Overview
Genesis WG4 Series speakers and speaker-strobe appliances are among the most versatile emergency appliances of their kind. Rated for indoor or outdoor use, they are suitable for a wide range of wet and harsh environments with a listed operating temperature range of as low as -31°F to as high as 151°F (-35°C to 66°C).
Field-configurable light and sound output settings add to their on­site flexibility, while optional FIRE markings make them ideal for fire alarm applications.
These appliances are suitable for indoor and outdoor applications, and are ideal for challenging conditions such as parking garages and process areas. They are listed for mounting on the ceiling or the wall, and thanks to an ingenious full backplane sealing gasket, can be installed to recessed (in-the-pour/block) electrical boxes. WG4 signals also mount to suitable surface boxes served by race­ways. Optional color-matched trim skirts provide a clean, finished appearance. All appliance wiring is accomplished room-side for easy installation.
WG4 Series appliances feature highly intelligible and efficient my­lar-cone loudspeakers. These are dual-voltage (25.2V or 70.7V), and have field-selectable output taps ranging from 80.8 dBA to
90.0 dBA. The multi-candela strobes are available with clear lens­es and in two output categories – standard and high-output. They are precision-timed to meet UL 1971 synchronization standards, and field-configurable for one of four candela intensities. Wattage and candela settings are viewable even after installation through an innovative sealed viewport display.
Standard Features
• Outdoor and indoor rated
• Low-profile design
• Wall or ceiling mount
• Room-side wiring accepts 18 to 12 AWG (0.75 to 2.5 mm2)
• Wide operating temperature range
• Field-selectable speaker wattage, voltage, and strobe candela settings
• Field-configurable temporal strobe output option
• Fully-compatible with Genesis synchronization protocols
• Standard and high-output strobe intensities
• Speaker only and Speaker/Strobe appliance options
Page 1 of 4 D A T A S H E E T S85001-0626
No t to be used for i nst allat ion p urp oses. Issue 1
Application
88
89
90
93
96
82
83
84
87
90
10ft (3.05m)
Radius
5ft (1.5m)
Radius
90° 75° 60° 45°
Speaker Application
The suggested sound pressure level for each signaling zone used with alert or alarm signals is a minimum of 15 dB above the aver­age ambient sound level or 5 dB above the maximum sound level having a duration of at least 60 seconds, whichever is greater. This is measured 5 feet (1.5 m) above the floor.
Doubling the distance from the signal to the ear will theoretically cause a 6dB reduction in the received sound pressure level. The actual effect depends on the acoustic properties of materials in the space. Dou­bling the power output of a device (e.g.: a speaker from 1W to 2W) will increase the sound pressure level by 3dBA.
Typical Sound Output
Distribution dBA
Measured in anechoic chamber
at two watts
Genesis Series Cone Speaker/strobe
Installation and Mounting
WG4 signals are rated for
Electrical box
Gasket
Optional skirt
Backplate
Front cover
Cover
screws (x6)
WG4WTS or WG4RTS trim skirt, a 449 or 2-1/8" deep box must be used.
The Genesis WG4 Speaker-Strobe may be wall- or ceiling-mount­ed, and may be placed in one of four positions: strobe above, strobe below, and strobe to either side. The shallow depth of Genesis devices leaves room behind the appliance for extra wiring.
outdoor use and are suitable for indoor or outdoor applications on walls or ceilings. For surface-mounting in outdoor or wet applica­tions, appliances must be mounted to an Edwards 449 electrical box. In dry conditions, they are compatible with standard 4-inch by 1½-inch deep electrical boxes. When using the optional
Strobe Application
Genesis clear-lensed strobes are UL 1971-listed for use indoors as wall- or ceiling-mounted public-mode notification appliances for the hearing impaired, and UL 1638-listed for outdoor applications. Prevailing codes require strobes to be used where ambient noise conditions exceed specified levels, where occupants use hearing protection, and in areas of public accommodation.
Visible appliance synchronization is required to avoid causing issues with people who have Photosensitive Epilepsy (PSE). Noti­fication appliance synchronization is also generally required when more than one strobe appliance are in the same field of view from any one location. All Genesis strobes meet UL synchronization requirements (within 10 milliseconds over a two-hour period) when used with a synchronization source.
WARNING: These devices will not operate without electrical power. As fires frequently cause power interruptions, we suggest you discuss further safeguards with your local fire protection specialist.
Edwards recommends that these devices always be installed in accordance with the latest recognized edition of national and local codes. Refer to the appropriate codes and standards for mounting height information.
Field Configuration
Genesis WG4 speakers may be set to 70- or 25-Volt operation, and for ¼, ½, 1, or 2 watt operation. The wattage setting (repre­sented by the letters Z,Y, X, and T) is changed by removing the cover and simply sliding the S1 switch until the desired setting ap­pears. The setting remains visible through a small window on the front of the device after the cover is installed. The voltage setting (70V or 25V) is toggled at S3. This setting is not visible after the cover is replaced.
