Electrolux Built-in 42 Service Manual

Built-in Side by Side Refrigerator
May 2005
1
5995432258
SAFE SERVICING PRACTICES - ALL APPLIANCES
To avoid personal injury and/or property damage, it is important that Safe Servicing Practices be observed. The following are some limited examples of safe
practices:
1. DO NOT attempt a product repair if you have any doubts as to your ability to complete it in a safe and satisfactory manner.
2. Before servicing or moving an appliance:
Remove the power cord from the electrical outlet, trip the circuit breaker to
the OFF position, or remove the fuse.
Turn off the gas supply.
Turn off the water supply.
3. Never interfere with the proper operation of any safety device.
4. USE ONLY REPLACEMENT PARTS CATALOGED FOR THIS APPLIANCE.
SUBSTITUTIONS MAY DEFEAT COMPLIANCE WITH SAFETY STANDARDS SET FOR HOME APPLIANCES.
5. GROUNDING: The standard color coding for safety ground wires is GREEN, or GREEN with YELLOW STRIPES. Ground leads are not to be used as current carrying conductors. It is EXTREMELY important that the service technician reestablish all safety grounds prior to completion of service. Failure to do so will create a hazard.
6. Prior to returning the product to service, ensure that:
All electrical connections are correct and secure
All electrical leads are properly dressed and secured away from sharp
edges, high-temperature components, and moving parts
All non-insulated electrical terminals, connectors, heaters, etc. are
adequately spaced away from all metal parts and panels
All safety grounds (both internal and external) are correctly and securely
connected
All panels are properly and securely reassembled
ATTENTION!!!
This service manual is intended for use by persons having electrical and mechnical training and a level of knowledge of these subjects generally considered acceptable in the appliance repair trade. Electrolux Home Products cannot be responsible, nor assume any liability, for injury or damage of any kind arising from the use of this manual.
© 2001 White Consolidated Industries
25995432258
Table of Contents
3-Way Valve .................................................................................................................................40
Auger Motor .................................................................................................................................32
Casters and Leveling ....................................................................................................................26
Components ................................................................................................................................. 23
Component Locator Views ...........................................................................................................12
Component Resistance Values ...................................................................................................... 8
Compressor .................................................................................................................................. 39 - 61to 65
Control Features ............................................................................................................................10
Cube Motor and Cube Reed Switch ..............................................................................................32
Defrost Cycles ...............................................................................................................................43
Diagnostic Mode ...........................................................................................................................54
Dispenser Control Panel ................................................................................................................34
Dispenser Heater ...........................................................................................................................37
Dispenser Switch ...........................................................................................................................37
Doors ............................................................................................................................................ 23
Door Closer Assembly ...................................................................................................................25
Door Switches ............................................................................................................................... 41
Door Water Line Replacement .......................................................................................................38
Drain Pan ...................................................................................................................................... 26
Drier .............................................................................................................................................. 40
Duct Door Assembly ......................................................................................................................36
Evacuation and Charging Procedure ............................................................................................. 16
Fans .............................................................................................................................................. 44
Freezer Evaporator Assembly ....................................................................................................... 46
Freezer Evaporator Components .................................................................................................. 49
Freezer Heater Testing .................................................................................................................. 46
Fresh Food Evaporator Assembly ................................................................................................. 50
Fresh Food Evaporator Components ............................................................................................ 52
Fresh Food Heater Testing ............................................................................................................ 50
Heat Exchanger ............................................................................................................................. 39
Icemaker Controls ..........................................................................................................................11
Icemaker Fill Tube and Heater .......................................................................................................31
Ice Bin and Icemaker .....................................................................................................................31
Ice Dispenser ................................................................................................................................ 35
Installation Example 42" Model ......................................................................................................5
Interior Airfl ow .............................................................................................................................17
Interior Lights ................................................................................................................................42
Introduction ................................................................................................................................... 4
Machine Compartment Access Door .............................................................................................23
Main Switch ..................................................................................................................................34
Mufflers .........................................................................................................................................39
Nomenclature ............................................................................................................................... 9
Power Control Board (PCB) ..........................................................................................................27
Refrigerant Flow ............................................................................................................................14
Refrigeration Components .............................................................................................................13
Refrigeration System .....................................................................................................................13
Replacing the Freezer or Fresh Food Evaporator ........................................................................ 52
Schematics ................................................................................................................................... 58
Service Diagnostics ...................................................................................................................... 54 to 65
Technical Data ............................................................................................................................... 8
Terminal Block Panel .....................................................................................................................29
Thermistors ................................................................................................................................... 42
Troubleshooting Notes .........................................................................................................
