890123456789
2345678901234567890123456789
2345678901234567890123456789
2345678901234567890123456789
2345678901234567890123456789
2345678901234567890123456789
Pump Motor Cntrl
2345678901234567890123456789
2345678901234567890123456789
2345678901234567890123456789
001:=Off, # to Chg
2345678901234567890123456789
2345678901234567890123456789
2345678901234567890123456789
2345678901234567890123456789
4-Temperaturer
2345678901234567890123456789
2345678901234567890123456789
2345678901234567890123456789
Sensor
2345678901234567890123456789
2345678901234567890123456789
2345678901234567890123456789
2345678901234567890123456789
Outside
2345678901234567890123456789
2345678901234567890123456789
2345678901234567890123456789
S01:=032 Degrees
2345678901234567890123456789
2345678901234567890123456789
2345678901234567890123456789
2345678901234567890123456789
5-Keypadr
2345678901234567890123456789
2345678901234567890123456789
2345678901234567890123456789
Temperature
2345678901234567890123456789
2345678901234567890123456789
2345678901234567890123456789
2345678901234567890123456789
2345678901234567890123456789
Keypad 01
2345678901234567890123456789
2345678901234567890123456789
2345678901234567890123456789
K01:=073 Degrees
† Lighting allows the individual control of lights and/or appliances which have been assigned
through the ELK-RP software. Press the RIGHT arrow key to select Lighting, then press the
UP or DOWN arrow keys to scroll through the list. If you know the three digit number, you may
enter it to jump directly to that Lighting/Appliance. The current state of the unit will be
displayed. Press the # key to toggle (change) the unit from on > off or from off > on.
Outputs might be relays or voltages used to actuate something like a motor, fan, pump, etc.
Outputs can be turned on or turned off from this menu. Press the RIGHT arrow key to select
Outputs, then press the UP or DOWN arrow keys to scroll through the list. If you know the
three digit number, you may enter it to jump directly to that Output. The current state of the
output will display. Press the # key to toggle (change) the output from on > off or from off > on.
Remote “Zone” Temperature Sensors can be read from this menu. Press the RIGHT arrow
key to select this menu, then press the UP or DOWN arrow keys to scroll through the list of
available sensors. To jump directly to a particular sensor enter it’s two digit number. The
current temperature will be displayed. Press the * key to exit.
Keypad Temperature Sensors can be read from this menu. Press the RIGHT arrow key to
select this menu, then press the UP or DOWN arrow keys to scroll through the list of available
keypads. To jump directly to a particular keypad enter it’s two digit number. The current
temperature at the keypad will be displayed. Press the * key to exit.
2345678901234567890123456789
2345678901234567890123456789
2345678901234567890123456789
6-Thermostatr
2345678901234567890123456789
2345678901234567890123456789
2345678901234567890123456789
Temperature
2345678901234567890123456789
2345678901234567890123456789
2345678901234567890123456789
2345678901234567890123456789
2345678901234567890123456789
Hallway
2345678901234567890123456789
2345678901234567890123456789
2345678901234567890123456789
T01:=072 Degrees
2345678901234567890123456789
2345678901234567890123456789
2345678901234567890123456789
2345678901234567890123456789
2-Resetr
2345678901234567890123456789
2345678901234567890123456789
2345678901234567890123456789
Smoke Detectors
2345678901234567890123456789
2345678901234567890123456789
2345678901234567890123456789
2345678901234567890123456789
5 Seconds Smoke
2345678901234567890123456789
2345678901234567890123456789
2345678901234567890123456789
Output Resetr
Continued on next page..
Page 16
† Thermostats can be read from this menu. Press the RIGHT arrow key to select this menu,
then press the UP or DOWN arrow keys to scroll through the list of available thermostats. To
jump directly to a particular thermostat enter it’s two digit number. The current temperature at
the thermostat will be displayed. Press the * key to exit.
Used for resetting latched smoke detectors after a fire alarm activation..
Press the RIGHT arrow key to actuate the Reset Smoke Detector feature. This causes the
power to smoke detectors to be removed for 5 seconds. During this time all fire zones will be
ignored to keep an accidental alarm from occurring.
