Eemax EX190 TC Service manual

Page 1
ELECTRIC INSTANTANEOUS WATER HEATER
INSTALLATION GUIDE AND OWNERS MANUAL
IF YOU REQUIRE ANY HELP OR HAVE ANY QUESTIONS RELATING TO THE INSTALLATION OR PERFORMANCE OF THIS HEATER, PLEASE CALL OUR TECHNICAL SERVICE DEPARTMENT TOLLFREE : 1-800-543-6163. HAVE THE INFORMATION LISTED BELOW BEFORE CALLING :
SERIAL NO. MODEL NO. EX INSTALLATION DATE
MODELS COVERED:- EX190 TC, T2 - 240/208 V
EX144 TC, T2 - 240/208 V EX1608 TC, T2 – 208V
EX160 TC, T2 - 277 V
EX200 TC, T2 - 277 V
READ THE GENERAL SAFETY SECTION BEGINNING ON THE INSIDE COVER AND THEN THIS ENTIRE MANUAL BEFORE INSTALLING OR OPERATING THIS WATER HEATER. IF YOU DON’T FOLLOW THE SAFETY RULES, THE UNIT WILL NOT OPERATE PROPERLY AND IT COULD CAUSE DEATH, SERIOUS BODILY INJURY AND/OR PROPERTY DAMAGE. READ ALSO THE ENCLOSED WARRANTY CARD. WARRANTY OF THIS WATER HEATER WILL DEPEND ON PROPER INSTALLATION AND OPERATION. THE WARRANTY SHALL BE VOID IF THE DESIGN HAS BEEN ALTERED IN ANY WAY WHATSOEVER. THE MANUFACTURER OF THIS HEATER WILL NOT BE LIABLE FOR ANY DAMAGES BECAUSE OF FAILURE TO COMPLY WITH THE INSTALLATION AND OPERATING INSTRUCTIONS OUTLINED ON THE FOLLOWING PAGES.
THE INSTALLATION MUST CONFORM WITH THE INSTRUCTIONS IN THIS MANUAL; ELECTRIC COMPANY RULES; AND THE LOCAL CODES, OR IN THE ABSENCE OF LOCAL CODES, WITH THE LATEST EDITION OF THE NATIONAL ELECTRICAL CODE. THIS PUBLICATION IS AVAILABLE FROM YOUR LOCAL GOVERNMENT OR PUBLIC LIBRARY OR ELECTRIC COMPANY OR BY WRITING UNDERWRITERS LABORATORIES, 333 PFINGSTEN ROAD NORTHBROOK, IL, 60062.
WARNING
1
Page 2
GENERAL SAFETY
The “Eemax Series Two” heater is specifically designed to take in cold water and heat it to temperatures suitable for normal domestic usage up to a maximum of 140 F (60 C). To obtain optimum performance and energy savings, the unit should be located as near as possible to the point of use.
The unit is supplied with compression rings and nuts suitable for direct coupling to standard 1/2” (5/8” outside diameter) copper or plastic piping. There is no need for additional screwed fittings and under no circumstances use a blow torch on pipe while pipe is connected to the heater (serious damage to the electronic flow switch will result).
Also, ensure that the pipes are clear of installation debris before fitting the heater.
THIS HEATER MUST HAVE TWO DEDICATED INDEPENDENT CIRCUITS, USING CORRECTLY RATED WIRES AND CIRCUIT
BREAKERS.
WARNING
IMPROPER INSTALLATION, ADJUSTMENT, ALTERATION, SERVICE OR MAINTENANCE CAN CAUSE DEATH, SERIOUS BODILY INJURY OR PROPERTY DAMAGE. REFER TO THIS MANUAL FOR ASSISTANCE OR CONSULT THE LOCAL ELECTRIC UTILITY FOR FURTHER INFORMATION.
FAILURE TO GROUND THE SYSTEM MAY RESULT IN DEATH OR SERIOUS INJURY.
