EFCO 8800 Assembly Instructions Vol.5

Page 1
Concealed Vent Assembly Instructions Volume 5 of 6 - Sections 15 - 32
July 2011
PART NO. Y805
Page 2
EFCO 2009 Page 2
Series 8700 / 8800 Unitized Curtain Wall Assembly Instructions - Volume 5
Table of Contents
Volume 1 of 6
1. General Notes and Guidelines
2. Parts Identification
3. Frame Assembly
Volume 2 of 6
4. Unit Glazing Preparation : SSG and Captured
5. SSG Unit Glazing
6. Captured Unit Glazing
Series 8700 / 8800 Unitized Curtain Wall Assembly Instructions - Volume 5
Volume 3 of 6
7. Outside 90° Corner Frame Assembly
9. Outside 90° Corner Unit Glazing Preparation : SSG and Captured
10. Inside 90° Corner Unit Glazing Preparation : SSG and Captured
Volume 4 of 6
11. Outside 90° Corner SSG Unit Glazing
12. Inside 90° Corner SSG Unit Glazing
13. Outside 90° Corner Captured Unit Glazing
14. Inside 90° Corner Captured Unit Glazing
Note: Assembly Instructions are provided as a supplement, and should be used in conjunction with
the approved shop drawings.
EFCO 2009 Page 2
Page 3
EFCO 2009 Page 3
Series 8700 / 8800 Unitized Curtain Wall Assembly Instructions - Volume 5

Table of Contents

Volume 5 of 6
SECTION PAGE
15. General Notes and Guidelines……..……………………………………………………
16. Size Limitations…………………………………………………………………………….
17. Standard Hardware Identification……………………………………………………….
18. Frame Assembly - Vent at Fixed Horizontal…………………………………………..
19. Frame Assembly - Vent at Stack Sill……….…………………………………………..
20. Unit Glazing Preparation - Vent at Fixed Horizontal…………………………………
21. Unit Glazing Preparation - Vent at Stack Sill……….…………………………………
22. SSG Vent Unit Glazing at Fixed Horizontal
A. Temporary Glazing Locators…………………………......................................
B. Setting and Caulking Glazing …………………………………………………… C. Adapter Installation………………….…………………………………………….. D. Weather Seal Application…………………………………………………………
23. SSG Vent Unit Glazing at Stack Sill
A. Temporary Glazing Locators…………………………......................................
B. Setting and Caulking Glazing …………………………………………………… C. Adapter Installation………………….…………………………………………….. D. Weather Seal Application…………………………………………………………
24. Captured Vent Unit Glazing at Fixed Sill
A. Temporary Glazing Locators…………………………......................................
B. Setting and Caulking Glazing …………………………………………………… C. Adapter and Cover Installation………………………………………………….. D. Joint Plug Installation…………………………………………………………….
Series 8700 / 8800 Unitized Curtain Wall Assembly Instructions - Volume 5
6 7 8 - 9 10 - 13 14 - 17 18 - 19 20 - 21
22 23 - 24 25 - 27 28
29 30 - 31 32 - 34 35
36 37 - 38 39 - 42 43
Note: Assembly Instructions are provided as a supplement, and should be used in conjunction with
the approved shop drawings.
EFCO 2009 Page 3
Page 4
Series 8700 / 8800 Unitized Curtain Wall Assembly Instructions - Volume 5
Series 8700 / 8800 Unitized Curtain Wall Assembly Instructions - Volume 5
Table of Contents
Volume 5 of 6
SECTION PAGE
25. Captured Vent Unit Glazing at Stack Sill
A. Temporary Glazing Locators…………………………......................................
B. Setting and Caulking Glazing …………………………………………………… C. Adapter and Cover Installation………………………………………………….. D. Joint Plug Installation……………………………………………………………...
26. Assembly and Glazing - SSG Vent at Fixed Horizontal……………………………..
27. Assembly and Glazing - SSG Vent at Stack Sill………………………………………
28. Assembly and Glazing - Captured Vent at Fixed Horizontal……………………….
29. Assembly and Glazing - Captured Vent at Stack Horizontal……………………….
30. Hardware Mounting On Unit Assembly………………………………………………..
31. Hardware Mounting On Sash…………………………………………………………….
32. Mounting Vent Assembly Into Unit Assembly………………………………………..
45 46 - 47 48 - 52 53 54 - 58 59 - 63 64 - 68 69 - 73 74 - 75 76 - 85 86 - 90
Volume 6 of 6
33. Shadow Box Assembly
34. Shadow Box Installation
35. Shadow Box Insulation Installation
36. Back Panel Installation
37. Back Panel Insulation Installation
38. Final Cleaning
Minimizing Condensation
Note: Please reference EFCO's "Understanding Condensation" brochure which can be obtained through your EFCO representative. Condensation will form on any surface when unfavorable conditions (interior temperature and relative humidity and exterior temperature) are present. When the formation of excessive condensation is a concern, it is highly recommend ed that a design professional is utilized to perform an analysis of the shop drawings to recommend the best possible installation methods. Please contact your EFCO representative for information on EFCO's Thermal Analysis Services. Many current installation practices lead to an increase in the possibility of the formation of condensation. Though not all inclusive, the list of examples below illustrates conditions under which condensation is lik ely to occur:
1. Bridging system thermal break with non-thermally broken metal flashing or lintels th at are exposed to the exterior
2. System exposure to cold air cavities
3. Interior relative humidity levels not maintained at recommended levels, see EFCO’s “Understanding Condensation” brochure
4. Inadequate separation between system and surrounding condition at perimeter
5. Product combinations during the shop drawing stage that result in bridging thermal breaks of one or all products involved
Note: Assembly Instructions are provided as a supplement, and should be used in conjunction with the approved shop drawings.
EFCO 2011 Page 4
Page 5
Series 8700 / 8800 Unitized Curtain Wall Assembly Instructions - Volume 5

Section 15 - General Notes and Guidelines

1. Below illustrates the recommended hardware locations for various unit config urations.
2. The exact lock locations and quantities will be determined on a job by job basis and will vary with the design pressure and vent configuration for a given project. Refer to the final approved shop drawings for quantities and locations. Snubbers at the vent head may not be required depending on structural loads and the size of the vent.
3. Opening limiting hardware is required for all vent installations. The maximum opening size for vents will be determined by local code, but may not exceed more than opening at a 20 degree angle normal to the plane of the wall for safety reasons.
Snubber Locations
Jamb Lock Locations
Limit Arm Locations
Sill Lock Locations
Lock Handle Locations
Typical Hardware Locations
EFCO 2009 Page 5
Page 6
Series 8700 / 8800 Unitized Curtain Wall Assembly Instructions - Volume 5

Section 16 - Size Limitations

84”
80”
75”
70”
Maximum Rectangular Vent
Size 84” x 36” or 36” x 84”
Minimum Vent
Size 20” x 20”
65”
60”
55”
50”
45”
40”
35”
30”
25”
20”
Maximum Square
Vent Size 60” x 60”
30” 35” 55” 60” 65” 80” 40” 45” 50” 84” 70” 75”
25” 20”
EFCO 2009 Page 6
Page 7
Series 8700 / 8800 Unitized Curtain Wall Assembly Instructions - Volume 5

Section 17 - Hardware Identification

Image
Part # Description
H01U (SILVER)
H02U (WHITE) H03U (BLACK)
H04U
LOCK HANDLES Note: Handle can be configured for left hand or right hand operation.
CONNECTION BLOCKS H15 GS888
H05U
H06U
EFCO 2009 Page 7
CORNER DRIVE
CONNECTING ROD (250 meter rolls)
Page 8
Series 8700 / 8800 Unitized Curtain Wall Assembly Instructions - Volume 5
Section 17 - Hardware Identification
Image
Part # Description
H07U
H08U
ADJUSTABLE SNUBBER
ADJUSTABLE LOCKING POINT (KEEPER AND PAWL)
L20A (20”) L24A (24”)
4-BAR PROJECTED ARM
L28A (28”)
LA03 (5”) LA04 (8”)
EFCO 2009 Page 8
ALLEN KEYED RELEASE LIMIT ARM (USES “HM70” SECURITY ALLEN WRENCH AS KEY)
Page 9
Series 8700 / 8800 Unitized Curtain Wall Assembly Instructions - Volume 5

Section 18 - Frame Assembly - Vent at Fixed Horizontal

1. Assembly the concealed vent unit frame. Refer to Volume 1 and Volume 2 of the S-8000 Unitized Curtain Wall Assembl y Instructions for assembly details a s noted below.
Refer to Volume 1, Page 35 for Mullion Splice Bar application.
Refer to Volume 1, Page 26 for
mullion gasket installation.
Stack Head
17K2 Concealed
Vent Horizontal
H11B Frame Pad
Refer to Volume 1, Page 27 - 28
for frame pad application.
17K2 Concealed
Vent Horizontal
H11B Frame Pad
Refer to Volume 1, Page 28 - 29
for frame pad application.
Refer to Volume 1, Page 32 - 33
for anchor assembly and
application.
Refer to Volume 1, Page 34 for
frame assembly.
Figure 1
Stack Sill
Refer to Volume 1, Page 27 - 28
for Frame Pad application.
Refer to Volume 1, Page 29 - 30
“Z” clip installation.
EFCO 2009 Page 9
Page 10
Series 8700 / 8800 Unitized Curtain Wall Assembly Instructions - Volume 5
Section 18 - Frame Assembly - Vent at Fixed Horizontal
2. Using an approved solvent or cleaner, clean the sealant contact surfaces of the jamb adapters and mullions of all oils and other contaminants.
3. Apply sealant to the contact surfaces at the intersection of the concealed vent horizontals and the vertical mullions where the jamb adapter abuts into the horizontals (4 locations). See Figure 3 and 4 on page 11.
4. Apply sealant to each end of the concealed vent jamb adapters. See Figure 5 and 6 on page 11.
Apply sealant at the intersection of the concealed vent horizontals and the verticals where the ends of the jamb adapter will abut. (See Figures 3 and 4 on page 11).
HEAD
17L5 Concealed Vent
Jamb Adapter
Concealed Vent
opening
17L5 Concealed Vent
Jamb Adapter
Apply sealant to each end of
the jamb adapters. (See
Figures 5 and 6 on page 12).
SILL
Figure 2
EFCO 2009 Page 10
Page 11
Series 8700 / 8800 Unitized Curtain Wall Assembly Instructions - Volume 5
Section 18 - Frame Assembly - Vent at Fixed Horizontal
Apply sealant at the intersection of the
vent horizontals and the verticals where
the ends of the jamb adapter will abut.
17K2 Concealed
Vent Horizontal
Apply sealant to each end of the jamb adapters.
Figure 3
17K2 Concealed
Vent Horizontal
Apply sealant at the intersection of the
vent horizontals and the verticals where
the ends of the jamb adapter will abut.
Figure 4
Figure 5
Apply sealant to each end of the jamb adapters.
Figure 6
EFCO 2009 Page 11
Page 12
Series 8700 / 8800 Unitized Curtain Wall Assembly Instructions - Volume 5
Section 18 - Frame Assembly - Vent at Fixed Horizontal
5. Set the jamb adapter into the notched areas of the concealed vent horizontals where the sealant was applied. Ensure the adapter is flush with the horizontal as shown in Figure 9.
6. Match drill the vertical mullion through the holes in the jamb adapters and attach the adapters with SPZ0 screws. Cap seal the screws where they penetrate the mullion. See Figure 8. Tool the sealant smooth at each end of the adapter and remove excess sealant as shown in Figure 9.
7. Apply a continuous bead of sealant in the groove between the jamb adapter and mullion and tool smooth. See Figure 8 .
Tool sealant
into joints.
HEAD
Apply a continuous bead of sealant in the groove between the adapter and mullion and tool smooth.
Ensure surfaces
are flush.
Apply a continuous bead of sealant in the groove and tool smooth.
Cap seal fasteners
17L5 Concealed Vent Jamb Adapter
Match drill the
mullions and attach
the adapter with
SPZ0 fasteners.
Concealed Vent
opening
Figure 9
SILL
Figure 7 Figure 8
EFCO 2009 Page 12
Page 13
Series 8700 / 8800 Unitized Curtain Wall Assembly Instructions - Volume 5