† Not evaluated by UL
M1G Installation and Programming
123456789012345678901234567890
1
2345678901234567890123456789
0
1
0
1
0
1
0
1
0
1
0
1
0
123456789012345678901234567890
123456789012345678901234567890
1
0
1
0
1
0
1
0
1
0
1
0
1
0
123456789012345678901234567890
123456789012345678901234567890
1
0
1
0
1
0
1
0
1
0
1
0
1
0
123456789012345678901234567890
0
0
0
0
0
0
0
0
0
0
0
0
0
0
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
123456789012345678901234567890
1
0
1
0
1
0
1
0
1
0
1
0
1
0
123456789012345678901234567890
0
0
0
0
0
0
0
123456789012345678901234567890
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
123456789012345678901234567890
2345678901234567890123456789
2345678901234567890123456789
2345678901234567890123456789
3-Walk Test Area r
2345678901234567890123456789
2345678901234567890123456789
2345678901234567890123456789
< Area? Name >
2345678901234567890123456789
2345678901234567890123456789
2345678901234567890123456789
2345678901234567890123456789
000of016 Tested r
2345678901234567890123456789
2345678901234567890123456789
2345678901234567890123456789
A?-Violate Zones
2345678901234567890123456789
2345678901234567890123456789
2345678901234567890123456789
4-View Historyr
2345678901234567890123456789
2345678901234567890123456789
2345678901234567890123456789
Log
2345678901234567890123456789
2345678901234567890123456789
2345678901234567890123456789
2345678901234567890123456789
L001:01/01
2345678901234567890123456789
2345678901234567890123456789
2345678901234567890123456789
AreaArmed 103A1
2345678901234567890123456789
2345678901234567890123456789
2345678901234567890123456789
2345678901234567890123456789
2345678901234567890123456789
5-View Statusr
2345678901234567890123456789
2345678901234567890123456789
2345678901234567890123456789
of all zones
2345678901234567890123456789
2345678901234567890123456789
2345678901234567890123456789
2345678901234567890123456789
6-Changer
2345678901234567890123456789
2345678901234567890123456789
2345678901234567890123456789
User Codes
2345678901234567890123456789
bb
b08:00
bb
Requires Master or
Installer Code
2345678901234567890123456789
2345678901234567890123456789
2345678901234567890123456789
2345678901234567890123456789
001:Sel
2345678901234567890123456789
2345678901234567890123456789
2345678901234567890123456789
< User Name >
2345678901234567890123456789
2345678901234567890123456789
2345678901234567890123456789
2345678901234567890123456789
7--Automationr
2345678901234567890123456789
2345678901234567890123456789
2345678901234567890123456789
Custom Settings
b b
b Prgr
b b
Requires Master or
Installer Code
2345678901234567890123456789
2345678901234567890123456789
2345678901234567890123456789
2345678901234567890123456789
2345678901234567890123456789
2345678901234567890123456789
2345678901234567890123456789
bb
CS01:
b00:00Timer
bb
Sprklr On
Menu 3 permits a local walk test of all zones assigned to this keypad’s area. The siren(s) and
communicator are disabled during a walk test. Press the RIGHT arrow key to begin a Walk
Test. The keypad displays the total tested zones adjacent to the total number of zones involved.
When a zone is activated, it’s name is displayed across the bottom and can be audible if the
Chime mode is on.
Allows viewing of the past 512 activities stored in the history log. Press the RIGHT arrow key to
view. History activities include: Arm, Disarm, Alarm, Trouble, etc. The top line displays the Log
number, Mth/Day, Time, and event description. The log can ONLY be cleared from ElkRP.
L001 is always the most recent event. Press the UP or DOWN arrow keys to move forward and
back. Event 512 will be the oldest event. The bottom line displays the event description, the
extended data (zone, user, etc.) and the area number (A1-A8).
Allows viewing of the current status of all zones. Press the RIGHT arrow key to select. Press
UP or DOWN to scroll through the zones or enter a three digit number to jump directly to a
particular zone. I.E. for zone 16 enter 016. Press the * key to exit.
For changing a user code and/or name for codes which have been previously enabled by the
Installer. Only a Master code OR the installer code can access this menu. Press the RIGHT
arrow key to begin. Press UP or DOWN keys to locate a user, or enter 3 digits to jump. Press
RIGHT arrow key to view the existing code. To change, enter the new code digits and listen for 3
beeps to confirm. To edit the name, press the RIGHT arrow key once, then press the DOWN
arrow key. Enter the text using the letters on the keys. I.E. For “K” press the 5 key twice. Move
RIGHT or LEFT with the arrow keys. Press Chime to insert a space. Press Bypass to erases a
letter. The UP and DOWN arrow keys shift from upper to lower case letters. Press the ELK key
to save and exit.
.
Allows an end user to change up to 20 settings incorporated into an automation rule. These
settings can be: time of day, time duration (seconds), or a numeric value. Each custom setting
has a reference number (CS) and a text description: I.E. CS01: Sprkl On 00:00 [Time] implying
a time of day setting. Press the RIGHT arrow key to begin.
Press the UP or DOWN arrow keys to locate a setting, then press the RIGHT arrow key to
select. Enter the new value and press the ELK key to save and exit.