WARNING
WARNING
WATER HEATERS EQUIPPED FOR ONE VOLTAGE ONLY: THIS WATER HEATER IS EQUIPPED FOR ONE VOLTAGE TYPE ONLY: CHECK THE RATING PLATE ON THE FRONT COVER OF UNIT FOR THE CORRECT VOLTAGE. DO NOT USE THIS WATER HEATER WITH ANY OTHER VOLTAGE OTHER THAN THE ONE SHOWN ON THE MODEL RATING PLATE. FAILURE TO USE THE CORRECT VOLTAGE CAN CAUSE PROBLEMS WHICH CAN RESULT IN DEATH, SERIOUS BODILY INJURY, OR PROPERTY DAMAGE. IF YOU HAVE ANY QUESTIONS OR DOUBTS CONSULT EEMAX OR YOUR ELECTRIC COMPANY.
WARNING
HAZARD OF ELECTRICAL SHOCK! BEFORE REMOVING THE COVER OR SERVICING THE WATER HEATER, MAKE SURE THE ELECTRICAL SUPPLY TO THE WATER HEATER IS TURNED “OFF”. FAILURE TO DO THIS COULD RESULT IN DEATH, SERIOUS BODILY INJURY, OR PROPERTY DAMAGE.
2
Page 3
Inlet isolating valve­ball valve. (Always leave fully open when unit is in service.)
MINIMUM - 8” CLEARANCE ABOVE UNIT
G L N L N
TERMINAL BLOCK ELECTRICAL HOOK-UP 240/208 V
Outlet isolating valve­ball valve (leave open just enough to obtain adequate flow of hot water)
Figure 1
3
4”
MOUNTING HOLES
Temperature
Adjustment
knob
Two independent circuit breakers
G L L L L
TERMINAL
BLOCK
ELECTRICAL
HOOK-UP
277 V
ground
10 ½’’
10’’
Page 4
I. MOUNTING THE UNIT
1) The unit should be mounted as close to the point of use as possible. For example, directly beneath the sink is ideal.
Do not install the heater above a faucet or “point of use” because the siphoning effect may drain the heater which can cause premature element burn out.
2) This unit must only be mounted in a vertical position with the water fittings located at the bottom of the unit. Mounting other than in the vertical position WILL cause element burn out and cause permanent damage to the water heater.
3) The cold water inlet is on the right hand side and the hot water outlet is on the left hand side. Under NO circumstances can these be reversed.
4) Leave a minimum of 8” above the unit for easy replacement of the element.
5) The heater should be fixed to the wall using screws in the four mounting holes at each corner of the backplate. NOTE: The heater should be installed below the level of all hot water outlets serviced by this heater. NOTE: PRESSURE AND TEMPERATURE RELIEF VALVE These units are not required by UL to have a Pressure and Temperature Relief Valve (PTRV). You should check with local codes to find out if one is required in your area. If local codes require the use of a temperature and pressure relief valve it should be installed on the outlet hot water pipe before the outlet ball valve.
Cold
Installation directly beneath the
sink is ideal
EemaX
Figure 2
Hot
4
TO SHOWER
HOT OUTLET COLD INLET
Page 5
II. PLUMBING HOOK-UP
1) The unit is supplied with compression fittings (Figure 3), USE THESE. DO NOT USE TAPERED THREADED PIPE FITTINGS AND DO NOT SOLDER TO THE INLET OR OUTLET. DO NOT USE ANY PIPE DOPE OR TEFLON TAPE WITH THESE COMPRESSION FITTINGS.
2) Take care to ensure that the pipes are correctly aligned with the inlet and outlet bosses in order to avoid excessive stress on the heater body molding. NOTE: When soldering pipe joints remove heater from the wall. Serious damage can occur if any soldering is done while pipes are connected to the heater.
Run water through the supply pipe to remove all debris from the pipe before connecting the heater. Failure to do so could cause damage to the flow switch.
3) Install isolating valves (full flow ball valve type) on both inlet and outlet pipes. This allows unit to be isolated for maintenance purposes. (Fig. 1)
4) When all plumbing is complete, fully check the system for water leaks at all the plumbing connections. If a leak is present take corrective action. If the leak is at a compression fitting, slowly tighten the compression nut until it stops. Ensure fittings are secure. Tighten 5/8’’ compression sleeve to 18 FT.LB.Fully open both inlet and outlet BALL VALVES. Run all the hot water outlets fed by this heater one at a time, for a minute or two, until the water flow is continuous, free from “gulping” and from all visible air pockets.