Section 19 - Frame Assembly - Vent at Stack Sill

1. Assembly the concealed vent unit frame. Refer to Volume 1 and Volume 2 of the S-8000 Unitized Curtain Wall Assembl y Instructions for assembly details a s noted below.
Refer to Volume 1, Page 35 for Mullion Splice Bar application.
Refer to Volume 1, Page 26 for
Stack Head
mullion gasket installation.
Refer to Volume 1, Page 32 - 33
for anchor assembly and
application.
Refer to Volume 1, Page 34 for
frame assembly.
Intermediate
Horizontal
17K2 Concealed
Vent Horizontal
H11B Frame Pad
Refer to Volume 1, Page 27 - 28
for frame pad application.
Figure 10
H11B Frame Pad
Refer to Volume 1, Page 27 - 28
for frame pad application.
1H65 Concealed
Vent Stack Sill
Refer to Volume 1, Page 27 - 28
for Frame Pad application.
Refer to Volume 1, Page 29 - 30
“Z” clip installation.
EFCO 2009 Page 13
Page 14
Series 8700 / 8800 Unitized Curtain Wall Assembly Instructions - Volume 5
Section 19 - Frame Assembly - Vent at Stack Sill
2. Using an approved solvent or cleaner, clean the sealant contact surfaces of the jamb adapters and mullions of all oils and other contaminants.
3. Apply sealant to the contact surfaces at the intersection of the concealed vent horizontals and the vertical mullions where the jamb adapter abuts into the horizontals (4 locations). See Figures 12 and 13 on page 15.
4. Apply sealant to each end of the concealed vent jamb adapters. See Figures 14 and 15 on page 15.
HEAD
Apply sealant at the intersection of the concealed vent horizontals and the verticals where the ends of the jamb adapter will abut. (See Figures 12 and 13 on page 16).
17L5 Concealed Vent
Jamb Adapter
17L5 Concealed Vent
Jamb Adapter
Concealed Vent
opening
SILL
Apply sealant to each end of
the jamb adapters. (See
Figures 14 and 15 on page 16).
Figure 11
EFCO 2009 Page 14
Page 15
Series 8700 / 8800 Unitized Curtain Wall Assembly Instructions - Volume 5
Section 19 - Frame Assembly - Vent at Stack Sill
Apply sealant at the intersection of the
vent horizontals and the verticals where
the ends of the jamb adapter will abut.
17K2 Concealed
Vent Horizontal
Apply sealant to each end of the jamb adapters.
Figure 14
Apply sealant to each end of the jamb adapters.
Figure 15
17K2 Concealed
Vent Stack Sill
Figure 12
Apply sealant at the intersection of the
vent horizontals and the verticals where
the ends of the jamb adapter will abut.
Figure 13
EFCO 2009 Page 15
Page 16
Series 8700 / 8800 Unitized Curtain Wall Assembly Instructions - Volume 5
Section 19 - Frame Assembly - Vent at Stack Sill
5. Set the jamb adapter into the notched areas of the concealed vent horizontals where the sealant was applied. Ensure the adapter is flush with the horizontal as shown in Figure 18.
6. Match drill the vertical mullion through the holes in the jamb adapters and attach the adapters with SPZ0 screws. Cap seal the screws where they penetrate the mullion. See Figure 17. Tool the sealant smooth at each end of the adapter and remove excess sealant as shown in Figure 18.
7. Apply a continuous bead of sealant in the groove between the jamb adapter and mullion and tool smooth. See Figure 1 7.
Tool sealant
into joints.
HEAD
Apply a continuous bead of sealant in the groove and tool smooth.
Cap seal fasteners
17L5 Concealed Vent Jamb Adapter
Match drill the
mullions and attach
the adapter with
SPZ0 fasteners.
Ensure surfaces
are flush.
Apply a continuous bead of sealant in the groove between the adapter and mullion and tool smooth.
Figure 18
SILL
Concealed Vent
opening
Figure 16 Figure 17
EFCO 2009 Page 16
Page 17
Series 8700 / 8800 Unitized Curtain Wall Assembly Instructions - Volume 5

Section 20 - Unit Glazing Preparation - Vent at Fixed Horizontal

1. Using an approved solvent or cleaner, clean the surfaces of the mullions to receive the WC18 spacer gasket and sealant of all oils and other contaminants. The sealant manufacturer’s preparation and application instructions should be followed exactly.
2. If sealant primer is required, apply it per the primer/sealant manufacturer’s instructions. See Figures 20 - 22 of page 18 for more detail.
3. Refer to Volume 2, pages 6 of the S-8000 Unitized Curtain Wall Assembly Instructions for more information.
Apply WC18 spacer gasket to the mullions.
HEAD
Concealed Vent
opening
Apply WC18 spacer
gasket to the mullions.
Figure 19
SILL
EFCO 2009 Page 17
Page 18
Series 8700 / 8800 Unitized Curtain Wall Assembly Instructions - Volume 5
Section 20 - Unit Glazing Preparation - Vent at Fixed Horizontal
4. Apply the WC18 spacer gasket to the mullions as shown below and on the previous page. The gaskets will run through as shown below. Butt the gaskets together at the corners (see Figure 22). “Crowd” in extra gasket, (approximately 4% to 5% extra) where it runs between the gaskets to ensure a snug butt joint at the corners. It is important that there are no gaps in the gaskets where they meet in the corners. Note that the gasket is not symmetrical, and must be installed so that it is flush with the side of the mullions (see Figure 20).
5. A 3/8” backer rod should be applied into the isolator reglet to prevent sealant from getting into the reglet. Remove the backer rod immediately after the sealant is applied, and before the sealant begins to cure or skin over (See Figure 21).
Apply gaskets
flush with the side
of the mullions.
Butt gaskets at D.L.O.
corners (vertical
gasket runs through).
Insert a 3/8” backer rod into isolator reglets to
Isolator Reglet
Figure 65
Figure 20 Figure 21
Butt gaskets at D.L.O.
corners (vertical
HEAD
JAMB
gasket runs through).
INTERMEDIATE
keep free of sealant. Remove the backer rod
immediately, before sealant begins to skin over.
JAMB
Butt gaskets at D.L.O.
gasket runs through).
JAMB
corners (vertical
SILL
Figure 22
EFCO 2009 Page 18
Page 19
Series 8700 / 8800 Unitized Curtain Wall Assembly Instructions - Volume 5

Section 21 - Unit Glazing Preparation - Vent at Stack Sill

1. Using an approved solvent or cleaner, clean the surfaces of the mullions to receive the WC18 spacer gasket and sealant of all oils and other contaminants. The sealant manufacturer’s preparation and application instructions should be followed exactly.
2. If sealant primer is required, apply it per the primer/sealant manufacturer’s instructions. See Figures 24 - 26 of page 20 for more detail.
3. Refer to Volume 2, page 6 of the S-8000 Unitized Curtain Wall Assembly Instructions for more information.
Apply WC18 spacer gasket to the mullions.
HEAD
Concealed Vent
opening
SILL
Figure 23
EFCO 2009 Page 19
Page 20
Series 8700 / 8800 Unitized Curtain Wall Assembly Instructions - Volume 5
Section 21 - Unit Glazing Preparation - Vent at Stack Sill
4. Apply the WC18 spacer gasket to the mullions as shown below and on the previous page. The gaskets will run through as shown below. Butt the gaskets together at the corners (see Figure 26). “Crowd” in extra gasket, (approximately 4% to 5% extra) where it runs between the gaskets to ensure a snug butt joint at the corners. It is important that there are no gaps in the gaskets where they meet in the corners. Note that the gasket is not symmetrical, and must be installed so that it is flush with the side of the mullions (see Figure 24).
5. A 3/8” backer rod should be applied into the isolator reglet to prevent sealant from getting into the reglet. Remove the backer rod immediately after the sealant is applied, and before the sealant begins to cure or skin over (See Figure 25).
Apply gaskets
flush with the side
of the mullions.
Butt gaskets at D.L.O.
corners (vertical
gasket runs through).
JAMB
Insert a 3/8” backer rod into isolator reglets to
Isolator Reglet
Figure 65
Figure 24 Figure 25
HEAD
keep free of sealant. Remove the backer rod
immediately, before sealant begins to skin over.
Butt gaskets at D.L.O.
corners (vertical
gasket runs through).
Butt gaskets at D.L.O. corners (vertical gasket runs through).
INTERMEDIATE
INTERMEDIATE
JAMB
JAMB
Figure 26
EFCO 2009 Page 20
Page 21
Series 8700 / 8800 Unitized Curtain Wall Assembly Instructions - Volume 5

Section 22 - SSG Vent Unit Glazing at Fixed Horizontal : A. Temporary Glazing Locators

1. Apply two temporary glazing locators (KV01 and KV02) with isolators and setting blocks at approximate quarter points at the sill and intermediate horizontal locations.
2. Refer to Volume 2, page 8 and 9 of the S-8000 Unitized Curtain Wall Assembly Instructions for assembly details and notes.
HEAD
Concealed Vent
opening
Temporary Glazing
Locators (KV02)
Intermediate
Horizontal
KV01 KV02
Intermediate Horizontal Stack Sill
Figure 27
Temporary Glazing
Locators (KV01)
SILL
Stack Sill
EFCO 2009 Page 21
Page 22
Series 8700 / 8800 Unitized Curtain Wall Assembly Instructions - Volume 5

Section 22 - SSG Vent Unit Glazing at Fixed Horizontal : B. Setting and Caulking Glazing

1. Set the glazing on the silicone spacer gaskets making sure glazing is pressed firmly onto the setting blocks of the temporary retainers.
2. Refer to Volume 2, pages 9 and 10 of the S-8000 Unitized Curtain Wall Assembly Instructions for assembly details and notes.
HEAD
Note: Unit frame squareness is critical when operable units are incorporated into the unit. The taller the operable unit becomes, the more important that the frame is completely square.
Set glazing onto the silicone spacer gaskets and against the setting blocks at the temporary glazing locators.
Concealed Vent
opening
Temporary Glazing
Locators (KV02)
SILL
Temporary Glazing
Locators (KV01)
Figure 28
EFCO 2009 Page 22
Page 23
Series 8700 / 8800 Unitized Curtain Wall Assembly Instructions - Volume 5
Section 22 - SSG Vent Unit Glazing at Fixed Horizontal : B. Setting and Caulking Glazing
3. Remove the temporary glazing retainers.
4. Apply structural silicone sealant into the voids between the glass and mullions per the sealant manufacturer’s application instructions. Frames should not be moved until the sealant has cured and per the sealant manufacturer’s recommendations.
5. Refer to Volume 2, page 9 and 10 of the S-8000 Unitized Curtain Wall Assembly Instructions for glazing instructions, details and note s.
Apply structural silicone sealant into the voids between the glass and mullions.
HEAD
Concealed Vent
opening
Note: Only silicone sealants which have been developed and tested specifically for structural glazing applications should be used for glazing purposes.
SILL
Apply Structural
silicone.
Figure 29
Pack sealant
into joints.
Apply structural silicone sealant into the voids between the glass and mullions.
EFCO 2009 Page 23
Page 24
Series 8700 / 8800 Unitized Curtain Wall Assembly Instructions - Volume 5

Section 22 - SSG Vent Unit Glazing at Fixed Horizontal : C. Adapter Installation

1. Apply L142 thermal isolator clip to the verticals and horizontals. Apply WC16 to the head member. Refer to Volume 2, page 11 of the S-8000 Unitized Curtain Wall Assembly Instructions for more information.
2. Apply the 17B7 SSG glazing adapter to the stack sill. Slide the WC17 horizontal stack joint rain screen gasket into position. Refer to Volume 2, page 12 of the S-8000 Unitized Curtain Wall Assembly Instructions for more information.
3. Insert HS32 setting blocks between the stack sill glazing adapters and the glass at quarte r points, or as directed per the final approved shop drawings. Refer to Volume 2, page 12 of the S-8000 Unitized Curtain Wall Assembly Instructions for more information.
4. Install 17B6 SSG gutter to the frame at the head horizontal and secure with SPZ1 fasteners. Critical seals are not shown below. Refer to Volume 2, page 13 of the S-8000 Unitized Curtain Wall Assembly Instructions for more information.
5. Slide WC20 bulb gaskets into 17A6 fin bars and then roll the 17A6 SSG vertical fin bars into the isolator in each vertical mullion of the assembled unit.
Apply L142 to the verticals and
Install 17B6 gutter to head with
SPZ1. Slide WC19 and LC23
gaskets into the gutter. Refer to
Volume 2, Page 13.
HEAD
horizontals. Apply WC16 to the head. Refer to Volume 2, Page 11.
Slide WC20 gasket into 17A6 and apply 17A6 fin bar to the verticals. Refer to Volume 2, Page 14.
Apply L142 to the verticals and horizontals. Apply WC16 to the head. Refer to Volume 2, Page 11.
Slide WC20 gasket into 17A6 and
apply 17A6 fin bar to the verticals.
Refer to Volume 2, Page 14.
Figure 30
SILL
Apply 17B7 adapter to the sill. Slide WC17 into the adapter. Insert HS32 setting blocks. Refer to Volume 2, Page 12.
EFCO 2009 Page 24
Page 25
Series 8700 / 8800 Unitized Curtain Wall Assembly Instructions - Volume 5
Section 22 - SSG Vent Unit Glazing at Fixed Horizontal : C. Adapter Installation
6. Slide the WS00 vent surround gasket into the 17A6 adapters that will be applied to the intermediate horizontals above and below the concealed vent opening. Cut the WS00 gasket about 1/4” longer than the 17A6 adapter that will be applied at the head of the vent opening. Cut the WS00 gasket about 3” shorter than the 17A6 adapter that will be applied at the sill of the vent opening. See Figures 32 through 35 on page 26.
7. Roll the 17A6 adapter into the isolators in the intermediate horizontals at the head and sill of the vent opening. Crowd the WS00 gasket at the head between the vertical fin bar adapters as the adapter is inserted in place. Center the WS00 gasket in the opening at the sill of the vent opening.
8. Insert HS32 setting blocks between the 17A6 adapter at the head of the vent opening and the upper lite of glazing at quarter points or as directed in the final approved shop drawings. See Figures 32 through 35 on page 26.
9. Insert WA07 vent bulb gasket into each jamb on each side of the vent opening. Cut the WA07 gasket so that it butts into the 17A6 adapter at the head and sill of the vent opening. See Figures 32 through 35 on page 26.
Slide WS00 gasket into 17A6 and apply 17A6 fin bar to the horizontals at
HEAD
Insert HS32 setting blocks.
the head and sill of the vent opening. See Figures 32 - 35 on Page 26.
Concealed Vent
opening
Insert WA07 vent bulb gasket
into each jamb on each side of
the vent opening. See Figures
32 - 35 on page 26.
Slide WS00 gasket into 17A6 and
apply 17A6 fin bar to the horizontals at
the head and sill of the vent opening.
See Figures 32 - 35 on Page 27.
SILL
Figure 31
EFCO 2009 Page 25
Page 26
Series 8700 / 8800 Unitized Curtain Wall Assembly Instructions - Volume 5
Section 22 - SSG Vent Unit Glazing at Fixed Horizontal : C. Adapter Installation
WS00 gasket is cut 3”
WS00 gasket butts into
17A6 at the head
horizontal on each end.
WA07 runs under
WS00 and butts
into adapter.
short of the adapter at the sill horizontal and is centered in the opening.
WA07 butts
into adapter.
VENT SILL VENT HEAD
Slide WS00 gasket into
17A6 and apply 17A6 fin
bar to the horizontals.
VENT HEAD VENT SILL
Figure 32
Insert HS32 setting blocks.
WA07 butts
into adapter.
Figure 33
Insert WA07 vent bulb
gasket into each jamb.
WA07 butts
into adapter.
Slide WS00 gasket into
17A6 and apply 17A6 fin
bar to the horizontals.
VENT JAMB VENT JAMB
Figure 35 Figure 34
EFCO 2009 Page 26
Page 27
Series 8700 / 8800 Unitized Curtain Wall Assembly Instructions - Volume 5