2345678901234567890123456789
2345678901234567890123456789
2345678901234567890123456789
8-Systemr
2345678901234567890123456789
2345678901234567890123456789
2345678901234567890123456789
Settings
2345678901234567890123456789
Requires Master or
Installer Code
2345678901234567890123456789
2345678901234567890123456789
2345678901234567890123456789
81-Set Sys Clock r
2345678901234567890123456789
2345678901234567890123456789
2345678901234567890123456789
24hr format
2345678901234567890123456789
2345678901234567890123456789
2345678901234567890123456789
2345678901234567890123456789
2345678901234567890123456789
82-Out1 Voice
2345678901234567890123456789
2345678901234567890123456789
2345678901234567890123456789
Adjust Volumer
2345678901234567890123456789
2345678901234567890123456789
2345678901234567890123456789
2345678901234567890123456789
83-Keypadr
2345678901234567890123456789
2345678901234567890123456789
2345678901234567890123456789
Adjustments
23456789012345678901234567890
23456789012345678901234567890
23456789012345678901234567890
1:Set Keypadr
23456789012345678901234567890
23456789012345678901234567890
23456789012345678901234567890
Beep Tone
23456789012345678901234567890
23456789012345678901234567890
23456789012345678901234567890
23456789012345678901234567890
23456789012345678901234567890
2:Set Keypressr
23456789012345678901234567890
23456789012345678901234567890
23456789012345678901234567890
Beep Volume
23456789012345678901234567890
23456789012345678901234567890
23456789012345678901234567890
23456789012345678901234567890
3:Set Backlightr
23456789012345678901234567890
23456789012345678901234567890
23456789012345678901234567890
Dim Level
M1G Installation and Programming
Menu 8 consists of 8 sub-menus used for advanced system settings. Press the right arrow key
and enter a valid user code. Press the UP or DOWN arrow keys to select a sub-menu or enter
the one digit number to jump directly to any sub-menu. I.E. enter 6 to jump to 86.
To set the system clock press the RIGHT arrow key, then press the UP or DOWN arrow key to
select the day. Next, press the RIGHT arrow key to move to Date/Time setting. Enter two digits
for month, date, year, hour, and min. To exit press the * key.
To set the volume for output 1 voice messages (non-alarm) press the RIGHT arrow key and set
desired volume with the UP or DOWN keys. There are 8 settings (0-7). WARNING: PROTECT
EARS! Each adjustment broadcasts a test message through Output 1. To exit press the * key.
To set keypad adjustments press the RIGHT arrow key. Then press the UP or DOWN keys to select
one of the three options.
To set keypad beep tones press the RIGHT arrow key, then select the desired tone using the UP or
DOWN keys. There are 9 settings (0-8). When done, exit by pressing the * key.
To set key-press beep volume press the RIGHT arrow key, then select the desired volume using
the UP or DOWN keys. There are 7 volume levels (1-7) plus Off (0). To exit press the * key.
To set backlight dim level press the RIGHT arrow key, then select the desired level using the UP or
DOWN keys. There are 9 backlight levels (1-9) plus Off (0). The keypad automatically dims to this
setting after 30 seconds of no activity in order to save energy. To exit press the * key.
Page 17
123456789012345678901234567890
1
0
1
0
1
0
1
0
1
0
1
0
1
0
123456789012345678901234567890
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
1
1
1
1
1
1
1
123456789012345678901234567890
1
0
1
0
1
0
1
0
1
0
1
0
1
0
123456789012345678901234567890
123456789012345678901234567890
1
0
1
0
1
0
1
0
1
0
1
0
1
0
123456789012345678901234567890
123456789012345678901234567890
1
0
1
0
1
0
1
0
1
0
1
0
1
0
123456789012345678901234567890
123456789012345678901234567890
1
0
1
0
1
0
1
0
1
0
1
0
1
0
123456789012345678901234567890
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
2345678901234567890123456789
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
2345678901234567890123456789
2345678901234567890123456789
84-Systemr
2345678901234567890123456789
2345678901234567890123456789
2345678901234567890123456789
Tests
2345678901234567890123456789
2345678901234567890123456789
2345678901234567890123456789
2345678901234567890123456789
2345678901234567890123456789
1:Battery Testr
2345678901234567890123456789
2345678901234567890123456789
2345678901234567890123456789
for 30 Seconds
2345678901234567890123456789
2345678901234567890123456789
2345678901234567890123456789
2345678901234567890123456789
2:LCD Testr
2345678901234567890123456789
2345678901234567890123456789
2345678901234567890123456789
2345678901234567890123456789
2345678901234567890123456789
2345678901234567890123456789
2345678901234567890123456789
3:Communicator r
2345678901234567890123456789
2345678901234567890123456789
2345678901234567890123456789
Manual Test
2345678901234567890123456789
2345678901234567890123456789
2345678901234567890123456789
2345678901234567890123456789
2345678901234567890123456789
Send Testr
2345678901234567890123456789
2345678901234567890123456789
2345678901234567890123456789
Silently
2345678901234567890123456789
2345678901234567890123456789
2345678901234567890123456789
2345678901234567890123456789
Send Test w/r
2345678901234567890123456789
2345678901234567890123456789
2345678901234567890123456789
speaker monitor
2345678901234567890123456789
2345678901234567890123456789
2345678901234567890123456789
Turn Butt Setr
2345678901234567890123456789
2345678901234567890123456789
2345678901234567890123456789
Monitor Mode On
2345678901234567890123456789
To perform system tests press the right arrow key. Then press the up or down arrow keys to
select one of the three tests.
