Edwards Signaling Genesis Temporal Horn User Manual

Page 1
Table

Description

Temporal horn, white
Temporal horn, white, with FIRE marking
Temporal horn, red
Temporal horn, red, with FIRE marking
Trim plate, white
Trim white, with FIRE marking
Trim plate, red
Trim plate, red, with FIRE marking
J2
J3
J1
1
2
1. To change the horn signal from temporal to steady, cut from circle
cut J3 by snipping the board trace between holes
Genesis Temporal Horn Installatio n Sheet
Description
The Genesis Temporal Horn is an audible fire alarm notification appliance designed for indoor walls. See Table 1 for a list of model numbers.
The horn includes field configurable jumper options for selecting:
Temporal or steady horn output (see Figure 1 item 1)
High dB or low dB output (see Figure 1 item 2)
1: Models
Number
plate,
ADTG1-HD MG1-HD EG1-HD XLSG1-HD G1-HD ZG1-HD G1-HD-LG
ADTG1F-HD MG1F-HD EG1F-HD XLSG1F-HD G1F-HD ZG1F-HD G1F-HD-LG
ADTG1R-HD MG1R-HD EG1R-HD XLSG1R-HD G1R-HD ZG1R-HD G1R-HD-LG
ADTG1RF-HD MG1RF-HD EG1RF-HD XLSG1RF-HD G1RF-HD ZG1RF-HD G1RF-HD-LG
ADTG1T MG1T EG1T XLSG1T G1T ZG1T G1T-LG
ADTG1T MG1T EG1T XLSG1T G1T ZG1T G1T-LG
ADTG1RT MG1RT EG1RT XLSG1RT G1RT ZG1RT G1RT-LG
ADTG1RT MG1RT EG1RT XLSG1RT G1RT ZG1RT G1RT-LG

Installation

Install this device in accordance with applicable requirements in the latest editions of the NFPA codes and standards; the
National Building Code of Canada; the Canadian Electrical Code, Part 1, Section 32, and in accordance with the local
authorities having jurisdi cti on.
Caution: Electrical supervision requires breaking the wire run
at each terminal. Do not loop the signaling circuit field wires around the terminals.
To install the horn:
1. Remove the cover by depressing both tabs on the top of the unit with a small screwdriver and twisting slightly.
2. Set the horn signal and sound output level to desired settings. See Figure 1.
3. Connect the horn terminals to the signal circuit field wiring. Observe polarity for the unit to function properly. See Figure 1.
4. Mount the unit onto a compatible electrical box, making sure not to overtighten the mounting screws.
5. Replace the cover by aligning at the bottom, then snapping in at the top.
6. Test the unit for proper operation.
Figure 1: Horn settings
J2 to edge of circuit board
2. To change the horn sound output level from high dB to low dB.
© 2013 UTC Fire & Security. All rights reserved. 1 / 4 P/N 3100558 • REV 04 • REB 30JAN13
Page 2
Figure 2: Wiring diagram
1 2
-
+
1. From NAC output 2 Note: Polarity is shown in the alarm condition.
Signal and voltage
Temporal
Continuous
UL 464: Sound level output reverberant room.
Tonal and voltage
16 VDC
24 VDC
33 VDC
16 VFWR
24 VFWR
33 VFWR
CAN/ULC
85 dBA in an anechoic chamber at
10 ft. (3.05 m)
Voltage
16 VDC
24 VDC
33 VDC
16 VFWR
24 VFWR
33 VFWR
VDC = Volts direct current, regulated and filtered VFWR = Volts full wave rectified
Angle (°) [1]
90
30
45
90
[1] Angles are measured from a perpendicular axis; positive angles to the right
[2] Peak output at 24 VDC, set for temporal tone.
Angle (°) [1]
90
35
45
90
[1] Angles are measured from a perpendicular axis; positive angles are up.
[2] Peak output at 24 VDC, set for temporal tone.
Table 4: Operating current in RMS (A)
High Low
0.026 0.019
0.036 0.027
0.041 0.033
0.051 0.037
0.069 0.052
0.076 0.070
. To next NAC output

Maintenance

Caution: To maintain the required agency listings, do not
change factory applied finishes.
This unit is not serviceable or repairable. Should the unit fail to operate, contact the supplier for replacement.
Perform a visual inspection and an operational test twice a year or as directed by the local authority having jurisdiction.
Table 2: Sound level output (dBA)
Low High
16 VDC 76.0 81.4
24 VDC 79.4 84.4 33 VDC 82.1 86.3
16 VDC 80.1 85.5
24 VDC 83.5 88.6 33 VDC 86.5 90.4
at 10 ft. (3.05 m) measured in a
Table 5: Audible directional characteristics (horizontal pattern)
Sound output (dBA) [2]
90 94 45 97 (−6) 30 100 (−3 )
103 100 (3 ) 97 (6 ) 96
Table 6: Audible directional characteristics (vertical pattern)
Sound output (dBA) [2]
90 94 40 97 (−6) 25 100 (−3)
103 dBA 100 (3) 97 (6) 96
Table 3: Sound level output (dBA, temporal tone, peak)
High
98.8
102.7
104.3
102.4
105.0
106.9
-S525: Meets or exceeds
2 / 4 P/N 3100558 • REV 04 • REB 30JAN13
Page 3

Specifications

Operating Voltage
Current
Sound level output
Audible directional characteristics
Wire size
Compatible electrical boxes Operating environment
Note: This device was te voltage limits of 16 V and 33 V. Do not apply 80% and 110% of these values for system operation.
Manufacturer Year of manufacture UL rating
North American standards
European Union directives
unsorted municipal waste in the European Union.
Regulated 16 to 33 VDC, 16 to 33 VFWR
Alarm Operating
See Table 2 and Table 3
12 to 18 AWG (0.75 to 2.50 mm²)
Temperature Relative humidity
40 mA at 24 VDC See Table 4
See Table 5 and Table 6
North American 2-1/2 in. (64 mm) deep single-gang box Standard 4 in. square box 1-1/2 in. (38 mm) deep box European 100 mm² box
32 to 120°F (0 to 49°C) 0 to 93% noncondensing
sted to the regulated 24 DC/FWR operating

Certification and compliance

Edwards, A Division of UTC Fire & Security Americas Corporation, Inc. 8985 Town Center Parkway, Bradenton, FL 34202, USA
Regulated 24 DC and 24 FWR
The first two digits of the date code (located on the product identification label) are the year of manufacture.
CAN/ULC-S525 and UL 464
1999/5/EC (R&TTE directive): Hereby, UTC Fire & Security declares that this device is in compliance with the essential requirements and other relevant provisions of Directive 1999/5/EC.
2002/96/EC (WEEE directive): Products marked with this symbol cannot be disposed of as
For proper recycling, return this product to your local supplier upon the purchase of equivalent new equipment, or dispose of it at designated collection points. For more information see: www.recyclethis.info.
2004/108/EC (EMC directive): Non-European manufacturers must designate an authorized representative in the Community. Our authorized manufacturing representative is:
UTC Fire & Sec u r ity B.V. Kelvinstraat 7, 6003 DH Weert, Netherlands

Contact information

For contact information, see www.edwardsutcfs.com.
P/N 3100558 • REV 04 • REB 30JAN13 3 / 4
Page 4
4 / 4 P/N 3100558 • REV 04 • REB 30JAN13
Loading...