Water Valve and Water T ank ......................................................................................................... 35
......... 57
IntroductionINTRODUCTION
3
5995432258
INTRODUCTION
The new Profi le Built-In Side by Side refrigerator has the following features:
Separate freezer and fresh food evaporators are recessed into the machine compartment for increased effi ciency and interior space savings. 3-Way valve directs refrigerant fl ow where needed. High-and low-side sealed system muffl ers quiet the operation. Inverter is built into the power control board (PCB). Combined dispenser and temperature control board provides customer control and test mode operations. Dispenser cube motor and cam replaces solenoid-operated cube mechanism. Room ambient thermistor aids power control board (PCB) operation. Component electrical testing is performed at the machine compartment-mounted terminal block. Rear leveling mechanism is front-adjustable.
Installation Example 42" Mo
45995432258
INSTALLATION EXAMPLE 42” MODEL
THE INSTALLATION SPACE
7”
* The finished cutout width must be: 41-1/2” for 42” models
Water and Electrical Locations
The opening must be prepared with the electrical and water supply located as shown.
The cutout depth must be 24"
The refrigerator will project forward, slightly beyond adjacent cabinets, depending on your installation.
Additional Specifications
• A 120 volt, 60Hz, 15 or 20 amp power supply is required. An individual properly grounded branch circuit or circuit breaker is recommended. Install a properly grounded 3-prong electrical receptacle recessed into the back wall. Electrical must be located on rear wall as shown. Note: GFI (ground fault interrupter) is not recommended.
• Water line can enter the opening through the floor or rear wall. The water line installed should be 1/4" O.D. copper tubing between the cold water line and water connection location. The line should be long enough to extend to the front of the refrigerator. Installation of an easily accessible shutoff valve in the water line is required.
Wood Panel 70 LB food door 30 LB freezer door
DIMENSIONS AND CLEARANCES
*Shipping height The front height may be adjusted from 83-1/2" to 84-1/2" by adjusting front and rear leveling legs a maximum of 1".
Product Clearances
These refrigerators are equipped with a 2 position door stop. The factory set 130° door swing can be adjusted to 90° if clearance to adjacent cabinets or walls is restricted
May Change with our handle
Allow minimum clearances for Freezer door (Dimension A) and Fresh Food door (Dimension B) for a full 130° door swing and to allow for drawer removal. Four inch (4") minimum clearance is required when door swing is adjusted to 90°. If the 90° door stop position is used, drawer access is maintained, but drawer removal is restricted.
5
5995432258
65995432258
DISCONNECT POWER CORD BEFORE SERVICING IMPORTANT - RECONNECT ALL GROUNDING DEVICES
7
5995432258
TECHNICAL DATA
All parts of this appliance capable of conducting electrical current are grounded. If grounding wires, screws, straps, clips, nuts or washers used to complete a path to ground are removed for service, they must be returned to their original position and properly fastened.
CAUTION
To avoid personal injury when servicing the condensing unit, stand on a ladder which will give enough support to allow removal of the top panel and safely allow access to service the unit.