The control’s standby battery is load tested automatically every 24hrs. However, it can also be
manually load tested anytime using this option. Press the right arrow key to start the test. The
battery is placed under load for 30 seconds and the battery voltage and system current is
displayed. If the battery falls below a set level, a Low Battery trouble will occur. If it’s necessary
to replace the battery, this test should be used to test and clear a Low Battery Trouble condition.
To test the keypad’s LCD screen press the RIGHT arrow key. The entire screen should appear
black indicating all pixels are working. To exit press the * key.
To manually test the communicator (dialer) press the RIGHT arrow key. Testing is done using
the first phone number that is programmed to send a test code. If there is no phone number
programmed to send a test code, the test will end. To exit this menu press the * key.
There are two types of test, silent and monitored. To silently send a test press the right
arrow key from this display. To hear the test using the inside speakers (OUT1) press the up
or down arrow key to bring up the following display.
This unique feature permits you to hear or “monitor” a single communicator test using the
inside speakers (OUT1) eliminating the need for a telephone “Butt” set. Simply press the
right arrow key from this display to begin.
Similar to above, this works for multiple communicator tests. Press the right arrow key to
enable. Each communicator transmission will be monitored until mode is cancelled. Press
the star (*) key three times to cancel. Cancelled automatically after 24hr daily battery test.
2345678901234567890123456789
2345678901234567890123456789
2345678901234567890123456789
Clear Pendingr
2345678901234567890123456789
2345678901234567890123456789
2345678901234567890123456789
Dialer Reports
2345678901234567890123456789
2345678901234567890123456789
2345678901234567890123456789
2345678901234567890123456789
2345678901234567890123456789
85-Connect ‘RP’ r
2345678901234567890123456789
2345678901234567890123456789
2345678901234567890123456789
Remote Program
2345678901234567890123456789
2345678901234567890123456789
2345678901234567890123456789
2345678901234567890123456789
1:Seize Liner
2345678901234567890123456789
2345678901234567890123456789
2345678901234567890123456789
Attended Mode
2345678901234567890123456789
2345678901234567890123456789
2345678901234567890123456789
2:Seize Liner
2345678901234567890123456789
2345678901234567890123456789
2345678901234567890123456789
UnAttended Mode
2345678901234567890123456789
23456789012345678901234567890
23456789012345678901234567890
23456789012345678901234567890
86-Systemr
23456789012345678901234567890
23456789012345678901234567890
23456789012345678901234567890
Diagnostics
23456789012345678901234567890
2345678901234567890123456789
2345678901234567890123456789
2345678901234567890123456789
2345678901234567890123456789
1:DataBusErrors b
2345678901234567890123456789
2345678901234567890123456789
2345678901234567890123456789
T2A1 Retry 00000
2345678901234567890123456789
2345678901234567890123456789
2345678901234567890123456789
2:Sys Volt/Curr b
2345678901234567890123456789
2345678901234567890123456789
2345678901234567890123456789
13.8V 0.440Amps
2345678901234567890123456789
2345678901234567890123456789
2345678901234567890123456789
2345678901234567890123456789
3:Zone=001 Volts
2345678901234567890123456789
2345678901234567890123456789
2345678901234567890123456789
Display Levelr
2345678901234567890123456789
2345678901234567890123456789
2345678901234567890123456789
2345678901234567890123456789
Zn=001Volt=07.2
2345678901234567890123456789
2345678901234567890123456789
2345678901234567890123456789
L04.6 H09.0A132
2345678901234567890123456789
2345678901234567890123456789
2345678901234567890123456789
2345678901234567890123456789
4:LastOnHookTele
2345678901234567890123456789
2345678901234567890123456789
2345678901234567890123456789
Line V=57,+-20%
2345678901234567890123456789
This special option allows any pending (not reported) dialer communications to be cleared
or cancelled. Typically this will be used only for initial installation and testing.
NOTE: ALWAYS NOTIFY THE MONITORING STATION BEFORE TESTING THE DIALER! If the test
should fail, a Comm Fail trouble will occur. To clear a Comm Fail the dialer must be able to
complete a good communication.
To connect ELK’s Remote Program PC software (RP) via the user assisted method, press the
RIGHT arrow key and then select the connection mode with the UP or DOWN arrow keys.
1:Seize Line Attended Mode - 1) Allows RP connection to begin on an already established voice
connection between the control phone line and the RP Computer. 2) Also useful for manually
answering an incoming call from the RP Computer with programming Rings to Auto Answer.
