Elite ELS090S4S, ELS072S4S Installation Instructions Manual

Page 1
THIS MANUAL MUST BE LEFT WITH THE
BUILDING OWNER FOR FUTURE REFERENCE
WARNING
Improper installation, adjustment, alteration, service or maintenance can cause property damage, personal injury or loss of life. Installation and service must be performed by a licensed professional HVAC installer or equivalent, or service agency.
IMPORTANT
The Clean Air Act of 1990 bans the intentional venting of refrigerant (CFCs, HCFCs and HFCs) as of July 1, 1992. Approved methods of recovery, recycling or reclaiming must be followed. Fines and/or incarceration may be levied for noncompliance.
INSTALLATION INSTRUCTIONS
Elite® ELS Series 6 – 20 Ton
AIR CONDITIONERS 6 - 20 TONS 507743-01 8/2018
Table of Contents
Shipping and Packing List .............................................1
Outdoor Unit ..................................................................1
Unit Dimensions, Corner Weights and Centers of Gravity ...2
Unit Plumbing Parts Arrangement ..................................5
Model Number Identication ........................................ 10
Unit Control Box Components Arrangement ................11
Rigging the Unit for Lifting ...........................................12
Installation Clearances ................................................13
Line Set .......................................................................13
Electrical Connections ................................................. 13
Refrigerant Charge ...................................................... 19
System Operation ........................................................ 21
Maintenance ................................................................ 21
Shipping and Packing List
CAUTION
As with any mechanical equipment, contact with sharp sheet metal edges can result in personal injury. Take care while handling this equipment and wear gloves and protective clothing.
Check the unit for shipping damage. If damaged or parts are missing, immediately contact the last shipping carrier.
1 - Assembled outdoor unit
1 - Installation instructions
Outdoor Unit
ELS Series Air Conditioners, which will also be referred to in this instruction as the outdoor unit, use HFC-410A re­frigerant. This outdoor unit must be installed with a match­ing indoor unit and line set as outlined in the ELS Series Engineering Handbook.
This outdoor unit is designed for use in thermal expansion valve (TXV) systems only.
Page 1
Page 2
Unit Dimensions, Corner Weights and Centers of Gravity
ELS072S4S AND ELS090S4S
Model No.
ELS072S4S
ELS090S4S 75 34 89 40 112 51 88 40
INCHES (MM)
5
(127)
2−1/8
(54)
AA BB CC DD
lbs. kg lbs. kg lbs. kg lbs. kg
30 73 33 97 44 82 37
66
1−1/8
(29)
1−1/8
(29)
REFRIGERANT LINE
CONNECTIONS DETAIL
OPTIONAL COIL GUARD
(Field Installed All Coil Sides)
(Not used with Hail Guard)
DISCHARGE
AIR
Corner Weights
9−1/8 (232)
37−5/8
(956)
LIQUID LINE
SUCTION LINE
OPTIONAL HAIL GUARD
(Field Installed All Coil Sides)
(Not used with Coil Guard)
FF
ELECTRICAL INLETS (Above Refrigerant Lines)
Centers of Gravity
Model No.
ELS072S4S
ELS090S4S 25 635 20.3 515.6
INLET AIR
CENTER OF
GRAVITY
EE
DD
INLET AIR
TOP VIEW
DISCHARGE
AIR
EE FF
inch mm inch mm
23.2 589.3 19.2 487.7
BBAA
OUTDOOR FAN GUARD
(Field Installed All Coil Sides)
(Not used with Hail Guard)
46−1/8 (1172)
INLET AIR
CC
OPTIONAL
COIL GUARD
11−1/4
(286)
2 (51)
OPTIONAL
HAIL GUARD
(Field Installed
All Coil Sides)
(Not used with
Coil Guard)
COMPRESSOR
LIFTING HOLES (For Rigging)
39−7/8 (1013)
BASE
CONTROL BOX ACCESS
REFRIGERANT
LINE CONNECTIONS
SEE DETAIL
ELECTRICAL INLETS (Above Refrigerant Lines)
Page 2
COMPRESSOR
FORKLIFT SLOTS (Both Sides)
48−3/8 (1229)
BASE
WEIVEDISWEIVTNORF
45−1/4 (1149)
48−3/4 (1238)
3−1/2
(89)
OPTIONAL
COIL GUARD
(Field Installed All Coil Sides)
(Not used with Hail Guard)
Page 3
ELS120S4S, ELS120S4D AND ELS150S4D
Corner Weight
Model No.