REFRIGERA TION DIAGNOSIS
ELECTRICAL SPECIFICA TIONS
Max Defrost Control
w/No Door Openings........................16 hrs
Evap Defrost Thermistor........68°F (FZ)..63°F (FF)
Electrical Rating: 115V AC 60 HZ.............5.4 amp
Maximum Current Leakage......................0.75 mA
Maximum Ground Path Resistance...............0.1 W
Energy Consumption Model 42........50.5 KWh/mo
Energy Consumption Model 48......53.75 KWh/mo
COMPOENENT RESISTANCE VALUES
FF fan motor ……………………..............1600 &! ± 20%
FZ fan motor ………………………….......1600 &! ± 20%
Condenser fan motor ………………........1600 &! ± 20%
Auger motor ………………………..............3.7 &! ± 15%
Cube motor …………………………….....2091 &! ± 10%
Cover motor ……………………………....2091 &! ± 10%
Defrost heater FZ ……..................................44 &! ± 7%
Drain heater FZ ..........................................377 &! ± 7%
Sub-heater FZ ………...............................1322 &! ± 7%
Defrost heater FF .......................................120 &! ± 7%
Drain heater FF …......................................440 &! ± 7%
Fill-tube heater .……….............................2645 &! ± 7%
Dispenser heater (Recess)………………..1889 &! ± 7% Compressor (between the different
phase) …………….....................11. 7 &! ± 7% / 1 phase
3- way valve …………………………..40 ± 4 &!/ 1 phase
Water valve (Ice maker) …………...............180 &! ± 7%
Water valve (Dispenser) ..………................325 &! ± 7%
IMPORTANT SAFETY NOTICE
This information is intended for use by individuals possessing adequate backgrounds of electrical, electronic and mechanical experience. Any attempt to repair a major appliance may result in personal injury and property damage. The manufacturer or seller cannot be responsible for the interpretation of this information, nor can it assume any liability in connection with its use.
NO LOAD PERFORMANCE
Control Position 37-0°F and Ambient T emperature of: 70°F 90°F Fresh Food °F 37-42 36-43 Frozen Food °F (-2)-2 (-2)-5
Percent Running Time, %..........35-45 65-75
REFRIGERATION DIAGNOSIS
To access the low pressure side of the system, install a line tap valve on the process tube extending from the compressor case.
REFRIGERATION SYSTEM
Refrigerant Charge (R134a)......................8.11 ounces
Compressor......................................738-1270 BTU/hr
Minimum Compressor Capacity
Vacuum..........................................................26 inches
Minimum Equalized Pressure
@70°F.............................................................66 PSIG
@90°F.............................................................74 PSIG
To change the
Technical Data
Nomenclature
Icemaker Controls
85995432258
MODEL AND SERIAL NUMBER INFORMATION
E42BS85EPS THE PS IS FOR STAINLESS STEEL E42BS75ETT THE TT IS FOR MODEL WITH TRIM ON DOORS
Serial Plate Location
The Serial plate is located at the top of the fresh food section on the right-side wall. It contains the model and serial numbers and specifi es
the minimum installation clearances, electrical voltage, frequency, maximum amperage rating, and refrigerant charge.
Mini-Manual
The mini-manual is located behind the grille panel at the top of the refrigerator. When service is completed, return the mini-manual to its original location for future use.
Serial Number
The first letter tells us where the product was made, the second letter tells us what type product it is. The first number is the year the product was made. The next two numbers are the week the product was made. Example BA51400000, B - Is the Anderson refrigerator factory. A - Is a refrigerator 5 - Is 2005 14 - Is week 14 The rest of the numbers are the sequence number for week 14 of 2005.
9
5995432258
Control Features
The temperature controls are preset in the factory at 37°F for the refrigerator compartment and 0°F for the freezer compartment. Allow 24 hours for the temperature to stabilize to the preset recommended settings. The temperature controls can display both the SET temperature as well as the actual temperature in the refrigerator and freezer.
The actual temperature may vary slightly from the SET temperature based on usage and operating environment. NOTE: The refrigerator is shipped with protective film covering the
temperature controls. If this film was not removed during installation, remove it now.
Icemaker Controls
Once the desired temperature has been set, the temperature display will clear after 10 seconds. To display the temperature, the DISPLAY TEMP button may be tapped. Several adjustments may be required. Each time you adjust controls, allow 24 hours for the refrigerator to reach the temperature you have set.
105995432258
To Use the Dispenser
Select CUBED , CRUSHED or WATER . Press the glass gently against the middle of the dispenser pad. The spill shelf is not self-draining.To reduce water spotting, the shelf and its grille should be cleaned regularly.
If no water is dispensed when the refrigerator is first installed, there may be air in the water line system. Press the dispenser arm for at least two minutes to remove trapped air from the water line and to fill the water system. To flush out impurities in the water line, throw away the first six glassfuls of water.
CAUTION:
Never put fingers or any other objects into the ice crusher discharge opening.
Locking the Dispenser
Press the LOCK/LIGHT button for 3 seconds to lock the dispenser and control panel. To unlock, press and hold the button again for 3 seconds.