2:Seize Line Unattended Mode - Pressing the RIGHT arrow key causes the control to dial the
programmed RP telephone number. The RP Computer must be in the “wait for call” mode.
NOTE: UL requires that a Technician be On-Site when doing Remote Programming.
This is a collection of tools for diagnosing system problems. Press the RIGHT arrow key and
enter a valid user code to begin. Press the UP or DOWN keys to select one of the four tools:
This tool is for use in conjunction with Tech Support to diagnose data bus retries and errors. It
displays the device type and number of retries accumulated since the last power-up. T=Device
type, A=The Address within the device type
This tool displays the control’s voltage and average current being drawn from the power supply.
This tool allows the voltage on each zone to be displayed in real time. It changes as contacts
or devices are violated. Press the RIGHT arrow key to begin.
Use the UP or DOWN keys to scroll through each zone. The displayed information consists of:
the present zone voltage, the L low and H high alarm thresholds, and the analog (A to D)
equivalent of the zone voltage..
This is a read only screen displaying the telephone line voltage during the last on-hook
condition. It is an approximate measurement accurate to only +-20%.
Page 18
M1G Installation and Programming
123456789012345678901234567890
1
0
1
0
1
0
1
0
1
0
1
0
1
0
123456789012345678901234567890
2345678901234567890123456789
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
2345678901234567890123456789
2345678901234567890123456789
87-Custom
2345678901234567890123456789
2345678901234567890123456789
2345678901234567890123456789
Message Record r
2345678901234567890123456789
2345678901234567890123456789
2345678901234567890123456789
2345678901234567890123456789
2345678901234567890123456789
VM01b 1 Block(s)
2345678901234567890123456789
2345678901234567890123456789
2345678901234567890123456789
Record<Play>
† This option is used in conjuction with a house telephone (microphone) to record up to 10
custom voice messages. Each message occupies a 6 second block. Two or more
consecutive blocks may be linked together for longer times. Total record time cannot exceed
60 seconds. These messages require the Elk-RP software, which utilize these messages
together with the built-in 500+ word vocabulary to construct voice phrases for many uses,
including the voice dialer. Press the RIGHT arrow key to begin custom message record.
Selects any one of the custom messages (VM01-VM10) for playback or recording. Press the
UP or DOWN arrow keys to select. To Play the selected message press the RIGHT arrow key.
The message will play through Output 1 speakers. To record a new message press the LEFT
arrow key. To exit press the * key.
2345678901234567890123456789
2345678901234567890123456789
2345678901234567890123456789
6 Sec Blocks=01b
2345678901234567890123456789
2345678901234567890123456789
2345678901234567890123456789
Record< PlayAll>
2345678901234567890123456789
This sets the number of consecutive 6 sec. record blocks. The default is 01 blocks which is
normally long enough for most applications. However, to create a longer message press the
RIGHT arrow key and enter the number 01 to 02, etc. NOTE: Creating longer messages
reduces the total number of custom messages. This screen also allows all messages to be
played “PlayAll” by pressing the RIGHT arrow key. When ready to record press the LEFT arrow
key.
2345678901234567890123456789
2345678901234567890123456789
2345678901234567890123456789
6 Sec Blocks=01b
2345678901234567890123456789
2345678901234567890123456789
2345678901234567890123456789
Rec<LiftPhone!
2345678901234567890123456789
This is the prerecord screen. To begin recording: 1) lift the house phone (off hook), 2) press
the LEFT arrow key, 3) start speaking. To stop recording press the “0” key. If stop is not
pressed, recording will automatically end after 6 sec. (or the total number of blocks times 6
seconds).
NOTE: A local house phone is used as the microphone. Installer programming menu 07,
option 1, must be set to a 1 in order for the local phone to be recognized by the control.
2345678901234567890123456789
2345678901234567890123456789
2345678901234567890123456789
2345678901234567890123456789
VM01b 1 Block(s)
2345678901234567890123456789
2345678901234567890123456789
2345678901234567890123456789
Record<Play>
This will display as soon as recording has stopped. To play the new message press the
RIGHT arrow key. To record the message again press the LEFT arrow key and follow the
same procedures again. To exit press the * key.
Step by step summary of procedures for recording a custom message:
1)Verify that a house telephone is connected to the control’s T1 and R1 terminals and that Installer menu 07, option 1
is set to a 1. This allows the control to recognize the telephone and allow it to be used as a microphone.
2)Go to the user menu 8-System Settings by pressing the ELK key and entering 8. Press the r key and enter a valid
user code. Press 87 to reach the custom message record screen.
3)Using the Up/Down arrow keys, select the voice message to record VM01 to VM10. There are 10 custom
messages.
4)Press the l key and select the number of 6 second blocks for your message. Hint-rehearse and time the message,
if it is greater than 6 seconds then increase the number of consecutive blocks as required.
