Edwards Signaling Genesis Strobe User Manual

Product information
Genesis Strobe
Table 1: Models
Description Model number
The Genesis Strobe is a visible fire alarm notification appliance designed for indoor walls. See Table 1 for a list of model numbers.
The strobe includes a field configurable switch for selecting the desired candela output and a field configurable jumper for the strobe signal output. The candela output setting is locked in place and remains visible after final installation.
This strobe features an enhanced synchronization circuit to comply with the latest requirements of UL 1971 Signaling Devices for the Hearing Impaired and the latest Canadian standard CAN/ULC S526-02. Synchronized operation requires a separately installed synchronization control module. See Table 2 for a list of compatible synchronization modules.
Install this device in accordance with applicable requirements in the latest editions of the NFPA codes and standards and Canadian Electrical Code, Part 1, Section 32, CAN/ULC S524­01, Standard for the Installation of Fire Alarm Systems, and in accordance with the local authorities having jurisdiction.
Table 1: Models
Description Model number
Strobe, 15 to 110 multi-cd, white
Strobe, 15 to 110 multi-cd, white, with FIRE marking
Strobe, 15 to 110 multi-cd, red
ADTG1-VM MG1-VM EG1-VM XLSG1-VM G1-VM ZG1-VM G1-VM-LG
ADTG1F-VM MG1F-VM EG1F-VM XLSG1F-VM G1F-VM ZG1F-VM G1F-VM-LG
ADTG1R-VM MG1R-VM EG1R-VM XLSG1R-VM G1R-VM ZG1R-VM G1R-VM-LG
Strobe, 15 to 110 multi-cd, red, with FIRE marking
Trim plate, white
Trim plate, white, with FIRE marking
Trim plate, red
Trim plate, red, with FIRE marking
Table 2: Compatible synchronization modules
Description Model number
Auto-Sync Output Module
Genesis Signal Master Snap-on Mount
Genesis Signal Master ­Remote Mount
ADTG1RF-VM MG1RF-VM EG1RF-VM XLSG1RF-VM G1RF-VM ZG1RF-VM G1RF-VM-LG
ADTG1T MG1T EG1T XLSG1T G1T ZG1T G1T-LG
ADTG1T MG1T EG1T XLSG1T G1T ZG1T G1T-LG
ADTG1RT MG1RT EG1RT XLSG1RT G1RT ZG1RT G1RT-LG
ADTG1RT MG1RT EG1RT XLSG1RT G1RT ZG1RT G1RT-LG
SIGA-CC1S SIGA-MCC1S SIGA-CC1S-LG SIGA-MCC1S-LG
ADTG1M MG1M EG1M XLSG1M G1M ZG1M G1M-LG
ADTG1M-RM MG1M-RM EG1M-RM XLSG1M-RM G1M-RM ZG1M-RM G1M-RM-LG
Specifications
Operating voltage: 24 Vdc or 24 Vfwr, nominal Strobe operating current: See Table 3 Light output: Selectable at 15, 30, 75, and 110 cd Synchronization: Meets UL 1971 requirements. Maximum
allowed resistance between any two devices is 20 Ω. Refer to specifications for the synchronization control module, this strobe, and the control panel to determine
allowed wire resistance. Wire size: 12 to 18 AWG (2.50 to 0.75 sq mm) Compatible electrical boxes
North American 2-1/2 in (64 mm) deep 1-gang box
Standard 4 in square box 1-1/2 in (38 mm), 2-gang, or 4 in
octagonal with G1T or G1RT trim accessory Operating environment
Temperature: 32 to 120 °F (0 to 49 °C)
Humidity: 0 to 93% RH, noncondensing at 90 °F (32 °C)
Installation Sheet 07OCT05 P/N: 3100559 REV: 3.0 Genesis Strobe 1 / 2
Agency listings: Meets year 2004 UL requirements for
standards UL1638 and UL1971 (see Figure 1) and Canadian requirements for standards CAN/ULC S526-02
and CAN/ULC S524-01 UL ratings: Regulated 24 DC, Regulated 24 FWR ULC ratings: 20 to 31 Vdc or 20 to 31 Vfwr
Table 3: Strobe operating current in RMS (A)
15 cd 30 cd 75 cd 110 cd
16 Vdc 0.103 0.141 0.255 0.311
110
75 30 15
16 Vfwr 0.125 0.179 0.346 0.392 Vdc = Volts direct current, regulated and filtered
Vfwr = Volts full wave rectified
Angle
0
5
-25
-30
-35
-40
-45
-50
-55
-60
-65
-70
-75
-80
-85
-90 9590858075706560555045403530252015
100
Horizontal and vertical outputs reflect the same pattern.
-5
-10
-15
-20
Percentage of rated output
10
15
20
25
30
505
10
1015202530354045505560657075808590
35
40
45
50
55
60
65
70
75
80
95
Figure 1: UL 1971 minimum light output (% of rating vs. angle)
Installation instructions
Warning: To reduce the risk of shock, disconnect all power
and allow 10 minutes for stored energy to dissipate before handling.
Figure 2: Candela switch
To change the strobe to temporal (private mode) cut from circle J1 to edge of circuit board
J1
85
90
100
Figure 3: Strobe signal setting
Note: If the strobe is set to temporal (private mode), this
J2
J3
device is no longer UL 1971 listed and FM Approved but is UL 1638 listed.
From compatible fire alarm control panel
To next device or end of line device
­+
-
+
Caution: Electrical supervision requires the wire run to be
+
+
broken at each terminal. Do not loop the signaling circuit field wires around the terminals.
-
-
To install the strobe:
1. Remove the cover by depressing both tabs on the top of the unit with a small screwdriver and twisting slightly.
2. Slide the candela switch to the desired candela output (15,
Note: Polarity shown in alarm condition
30, 75, or 110 cd) by aligning it with the indicator located beside the switch. See Figure 2.
3. Set the strobe signal if required. See Figure 3.
4. Connect the strobe terminals to the signal circuit field wiring. You must observe polarity for the unit to function properly. See Figure 4.
5. Mount the unit onto a compatible electrical box, making sure not to over-tighten the mounting screws.
Figure 4: Wiring diagram
Maintenance
This unit is not serviceable or repairable. Should the unit fail to operate, contact the supplier for replacement.
Perform a visual inspection and an operational test twice a year or as directed by the local authority having jurisdiction.
6. Replace the cover by aligning at the bottom, then snapping in at the top.
7. Test the unit for proper operation.
P/N: 3100559 REV: 3.0 07OCT05 Installation Sheet 2 / 2 Genesis Strobe