Protective Signaling Systems
Wiring Practices Manual
Edwards Signaling Products
90 Fieldstone Court, Cheshire, CT 06410-1212
Edwards Protective Signaling System Wiring Practices
Figure 1
INTRODUCTION
The installation of fire alarm system wiring is similar in many respects to any
other low voltage system wiring. Because the nature of the system affects life
and property, additional measures are required during installation to insure
the system is operational at all times. The most sophisticated of control
panels will not operate properly if the field wiring is installed incorrectly. It is
the goal of this chapter to explain why correctly installed field wiring is vital in
the operation of a fire alarm system, and how to recognize proper and
improper installations. The process requires four basic steps: SELECT the
proper cable for the application; INSTALL the cable properly; TEST the cable
to make sure it is free of shorts, opens, and ground faults; and TERMINATE
the cable properly.
BASIC CIRCUIT SUPERVISION
There are two types of circuit supervision widely used in fire alarm systems
today. Direct Current (DC) continuity supervision is used extensively on small
systems. Large fire alarm systems use sophisticated electronic multiplex
circuitry and "electronic questions and answers" to supervise field wiring and
devices.
Figure 1 shows a simplified fire alarm panel supervising a single Initiating
Device Circuit or zone using Direct Current (DC) continuity supervision. The
supervisory current from the battery flows through terminal #1, the field
wiring, the EOL resistor, terminal #2 of the control panel through a second
resistor, and returns to the battery. The internal resistor and EOL resistor
have equal resistance values. The voltage at the zone test point VZ is
1
measured by voltage sensing circuits. As long as the supervisory current
Figure 2
Figure 3
flows through the EOL resistor, the voltage at VZ is one half the supply
voltage VS, and the voltage sense circuitry generates a normal panel
response.
When a smoke detector or pull station operates, it effectively puts a short
across terminals #1 & #2 as shown in Figure 2. This brings the zone test
point voltage VZ up to the supply voltage VS. When the voltage sense circuitry
sees VZ = VS, it generates an alarm response, such as ringing a bell.
Should the field wiring open as shown in Figure 3, the supervisory current no
longer flows through the field wiring and EOL resistor and VZ goes to zero.
When the voltage sense circuitry sees VZ = 0, it generates a trouble
response, such as sounding the trouble buzzer.
2
Figure 4 shows an improperly wired Initiating Device Circuit. Because the
supervisory current is not forced to flow through the top and bottom
branches, the break in the top branch doesn't interrupt the supervisory
current, and there is no indication of the trouble. Should the top device detect
a fire, the signal would never reach the control panel. Note that the lower
device would send a fire alarm signal but would not send a trouble signal to
the fire alarm panel, a classic symptom of mis-wiring.
Figure 4
Large multiplex systems use sophisticated electronics that employs a system
of "electronic questions and answers" to verify circuit viability. The control
panel knows the "names" of all the devices that should be connected to it.
After asking a "question" of each name or device on its list, the control panel
must receive an answer from that device only. Failure to receive the proper
answer causes the panel to generate a trouble signal. Because multiplex
systems do not depend on the wiring path for supervision, some multiplex
systems permit limited branch wiring or T-taps.
3
CABLE SELECTION:
The majority of fire alarm systems installed today use power limited circuits.
These are low voltage circuits that automatically restrict the electrical current
delivered to the field wiring. Power limited wiring is governed by the National
Electric Code (NEC) Article 760. Field wiring size and distance limits are set
by the fire alarm manufacturer. The manufacturer may also prohibit
combining certain types of circuits in the same conduit. Installation
requirements are set by local, state and national codes. All Power Limited
Fire-Protective Signaling Cable must have its type designation marked on the
cable. NEC Article 760 requires the following insulation types to be used on
conductors installed as power limited wiring:
FPL
Type "FPL" cable may be used for general purpose fire alarm use without
conduit, with the exception of riser, duct, or plenum applications.
FPLP
Limited energy cables installed in environmental air plenum spaces without
conduit must carry a type "FPLP" designation.
FPLR
Limited energy cables installed in vertical riser shafts without conduit must
carry the type "FPLR" or the "FPLP" designation.
Note that the cables used for power limited applications do NOT have the
voltage rating stamped on the cable to avoid misapplication of power limited
cable.
All wiring should use the cables approved by the fire alarm system
manufacturer. Edwards recommended cables are shown in Table 1.
MFG. TYPE #14 TWISTED PAIR #16 TWISTED PAIR #18 TWISTED PAIR
ATLAS FPL 218-14-1-1TP* 218-14-1-1STP 218-16-1-1TP* 218-16-1-1STP 218-18-1-1TP*] 218-18-1-1STP
BELDEN FPL 9580 9581 9572 9575 9571 9574
WEST
PENN
UNSHIELDED SHIELDED UNSHIELDED SHIELDED UNSHIELDED SHIELDED
FPLP 1762-14-1-2J 1761-16-1-2J 1762-16-1-2J 1761-18-1-2J 1762-18-1-2J
FPLP - 83752 - - - -
FPL 994 995 990 991 D980* D975*
FPLP 60993 60992 60991 60990 60980 60975
TABLE 1 - Edwards APPROVED CABLE MANUFACTURER'S PART NUMBERS
4