www.edwardssignaling.com
P/N 1030522 • REV D • REB 20MAR13
Integrity Series
Description
The INT-03-024 or INT-03-120 Safety Monitor Relay is intended for use as a part of a
safety circuit in guard interlock applications. It is a safety relay which uses positiveguided relays, configured for self-checking, to inhibit machine start-up in the event of
an internal component failure.
Both normally-open and normally-closed inputs are required. Multiple N.O. contacts
can be wired in series while multiple N.C. contacts can be wired in parallel. Upon
failure of either the N.O. or N.C. contact, the relay will turn off and prevent restart.
The INT-03 relay can also monitor contacts on external relays for controlling expansion
block relays (Sentrol INT-05 and INT-06).
TUV Notes:
1. Relay conforms to Pollution Degree II, meets EN1760-1:1998, and must be installed
in an IP54-type enclosure.
2. The wire insulation of connected devices must be rated for 250VAC. The relay meets
basic insulation requirements only.
3. Input devices must meet requirements of EN60947-5-1.
4. The relay must be connected to a primary disconnect device that meets the
requirements of EN60947-3.
5. System total response time must not exceed 200ms.
6. Controller meets IP20 and must be connected to safety category 4 mat or
sensing device.
7. Test system before operation and after machine maintenance. Controller does not
require maintenance.
8. The complete system should be tested weekly. If a fault occurs, contact
Sentrol Industrial.
Dimensions
2.17"
5.5cm
2.95"
7.5cm
4.53"
11.5cm
0.26"
0.66cm
INT Monitor Relay
INT-03-024
INT-03
INT-03-120
Installation
Guardswitch™ Inputs: Wire the GuardSwitches™ in series and in parallel as shown in
the wiring diagram. When first applying power to the GuardSwitch™ Monitor Relay,
with no jumper or button from Terminal 1 to Terminal 2, realy will not energize.
With a jumper installed from Terminal 1 to Terminal 2, relay energizes when all guards
are in place (autostart).
With a RESET button installed from Termainal 1 to Terminal 2, relay energizes after
all guards are in place and RESET button is pressed. The monitor contacts must also
be closed.
Authorized Outputs: The designer must perform a risk analysis and be aware of the
applicable safety standards of their machine. The designer has a choice of how to use
the output contacts. The output contacts can be used in combination with an
Emergency Stop Relay circuit with a “reset” function. (“The restoring of an interlocked
safeguard shall not initiate machine motion or operation where this can result in a
hazardous condition. IEC 204-1.) The reset circuit should not be wired to disconnect
power to the GuardSwitch Monitor Relay, or it will be difficult to distinguish between a
GuardSwitch failure and a normal reset function.
Input Power: The GuardSwitch Monitor Relay is available in either a 24 VDC or 120
VAC model. Make sure the correct model is used before applying power as shown in the
wiring diagram.
INT-03 __________
1.48"
3.75cm
2.46"
6.25cm
Slot for 35mm
DIN rail mount
Typical Wiring Diagram
RESET
120 VAC
FUSE
L1 L2 1 2 X1 X2 Y1 Y2
–
+
Safety Monitor Relay
INT-03
SAFE AUX.
A
BCD
N.O. N.C.
OUTPUTS
EFG
INT03WIR
230 VAC
60 VDC
LOADS
120 VAC
30 VDC
Multiple Switch Wiring Diagram
GuardSwitches™ are shown with the actuators in position—guard is closed. One 300-BT Series GuardSwitch™ is required for each safety gate. Up to 50 switches can be used with
INT-03. When using the BLT switch models, the voltage drop (30 ohms) must be taken into consideration.
(–)
INT-03-230: 230V AC
INT-03-120: 120V AC
INT-03-024: 24V DC
(+)
Required Fast or
Slow-Acting Fuse:
(250V, 5x20 mm F)
INT-03-230: 40mA
INT-03-120: 80mA
INT-03-024: 1/4A
RESET
L1 L2 1 2 X1 X2 Y1 Y2
–
+
Safety Monitor Relay
INT-03
SAFE AUX.
A
BCD
N.O. N.C.
OUTPUTS
EFG
W
B
H
L
T
K
*300-BLT-
*Or other DPST GuardSwitch
(See the 300-BT Series installation instructions)
Series Circuit
R
B
E
L
D
U
W
H
T
R
B
E
L
D
K
*300-BLT-
Parallel Circuit
B
L
U
W
H
T
R
B
E
L
D
K
*300-BLT-
B
L
U
Required Fast or SlowActing Fuses: 4A (250V,
5x20 mm F
230 VAC
60 VDC
LOADS
120 VAC
30 VDC
Note – The LED on the BLT model will be ON when the guard is open
Fuses: 1 A (250 v)
Multiple DPST GuardSwitches – Shown with actuators in position, all guards closed.
The L.E.D of the BLT model will be on when the guard is open. If multiple guards
are open, L.E.D will be dimmer. The maximum number of GuardSwitches that can
be used is 50, although troubleshooting and line resistance must be considered.
(Do not exceed 30 Ohms of combined contact and line resistance. Each GuardSwitch
will have less than 0.5 Ohms of resistance.)
Note: Only outputs AB and CD are safety outputs. Auxiliary form C output E, F, G may fail in an unsafe condition and should only be used for signaling.