Section 22 - SSG Vent Unit Glazing at Fixed Horizontal : D. Weather Seal Application

1. Using an approved solvent or cleaner, clean the sealant contact surfaces of the glazing and adapters of all oils and other contaminants.
2. If sealant primer is required, apply it per the primer/sealant manufacturer’s instructions.
3. Insert 3/8” diameter backer rod between the glazing and adapters around all four corners of each lite of glazing. Refer to Volume 2, Figure 38 page 17 for more information.
4. Apply sealant into the void between the adapters and glazing to form the weather seal and tool smooth. If the sealant is properly and carefully applied, masking tape on the adjacent surfaces is not necessary.
5. Seal the ends of adapter at the head of the vent, running the sealant to the face of the vertical, but not across the face of the vertical. This allows weeps for the glazing pocket of the lite above the vent. Tool the sealant neatly into the adjacent surfaces. Slide the WS00 gasket out of the way to apply this seal. Return WS00 to its former position after sealing. See Figure 38.
6. Seal the ends of the adapter at the sill of the vent, running the sealant to the vertical and across the face and around to where the adapter meets the horizontal. Lift WA07 gasket out of the way to apply this seal. Tool the sealant neatly into the adjacent surfaces. Return WA07 to its former position after sealing. See Figure 39.
7. Before the sealant begins to cure or skin over, tool the sealant into the joints smoothly, taking care to smooth and blend the sealant in the corners and intermediate intersections as shown below. See Figures 37 through 40. Seen in section view, the sealant should have an hourglass shape and maintain a 2:1 width to depth ratio as shown in Volume 2, Figure 38 on page 17. Remove any excess sealant from the surrounding surfaces before the sealant begins to cure.
HEAD SILL
Figure 36
Seal the ends of the adapter, along the face of the vertical, and around to the horizontal.
VENT SILL
Sealant continuity
joint and weather
seals.
Figure 37
Sealant continuity joint and weather seals.
Slide back WS00 gasket and seal the adapters as shown.
VENT HEAD
Figure 38 Figure 39 Figure 40
Omit sealant at the face of the vertical to create weeps for the lite above.
Lift WA07 gasket back and seal the adapters as shown.
EFCO 2009 Page 27
Page 28
Series 8700 / 8800 Unitized Curtain Wall Assembly Instructions - Volume 5

Section 23 - SSG Vent Unit Glazing at Stack Sill : A. Temporary Glazing Locators

1. Apply two temporary glazing locators (KV02) with isolators and setting blocks at approximate quarter points at the intermediate horizontal locations.
2. Refer to Volume 2, page 8 of the S-8000 Unitized Curtain Wall Assembly Instructions for assembly details and notes.
HEAD
Intermediate
Horizontal
Temporary Glazing
Locators (KV02)
Concealed Vent
opening
Concealed Vent
Horizontal
KV02 KV02
SILL
Stack Sill
Intermediate Horizontal
Concealed Vent Horizontal
Figure 41
EFCO 2009 Page 28
Page 29
Series 8700 / 8800 Unitized Curtain Wall Assembly Instructions - Volume 5

Section 23 - SSG Vent Unit Glazing at Stack Sill : B. Setting and Caulking Glazing

1. Set the glazing on the silicone spacer gaskets making sure glazing is pressed firmly onto the setting blocks of the temporary retainers.
2. Refer to Volume 2, pages 9 and 10 of the S-8000 Unitized Curtain Wall Assembly Instructions for assembly details and notes.
Set glazing onto the silicone spacer gaskets and against the setting blocks at the temporary glazing locators.
HEAD
Concealed Vent
opening
Temporary Glazing
Locators (KV02)
Note: Unit frame squareness is critical when operable units are incorporated into the unit. The taller the operable unit becomes, the more important that the frame is completely square.
Figure 42
SILL
EFCO 2009 Page 29
Page 30
Series 8700 / 8800 Unitized Curtain Wall Assembly Instructions - Volume 5
Section 23 - SSG Vent Unit Glazing at Stack Sill : B. Setting and Caulking Glazing
3. Remove the temporary glazing retainers.
4. Apply structural silicone sealant into the voids between the glass and mullions per the sealant manufacturer’s application instructions. Frames should not be moved until the sealant has cured and per the sealant manufacturer’s recommendations.
5. Refer to Volume 2, page 9 and 10 of the S-8000 Unitized Curtain Wall Assembly Instructions for glazing instructions, details and note s.
Apply structural silicone sealant into the voids between the glass and mullions.
HEAD
Note: Only silicone sealants which have been developed and tested specifically for structural glazing applications should be used for glazing purposes.
Concealed Vent
opening
Apply structural silicone sealant into the voids between the glass and mullions.
SILL
Figure 43
Apply Structural
silicone.
Pack sealant
into joints.
EFCO 2009 Page 30
Page 31
Series 8700 / 8800 Unitized Curtain Wall Assembly Instructions - Volume 5

Section 23 - SSG Vent Unit Glazing at Stack Sill : C. Adapter Installation

1. Apply L142 thermal isolator clip to the verticals and horizontals. Apply WC16 to the head member. Refer to Volume 2, page 11 of the S-8000 Unitized Curtain Wall Assembly Instructions for more information.
2. Slide the WC17 horizontal stack joint rain screen gasket into the concealed vent stack sill. Refer to Volume 2, page 12 of the S-8000 Unitized Curtain Wall Assembly Instructions for more information.
3. Insert HS32 setting blocks between the stack sill and the glass at quarter points, or as directed per the final approved shop drawings. Refer to Volume 2, page 12 of the S-8000 Unitized Curtain Wall Assembly Instructions for more information.
4. Install 17B6 SSG gutter to the frame at the head horizontal and secure with SPZ1 fasteners. Critical seals are not shown below. Refer to Volume 2, page 13 of the S-8000 Unitized Curtain Wall Assembly Instructions for more information.
5. Apply sealant as required and roll 17H6 adapter into the isolator at the intermediate horizontal. Insert HS32 setting blocks. Refer to Volume 2, Page 15.
6. Slide WC20 bulb gaskets into 17A6 fin bars and then roll the 17A6 SSG vertical fin bars into the isolator in each vertical mullion of the assembled unit.
Install 17B6 gutter to head with
SPZ1. Slide WC19 and LC23
gaskets into the gutter. Refer to
Volume 2, Page 13.
HEAD
Apply sealant as required and roll
17H6 adapter into the isolator at
the intermediate horizontal.
Insert HS32 setting blocks. Refer
to Volume 2, Page 15.
Apply L142 to the verticals and horizontals. Apply WC16 to the head. Refer to Volume 2, Page 11.
Slide WC20 gasket into 17A6 and apply 17A6 fin bar to the verticals. Refer to Volume 2, Page 14.
SILL
Slide WC20 gasket into 17A6 and
apply 17A6 fin bar to the verticals.
Refer to Volume 2, Page 14.
Figure 44
Slide WC17 into the sill. Insert HS32 setting blocks. Refer to Volume 2, Page 12.
EFCO 2009 Page 31
Page 32
Series 8700 / 8800 Unitized Curtain Wall Assembly Instructions - Volume 5
Section 23 - SSG Vent Unit Glazing at Stack Sill : C. Adapter Installation
7. Drill tap sized holes (.113 diameter or #33 drill) in the face of the vertical assemblies, 1” from the sill end of the vent opening, and 18” on center to the top of the vent opening. See figure 46 below. Drill the holes in the groove formed where the adapter meets the mullion. The holes should penetrate the adapter, the isolator, and the first wall of the mullion where the isolator is seated. See Figure 47 below. Ensure the adapter is properly positioned and seated into the isolator before drilling.
8. Apply STC6 fasteners in each hole to retain the adapters where they span the vent opening.
HEAD
Drill tap sized holes in the face of the vertical assembly 1” from the sill end of the vent opening, and 18” on center to the top of the vent opening.
Apply STC6 fasteners in each hole to retain the adapters where they
Apply STC6 fasteners in each
hole to retain the adapters where
they span the vent opening.
Figure 46
STC6 18” o/c
Drill tap sized holes in the
groove formed where the
adapter meets the mullion.
Figure 47
span the vent opening.
SILL
Concealed Vent
opening
Figure 45
EFCO 2009 Page 32
Page 33
Series 8700 / 8800 Unitized Curtain Wall Assembly Instructions - Volume 5
Section 23 - SSG Vent Unit Glazing at Stack Sill : C. Adapter Installation
9. Slide the WS00 vent surround gasket into the 17A6 adapters that will be applied to the intermediate horizontals at the head of the concealed vent opening. Cut the WS00 gasket about 1/4” longer than the 17A6 adapter that will be applied at the head of the vent opening. See Figures 49 through 52 on page 34.
10. Roll the 17A6 adapter into the isolators in the intermediate horizontals at the head and sill of the vent opening. Crowd the WS00 gasket at the head between the vertical fin bar adapters as the adapter is inserted in place. Center the WS00 gasket in the opening at the sill of the vent opening.
11. Insert HS32 setting blocks between the 17A6 adapter at the head of the vent opening and the upper lite of glazing at quarter points or as directed in the final approved shop drawings. See Figures 49 through 52 on page 34.
12. Insert WA07 vent bulb gasket into each jamb on each side of the vent opening. Cut the WA07 gasket so that it butts into the 17A6 adapter at the head and sill of the vent opening. See Figures 49 through 52 on page 34.
HEAD
Slide WS00 gasket into 17A6 and apply 17A6 fin bar to the horizontals at the head and sill of the vent opening. See Figures 49 - 52 on Page 34.
Concealed Vent
opening
Insert HS32 setting blocks.
Insert WA07 vent bulb gasket
into each jamb on each side of
the vent opening. See Figures
46 - 52 on page 34.
SILL
Figure 48
EFCO 2009 Page 33
Page 34
Series 8700 / 8800 Unitized Curtain Wall Assembly Instructions - Volume 5
Section 23 - SSG Vent Unit Glazing at Stack Sill : C. Adapter Installation
WS00 gasket butts into
17A6 at the head
horizontal on each end.
VENT HEAD
Figure 49
Insert HS32 setting blocks.
WA07 butts
into adapter.
WA07 runs under
WS00 and butts
into adapter.
Insert WA07 vent bulb
gasket into each jamb.
WA07 butts
into sill.
VENT SILL
Figure 50
WA07 butts
into sill.
Slide WS00 gasket into
17A6 and apply 17A6 fin
bar to the horizontals.
VENT JAMB VENT JAMB
VENT HEAD VENT SILL
Figure 52 Figure 51
EFCO 2009 Page 34
Page 35
Series 8700 / 8800 Unitized Curtain Wall Assembly Instructions - Volume 5

Section 23 - SSG Vent Unit Glazing at Stack Sill : D. Weather Seal Application

1. Using an approved solvent or cleaner, clean the sealant contact surfaces of the glazing and adapters of all oils and other contaminants.
2. If sealant primer is required, apply it per the primer/sealant manufacturer’s instructions.
3. Insert 3/8” diameter backer rod between the glazing and adapters around all four corners of each lite of glazing. Refer to Volume 2, Figure 3 8 pag e 17 for more information.
4. Apply sealant into the void between the adapters and glazing to form the weather seal and tool smooth. If the sealant is properly and carefully applied, masking tape on the adjacent surfaces is not necessary.
5. Seal the ends of adapter at the head of the vent, running the sealant to the face of the vertical, but not across the face of the vertical. This allows weeps for the glazing pocket of the lite above the vent. Tool the sealant neatly into the adjacent surfaces. Slide the WS00 gasket out of the way to apply this seal. Return WS00 to its former position after sealing. See Figure 56.
6. Before the sealant begins to cure or skin over, tool the sealant into the joints smoothly, taking care to smooth and blend the sealant in the corners and intermediate intersections as shown below. See Figures 54 through 57. Seen in section view, the sealant should have an hourglass shape and maintain a 2:1 width to depth ratio as shown in Volume 2, Figure 38 on page 17. Remove any excess sealant from the surrounding surface s before the sealant begins to cure.
HEAD SILL
Figure 53
Slide back WS00 gasket and seal the adapters as shown.
Sealant continuity joint and weather seals.
Figure 54 Figure 56 Figure 55 Figure 57
Sealant continuity joint and weather seals.
VENT HEAD
Omit sealant at the face of the vertical to create weeps for the lite above.
No sealant is required
at this location.
VENT SILL
EFCO 2009 Page 35
Page 36
Series 8700 / 8800 Unitized Curtain Wall Assembly Instructions - Volume 5

Section 24 - Captured Vent Unit Glazing at Fixed Horizontal : A. Temporary Glazing Locators

1. Apply two temporary glazing locators (KV03 and KV04) with isolators and setting blocks at approximate quarter points at the sill and intermediate horizontal locations.
2. Refer to Volume 2, page 20 and 21 of the S-8000 Unitized Curtain Wall Assembly Instructions for assembly details an d notes.
HEAD
Concealed Vent
opening
Temporary Glazing
Locators (KV03)
KV03 KV04
Concealed Vent Head
Stack Sill
Intermediate
Horizontal
Figure 58
Temporary Glazing
Locators (KV04)
SILL
Stack Sill
EFCO 2009 Page 36
Page 37
Series 8700 / 8800 Unitized Curtain Wall Assembly Instructions - Volume 5