ELS 120S4S 130 59 124 56 107 49 111 50
ELS 120S4D 122 55 119 54 127 58 131 59
ELS 150S4D
5
(127)
2−1/8
(54)
AA BB CC DD
lbs. kg lbs. kg lbs. kg lbs. kg
144 66 132 60 13 3 60 145 66
9−1/8
(232)
6−1/2 (165)
3−3/4
(95)
1−1/8
(29)
1−1/8
(29)
LIQUID LINES
SUCTION LINES
Model No.
ELS 120S4S ELS 120S4D 21.0 533 28.5 724
ELS 150S4D
OUTDOOR FAN
GUARDS (2)
CENTER OF
GRAVITY
FF
Centers of Gravity
EE FF
inch mm inch mm
20.5 521 33.5 851
19.0 483 30.0 762
OPTIONAL HAIL GUARD
(Field Installed All Coil Sides)
(Not used with Coil Guard)
INLET AIR
BBAA
EE
INLET AIR
SINGLE STAGE
ELS120S4S
REFRIGERANT LINE
CONNECTIONS DETAIL
OPTIONAL COIL GUARD
(Field Installed All Coil Sides)
(Not used with Hail Guard)
57−7/8 (1470)
DISCHARGE
COMPRESSOR
FORKLIFT SLOTS (Both Sides)
FRONT VIEW
STAGE 1
ELS120S4D ELS150S4D
AIR
60−1/8 (1527)
BASE
STAGE 2
ELS120S4D ELS150S4D
OPTIONAL HAIL GUARD
(Field Installed All Coil Sides)
(Not used with Coil Guard)
CONTROL BOX ACCESS
REFRIGERANT
LINE CONNECTIONS
SEE DETAIL
ELECTRICAL INLETS (Above Refrigerant Lines)
DD
ELECTRICAL INLETS (Above Refrigerant Lines)
DISCHARGE
AIR
LIFTING HOLES (For Rigging)
INLET AIR
TOP VIEW
41−3/8 (1051)
43−5/8 (1108)
SIDE VIEW
BASE
CC
OPTIONAL
COIL GUARD
(Field Installed
All Coil Sides) (Not used with
Hail Guard)
11−1/4
(286)
2(51)
48−3/4 (1238)
45−1/4 (1149)
OPTIONAL
COIL GUARD
(Field Installed
All Coil Sides)
(Not used with
Hail Guard)
3−1/2
(89)
Page 3
Page 4
ELS180S4D AND ELS240S4D
Model No.
(127)
ELS180S4D 181 82 177 81 215 98 221 100
ELS240S4D 192 87 189 86 232 105 238 108
AA BB CC DD
lbs. kg lbs. kg lbs. kg lbs. kg
3−3/4
(95)
1−1/8
(29)
5
1−1/8
(29)
2−1/8
(54)
REFRIGERANT LINE
CONNECTIONS DETAIL
OPTIONAL COIL GUARD
(Field Installed All Coil Sides)
(Not used with Hail Guard)
DISCHARGE
Corner Weight
9−1/8
(232)
6−1/2
(165)
STAGE 1
AIR
LIQUID LINE (2)
STAGE 2
SUCTION LINE (2)
OPTIONAL
HAIL GUARD
(Field Installed
All Coil Sides)
(Not used with
Coil Guard)
OUTDOOR FAN
GUARDS (4)
AA
CENTER OF
GRAVITY
EE
DD
ELECTRICAL INLETS (Above Refrigerant Lines)
Centers of Gravity
Model No.
