Electronics LP-24 User Manual

Instruction Manual
Low Profile MagnaValves
Electronics Inc.
56790 Magnetic Drive
Mishawaka, Indiana 46545
Phone: 1-574-256-5001 Fax: 1-574-256-5222 E-mail: sales@electronics-inc.com Website: www.electronics-inc.com
Model LP-24 and Model VLP-24
IM:0083 Revision: B Date: 11/1/2012
Made in the USA
y
(
)
WIRE CONNECTIONS FOR VLP-24 OR LP-24 TO AN AC-24 A MPERA GE CONTR OLLER
NOTE : The valve must be loc ate d as close to the wheel
as possible for bes t servo cont r ol stabili t
5 feet or close r
Customer CT 100:5 etc.
PANEL METER
(IF USED)
0
VLP-24/LP-24
4) Orange 0-10 Vdc input
6) Blue 24 Vdc Enable
2) Red 24 Vdc Supply
5) Black 0 Vdc Common
WHEEL MOTOR
AC-24 Controll er
8) Servo Out
9) Valve Enable
19) 24 Vdc Supply
20) 0 Vdc Common
3
1. WHITE
4
5
6
NOTE: The Controller's Full Scale display (typical
100.0) must match the customer's current transformer rating (typical 100:5 ratio). Adjust the control display range to match the actual transform er ratio. See instru ction manual.
2
2. RED
3. GREEN
4. ORANGE
5. BLACK
1
6. BLUE
0-5 amps
L3
L2
L1
Use 12 AWG wire for current loop. Use 10 AWG or larger for runs over 15 ft.
AC-24 Rear Terminal
Current Shunt .05 ohm 5 watt. P/N 999200 Included with controller.
7
.
100
(0-5A)
*
Remote setpoint can come from customer potentiometer or 0-10 Vdc signal. Also see model Pot-24 rem ote pot.
.05 Ohm shunt
.05 Ohm shunt
VLP-24 Or ange
VLP-24 Blu e +24Vdc to VLP-24 RED
Note: Connect power supply directly to the MagnaValve first and then run power back to the control using minimum 16 AWG wire size t o prevent (high curr ent ) voltage drops. Pow er supply should be re gulated and rated at 50VA per valve.
CW
2
0 Vdc common
5
Alternate: Long length of curren t loop may cause inaccuracy. To keep the 0-5 Amp current loop sh ort you may place the .05 ohm shunt at the transformer termina ls and run 18 AWG shielded ca bl e f rom shunt to control.
0Vdc to VLP-24 BLACK
www.magnavalve.com
2
Diagnostic LED’s
VALVE ON – When this LED is on or blinking, the electromagnet is receiving power. When the LED
is off, the permanent magnets will hold or block the shot flow. When the LED is on, but not blinking, the valve flow rate is at full capacity. When the LED is blinking, the electromagnet is regulating the shot flow.
Vin > 0.25 Vdc- This LED indicates that the valve is receiving an analog signal input greater than
0.25 Vdc. When this LED is off there is no media flow allowed. The input signal range is 0-10 Vdc. At 10 Vdc the valve will “open” to full capacity, which is usually 10% to 50% higher than the calibrated range. The relationship between the 0-10 Vdc input signal and actual flow rate is nonlinear. The out­put signal 0-10 Vdc signal is linear and this makes accurate regulation by the AC-24 control possi­ble.
24Vdc ENABLE – This LED indicates that the valve is receiving a 24 Vdc Enable signal. When this LED is off, the valve is inhibited, and no shot will flow. This feature is an on-off action so there is no need to disable or remove the 0-10 Vdc input signal.
24 Vdc Power – This LED indicates that 24 Vdc is available to operate the electromagnets for me­dia flow. It should always be available and able to supply 2 Amps. If the LED is blinking, the supply is above the recommended operating range +/- 2VDC (22-26VDC). If the LED is OFF, then the sup­ply is below the recommended range. If that condition occurs, please call for technical support.
All of the LED’s must be on in order to have media flow.
3
This manual will explain how to replace the mechanical media (grit) valve on a wheel type blast cleaning machine with the new MagnaValve automatic media regulator. The two most prominent reasons for this type of upgrade are:
a) to eliminate maintenance required for the air cylinder that operates the mechanical valve b) to provide an automatic alarm to alert the operator to replenish the shot/grit supply
The machine used for illustration in this manual is a RotoPeen system from Pangborn Corporation modified to shot blast clean 20 foot lengths of round pipe. It is a single wheel, 20 horsepower, pass­thru cabinet design as shown in Fig. 1 below.
Fig. 1
The following text will describe each of the remaining photos in three sections, before, during and after the installation of the MagnaValve. The entire project required less than one day for the con­version.
Note: To operate properly and prevent damage to the MagnaValve, always supply the full flow ca­pacity of the valve. For example, a VLP will flow 1000lbs/min. While only 400lbs maximum is re­quired for the application, the MagnaValve must be supplied the full 1000lbs to operate correctly. If an amount less than 1000lbs is supplied, the shot travels through the valve at a high velocity, and can damage the valve.
4
Fig. 2 An air cylinder was used to open and close the original mechanical valve as shown. This air cylinder was controlled by a manually operated 2­way air valve. The air cylinder moves the mechanical valve from its closed to open position. The amount of opening was pre-set by the operator by adjust­ing a nut on the linkage of the air cylin­der to limit the stroke.
Fig. 2
Fig. 3 This figure shows an ammeter
reading of approximately 8 amps, the no-load or no shot flow condition. A conventional panel ammeter (0-30 Amps) was used to indicate motor amps and relative shot flow rate. It is not uncommon for these meters to be inaccurate because metallic dust col­lects inside the meter movement mech­anism. This prevents the meter from displaying the proper amperage.
Fig. 3
5
Loading...
+ 10 hidden pages