Section 24 - Captured Vent Unit Glazing at Fixed Horizontal : B. Setting and Caulking Glazing

1. Set the glazing on the silicone spacer gaskets making sure glazing is pressed firmly onto the setting blocks of the temporary retainers.
2. Refer to Volume 2, pages 20 and 21 of the S-8000 Unitized Curtain Wall Assembly Instructions for assembly details and notes.
HEAD
Set glazing onto the silicone spacer gaskets and against the setting blocks at the temporary glazing locators.
Concealed Vent
opening
Temporary Glazing
Locators (KV03)
Note: Unit frame squareness is critical when operable units are incorporated into the unit. The taller the operable unit becomes, the more important that the frame is completely square.
SILL
Temporary Glazing
Locators (KV04)
Figure 59
EFCO 2009 Page 37
Page 38
Series 8700 / 8800 Unitized Curtain Wall Assembly Instructions - Volume 5
Section 24 - Captured Vent Unit Glazing at Fixed Horizontal : B. Setting and Caulking Glazing
3. Remove the temporary glazing retainers.
4. Apply structural silicone sealant into the voids between the glass and mullions per the sealant manufacturer’s application instructions. Frames should not be moved until the sealant has cured and per the sealant manufacturer’s recommendations.
5. Refer to Volume 2, page 21 and 22 of the S-8000 Unitized Curtain Wall Assembly Instructions for glazing instru ctions, details and notes.
Apply structural silicone sealant into the voids between the glass and mullions.
HEAD
Concealed Vent
opening
Note: Only silicone sealants which have been developed and tested specifically for structural glazing applications should be used for glazing purposes.
SILL
Figure 60
Apply structural silicone
Apply Structural
silicone.
Pack sealant
into joints.
sealant into the voids between the glass and mullions.
EFCO 2009 Page 38
Page 39
Series 8700 / 8800 Unitized Curtain Wall Assembly Instructions - Volume 5

Section 24 - Captured Vent Unit Glazing at Fixed Horizontal : C. Adapter Installation

1. Apply L142 thermal isolator clip to the verticals and horizontals. Apply WC16 to the head member. Refer to Volume 2, page 25 of the S-8000 Unitized Curtain Wall Assembly Instructions for more information.
2. Apply the 17B5 SSG glazing adapter to the stack sill. Slide the WC17 horizontal stack joint rain screen gasket into position. Refer to Volume 2, page 24 of the S-8000 Unitized Curtain Wall Assembly Instructions for more information.
3. Insert HS31 setting blocks between the stack sill glazing adapters and the glass at quarte r points, or as directed per the final approved shop drawings. Refer to Volume 2, page 24 of the S-8000 Unitized Curtain Wall Assembly Instructions for more information.
4. Install 17B1 captured gutter to the frame at the head horizontal and secure with SPZ1 fasteners. Critical seals are not shown below. Refer to Volume 2, page 25 of the S-8000 Unitized Curtain Wall Assembly Instructions for more information.
Apply L142 to the verticals and horizontals. Apply WC16 to the
Install 17B1 gutter to head with
SPZ1. Slide WC19 and LC23
gaskets into the gutter. Refer to
Volume 2, Page 25.
HEAD
head. Refer to Volume 2, Page 23.
Apply L142 to the verticals and
horizontals. Apply WC16 to the
head. Refer to Volume 2, Page 11.
Figure 61
SILL
Apply 17B5 adapter to the sill. Slide WC17 into the adapter. Insert HS31 setting blocks. Refer to Volume 2, Page 24.
EFCO 2009 Page 39
Page 40
Series 8700 / 8800 Unitized Curtain Wall Assembly Instructions - Volume 5
Section 24 - Captured Vent Unit Glazing at Fixed Horizontal : C. Adapter Installation
5. Install 17K0 and drive in WC22 wedge gasket.
6. Install 17K1 and drive in WC22 wedge gasket.
7. Slide WC20 bulb gasket into the 17A2 captured glazing adapter and insert the adapter into the isolator in the vertical.
8. For items 5 through 7, refer to Volume 2, Page 26 and 27 of the S-8000 Unitized Curtain Wall Assembly Instructions for more information.
9. Insert 17A3 cover into 17A2 captured glazing adapter at each unit jamb and rotate into place as shown in Figures 63 and 64.
10. Cut the WC22 gaskets approximately 2” longer than the D.L.O. dimension.
11. Drive in WC22 wedge gaskets as shown in Figure 64. The gaskets should be applied starting in the center of the D.L.O., and then working from the ends, work the gaskets in place to the center of the lite.
Install 17K0 and drive in
WC22 wedge gasket. Refer
to Volume 2, Page 26.
HEAD
WC22 Wedge Gasket
Insert 17A3 cover into 17A2
captured glazing adapter and drive
in wedge gaskets on each end of the
cover. See Figures 60 and 61 below.
17A3 Cover
17A2 Adapter
Figure 63 Figure 64
WC22 Wedge Gasket
WC22 Wedge Gasket
17A3 Covers
WC22 Wedge Gasket
Figure 62
Slide WC20 bulb gasket into 17A2 captured glazing adapter and insert it into the isolator in the vertical. Refer to Volume 2, Page 27.
Concealed Vent
opening
WC22 Wedge Gasket
Install 17K1 and drive in WC22 wedge gasket. Refer to Volume 2, Page 26.
SILL
Slide WC20 bulb gasket into 17A2 captured glazing adapter and insert it into the isolator in the vertical. Refer to Volume 2, Page 27.
EFCO 2009 Page 40
Page 41
Series 8700 / 8800 Unitized Curtain Wall Assembly Instructions - Volume 5
Section 24 - Captured Vent Unit Glazing at Fixed Horizontal : C. Adapter Installation
12. Slide WS00 vent surround gasket into the 17A2 glazing adapter, and apply the adapter to the vent head. See Figures 65 and 66.
13. Insert HS31 setting blocks at quarter points, or per the approved shop drawings, between the glazing and the 17A2 adapter at the vent head. See Figure 66.
14. Apply the 17L2 concealed vent cover to the 17A2 glazing adapter at the vent head. See Figures 65 and 66.
15. Apply the 17A2 glazing adapter to the vent sill. See Figures 62 and 65.
16. Apply the 17L3 glazing bead to the 17A2 adapter at the vent sill. See Figures 65 and 68.
17. Drive in WC22 wedge gaskets as shown in Figure 66 and 68. The gaskets should be applied starting in the center of the D.L.O., and then working from the ends, work the gaskets in place to the center of the lite.
18. Carefully and thoroughly seal each end of the adapter at the vent sill, where it meets the glazing pocket. Fill the voids behind the vertical cover, around the end of the adapter, and back to the face of the horizontal as shown in Figure 67. Note: These seals are only required at the sill of the vent opening.
Slide WS00 gasket into 17A2 adapter, and apply the adapter to the vent head.
HEAD SILL
17L2
Concealed
Vent Cover
WC22 Wedge
Gasket
(2) HS31
Setting Blocks
Apply (2) HS31 Setting Blocks
17A2 Glazing
Adapter
WS00 Vent
Surround
Gasket
Figure 66 - Vent Head Figure 68 - Vent Sill
Apply the 17L2 concealed vent cover to the 17A2 glazing adapter and drive in WC22 wedge gasket.
JAMB
Note: Apply this seal on each end of the adapter
at the vent sill only.
Figure 65
Figure 67
Apply the 17A2 adapter to
the vent sill, 17L3 glazing
bead into the adapter, then
drive in WC22 wedge gasket.
Fill the voids behind the vertical covers, around the ends of the adapters, and back to the face of the horizontals.
SILL
17L3 Glazing
17A2 Glazing
Adapter
Bead
WC22 Wedge
Gasket
EFCO 2009 Page 41
Page 42
Series 8700 / 8800 Unitized Curtain Wall Assembly Instructions - Volume 5
Section 24 - Captured Vent Unit Glazing at Fixed Horizontal : C. Adapter Installation
19. Slide WS00 vent surround gaskets into the 17L4 pocket fillers with the gaskets positioned with the rounded face of the gasket toward the exterior. WS00 runs the full length of the pocket filler.
20. Insert the pocket fillers into both glazing pockets of the jambs at the vent opening. Slide the pocket fillers to the exterior as shown in Figures 70 and 71.
21. Drive in the WVD1 wedge retainer gasket between the pocket filler and mullion. WVD1 runs the full length of the pocket filler. No sealant is required for
Slide WS00 gasket into
the 17L4 pocket filler and
insert the pocket filler
into the glazing pocket.
Drive in WVD1 gasket to
retain the pocket filler.
WC22 Wedge
Gasket
WS00 Vent
Surround Gasket
HEAD
WC22 Wedge
Gasket
WS00 Vent
Surround Gasket
17L4 Pocket
Filler
Slide WS00 gasket into
the 17L4 pocket filler and
insert the pocket filler
into the glazing pocket.
Drive in WVD1 gasket to
retain the pocket filler.
WS00 Vent
Surround Gasket
WC22 Wedge
Gasket
SILL
Figure 70 Figure 71
Figure 69
EFCO 2009 Page 42
Page 43
Series 8700 / 8800 Unitized Curtain Wall Assembly Instructions - Volume 5

Section 24 - Captured Vent Unit Glazing at Fixed Horizontal : D. Joint Plug Installation

1. HNC4 joint plugs will be required at the head and sill of the assembled unit frame. Using an approved solvent or cleaner, clean the surfaces of the mullions where the joint plug will be applied.
2. Apply joint plugs to the areas shown below as shown and noted in Volume 2, page 32 of the S-8000 Unitized Curtain Wall Assembly Instruct ions.
HEAD
HNC4
HNC4
HNC4
SILL
Figure 72
HNC4
HNC4 Joint Plug
Figure 73 Figure 74
HNC4 Joint Plug
EFCO 2009 Page 43
Page 44
Series 8700 / 8800 Unitized Curtain Wall Assembly Instructions - Volume 5

Section 25 - Captured Vent Unit Glazing at Stack Sill : A. Temporary Glazing Locators

1. Apply two temporary glazing locators (KV03) with isolators and setting blocks at approximate quarter points at the horizontal at the head of the vent opening and intermediate horizontal locations.
2. Refer to Volume 2, page 20 and 21 of the S-8000 Unitized Curtain Wall Assembly Instructions for assembly details an d notes.
KV03
HEAD
Temporary Glazing
Locators (KV03)
Temporary Glazing
Locators
Intermediate
Horizontal
Concealed Vent
opening
Concealed Vent
Head
KV03
SILL
Figure 75
Concealed Vent
Stack Sill
Intermediate Horizontal
Concealed Vent Head
EFCO 2009 Page 44
Page 45
Series 8700 / 8800 Unitized Curtain Wall Assembly Instructions - Volume 5

Section 25 - Captured Vent Unit Glazing at Stack Sill : B. Setting and Caulking Glazing

1. Set the glazing on the silicone spacer gaskets making sure glazing is pressed firmly onto the setting blocks of the temporary retainers.
2. Refer to Volume 2, pages 20 and 21 of the S-8000 Unitized Curtain Wall Assembly Instructions for assembly details and notes.
Set glazing onto the silicone spacer gaskets and against the setting blocks at the temporary glazing locators.
HEAD
Concealed Vent
opening
Temporary Glazing
Locators (KV03)
Note: Unit frame squareness is critical when operable units are incorporated into the unit. The taller the operable unit becomes, the more important that the frame is completely square.
Figure 76
SILL
EFCO 2009 Page 45
Page 46
Series 8700 / 8800 Unitized Curtain Wall Assembly Instructions - Volume 5
Section 25 - Captured Vent Unit Glazing at Stack Sill : B. Setting and Caulking Glazing
3. Remove the temporary glazing retainers.
4. Apply structural silicone sealant into the voids between the glass and mullions per the sealant manufacturer’s application instructions. Frames should not be moved until the sealant has cured and per the sealant manufacturer’s recommendations.
5. Refer to Volume 2, page 21 and 22 of the S-8000 Unitized Curtain Wall Assembly Instructions for glazing instru ctions, details and notes.
Apply structural silicone sealant into the voids between the glass and mullions.
HEAD
Note: Only silicone sealants which have been developed and tested specifically for structural glazing applications should be used for glazing purposes.
Concealed Vent
opening
SILL
Figure 77
Apply Structural
silicone.
Pack sealant
into joints.
EFCO 2009 Page 46
Page 47
Series 8700 / 8800 Unitized Curtain Wall Assembly Instructions - Volume 5