ELS180S4D 29 737 38 965
ELS240S4D 29 739 38 965
INLET
FF
INLET
TOP VIEW
86−1/2
(2197)
DISCHARGE
EE FF
inch mm inch mm
OPTIONAL
HAIL GUARD
(Field Installed
All Coil Sides)
(Not used with
Coil Guard)
AIR
AIR
AIR
BB
INLET
CC
OPTIONAL
COIL GUARD
(Field Installed
All Coil Sides)
(Not used with
Hail Guard)
2(51)
AIR
11−1/4
(286)
COMPRESSOR
LIFTING HOLES (For Rigging)
60−1/8
(1527)
BASE
FRONT VIEW
CONTROL BOX ACCESS
ELECTRICAL INLETS (Above Refrigerant Lines)
Page 4
REFRIGERANT
LINE CONNECTIONS
SEE DETAIL
FORKLIFT SLOTS (Both Sides)
SIDE VIEW
88−3/4
(2254)
48−3/4
(1238)
45−1/4
(1149)
BASE
OPTIONAL COIL GUARD
(Field Installed All Coil Sides)
(Not used with Hail Guard)
Page 5
Unit Plumbing Parts Arrangement
ELS072S4S
ELS090S4S
Page 5
Page 6
ELS120S4S
ELS120S4D – STAGE 2
Page 6
Page 7
ELS120S4D – STAGE 1
ELS150S4D – STAGE 2
Page 7
Page 8
ELS150S4D – STAGE 1
ELS180S4D – STAGE 2
Page 8
Page 9
ELS180S4D – STAGE 1
ELS240S4D – STAGE 2
Page 9
Page 10
ELS240S4D – STAGE 1
ELSY1120 S S4 D
Model Number Identication
Brand/Family
Elite™ Product Line
S = Split System Air Conditioner
Nominal Cooling Capacity -
090 = 7.5 Tons
120 = 10 To ns
150 = 12.5 Tons
180 = 15 To ns 240 = 20 To ns
Tons
072 = 6 Tons
Minor Design Sequence
1 = 1st Revision 2 = 2nd Revision 3 = 3rd Revision
Part Load Capability
S = Single Stage Compressor
T = Two Stage Compressor
Refrigerant Circuits
S = Single Circuit D = Dual Circuits
Refrigerant Type
4 = R-410A
Cooling Efficiency
S = Standard Efficiency
Voltage
Y = 208/230V‐3 phase60hz G = 460V‐3 phase60hz J = 575V‐3 phase60hz
M = 380/420V‐3 phase50hz
Page 10
Page 11
Unit Control Box Components Arrangement
Page 11
Page 12
Rigging the Unit for Lifting
Important - all panels must be in place for rigging.
Lifting point should be directly above the center of gravity.
Lifting point should be directly above the center of gravity.
Important - all panels must be in place for rigging.
Lifting point should be directly above the center of gravity.
Important - all panels must be in place for rigging.
Rig the unit for lifting by attaching four cables to the holes
in the base rail of the unit. See gures 1 through 3.
1 - Remove protective packaging before rigging the
unit for lifting.
2 - Connect the rigging to the holes in each corner of
the unit’s base.
3 - All panels must be in place for rigging.
4 - Place a eld-provided H-style frame just above the
top edge of the unit. The frame must be of adequate strength and length. (An H-style frame will prevent the top of the unit from being damaged.)
Caution - do not walk on unit.
Caution - do not walk on unit.
FIGURE 2. ELS120S4S, ELS120S4D
and ELS150S4D
FIGURE 1. ELS072S4S and ELS090S4S
Caution - do not walk on unit.
FIGURE 3. ELS180S4D and ELS240S4D
Page 12
Page 13
Installation Clearances
See Unit Dimensions on page 2 for sizing mounting slab,
platforms or supports. Refer to gures 4 through 6 for
mandatory installation clearance requirements.
NOTES:
• Clearance to one of the remaining two sides may be 12
in. (305 mm) and the nal side may be 6 in. (152 mm).
• A clearance of 24 in. (610 mm) must be maintained be­tween two units.
• 48 in. (1219 mm) clearance required on top of unit.