Quick Ice
When you need ice in a hurry, press this button to speed up ice production. This will increase ice production for the following 48 hours or until you press the button again.
Dispenser Light
This button turns the night light on the dispenser on and off. The light also comes on when the dispenser pad is pressed. If this light burns out, it should be replaced with a 6 watt 12V maximum bulb.
Door Alarm
To turn the Door Alarm on, press the DOOR ALARM button once. The ACTIVE light will come on. To turn it off, press it again. When the DOOR ALARM is active, the ACTIVE light will flash if you open the door and beep if you keep the door open for more than 2 minutes. The light goes out and the beeping stops when you close the door.
Spill Shelf
Note: When QUICK ICE is selected, the freezer temperature operates at -9°F for 48 hours or until QUICK
is pressed again. There is no change of temperature on
ICE
the display panel. In the event of a power loss, if the freezer temperature is above 40°F, Quick Ice will not restart. Below 40°F, the refrigerator will return to the Quick Ice mode.
Display after power failure:
After a power failure, the display will reset based on freezer temperature. If the freezer temperature is below 40°F, the display will retain the settings prior to power loss. The chart at the right describes the possible settings.
11
5995432258
Component Locator Views
Component Locator Views
125995432258
Refrigeration Components
Refrigeration System
13
5995432258
Refrigerant Flow
The compressor compresses R134a refrigerant, raising its pressure and temperature. Refrigerant vapor is pumped out the compressor discharge, down through the drain pan loop, up through the condenser coil, around the condenser loop, through the drier, and into the 3-way valve. By the time the refrigerant has reached the 3-way valve, it has completely condensed into a liquid. Depending upon whether the main control board opens the 3-way valve to the freezer evaporator
or the fresh food and freezer evaporators, refrigerant fl ows through the appropriate capillary tube and into the evaporator. As the high pressure liquid passes through the capillary and enters the low pressure evaporator, it quickly expands and evaporates. During evaporation, the refrigerant absorbs heat, becoming cold. At the outlet of the freezer evaporator, an accumulator captures any remaining liquid, allowing only low pressure vapor to return to the compressor through the suction line.
145995432258
Note: The refrigerator will operate with the 3-way valve set for freezer only or set for fresh food and freezer. There is no 3-way valve setting for fresh food only. If the fresh food thermistor is not satisfi ed, but the freezer thermistor is satisfi ed, the refrigerator will still operate with the 3-way valve set in the fresh food and freezer mode.
15
5995432258
Evacuation and Charging Procedure
Equipment Needed for Evacuation & Recharging:
• Heated charging cylinder
• Standard 3-port manifold gauge set: 4 charging hoses Tee fitting with valve core stem removed
(Robinair No. 40396)
Hand shut-off valve (Robinair No.40380)
• Two stage vacuum pump
• Process tube adapter kit (Robinair No. 12458)
• Tubing cutter
• Pinch-off tool capable of making leak proof seal
• Complete brazing torch set
• Small 3-corner file
• Grit cloth or Scotch-Brite
• 45% silver solder and flux
Installing Evacuation and Recharging Equipment
1. Disconnect refrigerator from electrical supply.
2. If compressor was replaced, install correct sized
process tube adaptor on process tube. If compressor was not replaced, cut process tube with tubing cutter leaving as much tube as possible and install correct size process tube adaptor.
3. Install correct sized process tube adaptor on high-side process tube.
4. Attach refrigeration service gauge manifold to system in following order:
Low-side (compound gauge) hose to
suction side process tube adaptor.
High-side (pressure gauge) hose to high-
side process tube adaptor.
Center port manifold hose before hand
shut-off valve to charging cylinder.
Center port manifold hose after hand
shut-off valve to vacuum pump.
Evacuating System
WARNING: R-134A SYSTEMS ARE PARTICULARLY SUSCEPTIBLE TO MOISTURE CONTAMINATION WHICH CAN ONLY BE PREVENTED BY EVACUATING THE SYSTEM FOR A MINIMUM OF 30 MINUTES TO ATTAIN A MINIMUM 29.9 INCH (500 MICRON OR LOWER) VACUUM.