5)Lift the telephone handset and press the l key to begin the recording. The recording will not start until the handset
is off-hook and the l key is pressed.
6)Record your message by speaking into the handset. If the message is shorter than the amount of time selected
then press 0 to stop recording. Otherwise, recording will stop when the number of blocks is reached.
7)Press the Right arrow key to play the message. The message will be heard through the telephone handset if it is
still off-hook. Otherwise the message will be directed to the amplifier connected to output 1.
2345678901234567890123456789
2345678901234567890123456789
2345678901234567890123456789
9-Installationr
2345678901234567890123456789
2345678901234567890123456789
2345678901234567890123456789
Programming(0)
2345678901234567890123456789
M1G Installation and Programming
Requires
Installer
From this menu you may press the RIGHT arrow to enter Installation Level Programming. If
the Installer Programming Code has not already been entered it will be required at this time.
Code
REFER TO PAGE 22 FOR PROGRAMMING INSTRUCTIONS
NOTE: The Remote Programming RP software can be used to lockout certain local program capabilities for “anti-
takeover” purposes. The number in the lower right corner of this menu will indicate the level of lockout as follows:
(0) = No lockout,
(1)=Lockout Telephone number programming - view everything,
(2)=Lockout ALL programming - view everything,
(3)=Lockout ALL Programming and Viewing. This can only be set or removed from the ELK-RP Software.
† Not evaluated by UL
Page 19
Menu 0 - Select Keypad Alternate Area - Multi-area (Partition) Operation
1234567890123456789012345678
1
8
1
8
1
8
1
8
1
8
1
8
1
8
1
8
1234567890123456789012345678
1234567890123456789012345678
1
8
1
8
1
8
1
8
1
8
1
8
1
8
1
8
1234567890123456789012345678
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
9
9
9
9
9
9
9
9
12345678901234567890123456789012
1
2
1
2
1
2
1
2
1
2
1
2
1
2
1
2
12345678901234567890123456789012
This menu allows the keypad to be mapped temporarily to any other area, allowing multi-area (partitioned) operation.
An individually mapped area can be armed, disarmed, and controlled just as if the keypad were permanently assigned
to that area. It may also be used to access a consolidated display of all areas at once, showing the status of each
area.
To reach the keypad menus press the center navigation key labeled “ELK”. A user code may be required depending on
how the control is programmed. The four arrow keys around the Elk key are used to scroll, backup, etc. Pressing the
RIGHT arrow key will select the displayed menu.
1.Press the ELK key. Enter a user code if prompted.
2.Use the UP or DOWN arrow keys to find menu “0-Select Keypad Alternate Area”.
23456789012345678901234567
23456789012345678901234567
23456789012345678901234567
23456789012345678901234567
0-Select Keypad
23456789012345678901234567
23456789012345678901234567
23456789012345678901234567
Alternate Area r
23456789012345678901234567
Press the RIGHT arrow key to select this menu and display the following:
23456789012345678901234567
23456789012345678901234567
23456789012345678901234567
23456789012345678901234567
Auth. Required
23456789012345678901234567
23456789012345678901234567
23456789012345678901234567
Enter Valid PIN
23456789012345678901234567
2345678901234567890123456789
2345678901234567890123456789
2345678901234567890123456789
2345678901234567890123456789
ChangeKPArea-1
2345678901234567890123456789
2345678901234567890123456789
2345678901234567890123456789
[Area Name] A1
2345678901234567890123456789
2345678901234567890123456789
2345678901234567890123456789
2345678901234567890123456789
2345678901234567890123456789
ChangeKPArea-0 r
2345678901234567890123456789
2345678901234567890123456789
2345678901234567890123456789
0=All Areas
2345678901234567890123456789
234567890123456789012345678
234567890123456789012345678
234567890123456789012345678
234567890123456789012345678
Area# 12345678
234567890123456789012345678
234567890123456789012345678
234567890123456789012345678
Status X r r r r r r r
234567890123456789012345678
Enter a valid user code. The control does not allow (restricts) mapping or viewing of
areas that are not authorized for the user code.
MAPPING TO AN INDIVIDUAL AREA
Enter an area number from 1 to 8 OR scroll UP and DOWN with the arrow keys.
r
Press the Right Arrow key to map the Keypad to the area shown. The LCD display
and the Ready / Armed LEDs will show the status for the mapped area for 1 minute.
During this minute, it is possible to arm, disarm, bypass, etc. the mapped area from
this keypad. Each time a key is pressed the 1 minute is restarted. However, after 1
minute of no keypress activity, the keypad will return to its original primary assigned
area.
ACCESSING A CONSOLIDATED DISPLAY OF ALL VALID AREAS
Entering “0” for the area number immediately maps the Keypad to a consolidated
‘snapshot’ of all authorized areas. This permits quick arming and disarming only. If an
area is not ready to arm it will be necessary to map individually to that area to view the
violated zone(s) and either secure or bypass them prior to arming.
