Edwards Signaling HPSA15 User Manual

5552 and HPSA15 Series Speakers Installation Sheet
Description
5552 Series and HPSA15 Series are high efficiency, UL Listed double re-entrant type loudspeakers.
They comply with the requirements of UL Standard 1480, Fire Protective Signaling Speakers.
They are designed to be used in conjunction with compatible control equipment for high intelligibility reproduction of audible emergency and protective signals as well as voice messages.
Includes a supervisory capacitor and is suitable for installation in systems employing supervised circuitry (25 V / 70.7 V). Maximum supervised circuit voltage is 24 VDC.
For use in ambient temperature ranges from -40˚C to 66˚C.
Figure 1: Power tap selector switch
Specifications
Power 15 W RMS frequency response 400 to 4,000 Hz Sound level 103 dB UL 10 ft. rating Conduit connection For 12 in. conduit
Note: Terminal #2 is the positive terminal.
© 2013 UTC Fire & Security. All rights reserved. 1 / 2 P/N 3101246 • REV 02 • REB 15FEB13
Figure 2: Mounting dimensions
To conform with UL requirements, wires must be connected as shown in wiring diagram (see Figure 3).
Note: The maximum wire size that can be connected to this device is 18 Gauge.
Figure 3: Wiring diagram
Caution: Do not loop wires under screw terminals. Break wire run to provide supervision of connection. Installation must comply
with all Building Codes and NFPA guidelines. Installation must adhere to N.E.C. and NFPA 70/72 wiring directives and comply with all National and Local Building Codes.
Contact information
For contact information, see www.edwardssignaling.com
2 / 2 P/N 3101246 • REV 02 • REB 15FEB13