To achieve the required levels of evacuation, a properly maintained two stage vacuum pump in good condition is required. It is absolutely essential to maintain your vacuum pump according to the manufacturer’s instructions including required oil changes at the recom­mended intervals. Vacuum pump oil should always be changed after evacuating a contaminated system.
Vacuum pump performance should be checked periodically with a micron gauge.
1. Make certain that charging cylinder valve, hand shut-off valve, and manifold gauge valves are closed.
2. Start vacuum pump.
3. Open hand shut-off valve and slowly open both manifold valves, turning counterclockwise, for two full rotations.
CAUTION: If high vacuum equipment is used, just crack both manifold valves for a few minutes and then open slowly for the two full turns counterclockwise. This will prevent the compressor oil from foaming and being drawn into the vacuum pump.
4. Operate the vacuum pump for a minimum of 30 minutes to a minimum of 29.9” (500 micron) vacuum.
5. Close hand shut-off valve to vacuum pump. Watch compound gauge for several minutes. If reading rises, there is a leak in the system, go to step 6. If no leak is indicated, stop vacuum pump. System is now ready for charging.
6. If a leak is indicated, stop vacuum pump and introduce a small charge of refrigerant into system by cracking valve on bottom of charging cylinder until system is pressurized to 40 or 50 l bs psig.
7. Leak test low-side. Close compound gauge. Run compressor for a few minutes and leak test high-side. When leak is found, recapture refrig erant using EPA approved recovery system Repair and go back to step 1.
Charging The System
CAUTION: Check the serial plate for the cor­rect refrigerant type. It is extremely important to verify the type of refrigerant in the system before starting any sealed system repairs.
CAUTION: After charging the system with liquid be certain to wait at least 5 minutes before starting the compressor to give the refrigerant a chance to disperse throughout the system. Otherwise the compressor could be damaged by attempting to pump exces­sive quantities of liquid.
Preparing The Charging Cylinder:
1. Make certain that hand shut-off valve to vacuum pump is closed.
2. Close high-side manifold gauge valve.
3. Set charging cylinder scale to pressure indicated on cylinder pressure gauge.
4. Observe refrigerant level in sight glass. Subtract amount to be charged into system and note shut off point.
5. Open charging cylinder valve slowly and allow proper charge to enter system.
165995432258
6. As soon as refrigerant in sight glass has gone down to predetermined level, close charging cylinder valve.
WARNING: DISCONNECT THE CHARGING CYLINDER HEATER AT THIS TIME TO PREVENT THE CYLINDER PRESSURE FROM EXCEEDING ITS MAXIMUM LIMITS.
7. Allow system to sit for five minutes.
8. Turn on refrigerator compressor. Run compres sor for a few minutes and monitor system pressures.
9. When satisfied that the unit is operating cor rectly, clamp the high-side process tube with the pinch-off tool while the unit is still running.
10.Slowly open the high-side manifold gauge valve to allow the compressor to remove any refriger ant trapped in the high-side hose and the process fitting.
11.Close both of the manifold gauge valves. If the high-side gauge reading rises, the pinch-off must be corrected before proceeding.
12.Remove the high-side process tube adaptor and solder the process tube closed.
13.Clamp the low-side process tube with the pinch­off tool while the unit is running. Remove the low-side process tube adaptor and solder the process tube closed.
14.Check the process tubes for refrigerant leaks.
Final leak test
1. With the refrigerator turned OFF leak test all low-side system components.
2. Turn the unit ON and run until the condenser is warm. Leak test the high-side system compo­nents.
HOT
TUBE
EVAPORATOR
CONDENSER
FILTER DRIER
TEE
FITTING
PROCESS TUBE
ADAPTERS
COMPOUND
GAUGE
PRESSURE
GAUGE
GAGE
MANIFOLD
HAND SHUTOFF
VALVE
HEATED CHARGING CYLINDER
COMPRESSOR
Figure E2
17
2 STAGE VACUUM
PUMP
5995432258
R-134a service information
NOTICE: Instructions given here are furnished as a guide. Persons attempting to use these instructions to make
repairs to the sealed refrigeration system should have a working knowledge of refrigeration and previous training on sealed system repair.
Verify refrigerant type in the system
CAUTION: R-134a and R-12 are completely incompatible. Before starting any sealed system repair, it is extremely important to check serial plate of product to verify the type of refrigerant in the system.