Section 25 - Captured Vent Unit Glazing at Stack Sill : C. Adapter Installation

1. Apply L142 thermal isolator clip to the verticals and horizontals. Apply WC16 to the head member. Refer to Volume 2, page 25 of the S-8000 Unitized Curtain Wall Assembly Instructions for more information.
2. Slide the WC17 horizontal stack joint rain screen gasket into position. Refer to Volume 2, page 24 of the S-8000 Unitized Curtain Wall Assembly Instructions for more information.
3. Install 17B1 captured gutter to the frame at the head horizontal and secure with SPZ1 fasteners. Critical seals are not shown below. Refer to Volume 2, page 25 of the S-8000 Unitized Curtain Wall Assembly Instructions for more information.
Apply L142 to the verticals and
Install 17B1 gutter to head with
SPZ1. Slide WC19 and LC23
gaskets into the gutter. Refer to
Volume 2, Page 25.
HEAD
horizontals. Apply WC16 to the head. Refer to Volume 2, Page 23.
Concealed Vent
opening
Apply L142 to the verticals and
horizontals. Apply WC16 to the
head. Refer to Volume 2, Page 11.
SILL
Slide WC17 into the adapter. Refer to Volume 2, Page 24.
Figure 78
EFCO 2009 Page 47
Page 48
Series 8700 / 8800 Unitized Curtain Wall Assembly Instructions - Volume 5
Section 25 - Captured Vent Unit Glazing at Stack Sill : C. Adapter Installation
4. Install 17K0 and drive in WC22 wedge gasket.
5. Slide WC20 bulb gasket into the 17A2 captured glazing adapter and insert the adapter into the isolator in the vertical.
6. For items 4 and 5, refer to Volume 2, Page 26 and 27 of the S-8000 Unitized Curtain Wall Assembly Instructions for more i nformation.
7. Clean the sealant contact surfaces, apply seals, and Roll the 17B9 captured glazing adapter into the isolator at the intermediate horizontal.
8. Insert HS31 setting blocks, (2) per location, between the glazing adapter and the glass at quarter points, or a s dire cted per the final approved shop drawings.
9. Insert 17B8 cover onto 17B9 captured glazing adapter at the intermediate horizontal and rotate into place.
10. Drive in WC22 wedge gaskets at the intermediate horizontal starting with the gasket on the setting block side of the glazing pocket. The gaskets should be applied starting in the center of the D.L.O., and then working from the ends, work the gasket in place to the center of the lite.
11. For steps 7 through 10, refer to Volume 2, Page 28 and 29 of the S-8000 Unitized Curtain Wall Assembly Instructions for more information.
Insert 17B8 cover onto 17B9 captured glazing adapter and rotate into
Install 17K0 and drive in
WC22 wedge gasket. Refer
to Volume 2, Page 26.
place. Drive in WC22 wedge gaskets starting with the gasket on the setting block side of the glazing pocket. Refer to Volume 2, Page 29.
Clean, Apply seals, and Roll the 17B9 captured glazing adapter into the isolator at the horizontal. Insert HS31 setting blocks between the glazing adapter and the glass. Refer to Volume 2, Page 28 and 29.
HEAD
Intermediate
Horizontal
Slide WC20 bulb gasket into 17A2
captured glazing adapter and insert
it into the isolator in the vertical.
Refer to Volume 2, Page 27.
Figure 79
Slide WC20 bulb gasket into 17A2 captured glazing adapter and insert it into the isolator in the vertical. Refer to Volume 2, Page 27.
SILL
EFCO 2009 Page 48
Page 49
Series 8700 / 8800 Unitized Curtain Wall Assembly Instructions - Volume 5
Section 25 - Captured Vent Unit Glazing at Stack Sill : C. Adapter Installation
12. Drill tap sized holes (.113 diameter or #33 drill) in the face of the vertical assemblies, 1” from the sill end of the vent opening, and 18” on center to the top of the vent opening. See figure 82 below. Drill the holes in the groove formed where the adapter meets the mullion. The holes should penetrate the adapter, the isolator, and the first wall of the mullion where the isolator is seated. See Figure 82 below. Ensure the adapter is properly positioned and seated into the isolator before drilling.
13. Apply STC6 fasteners in each hole to retain the adapters where they span the vent opening. See Figures 80 and 81.
14. Insert 17A3 cover into 17A2 captured glazing adapter at each unit jamb and rotate into place as shown in Figures 83 and 84.
15. Cut the WC22 gaskets approximately 2” longer than the D.L.O. dimension.
16. Drive in WC22 wedge gaskets as shown in Figure 84. The gaskets should be applied starting in the center of the D.L.O., and then working from the ends, work the gaskets in place to the center of the lite.
17A3 Covers
WC22 Wedge
Gaskets
Drill tap sized holes in the face of the vertical assembly 1” from the sill end of the vent opening, and 18” on
HEAD SILL
Figure 80
STC6 18” o/c
Drill tap sized holes in the
groove formed where the
adapter meets the mullion.
center to the top of the vent opening.
Apply STC6 fasteners in each hole to retain the adapters where they span the vent opening.
17A3 Cover
WC22 Wedge Gasket
Insert 17A3 covers into 17A2 captured glazing adapters and drive in wedge gaskets.
Apply STC6 fasteners in each
hole to retain the adapters where
they span the vent opening.
Figure 82 Figure 81
17A2 Adapter
Figure 83
Figure 84
EFCO 2009 Page 49
Page 50
Series 8700 / 8800 Unitized Curtain Wall Assembly Instructions - Volume 5
Section 25 - Captured Vent Unit Glazing at Stack Sill : C. Adapter Installation
17. Slide WS00 vent surround gasket into the 17A2 glazing adapter, and apply the adapter to the vent head. See Figures 85 and 86.
18. Insert HS31 setting blocks at quarter points, or per the approved shop drawings, between the glazing and the 17A2 adapter at the vent head. See Figures below.
19. Apply the 17L2 concealed vent cover to the 17A2 glazing adapter at the vent head. See Figures 85 and 86.
20. Drive in WC22 wedge gaskets as shown in Figure 86. The gaskets should be applied starting in the center of the D.L.O., and then working from the ends, work the gaskets in place to the center of the lite.
17L2
Concealed
Vent Cover
WC22 Wedge
Gasket
HEAD
Apply (2) HS31
Setting Blocks
17A2 Glazing
Adapter
Slide WS00 gasket into 17A2 adapter, and apply the adapter to the vent head.
Apply the 17L2 concealed vent cover to the 17A2 glazing adapter and drive in WC22 wedge gasket.
SILL
Figure 85
WS00 Vent
Surround
(2) HS31
Setting Blocks
Figure 86 - Vent Head
Gasket
EFCO 2009 Page 50
Page 51
Series 8700 / 8800 Unitized Curtain Wall Assembly Instructions - Volume 5
Section 25 - Captured Vent Unit Glazing at Stack Sill : C. Adapter Installation
19. Slide WS00 vent surround gaskets into the 17L4 pocket fillers with the gaskets positioned with the rounded face of the gasket toward the exterior. WS00 runs the full length of the pocket filler.
20. Insert the pocket fillers into both glazing pockets of the jambs at the vent opening. Slide the pocket fillers to the exterior as shown in Figures 88 and 89.
21. Drive in the WVD1 wedge retainer gasket between the pocket filler and mullion. WVD1 runs the full length of the pocket filler. No sealant is required for
Slide WS00 gasket into
the 17L4 pocket filler and
insert the pocket filler
into the glazing pocket.
Drive in WVD1 gasket to
retain the pocket filler.
WC22 Wedge
Gasket
WS00 Vent
Surround Gasket
HEAD
WC22 Wedge
Gasket
WS00 Vent
Surround Gasket
17L4 Pocket
Filler
Slide WS00 gasket into
the 17L4 pocket filler and
insert the pocket filler
into the glazing pocket.
Drive in WVD1 gasket to
retain the pocket filler.
WS00 Vent
Surround Gasket
WC22 Wedge
Gasket
SILL
Figure 88 Figure 89
Figure 87
EFCO 2009 Page 51
Page 52
Series 8700 / 8800 Unitized Curtain Wall Assembly Instructions - Volume 5

Section 25 - Captured Vent Unit Glazing at Stack Sill : D. Joint Plug Installation

1. HNC4 joint plugs will be required at the head of the assembled unit frame. Using an approved solvent or cleaner, clean the surfaces of the mullions where the joint plug will be applied.
2. Apply joint plugs to the areas shown below as shown and noted in Volume 2, page 32 (head only) of the S-8000 Unitized Curtain Wall Assembly Instructions.
HNC4
HEAD
HNC4
Figure 90
HNC4 Joint Plug
Figure 91
SILL
EFCO 2009 Page 52
Page 53
Series 8700 / 8800 Unitized Curtain Wall Assembly Instructions - Volume 5

Section 26 - Assembly and Glazing - SSG Vent at Fixed Horizontal

1. Clean and prepare the inside areas at the ends of the sash where the corner keys will be applied.
2. Apply two-part epoxy adhesive inside each void of the sash at the corners
3. Insert EF01 corner keys into the voids of the sash at the corner intersections.
4. Verify that the assembled sash are true, plumb, absolutely square, and clamped securely inside the crimper.
5. Crimp each corner in succession, making sure to check for squareness after each crimp.
1H67 SSG
Head Sash
EF01 Corner
Key
Apply two-part epoxy adhesive inside
each void of the sash at the corners
prior to inserting the corner keys.
1H66 SSG
Jamb Sash
EF01 Corner
Key
Figure 93
Figure 94
EF01 Corner
Key
1H66 SSG
Jamb Sash
Apply two-part epoxy adhesive inside
each void of the sash at the corners
prior to inserting the corner keys.
1H67 SSG
Sill Sash
Figure 92
EF01 Corner
Key
Figure 95
Figure 96
EFCO 2009 Page 53
Page 54
Series 8700 / 8800 Unitized Curtain Wall Assembly Instructions - Volume 5
Section 26 - Assembly and Glazing - SSG Vent at Fixed Horizontal
6. Using an approved solvent or cleaner, clean the surfaces of the sash to receive the WC18, WS10 s pacer gaskets and sealant of all oils and other contaminants. The sealant manufacturer’s preparation and application instructions should be followed exactly.
7. If sealant primer is required, apply it per the primer/sealant manufacturer’s instructions. See the note in Figure 97 below.
8. Frames must be true and square before being structurally glazed. Improperly squared units will ca use significant problems during vent operation. Check the frame for squareness by comparing the difference between the two diagon al measurements of the frame by measuring from corner to opposing corner for the two diagonal dimensions. The vent frame must be absolutely square for glazing.
9. Apply WS10 offset spacer gaskets to the vertical sash members. Ensure the gaskets are applied as shown in Figure 99 and are flush with the side of the sash at the D.L.O. WS10 runs through at the corners, with WC18 running in between. Cut the gasket long, so it can be trimmed flush with the WC18 gaskets, as shown in Figures 100 and 101. Notch the gasket dart on each end of WS10 to clear the miter at the corners of the frame.
10. Apply WC18 offset spacer gaskets to the head and sill sash members. WC18 runs between the WS10 gaskets at the vertical sash members.
Head Sash 1H67
Apply flush
with sash.
Sill Sash 1H67
Figure 98
WS10 Offset SSG Spacer
Apply flush
with sash.
WC18 Offset SSG Spacer
Note: After cleaning and priming the glazing substrates (priming when required), the glazing must be set and the structural silicone applied immediately. The time between cleaning, priming, and applying the structural silicone should be less than two hours. Otherwise, the substrates may become contaminated, and the primer will oxidize. If units have been prepared for glazing at the end of the day, and sealant has not yet been applied, cleaning and priming must be redone prior to glazing the next day.
HEAD
WC18 Offset
SSG Spacer
WS10 Offset SSG Spacer
WC18 Offset
SSG Spacer
WS10 Offset SSG Spacer
WS10 Offset
SSG Spacer
Figure 100-Head
WC18 Offset
SSG Spacer
Jamb Sash
1H66
Figure 99
SILL
Figure 97
WC18 Offset
SSG Spacer
Figure 101-Sill
WS10 Offset
SSG Spacer
EFCO 2009 Page 54
Page 55
Series 8700 / 8800 Unitized Curtain Wall Assembly Instructions - Volume 5
Section 26 - Assembly and Glazing - SSG Vent at Fixed Horizontal
11. Inspect the I.G. unit for the vent frame. Any excessive sealant or irregularities at the perimeter should be cleaned and trimmed. Check the glass for damage, particularly along the glass edges and discard any unacceptable units. The secondary sealant joints of the insulated glass units should be checked for proper size. The approved shop drawings will indicate the required secondary sealant joint size for the gl azing on the general information page. Check the alignment of each pane making up the I.G. unit to ensure they are within acceptable limits. The I.G. unit overall dimensions should be verified for proper size.
12. Using an approved solvent or cleaner, thoroughly clean the edges of the glazing that will contact the structural silicone and spacer of all oils and other contaminants. Once the glass has been cleaned, it should be han dled with gloves or glass manipulator to avoid to avoid contaminating the edges that come into contact with the structural silicone glazing joint.
13. Set the glazing on the silicone spacer gaskets positioned as shown below. The edge of the glazing extends past the edge of the vertical sash by 15/16”. Refer to Figures 103 and 105 below. Ensure the glazing is positioned with the exterior side out, and the bottom of the glazing to the setting blocks. Care should be exercised to avoid shifting or rolling the spacer gaskets when adjusting the position of the glass.
14. Temporarily insert the HS32 setting blocks between the sill sash fin and glazing to position the glazing to the sill. Remove the blocks after final alignment of the glazing to apply the structural silicone. See Figure 104.
Set glazing onto the
silicone spacer
gaskets and against
the setting blocks at
the sill sash fin.
Insert HS32 setting block.
15/16”
Figure 103 - Jamb Sash
Figure 102
Figure 105 - Jamb Sash
Insert HS32
setting block.
Sill sash fin.
Figure 104 - Sill Sash
15/16”
EFCO 2009 Page 55
Page 56
Series 8700 / 8800 Unitized Curtain Wall Assembly Instructions - Volume 5
Section 26 - Assembly and Glazing - SSG Vent at Fixed Horizontal
15. Apply structural silicone sealant into the void between the glass and mullion per the sealant manufacturer’s application instructions. See additional notes, and figures below for sealant application and tooling instructions. A 90 degree nozzle may be required at the head and sill sash due to the fin bar at those locations.
16. Immediately tool the sealant joint after application to insure the joint is completely filled with sealant on all four sides of each piece of glazing. Make sure no air bubbles or voids are present in the sealant joint. See Figure 110.
17. Insert the HS32 setting blocks between the sill sash fin and glazing at quarter points or as directed per the final approved shop drawings. See Figure 104 on page 55.
Structural
Fin bar
Figure 108 - Head (Sill Similar)
Silicone Sealant
Apply structural silicone
sealant into the void and
tool the joint to fill the
void completely.
Apply structural silicone sealant into the void.
Figure 107
Insert HS32 setting block.
Figure 106
Note: Only silicone sealants which have been developed and tested specifically for structural glazing applications should be used for glazing purposes.
Structural
Silicone Sealant
Figure 109 - Jamb
Tool the joint to fill
the void completely.
Figure 110
EFCO 2009 Page 56
Page 57
Series 8700 / 8800 Unitized Curtain Wall Assembly Instructions - Volume 5
Section 26 - Assembly and Glazing - SSG Vent at Fixed Horizontal
18. Using an approved solvent or cleaner, clean the sealant contact surfaces of the glazing and head and sill fins of all oils and other contaminants.
19. If sealant primer is required, apply it per the primer/sealant manufacturer’s instructions.
20. Insert backer rod between the glazing and head and sill fins. See Figures 113 and 114.
21. Apply sealant into the void between the adapters and glazing. If the sealant is properly and carefully applied, masking tape is not necessary on the adjacent surfaces.
22. Before the sealant begins to cure or skin over, tool the sealant into the joints smoothly, taking care to smooth and blend the sealant at each end of the head and sill fin bars as shown below. Seen in section view, the sealant should have an hourglass shape and maintain a 2:1 width to depth ratio Remove any excess sealant from the surrounding surfaces before the sealant begins to cure.
23. The glazed vent should not be moved before the structural sealant joints cure and per the sealant manufacturer’s recommendations.
Figure 112
Apply backer
rod silicone
sealant into
the void and
tool smooth.
Tool sealant smooth.
Apply backer
rod silicone sealant into
the void and
tool smooth.
Figure 114 - Head
Tool sealant
smooth.
Figure 111
Figure 113 - Sill
Figure 115
EFCO 2009 Page 57
Page 58
Series 8700 / 8800 Unitized Curtain Wall Assembly Instructions - Volume 5

