Product information
Genesis Strobe
Table 1: Models
Description Model number
The Genesis Strobe is a visible fire alarm notification appliance
designed for indoor walls. See Table 1 for a list of model
numbers.
The strobe includes a field configurable switch for selecting the
desired candela output and a field configurable jumper for the
strobe signal output. The candela output setting is locked in
place and remains visible after final installation.
This strobe features an enhanced synchronization circuit to
comply with the latest requirements of UL 1971 Signaling
Devices for the Hearing Impaired and the latest Canadian
standard CAN/ULC S526-02. Synchronized operation requires
a separately installed synchronization control module. See
Table 2 for a list of compatible synchronization modules.
Install this device in accordance with applicable requirements
in the latest editions of the NFPA codes and standards and
Canadian Electrical Code, Part 1, Section 32, CAN/ULC S52401, Standard for the Installation of Fire Alarm Systems, and in
accordance with the local authorities having jurisdiction.
Table 1: Models
Description Model number
Strobe,
15 to 110 multi-cd,
white
Strobe,
15 to 110 multi-cd,
white, with FIRE marking
Strobe,
15 to 110 multi-cd,
red
ADTG1-VM MG1-VM
EG1-VM XLSG1-VM
G1-VM ZG1-VM
G1-VM-LG
ADTG1F-VM MG1F-VM
EG1F-VM XLSG1F-VM
G1F-VM ZG1F-VM
G1F-VM-LG
ADTG1R-VM MG1R-VM
EG1R-VM XLSG1R-VM
G1R-VM ZG1R-VM
G1R-VM-LG
Strobe,
15 to 110 multi-cd,
red, with FIRE marking
Trim plate,
white
Trim plate,
white, with FIRE marking
Trim plate,
red
Trim plate,
red, with FIRE marking
Table 2: Compatible synchronization modules
Description Model number
Auto-Sync Output
Module
Genesis Signal Master
Snap-on Mount
Genesis Signal Master Remote Mount
ADTG1RF-VM MG1RF-VM
EG1RF-VM XLSG1RF-VM
G1RF-VM ZG1RF-VM
G1RF-VM-LG
ADTG1T MG1T
EG1T XLSG1T
G1T ZG1T
G1T-LG
ADTG1T MG1T
EG1T XLSG1T
G1T ZG1T
G1T-LG
ADTG1RT MG1RT
EG1RT XLSG1RT
G1RT ZG1RT
G1RT-LG
ADTG1RT MG1RT
EG1RT XLSG1RT
G1RT ZG1RT
G1RT-LG
SIGA-CC1S SIGA-MCC1S
SIGA-CC1S-LG SIGA-MCC1S-LG
ADTG1M MG1M
EG1M XLSG1M
G1M ZG1M
G1M-LG
ADTG1M-RM MG1M-RM
EG1M-RM XLSG1M-RM
G1M-RM ZG1M-RM
G1M-RM-LG
Specifications
Operating voltage: 24 Vdc or 24 Vfwr, nominal
Strobe operating current: See Table 3
Light output: Selectable at 15, 30, 75, and 110 cd
Synchronization: Meets UL 1971 requirements. Maximum
allowed resistance between any two devices is 20 Ω.
Refer to specifications for the synchronization control
module, this strobe, and the control panel to determine
allowed wire resistance.
Wire size: 12 to 18 AWG (2.50 to 0.75 sq mm)
Compatible electrical boxes
North American 2-1/2 in (64 mm) deep 1-gang box
Standard 4 in square box 1-1/2 in (38 mm), 2-gang, or 4 in
octagonal with G1T or G1RT trim accessory
Operating environment
Temperature: 32 to 120 °F (0 to 49 °C)
Humidity: 0 to 93% RH, noncondensing at 90 °F (32 °C)
Installation Sheet 07OCT05 P/N: 3100559 REV: 3.0
Genesis Strobe 1 / 2
Agency listings: Meets year 2004 UL requirements for
standards UL1638 and UL1971 (see Figure 1) and
Canadian requirements for standards CAN/ULC S526-02
and CAN/ULC S524-01
UL ratings: Regulated 24 DC, Regulated 24 FWR
ULC ratings: 20 to 31 Vdc or 20 to 31 Vfwr
Table 3: Strobe operating current in RMS (A)
15 cd 30 cd 75 cd 110 cd
16 Vdc 0.103 0.141 0.255 0.311
110
75
30
15
16 Vfwr 0.125 0.179 0.346 0.392
Vdc = Volts direct current, regulated and filtered
Vfwr = Volts full wave rectified
Angle
0
5
-25
-30
-35
-40
-45
-50
-55
-60
-65
-70
-75
-80
-85
-90
9590858075706560555045403530252015
100
Horizontal and vertical outputs reflect the same pattern.
-5
-10
-15
-20
Percentage of rated output
10
15
20
25
30
505
10
1015202530354045505560657075808590
35
40
45
50
55
60
65
70
75
80
95
Figure 1: UL 1971 minimum light output (% of rating vs. angle)
Installation instructions
Warning: To reduce the risk of shock, disconnect all power
and allow 10 minutes for stored energy to dissipate before
handling.
Figure 2: Candela switch
To change the strobe to
temporal (private mode) cut
from circle J1 to edge of circuit
board
J1
85
90
100
Figure 3: Strobe signal setting
Note: If the strobe is set to temporal (private mode), this
J2
J3
device is no longer UL 1971 listed and FM Approved but is UL
1638 listed.
From compatible fire
alarm control panel
To next device or
end of line device
+
-
+
Caution: Electrical supervision requires the wire run to be
+
+
broken at each terminal. Do not loop the signaling circuit field
wires around the terminals.
-
-
To install the strobe:
1. Remove the cover by depressing both tabs on the top of
the unit with a small screwdriver and twisting slightly.
2. Slide the candela switch to the desired candela output (15,
Note: Polarity shown in alarm condition
30, 75, or 110 cd) by aligning it with the indicator located
beside the switch. See Figure 2.
3. Set the strobe signal if required. See Figure 3.
4. Connect the strobe terminals to the signal circuit field
wiring. You must observe polarity for the unit to function
properly. See Figure 4.
5. Mount the unit onto a compatible electrical box, making
sure not to over-tighten the mounting screws.
Figure 4: Wiring diagram
Maintenance
This unit is not serviceable or repairable. Should the unit fail to
operate, contact the supplier for replacement.
Perform a visual inspection and an operational test twice a
year or as directed by the local authority having jurisdiction.
6. Replace the cover by aligning at the bottom, then
snapping in at the top.
7. Test the unit for proper operation.
P/N: 3100559 REV: 3.0 07OCT05 Installation Sheet