Product information
Genesis Temporal Horn
Table 1: Model numbers
Model description Model numbers
The Genesis Temporal Horn is an audible fire alarm
notification appliance designed for indoor walls. See Table 1
for a list of model numbers.
The horn includes field configurable jumper options for
selecting both the desired dB output and temporal or steady
horn output.
Install this device in accordance with applicable requirements
in the latest editions of the NFPA codes and standards and
Canadian Electrical Code, Part 1, Section 32, and in
accordance with the local authorities having jurisdiction.
Table 1: Model numbers
Model description Model numbers
Trim plate,
red
Trim plate,
red, with FIRE marking
ADTG1RT MG1RT
EG1RT XLSG1RT
G1RT ZG1RT
G1RT-LG
ADTG1RT MG1RT
EG1RT XLSG1RT
G1RT ZG1RT
G1RT-LG
Specifications
Operating voltage:
Regulated 16 to 33 Vdc, 16 to 33 Vfwr
This device was tested to the regulated 24 Vdc/fwr
operating voltage limits of 16 V and 33 V. Do not apply
80% and 110% of these values for system operation.
Sound level output: See Table 2
Operating current: See Table 3
Wire size: 12 to 18 AWG (2.50 to 0.75 sq mm)
Compatible electrical boxes
North American 2-1/2 in (64 mm) deep 1-gang box
Standard 4 in square box 1-1/2 in (38 mm), 2-gang, or 4 in
octagonal with G1T or G1RT trim accessory
Operating temperature range: 32 to 120 °F (0 to 49 °C)
Operating humidity range: 0 to 93% RH
Agency listings: Meets or exceeds ULC-S525 and UL464
Seventh Edition
Temporal horn,
white
Temporal horn,
white, with FIRE marking
Temporal horn,
red
Temporal horn,
red, with FIRE marking
Trim plate,
white
Trim plate,
white, with FIRE marking
ADTG1-HD MG1-HD
EG1-HD XLSG1-HD
G1-HD ZG1-HD
G1-HD-LG
ADTG1F-HD MG1F-HD
EG1F-HD XLSG1F-HD
G1F-HD ZG1F-HD
G1F-HD-LG
ADTG1R-HD MG1R-HD
EG1R-HD XLSG1R-HD
G1R-HD ZG1R-HD
G1R-HD-LG
ADTG1RF-HD MG1RF-HD
EG1RF-HD XLSG1RF-HD
G1RF-HD ZG1RF-HD
G1RF-HD-LG
ADTG1T MG1T
EG1T XLSG1T
G1T ZG1T
G1T-LG
ADTG1T MG1T
EG1T XLSG1T
G1T ZG1T
G1T-LG
Table 2: Sound level output (dBA)
Signal and voltage Low High
Temporal 16 Vdc 76.0 81.4
24 Vdc 79.4 84.4
33 Vdc 82.1 86.3
Continuous 16 Vdc 80.1 85.5
24 Vdc 83.5 88.6
33 Vdc 86.5 90.4
dBA = Decibels, A-weighted
UL464: Sound level output at 10 ft (3.05 m) measured in a
reverberant room.
ULC-S525: Meets or exceeds 85 dBA in an anechoic chamber
at 10 ft (3.05 m).
Installation Sheet 01MAY03
Genesis Temporal Horn 1 / 2
P/N: 3100558 REV: 1.0
Table 3: Operating current in RMS (A)
Voltage High Low
16 Vdc .026 .019
24 Vdc .036 .027
From compatible fire
alarm control panel
+
To next device or
end of line device
-
+
33 Vdc .041 .033
16 Vfwr .051 .037
24 Vfwr .069 .052
33 Vfwr .076 .070
Vdc = Volts direct current, regulated and filtered
Vfwr = Volts full wave rectified.
Installation instructions
Caution: Electrical supervision requires the wire run to be
broken at each terminal. Do not loop the signaling circuit field
wires around the terminals.
To install the horn:
1. Remove the cover by depressing both tabs on the top of
the unit with a small screwdriver and twisting slightly.
2. Set the horn signal and sound output level to desired
settings. See Figure 1.
3. Connect the horn terminals to the signal circuit field wiring.
You must observe polarity for the unit to function properly.
See Figure 2.
4. Mount the unit onto a compatible electrical box, making
sure not to over tighten the mounting screws.
5. Replace the cover by aligning at the bottom, then
snapping in at the top.