HOT OUTLET COMPRESSION FITTING DO NOT SOLDER
COLD INLET COMPRESSION FITTING DO NOT SOLDER
NOTE:
ALL MOUNTING AND PLUMBING MUST BE COMPLETE BEFORE YOU
PROCEED WITH ELECTRICAL HOOK-UP.
TEST THE INSTALLATION FOR LEAKS BEFORE CONNECTING THE ELECTRICAL SUPPLY.
4”
Figure 3
5
Page 6
III. ELECTRICAL HOOK-UP
WARNING BEFORE BEGINNING ANY WORK ON THE ELECTRICAL INSTALLATION, BE SURE THE SWITCH AT MAIN BREAKER PANEL IS “OFF” TO AVOID ANY DANGER OF ELECTRICAL SHOCK.
“Series-two” heaters are manufactured to the following specifications:
This unit must have its own independent circuits, using 2 SETS of UL listed 2 conductor and ground core copper wire cable of the appropriate size protected by 2 separate and independent correctly rated Double Pole breakers. (208, 220, 240 V, see Figures 4 and 5). For 277 Volt models use correctly rated single pole breakers.
Wire entry into the unit must be made through the hole provided in the flange on the backplate.
The “live” wires should be connected to the slots in the terminal block marked L1 and L2. The ground lead must be connected to the slot marked GND. (277 models have neutral “N” slots.) GROUND MUST BE BROUGHT TO THE “GROUND” AT THE CIRCUIT BREAKER PANEL.
DANGER FAILURE TO GROUND THE SYSTEM MAY RESULT IN DEATH OR SERIOUS INJURY.
* Units rated fo 240 V can operate at 220 V or 208V with reduced output.
The output will vary in accordance with the following ratios:
208 volts 220 volts 240 volts .75 .84 1.0output ratio
volts
MODEL TYPE OUTPUT / kW VOLTAGE / V AMPERAGE EX 190 19 240 2 x 39 Amps EX 144 15 240 2 x 32 Amps EX 200 20 277 2 x 36 Amps EX 160 16 277 2 x 29 Amps EX1608 16.6 208 2x39Amps
ONON
OFF
OFF
ONON
OFFOFF
2 Separate and independent
correctly rated Double pole
breakers (240/208 Volts)
Figure 4
Figure 5
6
* *
Circuit Breaker Panel
Page 7
IMPORTANT BEFORE SWITCHING “ON” THE POWER AT THE MAIN CIRCUIT BREAKER PANEL MAKE SURE THAT THE HOT WATER CIRCUIT IS FREE OF AIR POCKETS OR ELSE PREMATURE FAILURE OF THE ELEMENT WILL OCCUR. TO DO THIS OPEN ALL HOT WATER OUTLETS ONE AT A TIME FOR A MINUTE OR TWO UNTIL THE WATER FLOW IS CONTINUOUS AND FREE FROM “GULPING” AND FREE FROM VISIBLE AIR POCKETS.
1) Open fully both inlet and outlet valves at the heater.
2) Open any hot water outlet in the system. If the outlet is a “single lever” mixer type turn to the hottest position. Run for one minute to clear all the air from the system.
3) Slowly close OUTLET ball valve until the water flow from the faucet just starts to reduce. NOTE: This process has two effects. One, any air in the system will be purged out. Two, the heater units will be pressurized at the supply pressure. This will prevent the elements burning when energized.(Note: Keep water flowing whilst carrying out the procedures outlined below.)
GO TO APPROPRIATE SECTION FOR YOUR MODEL
NOTE: For the following sections the first unit is the right hand heating module and the second unit is the left hand heating module.
IV COMMISSIONING YOUR HEATER
“T” MODELS a) Switch on the power to the first unit. The power indicator light should illuminate. b) Switch on the power to the second unit, again the power indicator light should illuminate. Note: This light should pulse On and Off at first and after about 20- 30 seconds it should stay fully on. c) Use the OUTLET ball valve to gradually reduce the water flow until the power indicator light on the second unit begins to pulsate. The water temperature should now be approximately 140 F. d) The thermostat is now set and the water temperature will always be the same when the indicator light is pulsing. e) Increasing water flow (above the flow rate at which the thermostatic control is no longer effective) will reduce the water temperature.