Section 27 - Assembly and Glazing - SSG Vent at Stack Sill

1. Clean and prepare the inside areas at the ends of the sash where the corner keys will be applied.
2. Apply two-part epoxy adhesive inside each void of the sash at the corners
3. Insert EF01 corner keys into the voids of the sash at the corner intersections.
4. Verify that the assembled sash are true, plumb, absolutely square, and clamped securely inside the crimper.
5. Crimp each corner in succession, making sure to check for squareness after each crimp.
1H67 SSG
Head Sash
EF01 Corner
Key
Apply two-part epoxy adhesive inside
each void of the sash at the corners
prior to inserting the corner keys.
1H66 SSG
Jamb Sash
EF01 Corner
Key
Figure 117
Figure 118
EF01 Corner
Key
1H66 SSG
Jamb Sash
Apply two-part epoxy adhesive inside
each void of the sash at the corners
prior to inserting the corner keys.
1H69 SSG Sill Sash at Stack
Figure 116
EF01 Corner
Key
Figure 119
Figure 120
EFCO 2009 Page 58
Page 59
Series 8700 / 8800 Unitized Curtain Wall Assembly Instructions - Volume 5
Section 27 - Assembly and Glazing - SSG Vent at Stack Sill
6. Using an approved solvent or cleaner, clean the surfaces of the sash to receive the WC18, WS10 spacer gaskets and sealant of all oils and other contaminants. The sealant manufacturer’s preparation and application instructions should be followed exactly.
7. If sealant primer is required, apply it per the primer/sealant manufacturer’s instructions. See the note in Figure 121 below.
8. Frames must be true and square before being structurally glazed. Improperly squared units will cause significant problems during vent operation. Check the frame for squareness by comparing the difference between the two diagonal measurements of the frame by measuring from corner to opposing corner for the two diagonal dimensions. The vent frame must be absolutely square for glazing.
9. Apply WS10 offset spacer gaskets to the vertical and sill sash members. Ensure the gaskets are applied as shown in Figures 122 and 123 and are flush with the side of the sash at the D.L.O. WS10 runs through vertically at the corners, with the WC18 at the head and WS10 at the sill running in between. Cut the gasket long, so it can be trimmed flush with the WC18 gaskets, as shown in Figures 124 and 125. Notch the gasket dart on each end of WS10 to clear the miter at the corners of the frame.
10. Apply WC18 offset spacer gasket to the head sash member. The horizontal gaskets run between the WS10 gaskets at the vertical sash members.
Head Sash 1H67
Apply flush
with sash.
Sill Sash 1H69
Figure 122
WS10 Offset SSG Spacer
WC18 Offset
SSG Spacer
WS10 Offset
SSG Spacer
Note: After cleaning and priming the glazing substrates (priming when required), the glazing must be set and the structural silicone applied immediately. The time between cleaning, priming, and applying the structural silicone should be less than two hours. Otherwise, the substrates may become contaminated, and the primer will oxidize. If units have been prepared for glazing at the end of the day, and sealant has not yet been applied, cleaning and priming must be redone prior to glazing the next day.
HEAD
WC18 Offset
SSG Spacer
WS10 Offset SSG Spacer
WS10 Offset
SSG Spacer
WS10 Offset SSG Spacer
WS10 Offset
SSG Spacer
Figure 124-Head
WC18 Offset
SSG Spacer
Apply flush
with sash.
Jamb Sash
1H66
Figure 123
SILL
Figure 121
WS10 Offset
SSG Spacer
Figure 125-Sill
WS10 Offset
SSG Spacer
EFCO 2009 Page 59
Page 60
Series 8700 / 8800 Unitized Curtain Wall Assembly Instructions - Volume 5
Section 27 - Assembly and Glazing - SSG Vent at Stack Sill
11. Inspect the I.G. unit for the vent frame. Any excessive sealant or irregularities at the perimeter should be cleaned and trimmed. Check the glass for damage, particularly along the glass edges and discard any unacceptable units. The secondary sealant joints of the insulated glass units should be checked for proper size. The approved shop drawings will indicate the required secondary sealant joint size for the gl azing on the general information page. Check the alignment of each pane making up the I.G. unit to ensure they are within acceptable limits. The I.G. unit overall dimensions should be verified for proper size.
12. Using an approved solvent or cleaner, thoroughly clean the edges of the glazing that will contact the structural silicone and spacer of all oils and other contaminants. Once the glass has been cleaned, it should be han dled with gloves or glass manipulator to avoid to avoid contaminating the edges that come into contact with the structural silicone glazing joint.
13. Set the glazing on the silicone spacer gaskets positioned as shown below. The edge of the glazing extends past the edge of the vertical sash by 15/16”. Refer to Figures 127 and 129 below. Ensure the glazing is positioned with the exterior side out, and the bottom of the glazing to the setting blocks. Care should be exercised to avoid shifting or rolling the spacer gaskets when adjusting the position of the glass.
14. Temporarily insert the HS32 setting blocks between the sill sash fin and glazing to position the glazing to the sill. Remove the blocks after final alignment of the glazing to apply the structural silicone. See Figure 128.
Set glazing onto the
silicone spacer
gaskets and against
the setting blocks at
the sill sash fin.
Insert HS32 setting block.
15/16”
Figure 127 - Jamb Sash Figure 129 - Jamb Sash
Insert HS32
setting block.
Sill sash fin.
Figure 126
Figure 128 - Sill Sash
15/16”
EFCO 2009 Page 60
Page 61
Series 8700 / 8800 Unitized Curtain Wall Assembly Instructions - Volume 5
Section 27 - Assembly and Glazing - SSG Vent at Stack Sill
15. Apply structural silicone sealant into the void between the glass and mullion per the sealant manufacturer’s application instructions. See additional notes, and figures below for sealant application and tooling instructions. A 90 degree nozzle may be required at the head and sill sash due to the fin bar at those locations.
16. Immediately tool the sealant joint after application to insure the joint is completely filled with sealant on all four sides of each piece of glazing. Make sure no air bubbles or voids are present in the sealant joint. See Figure 134.
17. Insert the HS32 setting blocks between the sill sash fin and glazing at quarter points or as directed per the final approved shop drawings. See Figure 128 on page 60.
Structural
Fin bar
Figure 132 - Head (Sill Similar)
Silicone Sealant
Apply structural silicone
sealant into the void and
tool the joint to fill the
void completely.
Apply structural silicone sealant into the void.
Figure 131
Insert HS32 setting block.
Figure 130
Note: Only silicone sealants which have been developed and tested specifically for structural glazing applications should be used for glazing purposes.
Structural
Silicone Sealant
Figure 133 - Jamb
Tool the joint to fill
the void completely.
Figure 134
EFCO 2009 Page 61
Page 62
Series 8700 / 8800 Unitized Curtain Wall Assembly Instructions - Volume 5
Section 27 - Assembly and Glazing - SSG Vent at Stack Sill
18. Using an approved solvent or cleaner, clean the sealant contact surfaces of the glazing and head and sill fins of all oils and other contaminants.
19. If sealant primer is required, apply it per the primer/sealant manufacturer’s instructions.
20. Insert backer rod between the glazing and head and sill fins. See Figures 137 and 138.
21. Apply sealant into the void between the adapters and glazing. If the sealant is properly and carefully applied, masking tape is not necessary on the adjacent surfaces.
22. Before the sealant begins to cure or skin over, tool the sealant into the joints smoothly, taking care to smooth and blend the sealant at each end of the head and sill fin bars as shown below. Seen in section view, the sealant should have an hourglass shape and maintain a 2:1 width to depth ratio Remove any excess sealant from the surrounding surfaces before the sealant begins to cure.
23. The glazed vent should not be moved before the structural sealant joints cure and per the sealant manufacturer’s recommendations.
Figure 136
Apply backer
rod silicone
sealant into
the void and
tool smooth.
Tool sealant smooth.
Apply backer
rod silicone sealant into
the void and
tool smooth.
Figure 138 - Head
Tool sealant
smooth.
Figure 135
Figure 137 - Sill
Figure 139
EFCO 2009 Page 62
Page 63
Series 8700 / 8800 Unitized Curtain Wall Assembly Instructions - Volume 5

Section 28 - Assembly and Glazing - Captured Vent at Fixed Horizontal

1. Clean and prepare the inside areas at the ends of the sash where the corner keys will be applied.
2. Apply two-part epoxy adhesive inside each void of the sash at the corners
3. Insert EF01 corner keys into the voids of the sash at the corner intersections.
4. Verify that the assembled sash are true, plumb, absolutely square, and clamped securely inside the crimper.
5. Crimp each corner in succession, making sure to check for squareness after each crimp.
1H66 SSG
Head Sash
EF01 Corner
Key
Apply two-part epoxy adhesive inside
each void of the sash at the corners
prior to inserting the corner keys.
1H66 SSG
Jamb Sash
EF01 Corner
Key
Figure 141
Figure 142
EF01 Corner
Key
Apply two-part epoxy adhesive inside
each void of the sash at the corners
prior to inserting the corner keys.
1H68 Captured Sill
Sash at Stack
Figure 140
1H66 SSG
Jamb Sash
EF01 Corner
Key
Figure 143
Figure 144
EFCO 2009 Page 63
Page 64
Series 8700 / 8800 Unitized Curtain Wall Assembly Instructions - Volume 5
Section 28 - Assembly and Glazing - Captured Vent at Fixed Horizontal
6. Using an approved solvent or cleaner, clean the surfaces of the sash to receive the WC18, WS10 spacer gaskets and sealant of all oils and other contaminants. The sealant manufacturer’s preparation and application instructions should be followed e xactly.
7. If sealant primer is required, apply it per the primer/sealant manufacturer’s instructions. See the note in Figure 145 below.
8. Frames must be true and square before being structurally glazed. Improperly squared units will cause significant problems during vent operation. Check the frame for squareness by comparing the difference between the two diagonal measurements of the frame by measuring from corner to opposing corner for the two diagonal dimensions. The vent frame must be absolutely square for glazing.
9. Apply WS10 offset spacer gaskets to the vertical and head sash members. Ensure the gaskets are applied as shown in Figures 146 and 147 and are flush with the side of the sash at the D.L.O. WS10 runs through vertically at the corners, with the WC18 at the sill and WS10 at the head running in between. Cut the gasket long, so it can be trimmed flush with the horizontal gaskets, as shown in Figures 148 and 149. Notch the gasket dart on each end of WS10 to clear the miter at the corners of the frame.
10. Apply the WC18 offset spacer gasket to the sill sash member. The horizontal gaskets run between the WS10 gaskets at the vertical sash members.
Head Sash 1H66
Apply flush
with sash.
Sill Sash 1H68
Figure 146
WS10 Offset SSG Spacer
WS10 Offset SSG Spacer
WC18 Offset
SSG Spacer
Note: After cleaning and priming the glazing substrates (priming when required), the glazing must be set and the structural silicone applied immediately. The time between cleaning, priming, and applying the structural silicone should be less than two hours. Otherwise, the substrates may become contaminated, and the primer will oxidize. If units have been prepared for glazing at the end of the day, and sealant has not yet been applied, cleaning and priming must be redone prior to glazing the next day.
HEAD
WS10 Offset
SSG Spacer
WS10 Offset SSG Spacer
WC18 Offset
SSG Spacer
WS10 Offset SSG Spacer
WS10 Offset
SSG Spacer
Figure 148-Head
WS10 Offset
SSG Spacer
Apply flush
with sash.
Jamb Sash
1H66
Figure 147
SILL
Figure 145
WC18 Offset
SSG Spacer
Figure 149-Sill
WS10 Offset
SSG Spacer
EFCO 2009 Page 64
Page 65
Series 8700 / 8800 Unitized Curtain Wall Assembly Instructions - Volume 5
Section 28 - Assembly and Glazing - Captured Vent at Fixed Horizontal
11. Inspect the I.G. unit for the vent frame. Any excessive sealant or irregularities at the perimeter should be cleaned and trimmed. Check the glass for damage, particularly along the glass edges and discard any unacceptable units. The secondary sealant joints of the insulated glass units should be checked for proper size. The approved shop drawings will indicate the required secondary sealant joint size for the gl azing on the general information page. Check the alignment of each pane making up the I.G. unit to ensure they are within acceptable limits. The I.G. unit overall dimensions should be verified for proper size.
12. Using an approved solvent or cleaner, thoroughly clean the edges of the glazing that will contact the structural silicone and spacer of all oils and other contaminants. Once the glass has been cleaned, it should be han dled with gloves or glass manipulator to avoid contaminating the edges that come into contact with the structural silicone glazing joint.
13. Set the glazing on the silicone spacer gaskets positioned as shown below. The edge of the glazing is flush with the edge of the vertical sash as shown. Refer to Figures 151 and 153 below. Ensure the glazing is positioned with the exterior side out, and the bottom of the glazing to the setting blocks. Care should be exercised to avoid shifting or rolling the spacer gaskets when adjusting the position of the glass.
14. Temporarily insert the HS32 setting blocks between the sill sash fin and glazing to position the glazing to the sill. Remove the blocks after final alignment of the glazing to apply the structural silicone. See Figure 152.
Set glazing onto the
silicone spacer
gaskets and against
the setting blocks at
the sill sash fin.
Insert HS32
FLUSH
setting block.
FLUSH
Figure 150
Figure 151 - Jamb Sash
Insert HS32
setting block.
Sill sash fin.
Figure 152 - Sill Sash
Figure 153 - Jamb Sash
EFCO 2009 Page 65
Page 66
Series 8700 / 8800 Unitized Curtain Wall Assembly Instructions - Volume 5
Section 28 - Assembly and Glazing - Captured Vent at Fixed Horizontal
15. Apply structural silicone sealant into the void between the glass and mullion per the sealant manufacturer’s application instructions. See additional notes, and figures below for sealant application and tooling instructions. A 90 degree nozzle may be required at the sill sash due to the fin bar at this location.
16. Immediately tool the sealant joint after application to insure the joint is completely filled with sealant on all four sides of each piece of glazing. Make sure no air bubbles or voids are present in the sealant joint. See Figure 158.
17. Insert the HS32 setting blocks between the sill sash fin and glazing at quarter points or as directed per the final approved shop drawings. See Figure 152 on page 65.
Structural
Fin bar
Figure 156 - Sill (Head Similar)
Silicone Sealant
Apply structural silicone
sealant into the void and
tool the joint to fill the
void completely.
Apply structural silicone sealant into the void.
Figure 155
Insert HS32 setting block.
Figure 154
Note: Only silicone sealants which have been developed and tested specifically for structural glazing applications should be used for glazing purposes.
Structural
Silicone Sealant
Figure 157 - Jamb
Tool the joint to fill
the void completely.
Figure 158
EFCO 2009 Page 66
Page 67
Series 8700 / 8800 Unitized Curtain Wall Assembly Instructions - Volume 5
Section 28 - Assembly and Glazing - Captured Vent at Fixed Horizontal
18. Apply 17L2 cover to the sill sash member making it flush with each end of the sill sash.
19. Drive in the WC22 wedge gasket between the glazing and the 17L2 cover.
Apply 17L2 cover.
Drive in the WC22 wedge gasket .
Figure 159
Drive in the WC22
wedge gasket .
Apply 17L2
cover.
Figure 160 Figure 161
EFCO 2009 Page 67
Page 68
Series 8700 / 8800 Unitized Curtain Wall Assembly Instructions - Volume 5