6. Test the unit for proper operation.
+
-
Note: Polarity shown in alarm condition
Figure 2: Wiring diagram
+
-
Maintenance
This unit is not serviceable or repairable. Should the unit fail to
operate, contact the supplier for replacement.
Perform a visual inspection and an operational test twice a
year or as directed by the local authority having jurisdiction.
To change the horn
from temporal to steady cut
from circle J2 to edge of
circuit board
Figure 1: Horn settings
signal
J1
To change the horn
output level
to low dB cut J3 by snipping
the board trace between
holes
J2
J3
sound
from high dB
2 / 2 01MAY03 P/N: 3100558 REV: 1.0
Genesis Temporal Horn/Strobe
Product information
The Genesis Temporal Horn/Strobe is a fire alarm notification
appliance designed for indoor walls. See Table 1 for a list of
model numbers.
The horn includes field configurable jumper options for
selecting the desired dB output, temporal or steady horn
output, and strobe signal output.
The strobe includes a field configurable switch for selecting the
desired candela output. The candela output setting is locked in
place and remains visible after final installation.
This strobe features an enhanced synchronization circuit to
comply with the latest requirements of UL 1971 Signaling
Devices for the Hearing Impaired and the latest Canadian
standard CAN/ULC S526-02. Synchronized operation requires
a separately installed synchronization control module. See
Table 2 for a list of compatible synchronization modules.
Install this device in accordance with applicable requirements
in the latest editions of the NFPA codes and standards and
Canadian Electrical Code, Part 1, Section 32, CAN/ULC S52401, Standard for the Installation of Fire Alarm Systems, and in
accordance with the local authorities having jurisdiction.
Table 1: Model numbers
Model description Model numbers
Table 1: Model numbers
Model description Model numbers
Horn-strobe,
15 to 110 multi-cd,
red, with FIRE marking
Trim plate,
white
Trim plate,
white, with FIRE marking
Trim plate,
red
Trim plate,
red, with FIRE marking
Table 2: Compatible synchronization modules
Model description Model numbers
Auto-Sync Output
Module
Signal Master
snap on piggyback
(1-gang)
Signal Master - Remote
Mount
ADTG1RF-VM MG1RF-VM
EG1RF-VM XLSG1RF-VM
G1RF-VM ZG1RF-VM
G1RF-VM-LG
ADTG1T MG1T
EG1T XLSG1T
G1T ZG1T
G1T-LG
ADTG1T MG1T
EG1T XLSG1T
G1T ZG1T
G1T-LG
ADTG1RT MG1RT
EG1RT XLSG1RT
G1RT ZG1RT
G1RT-LG
ADTG1RT MG1RT
EG1RT XLSG1RT
G1RT ZG1RT
G1RT-LG
SIGA-CC1S SIGA-MCC1S
SIGA-CC1S-LG SIGA-MCC1S-LG
ADTG1M MG1M
EG1M XLSG1M
G1M ZG1M
G1M-LG
ADTG1M-RM MG1M-RM
EG1M-RM XLSG1M-RM
G1M-RM ZG1M-RM
G1M-RM-LG
Horn-strobe,
15 to 110 multi-cd,
white
Horn-strobe,
15 to 110 multi-cd,
white, with FIRE marking
Horn-strobe,
15 to 110 multi-cd,
red
Installation Sheet 01MAY03
Genesis Temporal Horn/Strobe 1 / 3
ADTG1-VM MG1-VM
EG1-VM XLSG1-VM
G1-VM ZG1-VM
G1-VM-LG
ADTG1F-VM MG1F-VM
EG1F-VM XLSG1F-VM
G1F-VM ZG1F-VM
G1F-VM-LG
ADTG1R-VM MG1R-VM
EG1R-VM XLSG1R-VM
G1R-VM ZG1R-VM
G1R-VM-LG
Specifications
Operating voltage: Regulated 16 to 33 Vdc, 16 to 33 Vfwr
This device was tested to the regulated 24 Vdc/fwr
operating voltage limits of 16 V and 33 V. Do not apply
80% and 110% of these values for system operation.
Sound level output: See Table 3
Strobe operating current: See Table 4
Light output: Selectable at 15, 30, 75, and 110 cd
Synchronization: Meets or exceeds UL 1971 requirements.
Maximum allowed resistance between any two devices is
20 Ω. Refer to specifications for the synchronization
control module, this strobe, and the control panel to
determine allowed wire resistance.
Wire size: 12 to 18 AWG (2.50 to 0.75 sq mm)
P/N: 3100560 REV: 1.0