“P2” MODELS a) Switch on the power to the first unit. The power indicator light should illuminate. b) Switch on the power to the second unit, again the power indicator light should illuminate. c) Temperature is controlled on this unit by controlling the amount of water flowing through it. e.g. The higher the water flow rate the lower the water temperature and vice-versa.
7
Page 8
“T2” MODELS a) Switch on the power to the first unit, the power indicator light should illuminate. Note: This light should pulse On and Off at first and after about 20- 30 seconds it should stay fully on. b) Switch on the power to the second unit, again the power indicator light should illuminate. Note: This light should pulse On and Off at first and after about 20- 30 seconds it should stay fully on. c) Use the OUTLET ball valve to gradually reduce the water flow until the power indicator lights on both units begin to pulsate. The water temperature should now be approximately 140 F.
For “T” and “T2” Models
If a lower temperature is required, turn the temperature adjustment screw(s) counter-clockwise about 1/8 of a turn (See Figure 1). Wait 15-20 seconds and check the temperature at the fixture. Repeat this process until the desired temperature has been achieved. (For T2 models try to adjust both temperature adjustment screws by about the same amount so that the lights pulse at the same rate.) If you have reduced the temperature considerably from the 140 F setting, you could now open up the outlet ball valve slightly to achieve a higher rate of flow.
When the indicator light is on continuously, the unit is emitting full power. When it is pulsing, the unit is modulating the power to achieve the temperature set by means of the temperature adjustment screw.
ALL HEATERS
In order to obtain good control at “single lever” mixer type faucets (single spout) the cold water supply to the faucet should be restricted to give approximately the same flow rate of cold water to the faucet as the hot water coming from your Eemax heater. The simplest method of doing this is by partially closing the cold water valve under the sink.
MAXIMUM TEMPERATURE RISE CHART ( 0F )
FLOW RATE ( GAL. PER MIN. )
OUTPUT 0.75 1 1.25 1.5 2 2.5 3
15 kW N/A 102 82 68 51 40 34 16 kW N/A 109 87 73 55 44 36 19 kW N/A 130 104 87 65 52 43 20 kW N/A 136 109 91 68 54 45
8
Page 9
TROUBLESHOOTING
SYMPTOM: NO HEAT INDICATOR LIGHT OFF
1) ELECTRIC SUPPLY IS OFF Turn on the main circuit breaker.
2) NO OR LOW WATER FLOW Ensure that the minimum flow rate to switch on your heater is met. “T” Models minimum flow rate = 0.75 gallons per minute “T2” Models minimum flow rate = 1.5 gallons per minute Also check that the inlet filter screen is clear from any debris. This is located in the brass inlet boss.
3) WATER CONNECTIONS ARE REVERSED Cold water inlet = right side, hot water outlet = left side.
4) ELEMENT BURNED OUT TURN OFF THE MAIN BREAKER! Using an ohmmeter test the resistance of the heating element across the two threaded termination rods on top of the element. The resistance reading should be under 10 ohms. If the resistance is much greater than this value, call Eemax for a replacement element.
SYMPTOM: NO HEAT OR LOW TEMPERATURE WITH INDICATOR LIGHT ON
1) WATER FLOW TOO HIGH Reduce the water flow by using an outlet ball valve. See page 5 for temperature rise at various flow rates.
2) INCORRECT POWER SUPPLY Make sure that the unit is connected to the voltage supply specified on the rating label on the the front cover of the unit and no other.
3) ELEMENT BURNED OUT TURN OFF THE MAIN BREAKER! Repeat the steps from paragraph 4 above.
4)THERMOSTAT ADJUSTMENT SCREW NOT TURNED UP (Models “T” and “T2” only.) Turn the thermostat adjustment screw clockwise in small increments until the indicator light(s) remains on. Take care not to force the screw past it’s stop position.
9
Page 10
10
ground
Replacement parts:
Heating element: EX630
Control Board: EX182DP – non thermo
EX100/240 – thermo
Triac: EX18 thermo side only
Relay: EX255
ECO:EX278
If you have any problems or questions please contact Eemax @ 800-543-6163
Loading...