This example shows all 8 areas, meaning that the User Code was valid for all 8.
The display only shows the areas for which the user code is authorized.
234567890123456789012345678901
234567890123456789012345678901
234567890123456789012345678901
234567890123456789012345678901
Area# 12345678
234567890123456789012345678901
234567890123456789012345678901
234567890123456789012345678901
Status X r r - - - - - r
234567890123456789012345678901
Page 20
Note the letter beneath each area number.
The single upper case “X” indicates the primary area. This area is controlled exclusively from
the regular operation screens.
A lower case “r” below an area indicates the area is Ready to Arm.
A lower case “n” below an area indicates the area is Not Ready.
A upper case “A” below an area indicates the area is Armed.
This example shows the user code was only authorized for areas 1, 2, and 3. The
unauthorized area(s) have a “-” below them.
To change or ‘toggle’ the arm status of an area, press the number key representing
the area number. IMPORTANT: The area status is not “real time”. It is a snapshot
taken when the RIGHT arrow key was pressed. If a zone has since become violated
the area will still be displaying “r”, however the letter will immediately change to “n”
and the keypad will emit an error tone when an attempt is made to arm by pressing
the area number.
When finished, press the “*” key to exit.
M1G Installation and Programming
Section 3 - Programming The Control
3.1 Introduction
The Security functionality of the M1 Control can be programmed either from an ELK-M1KP LCD Keypad OR from the ELK-RP
PC Software. The keypad features a menu-driven “Text” based interface with simple Yes/No answers for most options. After
just a short amount of experience the average installer will not even require an instruction manual to keypad program the
control.
For the Automation functionality the ELK-RP PC Software is a requirement. The options and capabilities available for
automation are so unique and powerful that it takes a PC to make use of all the benefits. The M1 features a powerful
“Whenever/And/Then” RULES based programming that allows almost any imaginable operation.
3.2 Local Keypad Programming
There are two levels of operation for programming the control locally, user level and installer level.
- User level programming provides the ability to add, change, or delete user passcodes and names. It also allows custom
automation settings to be viewed and changed. A master user code is required to access the user code and custom settings
screens. User programming is explained in the User’s Guide.
- Installer level programming allows total customizing of the Security operating features. Only the installer code may access
this level.
level programming should be familiar with the contents of this publication prior to programming the control panel. If remote
programming is used, it is possible to “lock out” or prevent takeover of a control by another installation company by selecting
“Lockout Local Prog.” This prevents the installer passcode from gaining access to programming via an LCD keypad. The
installer passcode may still be used for the non-programming functions described in Chapter 2. Lockout Local Prog does not
affect remote programming.
If the installer code is lost or forgotten, it is impossible to program the control locally. Anyone attempting installer
3.3 Local or Remote Computer Programming (ELK-RP) and Anti-Takeover
ELK-RP programming utilizes extensive error checking and security safeguards, including data encryption, password log-on,
serial number, and dealer assigned RP access code. The serial # identifies the control to RP while the RP access code
identifies the computer to the control prior to a programming session. RP loads the access code during the first connection. It
cannot be viewed or changed from local keypad programming. In addition to these safeguards, you can set an anti-takeover
option from RP which prevents certain keypad programming. Even a total default of the panel programming cannot reset the
anti-takeover option once it is set..
The Factory Default Elk-RP Access Code is: 2 4 6 8 0 1
NOTE: UL requires that a Technician be On-Site when doing Remote Programming.
3.4 Area Partitioning
The control may be divided into 1 to 8 independent areas (partitions). Each area appears as a full-featured system, allowing
one control to be shared by multiple, independent departments within a common structure. Zones, User Codes, and
Keypads may be assigned to any 1 area up to the maximum number available. An example is a single building divided into
room(s) to be armed/disarmed separately. Mount the control in a secure area (common utility closet) with dedicated and
uninterrupted AC power and telephone service. Then assign zones, codes, and keypads to each department.
Output 1 siren/voice activates on all alarms, regardless of the area. The RP Software Rules can be used create additional
(separate) outputs. When reporting to the central station events like AC Power Failure, Automatic tests, Low Battery, etc., are
considered system reports and are transmitted using the Area 1 account number. If area partitioning is not desired, simply
designate all zones to a single area (Area 1) which is the factory default setting for zones 1-16.
COMMON AREA - Another popular feature is the ability to have one or more areas made “common” to Area 1. This is often
referred to as a “Vestibule Feature”. Any of the Areas 2 thru 8 may be made common to Area 1. The result is: Area 1 cannot be
armed until all its common areas are armed. Once armed, Area 1 will disarm if any common area becomes disarmed. This
is good for lobbies or vestibules shared by two or more people. Each area must have its own keypad. NOTE: If you want
Area 1 to automatically arm when all its common areas become armed, use a Whenever/And/Then rule from the RP
software to do this.