Section 29 - Assembly and Glazing - Captured Vent at Stack Sill

1. Clean and prepare the inside areas at the ends of the sash where the corner keys will be applied.
2. Apply two-part epoxy adhesive inside each void of the sash at the corners
3. Insert EF01 corner keys into the voids of the sash at the corner intersections.
4. Verify that the assembled sash are true, plumb, absolutely square, and clamped securely inside the crimper.
5. Crimp each corner in succession, making sure to check for squareness after each crimp.
1H66 SSG
Head Sash
EF01 Corner
Key
Apply two-part epoxy adhesive inside
each void of the sash at the corners
prior to inserting the corner keys.
1H66 SSG
Jamb Sash
EF01 Corner
Key
Figure 163
Figure 164
EF01 Corner
Key
Apply two-part epoxy adhesive inside
each void of the sash at the corners
prior to inserting the corner keys.
1H70 Captured Sill
Sash at Stack
Figure 162
1H66 SSG
Jamb Sash
EF01 Corner
Key
Figure 165
Figure 166
EFCO 2009 Page 68
Page 69
Series 8700 / 8800 Unitized Curtain Wall Assembly Instructions - Volume 5
Section 29 - Assembly and Glazing - Captured Vent at Stack Sill
6. Using an approved solvent or cleaner, clean the surfaces of the sash to receive the WS10 spacer gaskets and sealant of all oils and other contaminants. Th e sealant manufacturer’s preparation and application instructions should be followed exactly.
7. If sealant primer is required, apply it per the primer/sealant manufacturer’s instructions. See the note in Figure 167 below.
8. Frames must be true and square before being structurally glazed. Improperly squared units will cause significant problems during vent operation. Check the frame for squareness by comparing the difference between the two diagonal measurements of the frame by measuring from corner to opposing corner for the two diagonal dimensions. The vent frame must be absolutely square for glazing.
9. Apply WS10 offset spacer gaskets to the vertical sash members. Ensure the gaskets are applied as shown in Figures 168 and 169 and are flush with the side of the sash at the D.L.O. WS10 runs through vertically at the corners, with the WS10 at the head and sill running in between. Cut the gasket long, so it can be trimmed flush with the horizontal gaskets, as shown in Figures 170 and 171. Notch the gasket dart on each end of WS10 to clear the miter at the corners of the frame.
10. Apply the WC18 offset spacer gasket to the head and sill sash member. The horizontal gaskets run between the WS10 gaskets at the vertical sash members.
Head Sash 1H66
Apply flush
with sash.
Sill Sash 1H70
Figure 168
WS10 Offset SSG Spacer
WS10 Offset SSG Spacer
WC18 Offset
SSG Spacer
Note: After cleaning and priming the glazing substrates (priming when required), the glazing must be set and the structural silicone applied immediately. The time between cleaning, priming, and applying the structural silicone should be less than two hours. Otherwise, the substrates may become contaminated, and the primer will oxidize. If units have been prepared for glazing at the end of the day, and sealant has not yet been applied, cleaning and priming must be redone prior to glazing the next day.
HEAD
WS10 Offset
SSG Spacer
WS10 Offset SSG Spacer
WS10 Offset
SSG Spacer
WS10 Offset
SSG Spacer
WS10 Offset
SSG Spacer
Figure 170-Head
WS10 Offset
SSG Spacer
Apply flush
with sash.
Jamb Sash
1H66
Figure 169
SILL
Figure 167
WS10 Offset
SSG Spacer
Figure 171-Sill
WS10 Offset
SSG Spacer
EFCO 2009 Page 69
Page 70
Series 8700 / 8800 Unitized Curtain Wall Assembly Instructions - Volume 5
Section 29 - Assembly and Glazing - Captured Vent at Stack Sill
11. Inspect the I.G. unit for the vent frame. Any excessive sealant or irregularities at the perimeter should be cleaned and trimmed. Check the glass for damage, particularly along the glass edges and discard any unacceptable units. The secondary sealant joints of the insulated glass units should be checked for proper size. The approved shop drawings will indicate the required secondary sealant joint size for the gl azing on the general information page. Check the alignment of each pane making up the I.G. unit to ensure they are within acceptable limits. The I.G. unit overall dimensions should be verified for proper size.
12. Using an approved solvent or cleaner, thoroughly clean the edges of the glazing that will contact the structural silicone and spacer of all oils and other contaminants. Once the glass has been cleaned, it should be han dled with gloves or glass manipulator to avoid contaminating the edges that come into contact with the structural silicone glazing joint.
13. Set the glazing on the silicone spacer gaskets positioned as shown below. The edge of the glazing is flush with the edge of the vertical sash as shown. Refer to Figures 173 and 175 below. Ensure the glazing is positioned with the exterior side out, and the bottom of the glazing to the setting blocks. Care should be exercised to avoid shifting or rolling the spacer gaskets when adjusting the position of the glass.
14. Temporarily insert the HS32 setting blocks between the sill sash fin and glazing to position the glazing to the sill. Remove the blocks after final alignment of the glazing to apply the structural silicone. See Figure 174.
Set glazing onto the
silicone spacer
gaskets and against
the setting blocks at
the sill sash fin.
Insert HS32
FLUSH
setting block.
FLUSH
Figure 172
Figure 173 - Jamb Sash
Insert HS32
setting block.
Sill sash fin.
Figure 174 - Sill Sash
Figure 175 - Jamb Sash
EFCO 2009 Page 70
Page 71
Series 8700 / 8800 Unitized Curtain Wall Assembly Instructions - Volume 5
Section 29 - Assembly and Glazing - Captured Vent at Stack Sill
15. Apply structural silicone sealant into the void between the glass and mullion per the sealant manufacturer’s application instructions. See additional notes, and figures below for sealant application and tooling instructions. A 90 degree nozzle may be required at the sill sash due to the fin bar at this location.
16. Immediately tool the sealant joint after application to insure the joint is completely filled with sealant on all four sides of each piece of glazing. Make sure no air bubbles or voids are present in the sealant joint. See Figure 180.
17. Insert the HS32 setting blocks between the sill sash fin and glazing at quarter points or as directed per the final approved shop drawings. See Figure 174 on page 70.
Structural Silicone Sealant
Fin bar
Figure 178 - Sill (Head Similar)
Apply structural silicone
sealant into the void and
tool the joint to fill the
void completely.
Apply structural silicone sealant into the void.
Figure 177
Insert HS32 setting block.
Figure 176
Note: Only silicone sealants which have been developed and tested specifically for structural glazing applications should be used for glazing purposes.
Structural
Silicone Sealant
Figure 179 - Jamb
Tool the joint to fill
the void completely.
Figure 180
EFCO 2009 Page 71
Page 72
Series 8700 / 8800 Unitized Curtain Wall Assembly Instructions - Volume 5
Section 29 - Assembly and Glazing - Captured Vent at Stack Sill
18. Apply 17L2 cover to the sill sash member making it flush with each end of the sill sash.
19. Drive in the WC22 wedge gasket between the glazing and the 17L2 cover.
Apply 17L2 cover.
Drive in the WC22 wedge gasket .
Figure 181
Apply 17L2
cover.
Figure 182 Figure 182
Drive in the WC22
wedge gasket .
EFCO 2009 Page 72
Page 73
Series 8700 / 8800 Unitized Curtain Wall Assembly Instructions - Volume 5

Section 30 - Hardware Mounting On Unit Frame

1. Measure and mark all centerline locations for the keeps and the snubbers. Refer to the final approved shop drawings and the factory order for locations.
2. Apply the snubbers at the head of the vent opening by inserting the tab of each snubber into the groove in the hardware reglet of the horizontal and rotate into position. Align the snubbers, centered on the marked centerline locations and tighten the pinning scre w with an Allen wrench. The number and location of snubbers will vary depending on vent size and design pressure. Snubbers will not be required for all vent configuration s. Refer to the final approved shop drawings and the factory order for quantities and locations. See Figures 182 below, and 185-187 on p age 74.
3. Apply the keepers at the jambs and sill of the vent opening by inserting the tab of each keeper into the groove in the hardware reglet of the jamb adapters and the sill and rotate into position. Align the keepers, centered on the marked centerline locations and tighten the pinning screw with an Allen wrench. The number and location of keepers will vary depending on vent size and design pressure. Keepers will not be required at the jambs for all vent configurations. Refer to the final approved shop drawings and the factory order for quantities and locations. See Figures 183 and 184 below, and 188-189 on page 74.
HEAD SILL
Figure 181
Adjustable Keeper Adjustable Snubber
Adjustable Snubbers Adjustable Keepers Adjustable Keepers
Figure 182
Figure 183 Figure 184
EFCO 2009 Page 73
Page 74
Series 8700 / 8800 Unitized Curtain Wall Assembly Instructions - Volume 5
Section 30 - Hardware Mounting On Unit Frame
Insert the snubbers into the reglet at the head.
Figure 185 Figure 186 Figure 187
Insert the keepers into the reglet at the jambs and sill.
Pinning Screw
Pinning Screw
Tighten the pinning screw with an Allen wrench.
Tighten the pinning screw with an Allen wrench.
Figure 188 Figure 189 Figure 190
EFCO 2009 Page 74
Page 75
Series 8700 / 8800 Unitized Curtain Wall Assembly Instructions - Volume 5

