Edwards Signaling K-270A-SPO User Manual

Protective Signaling Systems
Wiring Practices Manual
Edwards Signaling Products
90 Fieldstone Court, Cheshire, CT 06410-1212
Edwards Protective Signaling System Wiring Practices

Figure 1

INTRODUCTION The installation of fire alarm system wiring is similar in many respects to any other low voltage system wiring. Because the nature of the system affects life and property, additional measures are required during installation to insure the system is operational at all times. The most sophisticated of control panels will not operate properly if the field wiring is installed incorrectly. It is the goal of this chapter to explain why correctly installed field wiring is vital in the operation of a fire alarm system, and how to recognize proper and improper installations. The process requires four basic steps: SELECT the proper cable for the application; INSTALL the cable properly; TEST the cable to make sure it is free of shorts, opens, and ground faults; and TERMINATE the cable properly.
BASIC CIRCUIT SUPERVISION There are two types of circuit supervision widely used in fire alarm systems today. Direct Current (DC) continuity supervision is used extensively on small systems. Large fire alarm systems use sophisticated electronic multiplex circuitry and "electronic questions and answers" to supervise field wiring and devices.
Figure 1 shows a simplified fire alarm panel supervising a single Initiating Device Circuit or zone using Direct Current (DC) continuity supervision. The supervisory current from the battery flows through terminal #1, the field wiring, the EOL resistor, terminal #2 of the control panel through a second resistor, and returns to the battery. The internal resistor and EOL resistor have equal resistance values. The voltage at the zone test point VZ is
1
measured by voltage sensing circuits. As long as the supervisory current

Figure 2

Figure 3

flows through the EOL resistor, the voltage at VZ is one half the supply voltage VS, and the voltage sense circuitry generates a normal panel response.
When a smoke detector or pull station operates, it effectively puts a short across terminals #1 & #2 as shown in Figure 2. This brings the zone test point voltage VZ up to the supply voltage VS. When the voltage sense circuitry sees VZ = VS, it generates an alarm response, such as ringing a bell.
Should the field wiring open as shown in Figure 3, the supervisory current no longer flows through the field wiring and EOL resistor and VZ goes to zero. When the voltage sense circuitry sees VZ = 0, it generates a trouble response, such as sounding the trouble buzzer.
2
Figure 4 shows an improperly wired Initiating Device Circuit. Because the supervisory current is not forced to flow through the top and bottom branches, the break in the top branch doesn't interrupt the supervisory current, and there is no indication of the trouble. Should the top device detect a fire, the signal would never reach the control panel. Note that the lower device would send a fire alarm signal but would not send a trouble signal to the fire alarm panel, a classic symptom of mis-wiring.

Figure 4

Large multiplex systems use sophisticated electronics that employs a system of "electronic questions and answers" to verify circuit viability. The control panel knows the "names" of all the devices that should be connected to it. After asking a "question" of each name or device on its list, the control panel must receive an answer from that device only. Failure to receive the proper answer causes the panel to generate a trouble signal. Because multiplex systems do not depend on the wiring path for supervision, some multiplex systems permit limited branch wiring or T-taps.
3
CABLE SELECTION: The majority of fire alarm systems installed today use power limited circuits.
These are low voltage circuits that automatically restrict the electrical current delivered to the field wiring. Power limited wiring is governed by the National Electric Code (NEC) Article 760. Field wiring size and distance limits are set by the fire alarm manufacturer. The manufacturer may also prohibit combining certain types of circuits in the same conduit. Installation requirements are set by local, state and national codes. All Power Limited Fire-Protective Signaling Cable must have its type designation marked on the cable. NEC Article 760 requires the following insulation types to be used on conductors installed as power limited wiring:
FPL
Type "FPL" cable may be used for general purpose fire alarm use without conduit, with the exception of riser, duct, or plenum applications.

FPLP

Limited energy cables installed in environmental air plenum spaces without conduit must carry a type "FPLP" designation.

FPLR

Limited energy cables installed in vertical riser shafts without conduit must carry the type "FPLR" or the "FPLP" designation.
Note that the cables used for power limited applications do NOT have the voltage rating stamped on the cable to avoid misapplication of power limited cable.
All wiring should use the cables approved by the fire alarm system manufacturer. Edwards recommended cables are shown in Table 1.
MFG. TYPE #14 TWISTED PAIR #16 TWISTED PAIR #18 TWISTED PAIR
ATLAS FPL 218-14-1-1TP* 218-14-1-1STP 218-16-1-1TP* 218-16-1-1STP 218-18-1-1TP*] 218-18-1-1STP
BELDEN FPL 9580 9581 9572 9575 9571 9574
WEST
PENN
UNSHIELDED SHIELDED UNSHIELDED SHIELDED UNSHIELDED SHIELDED
FPLP 1762-14-1-2J 1761-16-1-2J 1762-16-1-2J 1761-18-1-2J 1762-18-1-2J
FPLP - 83752 - - - -
FPL 994 995 990 991 D980* D975*
FPLP 60993 60992 60991 60990 60980 60975
TABLE 1 - Edwards APPROVED CABLE MANUFACTURER'S PART NUMBERS
4
Loading...
+ 9 hidden pages