SEE
NOTES
30”
CONTROL
BOX ACCESS
36”
30”
(762)
SEE
NOTES
SEE
NOTES
FIGURE 4. ELS072 and ELS090
Installation Clearances
SEE
NOTES
SEE
NOTES
36”
FIGURE 5. ELS120S4S, ELS120S4D
and ELS150 Installation Clearances
CONTROL BOX ACCESS
36”
(914)
30”
CONTROL BOX ACCESS
SEE
NOTES
FIGURE 6. ELS180 and ELS240
Installation Clearances
Line Set
Field refrigerant piping consists of liquid and suction lines connecting the condensing unit and the indoor unit. Liquid and suction service valves are located in a compartment at the corner of the unit below the control box.
Piping can be routed directly from the service valves or
eld supplied elbows can be added to divert the piping as
required.
Refer to table 1 for eld-fabricated refrigerant line sizes for
runs up to 50 linear feet (15 m).
TABLE 1. Refrigerant Line Sizes for Runs
Up to 50 Linear Feet
Unit Liquid Line Suction Line
ELS072 3/8" (10mm) 1-1/8” (29mm)
ELS090 5/8" (16mm) 1-1/8” (29mm)
ELS120S4S 5/8” (16mm) 1-1/8” (29mm)
ELS120S4D 3/8” (10mm) 1-1/8” (29mm)
ELS150 3/8” (10mm) 1-1/8” (29mm)
ELS180 5/8” (16mm) 1-1/8” (29mm)
ELS240 5/8” (16mm) 1-1/8” (29mm)
Refrigerant Line Limitations
You may install the unit in applications that have line set lengths of up to 50 linear feet (15 m) with refrigerant line sizes as outlined in table 1 (excluding equivalent length of
ttings). Size refrigerant lines greater than 50 linear feet
(15m or greater) according to the Lennox Refrigerant Pip­ing Design and Fabrication Guidelines (Corp. 9351-L9) or latest version.
Electrical Connections
In the United States, wiring must conform with current lo­cal codes and the current National Electric Code (NEC). In Canada, wiring must conform with current local codes and the current Canadian Electrical Code (CEC).
Page 13
Page 14
TRANSFORMER – 24V
GROUND.
1
2
can be affected by sunlight, drafts or vibrations.
3
4
Use the transformer provided with the air conditioning unit for low-voltage control power (24V, 70VA)
NOTE – The addition of accessories to the system could exceed the 70VA power requirement of the factory-pro­vided transformer. Measure the system’s current and voltage after installation is complete to determine trans­former loading. If loading exceeds the factory-provided
transformer capacity, a larger eld-provided transformer
will need to be installed in the system.
CIRCUIT SIZING AND DISCONNECT SWITCH
MAIN FUSE
BOX/BREAKER
PANEL
DISCONNECT
SWITCH
INSTALL THERMOSTAT
THERMOSTAT
Install room thermostat (ordered separately) on an inside wall approximately in the center of the conditioned area and 5 feet (1.5m) from the floor. It should not be installed on an outside wall or where it
5 FEET
(1.5M)
TYPICAL CONTROL WIRING
Refer to the unit nameplate for minimum circuit ampacity amperage minimum, and maximum fuse or circuit breaker fusible (HACR per NEC). Install power wiring and properly sized disconnect switch.
NOTE UNITS ARE APPROVED FOR USE ONLY WITH COPPER CONDUCTORS. GROUND UNIT AT DISCONNE CT SWITCH OR TO AN EARTH
TYPICAL HIGH VOLTAGE POWER SUPPLY CONNECTIONS
Install low voltage wiring from outdoor to indoor unit and from thermostat to indoor unit as illustrated.
WARNING
Electric Shock Hazard. Can cause injury or death. Unit must be properly grounded in accordance with national and local codes.
Line voltage is present at all components when unit is not in operation on units with single-pole contactors. Disconnect all remote electric power supplies before opening access panel. Unit may have multiple power supplies.
Page 14
Page 15
TYPICAL UNIT CONTROL WIRE CONNECTIONS
5
WIRE RUN LENGTH AWG# INSULATION TYPE
LESS THAN 100’ (30M) 18 TEMPERATURE RATING
MORE THAN 100’ (30M) 16 35°C MINIMUM
A
RUN CONTROL WIRES THROUGH RIGHT CUTOUT.
B RUN CONTROL WIRES THROUGH WIRE TIES.
