Main features
• Photoelectric sensor for slow smouldering res (EWF1) / Com­bined photoelectric and electrochemical sensor for slow smoul­dering res and carbon monoxide (CO) detection (EWF1CO)
• TEST WEEKLY button
• Non-radioactive technology for environmental friendly
EWF1 is a wireless photoelectric-based smoke detector designed to detect smouldering re before bursting into ame, while EWF1CO is a wireless electrochemical-based carbon monoxide (CO) detector combined with photoelectric-based smoke detector designed to detect smouldering re. When the concentration of smoke/CO exceeds a given threshold, the system will cause resulting in built-in siren activa­tion and SMS text message and phone call delivery (by default) to the listed user phone number. By default, when more than one EWF1/ EWF1CO device is used, the system will automatically activate the interconnection fea ture. See 4.1. Interconnection.
ESIM264, EPIR2 and EPIR3 alarm systems support up to 16 EWF1 devices, while ESIM364 - up to 32 EWF1 devices. Up to 16 EWF1CO can be connected to EPIR3 alarm system, while ESIM364 supports up to 32 EWF1CO devices. The maximum wireless connection range is 150m (492.13ft) (in open areas).
NOTE: EWF1 contains a smoke sensor solely, while EWF1CO contains a carbon monoxide (CO) sensor and a smoke sensor.
NOTE: For complete information on device operation with ELDES alarm system, please refer to ELDES alarm system installation manual
located at www.eldes.lt/download
• EPIR3 all versions.
• PITBULL EPIR3 all versions.
• PITBULL EPIR3 V02.02.00 and up.
• High and stable sensitivity
• Quick x mounting plate for easy installation
• LED operation indicator
• Built-in speaker for audio alarm indication
• Auto-reset when smoke clears
1. PACKAGE CONTENT
Item Quantity
1. EWF1/EWF1CO..................................................1
2. User manual............................... .......................1
3. Primary 9V Lithium 1200mAh battery .........1
4. Screws ...............................................................2
2. TECHNICAL SPECIFICATIONS
2.1. Electrical & Mechanical Characteristics
Battery.......................................................................... Primary 9V Lithium 1604LC (ANSI/NEDA)
Number of batteries ................................................. 1
Battery operation time ............................................ 18 months*
Wireless band ............................................................. ISM868/ISM915
Wireless communication range .............................. Up to 30m (98.43ft) in premises; up to 150m (492.13ft) in open areas
Smoke detection type .............................................. Photoelectric chamber
Sensitivity to smoke ................................................. 3.0-6.0 % O bs/m
Carbon monoxide detection type ........................... Electrochemical
Carbon monoxide detection range ........................ 0-400 ppm
Alarm sound level ..................................................... 85dB at 3m (85dB at 9.84ft)
EWF1 lifetime ............................................................. 10 years
EWF1CO lifetime ........................................................ 7 years
Range of operating temperatures . ........................+5... +45°C (41... 113°F)
Humidity ..................................................................... 0-90% RH @ 0... +40°C (0-90% RH @ +32... +104°F) (non-condensing)
Dimensions ................................................................ 110mm (4.33in) Ø
* The specied operation time applies in case of no alarms and when having the device tested once a week. The operation time might vary
in dierent conditions.
2
2 EN
2.2. Main Unit & LED Functionality
TEST WEEKLY Button for testing the unit / restoring the zone
LED EWF1/EWF1CO status indication
SIREN Built-in speaker for audio alarm indication
RESET Button for restoring default parameters
TAMPER Tamper switch
1
SIREN
FRONT SIDE BACK SIDE
TEST WEEKLY
T
N
I
A
P
D
T
O
O
N
LED
3. PLACEMENT
1. Place the detector as close to the center of the ceiling as possible. If this is not practical, mount no closer than 10cm (0.33ft) from a wall
or corner. Also, if local codes allow, install the detectors on walls, between 10 and 30cm (0.33 and 0.98ft) from ceiling/wall intersec­tions.
2. Install a minimum of two units in every house, no matter how small the house is.
3. Place a detector in each room that is divided by a partial wall (either coming down from the ceiling at least 20cm (0.66ft), or coming up
from the oor).
NOTE: For best protection we recommend that you install a detector in every room.
Recommended EWF1/EWF1CO placement locations
2
ANYWHERE
IN THIS AREA
0,9m (2.95 ft) 0,9m (2.95 ft)
Ceiling
Acceptable
here
TAMPER
NEVER
HERE
Top of detector
acceptable here
0,1 m
(0.33ft)
BATTERY
0,1 m
(0.33ft)
Max.
0,3m
(0.98ft)
Max.
RESET
HORIZONTAL DISTANCE
NOTE: Measurements shown are to the closest edge of the detector.