Dedicated Equipment
R-134a must not be mixed with other types of refrigerants. R-134a must be recovered in dedicated and properly identified recovery bags and tanks.
It will be necessary to check with the manufacturer of your recovery equipment to determine R-134a compatibility. Some recovery equipment manufacturers have changeover instructions for switching between refrigerant types. Protect yourself and your equipment by following all manufacturer guidelines.
Also, ensure that your refrigeration hoses are specified for use with R-134a refrigerant. Research has shown that compounds in standard refrigeration hoses may enter sealed systems and ultimately restrict the cap tube in an R-134a system.
R-134a refrigeration systems
The sealed refrigeration system will consist of the same basic components being utilized in the R-12 systems.
There is a 10% to 15% discharge pressure increase using R-134a, with a 5% to 10% decrease in suction pressure when compared to the same product with an R­12 system operating at 90°F (32°C) ambient tempera­ture conditions. Lower suction pressures result from the lower density of R-134a refrigerant which effects refriger­ant flow rate. R-134a systems commonly operate in a 1”­2” vacuum on the suction side.
Products using R-134a refrigerant will generally have a longer capillary tube to maintain a similar flow rate and some models will have a larger condenser to reduce the discharge pressures and lower start-up sound transmis­sion.
Miscibility of r-134a and ester oil
A special synthetic oil known as Ester oil is used as a lubricant in refrigeration systems operating on R-134a. Ester oils are produced from alcohols and fatty acids
and are available in several different variants. Ester
oils have a pleasant aroma reminiscent of fruit.
Ester oils generally include various types of additives for improving certain properties such as viscosity, temperature sensitivity, etc. These additives are often aggressive, and skin contact with Ester oils should therefore be avoided.
One of the most important requirements made on a refrigerant system is that the oil mix with the refrigerant. Since mineral oil and ordinary synthetic oil DO NOT mix with R-134a, Ester oil is used for lubrication. Ester oil dissolves in R-134a.
Ester oil is broken down by chlorine and cannot be used with R-12 (R-12 contains chlorine) or any other compound containing chlorine. Therefore, R-134a refrigeration systems have virtually no tolerance for chlorine molecules from CFC refrigerants (R-134a is an HFC and contains no chlorine).
CAUTION: During R-134a service, it is extremely important to avoid using equipment that may contain residual amounts of mineral oil, CFC’s or HCFC’s which could enter and contaminate the sealed system.
For example, hoses that were used for a refrigeration system operating on R-12 may contain small quantities of mineral oil which can block the capillary tube in a system operating on R-134a. As little as one milligram may be sufficient to cause a blockage. In addition, sealed system components that have been used with CFC systems must not be used with R-134a systems. These components may contain residual amounts of refrigerant and oil which could damage an R-134a system.
At the earliest stage of development work on R­134a, tests were carried out on a different type of synthetic oil known as Poly-Alkaline Glycol (PAG). This oil is also used in certain air conditioning systems for cars. PAG and Ester oil DO NOT mix with one another. Service equip­ment used for R-134a / Ester oil must not come into contact with PAG.
185995432258
Water in the refrigeration system
Even in very small quantities, water in any refrigera-
tion system can cause the following problems:
• Ice plugs in capillary tubes.
• Copper plating in compressor.
• Reactions with organic materials in systems.
• Corrosion of metals.
R-134a and Ester oil will aggravate the problem of water in the refrigeration system. Ester oil may react with water vapor and is hydroscopic (it will absorb water if it comes in contact with humid air). Water is also more soluble in R-134a than R-12.
2-Stage Vacuum Pump
To minimize the water content whenever service work is performed, the refrigeration system should always be thoroughly evacuated through process tube adaptors on both the high and low sides of the system. Evacuation must be for a minimum of 30 minutes to at least a 29.9 inch (500 micron) vacuum.
TRAHCMUUCAV
muucaV
.gHsehcnI
snorciM
tnioPgnilioB
F°retaWfo
049.82000529.77
035.92000010.25
238.9200640.23
288.9200010
.1
109.920052.11-
519.920518.23-
719.920012.83-
919.92050.94-
Figure
E3
Vacuum pump maintenance
It is absolutely essential to maintain your vacuum pump according to the manufacturer’s instructions including required oil changes at the recommended intervals. Vacuum pump oil should always be changed after evacuating a contaminated system. Vacuum pump performance should be checked periodically with a micron gauge.