MAKE CONTROL WIRE CONNECTIONS USING FIELD
C
PROVIDED WIRE NUTS. SEE FIGURES 7 THROUGH 10 FOR CONNECTION REQUIREMENTS.
D
TIGHTEN WIRE TIE TO SECURE 24VDC CONTROL WIRING.
NOTE - FOR PROPER VOLTAGES, SELECT THERMOSTAT WIRE (CONTROL WIRING) GAUGE PER TABLE ABOVE.
NOTE - WIRE TIE PROVIDES LOW VOLTAGE WIRE STRAIN RELIEF AND MAINTAINS SEPARATION OF FIELD INSTALLED LOW AND HIGH VOLTAGE CIRCUITS.
NOTE - DO NOT BUNDLE ANY EXCESS 24VAC CONTROL WIRES INSIDE CONTROL BOX.
Page 15
Page 16
R
TB14
6
CB8
T1
208V
400V
240/460/575V
24V
C2
CB8
K10,-1 K67-1
S24 T1 TB14
C1
CIRCUIT BREAKER-TRANS T1
C
SWITCH-LOSS OF CHARGE,COMP 1
TRANSFORMER-CONTROL TERMINAL STRIP-CLASS II VOLTAGE
S24
4
1
4
COOL 2
COOL 1
1
3
2
1
3
2
LINE VOLTAGE FIELD INSTALLED
DENOTES OPTIONAL COMPONENTS
II
WIRING DIAGRAM
09/17
DUAL SPEED COMPRESSOR
ELS-072,090,120-G,J,M,Y
2011
SECTION A2
537903-01
REV. 0
FIGURE 7. Typical Wiring Diagram – ELS072S4S, ELS090S4S and ELS120S4S (G, J, M, Y Voltages)
Page 16
Page 17
R
TB14
6
4
208V
400V
240 / 460 / 575V
K1-2
240 / 460 / 575V
1
B5
208V
400V
3
CB8
T1
1
2
S25
3
K2-2
S24
1
4
3
2
B4
C2
C1
TB14
C
COOL 2
COOL 1
LINE VOLTAGE FIELD INSTALLED
DENOTES OPTIONAL COMPONENTS
CIRCUIT BREAKER-TRANS T1
CB8
K10,-1 K66,-1,2
K67,-1,2
SWITCH-LOSS OF CHARGE,COMP 1
S24
SWITCH-LOSS OF CHARGE,COMP 2
S25
TRANSFORMER-CONTROL
T1
TERMINAL STRIP-CLASS II VOLTAGE
TB14
II
WIRING DIAGRAM
ELS-120,150-G,J,M,Y
SECTION A 3
2008
FIGURE 8. Typical Wiring Diagram – ELS120S4D and ELS150S4D (G, J, M, Y Voltages)
Page 17
08/17
REV. 0
537904-01
Page 18
R
TB14
6
4
CB8
T1 AND
208V
400V
240 / 460 / 575V
9
6
2
9
6
CB8
5
3
S25
4
3
1
1
2
S24
T1
208V
400V
240 / 460 / 575V
3
1
2
SWITCH-LOSS OF CHARGE,COMP 1
S24 S25
SWITCH-LOSS OF CHARGE,COMP 2
T1
TRANSFORMER-CONTROL
4
3
3
1
2
TB14
TERMINAL STRIP-CLASS II VOLTAGE
1
2
C2
C1
TB14
C
COOL 2
COOL 1
DENOTES OPTIONAL COMPONENTS LINE VOLTAGE FIELD INSTALLED
II
K10,-1 K66,-1,2 K67,-1,2
CIRCUIT BREAKER-TRANS T1
CB8
K149,-1
WIRING DIAGRAM
SINGLE SPEED COMPRESSOR
ELS-180,240-G,J,M,Y
SECTION A 4
2008
537905-01
FIGURE 9. Typical Wiring Diagram – ELS180S4D and ELS240S4D (G, J, M, Y Voltages)
Page 18
08/17
REV. 0
Page 19
Refrigerant Charge
OUTDOOR WIT TESTIN
ELS units have a factory holding charge of 2 pounds of HFC-410A in each circuit. Additional refrigerant will need to be added during installation (table 2).
