Genesis Chime-Strobe Installation Sheet
Description
The Genesis Chime-Strobe is a fire alarm notification appliance designed for indoor ceilings and walls. See Table 1 for a list of model numbers.
Table 1: Models
Description |
Numbers |
|
Chime-strobe, 15 to 110 multi- |
ADTG1-CVM |
MG1-CVM |
cd, white |
EG1-CVM |
XLSG1-CVM |
|
G1-CVM |
ZG1-CVM |
|
|
|
Chime-strobe, 15 to 110 multi- |
ADTG1F-CVM |
MG1F-CVM |
cd, white, with FIRE marking |
EG1F-CVM |
XLSG1F-CVM |
|
G1F-CVM |
ZG1F-CVM |
|
|
|
Chime-strobe, 15 to 110 multi- |
ADTG1R-CVM |
MG1R-CVM |
cd, red |
EG1R-CVM |
XLSG1R-CVM |
|
G1R-CVM |
ZG1R-CVM |
|
|
|
Chime-strobe, 15 to 110 multi- |
ADTG1RF-CVM |
MG1RF-CVM |
cd, red, with FIRE marking |
EG1RF-CVM |
XLSG1RF-CVM |
|
G1RF-CVM |
ZG1RF-CVM |
|
|
|
Trim plate, white |
ADTG1T |
MG1T |
|
EG1T |
XLSG1T |
|
G1T |
ZG1T |
|
|
|
Trim plate, red |
ADTG1RT |
MG1RT |
|
EG1RT |
XLSG1RT |
|
G1RT |
ZG1RT |
|
|
|
There are field-configurable options for selecting dB output, chime signal, and constant noncoded voltage or single-stroke coded voltage operation. See Figure 1.
Note: A Genesis Signal Master is required when chimes are configured for coded operation.
The strobe includes a field-configurable switch for selecting the desired candela output. The candela output setting is locked in place and remains visible after final installation.
This strobe features an enhanced synchronization circuit to comply with the latest requirements of UL 1971 Signaling Devices for the Hearing Impaired. Synchronized operation requires a separately installed synchronization control module. See Table 2 for a list of compatible synchronization modules.
Table 2: Compatible synchronization module models [1]
Description |
Number |
|
|
Genesis Signal Master |
EG1M |
MG1M |
G1M |
Snap-on Mount |
ADTG1M |
XLSG1M |
ZG1M |
Genesis Signal Master - |
EG1M-RM |
MG1M-RM |
G1M-RM |
Remote Mount |
|
|
|
|
|
|
|
Auto-Sync Output Module |
SIGA-CC1S |
SIGA-MCC1S |
|
|
|
|
|
Dual Input Signal Module |
SIGA-CC2A |
SIGA-MCC2 A |
|
|
|
|
|
Auxiliary Power Supply |
APS6A |
APS10A |
|
|
|
|
|
Power Supply |
BPS6A |
BPS10A |
|
|
|
|
|
[1] Synchronization module requirements are determined by the application.
Installation
Install this device in accordance with applicable requirements in the latest editions of the NFPA codes and standards, and in accordance with the local authorities having jurisdiction.
WARNING: Electrocution hazard. To avoid personal injury or death from electrocution, remove all sources of power and allow stored energy to discharge before installing or removing equipment.
Caution: Electrical supervision requires the wire run to be broken at each terminal. Do not loop the signaling circuit field wires around the terminals.
To install the chime-strobe:
1. Remove the cover by depressing both tabs on the top of the unit with a small screwdriver and twisting slightly.
© 2010 UTC Fire & Security. All rights reserved. |
1 / 4 |
P/N 3100562 • REV 2.0 • ISS 19AUG10 |
2.Set the chime signal, sound output level, and desired operation settings. See Figure 1.
Wiring
• |
To change the chime signal from steady to temporal, |
Figure 3: Wiring for single-stroke coded voltage operation |
|
||||
|
cut from circle J1 to the edge of the circuit board. |
|
|
|
|
+ |
5 |
• |
To change the chime operation from noncoded to |
|
|
|
|
||
|
coded (single-stroke), cut from circle J2 to the edge of |
|
|
|
|
- |
|
|
|
|
|
|
|
|
|
|
the circuit board. |
|
4 |
|
|
|
|
• |
To change the chime sound output level from high dB |
|
|
|
|
|
|
|
|
|
|
+ |
|
||
|
to low dB, cut the J3 trace between the holes. |
|
|
S |
|
|
|
3. Slide the candela switch to the desired candela output by |
|
- |
|
3 |
- |
6 |
|
aligning it with the indicator located beside the switch. See |
|
H |
|
|
|||
Figure 2. |
|
|
|
|
|
|
|
4. Connect the chime terminals to the signal circuit field |
|
|
|
|
|
|
|
wiring. For the unit to function properly, observe polarity. |
|
|
|
|
|
|
|
See Figure 1. |
2 |
STROBE + |
|
|
|
|
|
|
|
|
|
|
|
||
• |
For single-stroke coded voltage operation, see |
STROBE - |
|
|
|
|
|
|
Figure 3. |
1 |
CHIME + |
|
|
|
|
• |
CHIME - |
|
|
|
|
||
For constant noncoded voltage operation, see |
|
|
|
|
|
|
|
Figure 4. |
1. |
Chime in (coded power signal) |
|
5. |
Mount the unit onto a compatible electrical box, making |
2. |
Strobe in (continuous power signal) |
|
3. |
Resistor, value determined by the control panel |
|||
|
sure not to overtighten the mounting screws. |
4. |
Genesis Signal Master |
|
6. |
Replace the cover by aligning it at the bottom, then |
5. |
To next appliance, EOL resistor, or Class A circuit return |
|
6. |
One wire each side of screw head |
|||
|
snapping it in at the top. |
|||
|
|
|
Notes
7. Test the unit for proper operation. • Polarity shown in alarm condition
• The strobe circuit can be silenced without turning off strobes
Figure 1: Chime settings
1 |
2 |
3 |
Figure 4: Wiring for constant noncoded voltage operation |
||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
J1 |
J2 |
J3 |
1.J1: Chime signal jumper
2.J2: Coded/non-coded jumper
3.J3: Chime sound output
|
+ |
1 |
+ |
- |
|
|
- |
+ |
|
+ |
2 |
- |
|
- |
|
Figure 2: Candela switch
110
75
30
15
1.From NAC output
2.To next appliance, EOL, or Class A return
Note: Signal polarity is shown in the alarm condition.
Maintenance
This unit is not serviceable or repairable. Should the unit fail to operate, contact the supplier for replacement.
Perform a visual inspection and an operational test twice a year or as directed by the local authority having jurisdiction.
Do no change the factory-applied finish.