M1G Installation and Programming
Page 21
3.5 Communicator Setup Checklist
4
4
4
4
4
4
4
4
4
4
The Communicator (Dialer) can dial up to 8 phone numbers plus RP. Digital reporting formats include: Pulse 4+2, SIA,
Contact ID, and Pager. There is also a Voice † format which can be commanded from the RP Rules Programming to call a
persons home or cellphone and deliver a voice message. Use the following checklist for each required telephone number.
1.Under
Menu 08 - Telephone Account Setup, select one of the telephone numbers and program the following:
Option 01: Select the desired reporting format - 0=Disable, 1=Contact ID, 2=SIA, 3=Pulse 4+2, 4=Pager, 5=Voice †
Note: The Voice format (5) cannot be enabled from keypad programming. It can only be programmed from the
Elk-RP Software using the Whenever/And/Then Rules.
Option 02: Set the priority for the first (primary number) to 0 = Always Report.
Option 03: Program the telephone number digits to be dialed. No special start or ending characters are required.
Option 04: Set the dial attempts to greater than 0. For Digital reports 8 is suggested. For Voice the max. is 2.
Option 05 Program the digits for the account number to report. Each area (partition) has its own Acct. Number.
Option 13: Select Yes to have Area info, Zone Alarms, Zone Restores, and Zone Unbypasses reported to this Tel #.
Option 14: Select Yes if you wish to have Zone Bypasses reported to this Tel #.
Option 15: Select Yes if you wish to have Zone Troubles reported to this Tel #.
Option 16: Select Yes if you wish to have User (Open/Close) Reports reported to this Tel #.
Option 17: Select Yes if you wish to have Global System Events (AC Fail, Low Battery, etc.) reported to this Tel #.
Option 18: Although not required, you may program a text name for each telephone number.
2.Under Menu 09 - Area Reporting Codes, select the area (partition) and program the desired options such as: Dialer
Delay, Alarm Abort, Auto Open/Closings, etc. then .
3.Under Menu 10 - Zone Reporting Codes, select the zone number and program the desired options such as: Zone Alarms,
Restores, Bypasses, or Trouble.
Option A: For Zone Alarm program a two digit code. To have the automatic SIA or Contact ID report codes transmitted
simply program a nonzero value. I.E. Program a 1 (01).
Option R: For Zone Restore program a two digit code. For automatic SIA or Contact ID codes program a 1 (01).
Option B: For Zone Bypass program a two digit code. For automatic SIA or Contact ID codes program a 1 (01).
Option T: For Zone Trouble program a two digit code. For automatic SIA or Contact ID codes program a 1 (01).
4.Under Menu 11 - F Key Reporting Codes, select and program the alarm code for each desired Keypad Panic Key. NOTE:
Keypad Panics only have Alarm report codes, they do not have restore codes. For automatic SIA or Contact ID codes
program a 1 (01).
5.Under Menu 12 - Sys Report Code Options & Codes, select and program each desired option such as: AC Fail, Low
Battery, Automatic Test, and other system wide options, including the time values for certain options. For automatic SIA or
Contact ID report codes program a 1 (01).
6.Under Menu 13 - User Report Codes, select and and program an Open or Close report code for any User(s) that you
wish to track arm/disarm events, including arm/disarm by the Installer Code or Elk-RP computer.
3.6 Entering Installer Level Programming
1.Press the center ‘ELK’ key once followed by the DOWN arrow key until display reads “9-Installation Programming”. NOTE:
The keypad may beep and display the following:
2.Enter the Installer Program Code when required.
Press the right arrow key to select the “Installation Programming” option.
The Factory Default Installer Program Code is: 1 7 2 8 3 9
For security against unauthorized programming changes, the installer code should be changed from its factory default setting.
This can be done from Menu 07 - Globals System Definitions, Option 42.
Once the Installer Code has been entered, the first programming menu will display and a 4 minute timer will be started.
If there is no key-press activity during this time period the control will automatically exit from the programming mode. It
is easy to navigate around and between the programming menus and options using the up and down arrow keys. When
the correct menu or option is located, press the right arrow key to proceed into that menu.
Refer to the Quick Reference Guide on the following page to locate a particular menu or to see what options
appear under each menu. Refer to the individual menus and their option descriptions for details about each of the
programmable items.
† Not evaluated by UL
Page 22
2345678901234567890123456789012123
2345678901234567890123456789012123
2345678901234567890123456789012123
2345678901234567890123456789012123
2345678901234567890123456789012123
Auth. Required
2345678901234567890123456789012123
2345678901234567890123456789012123
2345678901234567890123456789012123
2345678901234567890123456789012123
Enter Valid Pin
2345678901234567890123456789012123
M1G Installation and Programming
Loading...
+ 50 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.