TABLE 2. Adding Refrigerant
Stage 1
Models
ELS072S4S 18.5 N/A 3/8 1-1/8 0.7
ELS090S4S 21.75 N/A 5/8 1-1/8 1.7
ELS120S4S 23 N/A 5/8 1-1/8 1.7
ELS120S4D 12 12 3/8 1-1/8 0.7
ELS150S4D 15 15.5 3/8 1-1/8 0.7
ELS180S4D 23.75 23.5 5/8 1-1/8 1.7
ELS240S4D 22.5 23.5 5/8 1-1/8 1.7
1
If line set length is greater than 25 feet, add this amount
for 25ft line set
to each circuit. If line set is less than 25 feet, subtract this amount from each circuit. Refer to Lennox Refrigerant Piping Design and Fabrication Guidelines for more infor­mation.
NOTE - Refrigerant line sets longer than 200 feet (60 me- ters) are not recommended. For assistance contact Len­nox Application Department.
To charge the system, use either of the following proce­dures:
CHARGE PROCEDURE – NORMAL OPERATING PRESSURES
1 - Connect a manifold gauge set to the service valves:
A - Low pressure gauge to vapor service port.
B - High pressure gauge to liquid valve service port
2 - Operate system until pressures and temperatures
stabilize (5 minutes minimum).
3 - Use a thermometer to measure the outdoor
ambient temperature. The outdoor temperature will determine which charging procedure to use.
1 - Apply the outdoor ambient temperature to table
4 or 5 to determine normal operating pressures. Compare the normal operating pressures to the pressures obtained from the connected gauges. If discharge pressure is high, remove refrigerant from the system. If discharge pressure is low, add refrigerant to the system.
A - Add or remove charge in increments.
B - Allow the system to stabilize at least 5 minutes each
time refrigerant is added or removed
2 - Minor variations in these pressures may be
expected due to differences in installations.
Signicant differences could mean that the system
is not properly charged or that a problem exists with some component in the system.
lbs
Stage 2
lbs for 25ft line set
Liq.
Line
Dia.
Suction
Line Dia.
Outdoor Temp > 65ºF (18ºC)
Ounces
Adjustment
per foot of
line set
1
3 - Verify the charge, as described in the approach
method.
CARDBOARD OR PLASTIC SHEET
COIL SHOULD BE BLOCKED ONE SIDE AT A TIME
H CARDBOARD OR PLASTIC SHEET UNTIL PROPER
G PRESSURES ARE REACHED.
FIGURE 10. Blocking Outdoor Coil
Outdoor Temp < 65ºF (18ºC)
1 - When the outdoor ambient temperature is below
65F (18C) it may be necessary to restrict the air ow
through the outdoor coil to achieve liquid pressures in the 325-375 psig (2240-2585 kPa) range. These higher pressures are necessary for checking the charge. Block equal sections of the outdoor coil on all coil sides until the liquid pressure is in the 325-
375 psig range (gure 11).
2 - Charge the unit using the approach method in the
next section.
CHARGE PROCEDURE – APPROACH METHOD
Use the following approach method along with the normal
operating pressures to conrm readings.
1 - Using the same thermometer, compare liquid
temperature at service valve to outdoor ambient temperature.
Approach Temperature = Liquid temperature minus
ambient temperature
2 - Approach temperature should be as indicated in
table 3 for each stage. An approach temperature greater than this value indicates an undercharge. An approach temperature less than this value indicates an overcharge.
A - Add or remove charge in increments.
B - Allow system to stabilize at least 5 minutes each
time refrigerant is added or removed.
3 - Do not use the approach method if system pressures
do not match pressures in table 4 except when the outdoor ambient temperature is below 65ºF (18ºC). The approach method is not valid for grossly over or undercharged systems.