Section 31 - Gasket Application and Hardware Mounting On Vent Frame

1. The figures below show a vent configuration for a SSG vent with a fixed horizontal at the vent sill. All other vent configurations will receive the WA07 preset gasket in the same fashion. See Figures 197 - 200, page 77, 201 - 204, page 78, and 205 - 208, page 79.
2. Apply the interior WA07 preset gasket starting at the center of the head sash. The interior WA07 gasket wraps around on all four sides of the vent with one continuous piece. Form as tight a radius as possible at the corners with the gasket. Ensure the gasket is not stretched during application. Butt the ends together at the head, crowding in extra gasket to ovoid gaps later due to gasket shrinkage. See the Figures below and 194 - 196 on page 76.
3. Apply the exterior WA07 preset gasket to the jamb starting and ending 3” above the sill sash wrapping aro und the corners at the head. The exterior WA07 wraps around both jambs and the head on only three sides of the vent as one continuous piece. (See Figure 192).
4. Apply a piece of the WA07 preset gasket to the exterior leg of the sill sash of the vent that starts and stops 6” short of the jamb sash. See Figure 192 below.
Apply the interior WA07 preset gasket starting at the center of the head sash.
HEAD
SSG Vent at Fixed Horizontal
Figure 195
Page 77
INTERIOR VIEW
Figure 193
Page 77
Figure 196
Page 77
Exterior WA07 starts and ends 3”
above the sill sash and wraps
around on three sides of the vent.
Interior WA07 starts at the center of
the head sash and wraps around on
all four sides of the vent.
HEAD
INTERIOR VIEW
Apply a piece of the WA07 preset
gasket to the exterior leg of the sill
sash of the vent that starts and
stops 6” short of the jamb sash.
SILL
Apply exterior WA07
Figure 194
Page 77
preset gasket to the jamb
starting 3” above the sill
sash. (See Figure 192)
3”
SILL
Figure 191
Interior WA07 wraps around on all four sides of the vent.
WA07 Preset
Gasket
6”
Figure 192
Exterior WA07 wraps around
on three sides of the vent.
3”
6”
EFCO 2009 Page 75
Page 76
Series 8700 / 8800 Unitized Curtain Wall Assembly Instructions - Volume 5
Section 31 - Gasket Application and Hardware Mounting On Vent Frame
SSG Vent at Fixed Horizontal
Exterior WA07 starts and ends 3”
above the sill sash and wraps
around on three sides of the vent.
Interior WA07
starts at the center
of the head sash
and wraps around
on all four sides of
the vent.
Figure 193 HEAD
Interior WA07
starts at the center
of the head sash
and wraps around
on all four sides of
the vent.
Apply a piece of the WA07 preset
gasket to the exterior leg of the sill
sash of the vent that starts and stops
6” short of the jamb sash on each end.
Figure 194 SILL
Figure 195 JAMB
Exterior WA07 starts
and ends 3” above the
sill sash and wraps
around on three sides
of the vent.
Figure 196 JAMB
EFCO 2009 Page 76
Page 77
Series 8700 / 8800 Unitized Curtain Wall Assembly Instructions - Volume 5
Section 31 - Gasket Application and Hardware Mounting On Vent Frame
SSG Vent at Stack Sill
Exterior WA07 starts and ends 3”
above the sill sash and wraps
around on three sides of the vent.
Interior WA07
starts at the center
of the head sash
and wraps around
on all four sides of
the vent.
Figure 197 HEAD
Figure 199 JAMB
Interior WA07
starts at the center
of the head sash
Figure 198 SILL
and wraps around
on all four sides of
the vent.
Apply a piece of the WA07 preset gasket to the exterior leg of the sill sash of the vent that starts and stops 6” short of the jamb sash on each end.
Slide in a piece of the WS00 gasket into the fin bar of the sill sash of the vent. WS00 cut length to equal that of the fin where the gasket is applied.
Figure 200 JAMB
Exterior WA07 starts
and ends 3” above the
sill sash and wraps
around on three sides
of the vent.
EFCO 2009 Page 77
Page 78
Series 8700 / 8800 Unitized Curtain Wall Assembly Instructions - Volume 5
Section 31 - Gasket Application and Hardware Mounting On Vent Frame
Captured Vent at Fixed Horizontal
Exterior WA07 starts and ends 3”
above the sill sash and wraps
around on three sides of the vent.
Interior WA07
starts at the center
of the head sash
and wraps around
on all four sides of
the vent.
Figure 201 HEAD
Interior WA07
starts at the center
of the head sash
and wraps around
on all four sides of
the vent.
Apply a piece of the WA07 preset gasket to the exterior leg of the sill sash of the vent that starts and stops 6” short of the jamb sash on each end.
Slide in a piece of the WS00 gasket into the fin bar of the sill sash of the vent. WS00 cut length to equal that of the fin where the gasket is applied.
Figure 202 SILL
Figure 203 JAMB
Exterior WA07 starts
and ends 3” above the
sill sash and wraps
around on three sides
of the vent.
Figure 204 JAMB
EFCO 2009 Page 78
Page 79
Series 8700 / 8800 Unitized Curtain Wall Assembly Instructions - Volume 5
Section 31 - Gasket Application and Hardware Mounting On Vent Frame
Captured Vent at Stack Sill
Exterior WA07 starts and ends 3”
above the sill sash and wraps
around on three sides of the vent.
Interior WA07
starts at the center
of the head sash
and wraps around
on all four sides of
the vent.
Figure 205 HEAD
Interior WA07
starts at the center
of the head sash
and wraps around
on all four sides of
the vent.
Apply a piece of the WA07 preset gasket to the exterior leg of the sill sash of the vent that starts and stops 6” short of the jamb sash on each end.
Slide in a piece of the WS00 gasket into the fin bar of the sill sash of the vent. WS00 cut length to equal that of the fin where the gasket is applied.
Figure 206 SILL
Figure 207 JAMB
Exterior WA07 starts
and ends 3” above the
sill sash and wraps
around on three sides
of the vent.
Figure 208 JAMB
EFCO 2009 Page 79
Page 80
Series 8700 / 8800 Unitized Curtain Wall Assembly Instructions - Volume 5
Section 31 - Gasket Application and Hardware Mounting On Vent Frame
5. Install the lock handle to the sill of the vent. Insert the lock handle connection block bars into the slot in the sill, aligning it with the mounting holes. Attach it with the (2) supplied fasteners. Ensure the lock handle is properly installed so that when the handle is operated, it rotates away from the glazing. Left or right hand lock handles are available. Refer to the approved shop drawings and the factory order for the required handing. See figure s 210 and 211 on page 81.
6. Slide the connection blocks onto the connection block bars of the lock handle positioned as shown in Figure 212 on page 81.
7. Slide the (2) linkage struts and lock pawls on each side of the lock handl e into the hardware reglet in the sill. As the first strut is slid into position, slide in the adjacent lock pawl at the same time. Insert the stud on the lock pawl into the hole in the end of the strut and slide the pawl half way into the reglet. See Figure 213 on page 81. Insert the stud on the other end of the lock pawl into the hole in the end of the second strut and slide the pawl and the second strut into the reglet until the hole at the end of the first strut aligns with the hole in the connection block at the lock handle. See Figure 214 on page 81. Attach the strut to the connection block with the supplied fasteners. Repeat the steps above for the struts and lock pawl on the opp osite side of the lock ha ndle.
HEAD
Sill Linkage
Struts
Sill Linkage
Struts
INTERIOR VIEW
Lock Pawls
Figures 210,
211, 212
Page 81
SILL
Jamb Linkage
Struts
Lock Pawl
Corner Drive
Figure 209
Lock Pawls
Jamb Linkage
Struts
Lock Pawl
Corner Drive
EFCO 2009 Page 80
Page 81
Series 8700 / 8800 Unitized Curtain Wall Assembly Instructions - Volume 5
Section 31 - Gasket Application and Hardware Mounting On Vent Frame
Install lock handle and
attach with the (2)
supplied fasteners.
Lock Pawl
Figure 210
Linkage Struts
Insert lock pawl studs into holes in the struts and slide into reglet in vent sill sash.
Figure 211
Lock Handle
Connection
Block Bars
Connection Blocks
Figure 212
Slide struts to align with holes in connection blocks and attach with the (2) supplied fasteners.
Linkage Struts
Figure 213
Figure 214
EFCO 2009 Page 81
Page 82
Series 8700 / 8800 Unitized Curtain Wall Assembly Instructions - Volume 5
Section 31 - Gasket Application and Hardware Mounting On Vent Frame
8. Slide a lock pawl inserted on to a linkage strut into the hardware reglet of one of the vent jamb sash. See Figure 216 on page 83.
9. As the first strut and lock pawl are slid into position, Insert the second lock pawl studs into the holes in the first and second strut and slide them into the reglet in the vent jamb sash leaving the end of the strut extended from the sash. See Figure 217 on page 83.
10. Insert the stud of the corner drive into the hole in the end of the strut and slide the strut and corner drive into the reglet. See Figure 218 on page 83.
11. As the corner drive is slid in place, align the stud with the hole in the strut in the sill as show and mate them together. See Figure 219 on page 83.
12. Insert the corner drive retainer clip into the corner drive and reglet to lock the corner drive assembly in place. See Figure 220 on page 83.
13. Repeat the steps above for the struts, lock pawl, and corner drive on the opposite vent jamb sash.
HEAD
Jamb Linkage
INTERIOR VIEW
Struts
Lock Pawl
Corner Drive
SILL
Lock Pawl
Jamb Linkage
Struts
Lock Pawl
Figure 215
Corner Drive
EFCO 2009 Page 82
Page 83
Series 8700 / 8800 Unitized Curtain Wall Assembly Instructions - Volume 5
Section 31 - Gasket Application and Hardware Mounting On Vent Frame
Jamb Linkage
Strut
Lock Pawl Jamb Linkage
Insert lock the pawl stud into the hole in the strut and slide into reglet in vent jamb sash.
Insert lock pawl studs into holes in
Corner Drive
Corner Drive Retainer Clip
the struts and slide into reglet in
Figure 216
Align the stud in the corner
drive with the hole in the
strut and mate the corner
drive and strut together.
Jamb Linkage
Strut
Corner Drive Retainer Clip
Corner Drive
Figure 218 Figure 219 Figure 220
vent jamb sash.
Figure 217
Corner Drive
Insert the
corner drive
retainer clip
corner drive
and reglet.
Lock Pawl
into the
Struts
Corner Drive Retainer Clip
EFCO 2009 Page 83
Page 84
Series 8700 / 8800 Unitized Curtain Wall Assembly Instructions - Volume 5
Section 31 - Gasket Application and Hardware Mounting On Vent Frame
14. Measure and mark all centerline locations for the snubbers at the head sash. Refer to the final approved shop drawings and the factory order for locations.
15. Apply the snubbers at the head of the vent opening by sliding each snubber into the grooves in the hardware reglet. See Figure 223. Align the snubbers, centered on the marked centerline locations and tighten the pinning screw with an Allen wrench. The number and location of snubbers will vary depending on vent size and design pressure. Snubbers will not be required for all vent configurations. Refer to the final approved shop drawings and the factory order for quantities and locations. See Figures below.
SILL
Slid each snubber
HEAD
Adjustable Snubber Adjustable Snubber
into the grooves in
the hardware reglet.
HEAD
Figure 221
HEAD
Adjustable Snubbers
Figure 222 Figure 224
Figure 223
Pinning Screw
Adjustable Snubber
EFCO 2009 Page 84
Page 85
Series 8700 / 8800 Unitized Curtain Wall Assembly Instructions - Volume 5
Section 31 - Gasket Application and Hardware Mounting On Vent Frame
15. Attach four-bar arms to each jamb sash with (4) STT5 fasteners per arm in the pre-drilled holes provided. Install in the orientation shown below. Refer to the approved shop drawings and factory order for the specific arm required.
HEAD
INTERIOR VIEW
SILL
Attach 4-bar arms
to each jamb
Figure 225
STT5
EFCO 2009 Page 85
Page 86
Series 8700 / 8800 Unitized Curtain Wall Assembly Instructions - Volume 5

Section 32 - Mounting Vent Assembly Into Unit Frame

16. Lower the vent assembly to align the 4-bar arms with the pre-drilled holes provided in the jamb adapter at the top of the vent opening.
Lower the vent assembly to align the 4-bar arms with the pre-drilled holes in the jamb adapter.
Concealed Vent
opening
Figure 226
EFCO 2009 Page 86
Page 87
Series 8700 / 8800 Unitized Curtain Wall Assembly Instructions - Volume 5
Section 32 - Mounting Vent Assembly Into Unit Frame
17. Attach the four-bar arms to each jamb adapter with STT5 fasteners. At first, until final adjustments have been made to the location of the vent in the opening, attach the arms with (2) STT5 fasteners through the slots on the ends of the arm into the pre-drilled holes provided.
18. Once the adjustments on the vent’s location have been completed, match drill the (3) remaining mounting holes into the jamb adapter through the holes in the arm with a .150 diameter drill.
19. Secure each arm with STT5 in the (3) remaining locations per arm.
STT5
Attach 4-bar arms to each jamb, first,
through slots on each end of the arm.
Once the adjustments to the vent’s location have been made, match drill the (3) remaining holes and attach with STT5 (150 dia. drill).
Figure 227
EFCO 2009 Page 87
Page 88
Series 8700 / 8800 Unitized Curtain Wall Assembly Instructions - Volume 5
Section 32 - Mounting Vent Assembly Into Unit Frame
20. With the vent propped open for access, attach the Allen keyed release limit arm track to the vent sash and the mounting bracket to the jamb adapter with (4) STT5 fasteners into the pre-drilled holes provided to each jamb sash and each jamb adapter.
21. Check the operation of the vent and lock hardware to ensure the required hold-open is not exceeded and the vent locks properly. Adjust the keepers and snubbers if required for alignment with the lock pawls and snubbers on the unit frame. Check for proper closing compression and adjust the keepers if required.
Allen Key Release
Limit Arm
Figure 228
Jamb Adapter
Attach Allen keyed release limit arm to each jamb sash and each jamb adapter.
STT5
Vent Sash
Mounting Bracket
Adjust the closing compression by loosening the adjustment screw of the keeper and sliding the lock inward or outward as required.
Limit Arm Track
STT5
Figure 229 Figure 230
Allen Keyed Release Limit Arm
Adjustable Keeper
EFCO 2009 Page 88
Page 89
Series 8700 / 8800 Unitized Curtain Wall Assembly Instructions - Volume 5
Section 32 - Mounting Vent Assembly Into Unit Frame
Top Plate
Releasable Arm Procedure
Security Screw
Mounting Bracket
Arm
1 2
Secure Position
Security Screw
3 4
Loosen security
screw.
Guide Shoe With
Friction Pad
Limit Arm Track
Allen Keyed Release Limit Arm
Figure 230
Slide assembly
upward.
Disengage assembly from
mounting bracket.
EFCO 2009 Page 89
Loading...