Vacuum pump suppliers may or may not recommend changing the vacuum pump oil to the same type that’s in the system being evacuated. Some manufacturers may recommend a vacuum pump that’s dedicated to R-134a systems.
Robinair has stated that their current and discontinued vacuum pump models, using mineral oil currently specified for use in their vacuum pumps, can be used to evacuate R-134a/Ester oil systems. Robinair also states that it is acceptable to alternate between evacuating R-12/mineral oil and R-134a/Ester oil systems without adversely effecting the vacuum pump’s performance.
For other brands of vacuum pumps, check with the manufacturer for restrictions and guidelines when using with R-134a.
To achieve the required 29.9 inch (500 micron) vacuum, a properly maintained two-stage vacuum pump in good condition is required. A two stage pump can reach a deeper vacuum than a single stage because the exhaust from the first pumping stage is discharged into the second pumping stage. This means the second stage begins pumping at a lower pressure so a lower ultimate vacuum can be achieved (See 2-Stage Vacuum Pump, Figure E3).
CAUTION: If you use a vacuum pump with mineral oil to evacuate an R-134a system, it is ABSOLUTELY ESSENTIAL to have a shut­off valve between pump and your manifold gauge set as shown in Figure E4. The hand valve must be closed during all times when vacuum pump is not operating. This will prevent migration of mineral oil vapor into R134a/Ester oil system. If vacuum pump should stop during evacuation for any reason, the hand pump shut-off valve must be closed immediately.
19
5995432258
HOT
TUBE
EVAPORATOR
FILTER DRIER
TEE
FITTING
COMPOUND
GAUGE
PRESSURE
GAUGE
GAGE
MANIFOLD
HAND SHUTOFF
VALVE
HEATED CHARGING CYLINDER
CONDENSER
PROCESS TUBE
ADAPTERS
Evacuating and Recharging Connections
Refrigerant leaks
A system with R-134a and Ester oil will become saturated with moisture much faster than a system with R-12 and mineral oil. The compressor in an R-134a system will have to be replaced if the product has had a low side leak.
R-134a refrigerant molecules are smaller than R-12 molecules. This means that R-134a will pass more minor leaks and the rate of flow will be greater than for R-12. Therefore, it is now more important than ever to follow good brazing practices. Use a good grade of silver solder. 45% silver solder is recommended.
leak detection
R-134a system leaks can be pinpointed by means of an electronic leak detector or by bubble solution.
Electronic leak detectors for R-134a service are currently available from several manufacturers. The least expensive models are non-selective detectors that will detect any type of emission or vapor present, regardless of its chemical composition. Some non-selective detectors designed for use with R-12 may have a much lower sensitivity when used with R-134a. However, newly designed detectors with good R-134a sensitivity are now available. Be sure to consult with the manufacturer before selecting or using a non-selective detector with R-134a.
Halogen-specific detectors use a specialized sensor that allows detection of compounds containing chlorine, fluorine, bromine, and iodine without being activiated by other species. The major advantage of this type of detector is a reduction in the number of “nuisance alarms”. Halogen-specific detectors are generally more expensive
COMPRESSOR
Figure
E4
2 ST AGE VACUUM
PUMP
than non-selective detectors but feature higher sensitivity.R-134a properties
R-134a properties
The properties of R-134a are very similar to those of R12. The principal data for the two refrigerants are shown in the chart below.
STNAREGIRFER
21-Ra431-R
EMAN
alumroF
)lom/g(thgieWraluceloM
laitnetoPnoitelpeDenozO
)PDO(
laitnetoPgnimraWlabolG
)PWG(
F°tnioPgnilioB
)F°77(erusserPropaV
ytilibammalF
niretaWfoytilibuloS
)F°77@%tw(tnaregirfeR
-oroulfidorolhciD
enahtem
ICC2F
2
39.0213.201
10
1.33.0
6.12-7.51-
gisp08gisp28
enoNenoN
900.011.0
HC
-arteT--2,1,1,1
enahtemoroulf
FC-F
2
3
205995432258
Loading...
+ 45 hidden pages