Edwards Signaling Genesis Temporal Horn-Strobe User Manual

Genesis Temporal Horn-Strobe Installation Sheet
Description Number
Description
The Genesis Temporal Horn-Strobe is a fire alarm notification appliance designed for indoor walls. See Table 1 for a list of model numbers.
Description Number
Horn-strobe, 15 to 110 multi-cd, white
Horn-strobe, 15 to 110 multi-cd, white, with FIRE marking
Horn-strobe, 15 to 110 multi-cd, red
Horn-strobe, 15 to 110 multi-cd, red, with FIRE marking
Trim plate, white
Trim plate, white, with FIRE marking
ADTG1-HDVM EG1-HDVM G1-HDVM
ADTG1F-HDVM EG1F-HDVM G1F-HDVM
ADTG1R-HDVM EG1R-HDVM G1R-HDVM
ADTG1RF-HDVM EG1RF-HDVM G1RF-HDVM
ADTG1T EG1T G1T
ADTG1T-FIRE EG1T-FIRE G1T-FIRE
MG1-HDVM XLSG1-HDVM ZG1-HDVM
MG1F-HDVM XLSG1F-HDVM ZG1F-HDVM
MG1R-HDVM XLSG1R-HDVM ZG1R-HDVM
MG1RF-HDVM XLSG1RF-HDVM ZG1RF-HDVM
MG1T XLSG1T ZG1T
MG1T-FIRE XLSG1T-FIRE ZG1T-FIRE
Trim plate, red
Trim plate, red, with FIRE marking
There are field-configurable options for selecting dB output, horn signal, or strobe signal output. See Figure 1.
The strobe includes a field-configurable switch for selecting the desired candela output. The candela output setting is locked in place and remains visible after final installation. See Figure 2.
This strobe features an enhanced synchronization circuit to comply with the latest requirements of UL 1971
Devices for the Hearing Impaired
standard CAN/ULC-S526. Synchronized operation requires a separately installed synchronization control module. See Table 2 for a list of compatible synchronization modules.
Table 2: Compatible synchronization module models [1]
Description Number
Genesis Signal Master Snap-on Mount
Genesis Signal Master ­Remote Mount
Auto-Sync Output Module SIGA-CC1S SIGA-MCC1S
Dual Input Signal Module SIGA-CC2A SIGA-MCC2 A
Auxiliary Power Supply APS6A APS10A
Power Supply BPS6A BPS10A
[1] Synchronization module requirements are determined by the application.
Installation
Install this device in accordance with applicable requirements in the latest editions of the NFPA codes and standards; the
National Building Code of Canada; Code, Part 1
authorities having jurisdiction.
, Section 32, and in accordance with the local
ADTG1RT EG1RG 1RT
ADTG1RT-FIRE EG1RT-FIRE G1RT-FIRE
MG1RT XLSG1RT ZG1RT
MG1RT-FIRE XLSG1RT-FIRE ZG1RT-FIRE
and the latest Canadian
EG1M ADTG1M
EG1M-RM MG1M-RM G1M-RM
MG1M XLSG1M
the
Canadian Electrical
Signaling
G1M ZG1M
© 2010 UTC Fire & Security. All rights reserved. 1 / 4 P/N 3100560 • REV 5.0 • ISS 25AUG10
WARNING: Electrocution hazard. To avoid personal injury or
death from electrocution, remove all sources of power and allow stored energy to discharge before installing or removing equipment.
Caution: Electrical supervision requires breaking the wire run
at each terminal. Do not loop the signaling circuit field wires around the terminals.
To install the horn-strobe:
1. Remove the cover by depressing both tabs on the top of the unit with a small screwdriver and twisting slightly.
2. Set the horn signal, sound output level, and strobe signal to the desired settings. See Figure 1.
To change the strobe to temporal (private mode), cut
from circle J1 to the edge of circuit board.
To change the horn signal from temporal to steady,
cut from circle J2 to the edge of circuit board.
To change the horn output level from high dB to low
dB, cut the J3 trace between the holes.
3. Slide the candela switch to the desired candela output by aligning it with the indicator located left of the switch. See Figure 2.
Figure 2: Candela switch
110
75 30 15
Figure 3: Wiring diagram
+
1 2
-
4. Connect the strobe terminals to the signal circuit field wiring. You must observe polarity for the unit to function properly. See Figure 3.
5. Mount the unit onto a compatible electrical box, making sure not to overtighten the mounting screws.
6. Replace the cover by aligning it at the bottom, then snapping it in at the top.
7. Test the unit for proper operation.
Figure 1: Horn and strobe settings
1
1. J1: Strobe signal output
2. J2: Temporal/steady horn signal output
3. J3: dB sound output
Note: If the strobe is set to temporal (private mode), this device is no longer UL 1971 listed and FM Approved but is UL 1638 listed.
2
J1
J2
J3
3
1. From compatible fire alarm control panel
2. To next appliance, EOL, or return to source
Note: Polarity is shown in the alarm condition.
Maintenance
Caution: To maintain the required agency listings, do not
change factory applied finishes.
This unit is not serviceable or repairable. Should the unit fail to operate, contact the supplier for replacement.
Perform a visual inspection and an operational test twice a year or as directed by the local authority having jurisdiction.
2 / 4 P/N 3100560 • REV 5.0 • ISS 25AUG10
Loading...
+ 2 hidden pages