Page 19
Page 20
TABLE 3. Approach Temperatures – Commercial Matchups
TABLE 4. Normal Operating Pressures (Liquid + 10/Suction +5 psig) (Single-Stage Units)** - Commercial Matchups
Models Approach Temperature
Outdoor Indoor Stage (ºF) (+/- 1) (ºC) (+/- 0.5)
ELS072S4S ELA072S4S 1 4 2.2 ELS090S4S ELA090S4D 1 7 3.9 ELS120S4S ELA120S4D 1 4 2.2
ELS120S4D ELA120S4D
ELS150S4D ELA150S4D
ELS180S4D ELA180S4D
ELS240S4D ELA240S4D
1 5 2.8 2 5 2.8 1 7 3.9 2 5 2.8 1 4 2.2 2 4 2.2 1 7 3.9 2 8 4.4
Temp*
65 F (18 C)
75 F (24 C)
85 F (29 C)
95 F (35 C)
105 F (41 C)
115 F (46 C)
125 F (52 C)
STD. CFM
Liquid Suction Liquid Suction Liquid Suction
-072S4S -090S4S -120S4S
245 137 240 128 243 135
283 141 294 130 285 136
327 143 338 131 332 138
377 145 385 133 378 139
426 148 435 135 434 141
484 150 489 136 491 142
540 155 545 140 548 146
2600 2725 3850
*Temperature of air entering outdoor Coil
**With indoor conditions at 80°F dry bulb and 67°F wet bulb temperatures.
TABLE 5. Normal Operating Pressures (Liquid + 10/Suction + 5 psig) (Two-Stage Units)** - Commercial Matchups
-120S4D
Temp*
65 F (18 C) 244 133 240 133
75 F (24 C) 282 136 278 135
85 F (29 C) 326 139 322 137
95 F (35 C) 373 141 372 138
105 F (41 C) 423 142 420 141
115 F (46 C) 477 144 476 143
125 F (52 C) 534 147 539 145
STD. CFM 4000
STAGE 1
Liquid Suction Liquid Suction
-120S4D
STAGE 2
-150S4D
STAGE 1
Liquid Suction Liquid Suction
254 132 254 130
291 135 289 133
337 138 336 134
381 140 382 136
432 142 433 139
487 144 489 141
543 147 550 145
4400
-150S4D
STAGE
2
-180S4D
Temp*
F ( C)*
65 F (18 C) 233 110 236 110
75 F (24 C) 274 120 276 119
85 F (29 C) 317 128 319 125
95 F (35 C) 364 134 366 131
105 F (41 C) 418 138 416 132
115 F (46 C) 475 141 468 134
125 F (52 C) 536 143 529 136
STD. CFM 5150
STAGE 1
Liquid Suction Liquid Suction
*Temperature of air entering outdoor Coil **With indoor conditions at 80°F dry bulb and 67°F wet bulb temperatures.
NOTE – Operating pressures shown in Table 5 apply to commercial one-to-one matches.
-180S4D
STAGE 2
Page 20
-240S4D
STAGE 1
Liquid Suction Liquid Suction
236 129 236 128
275 132 275 129
321 134 322 131
370 137 368 133
420 139 425 136
477 142 478 139
539 146 534 144
6975
-240S4D
STAGE 2
Page 21
TABLE 6. Approach Temperatures – Residential Matchups
Models Approach Temperature
Outdoor Indoor Stage (ºF) (+/- 1) (ºC) (+/- 0.5)
ELS120S4D
ELS120S4D (2) CH33-62D
ELS120S4D (2) CH23-068
ELS120S4D (2) CX35-60C
ELS120S4D (2) CX35-60D
(2) CBA27UHE-060 or
(2) CBA38MV-060
1 4 2.2 2 4 2.2 1 4 2.2 2 4 2.2 1 4 2.2 2 4 2.2 1 4 2.2 2 4 2.2 1 4 2.2 2 4 2.2
TABLE 7. Normal Operating Pressures – Residential Matchups
ELS120S4D + (2) CBA27UHE-060
Temp
ºF (ºC) Liquid Suction Liquid Suction Liquid Suction Liquid Suction Liquid Suction Liquid Suction 65 (18) 251 133 250 131 240 125 241 125 241 128 242 128 75 (24) 292 135 287 134 280 129 282 128 281 131 283 131 85 (29) 340 137 333 136 324 132 326 131 325 134 326 133
95 (35) 391 140 384 139 372 135 374 134 373 137 375 136 105 (41) 446 143 441 142 425 139 427 137 427 141 428 139 115 (46) 505 145 501 144 483 143 484 141 484 144 486 142 125 (52) 569 148 566 147 545 146 548 145 547 147 550 146
STD. CFM 3615 3200 3200
or (2) CBA38MV-060
STAGE 1 STAGE 2 STAGE 1 STAGE 2 STAGE 1 STAGE 2
ELS120S4D + (2) CH33-62D ELS120S4D + (2) CH23-068
Temp
ºF (ºC) Liquid Suction Liquid Suction Liquid Suction Liquid Suction