Genesis WG4 speaker-strobes also feature selectable candela output. The actual light output for a given selection depends on whether it is a high output model or a standard output model. Re­fer to the specification tables for corresponding settings. The can­dela setting (represented by the letters D, C, B, and A) is changed by removing the cover and simply sliding the S2 switch until the desired setting appears. The setting remains visible through a small window on the front of the device after the cover is installed.
S1:
wattage
SPKR -
SPKR +
STROBE -
STROBE +
SPKR ­SPKR + STROBE ­STROBE +
S3: Speaker
voltage
Page 2 of 4 D A T A S H E E T S85001-0626
No t to be used for i nst allat ion p urp oses. Issue 1
S2:
Candela
JP1: Strobe temporal
mode selection
Genesis speaker-strobes may also be configured for temporal flash. This power-saving feature is intended for private mode signaling only. To set the device for temporal flash, snip the jumper at JP1.
Specifications
Operating voltage
Supervisory voltage 30 V max. Speaker response 400 to 4,000 Hz Wire size 12 to 18 AWG (0.75 to 2.50 mm²) Compatible strobe
synchronization sources
Compatible electrical boxes
Operating environment
Speaker
Default
Strobe
Temperature
Relative humidity
25 VRMS or 70 VRMS, switch selectable 70 VRMS 24 VDC, 24 VFWR nominal
E-NAC, EG1M-RM, EBPS6A, EBPS10A, E-FSC 3, 5, and 10 zone, E-FSA64, E-FSA250
Wet: Model 449 (WG4 trim skirt recommended) Dry: 4" square by 1-1/2" deep box when used
without a trim skirt. When trim skirt is used, box must be 4" square by 2-1/8" deep.
Wet
-31 to 151 °F (-35 to 66 °C) 0 to 95% noncondensing
Sound level output (dBA)
Wattage Switch Position 25 V 70 V
2 W T 90.0 89.7 1 W X 87.1 86.9 ½ W Y 84.0 83.9 ¼ W Z 80.8 80.8
dBA = Decibels, A-weighted. UL 1480: Sound level output at 10 ft. (3.05 m) measured in a reverberant room using 400 to 4,000 Hz band-limited pink noise.
Light output
0
5
-5
-10
-15
-20
-25
Angle
-55
-60
-65
-70
-75
-80
-85
95
100
90
-30
-35
-40
-45
-50
80
85
50
70
75
40
30
60
65
55
20
45
35
25
15
UL off-axis candela requirements as a percent of the UL rated output
Indoor rating per UL 1971 (candela)
Standard Output Models (-SVM)
High Output Models (-SVMH)
Candela 87 70 29 15
VDC 319 167 144 106
Current
FWR 386 347 178 120
Candela 161 147 123 102
VDC 495 494 390 324
Current
FWR 646 607 487 412
10
15
20
25
30
35
40
45
50
0
0
5
5
10
10
20
15
50
30
40
25
35
45
80
70
60
55
65
75
Strobe Switch Position
A B C D
55
60
65
70
75
80
85
90-90
90
85
95
100
Wiring
Field wiring is connected to Genesis signals with terminals that ac­commodate #18 to #12 AWG (0.75 mm² to 2.5 mm²) wiring.
Outdoor rating per UL 1638 (candela)
Standard Output Models (-SVM)
High Output Models (-SVMH)
Candela 35 28 12 6
VDC 319 167 144 106
Current
FWR 386 347 178 120
Candela 65 60 50 41
VDC 495 494 390 324
Current
FWR 646 607 487 412
Strobe Switch Position
A B C D
Page 3 of 4 D A T A S H E E T S85001-0626
No t to be used for i nst allat ion p urp oses. Issue 1
Detection & alarm since 1872
Ordering Information
WG4RF-S
WG4RF-SVMC
WG4RF-SVMHC
WG4WF-S
All speakers include field-selectable ¼, ½, 1, or 2 watt taps and selectable 25V or 70V operation.
Model Housing Marking Lens Strobe Output* Ship Wt.
Life safety Appliances
WG4RF-SVMC Red
WG4WF-SVMC White
WG4RN-SVMC Red
WG4WN-SVMC White
WG4RF-SVMHC Red
WG4WF-SVMHC White
WG4RN-SVMHC Red
WG4WN-SVMHC White
WG4RF-S Red
WG4WF-S White
WG4RN-S Red
WG4WN-S White
WG4WF-SVMC
WG4WF-SVMHC
FIRE
None
FIRE
None
FIRE
None
WG4RN-S
Clear
WG4RN-SVMC
WG4RN-SVMHC
Selectable standard output 15/29/70/87 cd
Selectable
high output
102/123/147/161 cd
Speaker Only
WG4WN-S
WG4WN-SVMC
WG4WN-SVMHC
1.5 lbs.
(0.68 kg)
Accessories
WG4WTS Surface Skirt for Genesis WG4 appliance family, white. WG4RTS Surface Skirt for Genesis WG4 appliance family, red. WG4GSKT Replacement Mounting Gasket 449 Surface mount box, outdoor rated
Page 4 of 4 D A T A S H E E T S85001-0626
No t to be used for i nst allat ion p urp oses. Issue 1