65 (18) 241 130 243 129 240 127 241 127 75 (24) 282 133 282 132 281 130 282 130 85 (29) 326 136 327 135 325 134 327 133
95 (35) 374 139 375 138 373 137 374 136 105 (41) 427 142 428 141 427 141 428 139 115 (46) 485 145 486 144 484 145 486 143 125 (52) 548 148 550 147 548 148 550 146
STD. CFM 3200 3200
ELS120S4D + (2) CX35-60C ELS120S4D + (2) CX35-60D
STAGE 1 STAGE 2 STAGE 1 STAGE 2
Page 21
Page 22
System Operation
The outdoor unit and indoor blower cycle on demand from the room thermostat. When the thermostat blower switch is in the ON position, the indoor blower operates contin­uously.
HIGH PRESSURE SWITCHES (S4 AND S7)
These units are equipped with a manual reset high pres­sure switch (single-pole, single-throw) which is located on the discharge line. The switch shuts off the compressor when discharge pressure rises above the factory setting. High Pressure (auto reset) – trip at 640 psig; reset at 512 psig.
LOSS OF CHARGE SWITCHES (S24 AND S25)
These units are equipped with a loss-of-charge switch that is located in the liquid line. The switch is a SPST, auto-re­set switch that is normally closed. The switch opens at 40 psi and closes at 90 psi.
Maintenance
At the beginning of each cooling season, the system should be checked as follows:
OUTDOOR UNIT
1 - Clean and inspect the condenser coil. You can ush
the coil with a water hose.
2 - The outdoor fan motor is prelubricated and sealed.
No further lubrication is necessary.
3 - Visually inspect connecting lines and coils for
evidence of oil leaks.
4 - Check wiring for loose connections.
5 - Check for correct voltage at the unit while the unit is
operating and while it is off.
6 - Check amp-draw of the outdoor fan motor.
Unit nameplate _________ Actual ____________
7 - Check amp-draw of the compressor.
Unit nameplate _________ Actual ____________
NOTE – If the owner complains of insufcient cooling,
gauge the unit and check the refrigerant charge. Refer to section on refrigerant charging in this instruction.
INDOOR COIL
1 - If necessary, clean the coil.
2 - Check connecting lines and coils for evidence of oil
leaks.
3 - If necessary, check the condensate line and clean it.
INDOOR UNIT
1 - Clean or change lters.
2 - Adjust the blower speed for cooling. Measure the
pressure drop over the coil to determine the correct blower CFM. Refer to the unit information service manual for pressure drop tables and procedure.
3 - On belt drive blowers, check the belt for wear and
proper tension.
4 - Check all wiring for loose connections.
5 - Check for correct voltage at the unit (blower
operating).
6 - Check amp-draw on blower motor.
Unit nameplate _________ Actual ____________
Page 22
Page 23
Start-Up and Performance Checklist
Job Name Job no. Date
Job Location City State
Installer City State
Unit Model No. Serial No. Service Technician
Nameplate Voltage
Rated Load Ampacity Compressor Amperage:
Maximum Fuse or Circuit Breaker
Electrical Connections Tight? Indoor Filter clean? Supply Voltage (Unit Off)
Indoor Blower RPM S.P. Drop Over Indoor (Dry) Outdoor Coil Entering Air Te mp.
Vapor Pressure;
Refrigerant Lines: Leak Checked? Properly Insulated? Outdoor Fan Checked?
Service Valves: Fully Opened? Caps Tight? Voltage With Compressor Operating
SEQUENCE OF OPERATION
Heating Correct? Cooling Correct?
Calibrated?
THERMOSTAT
Properly Set?
Level?
Page 23
Loading...