Edwards Signaling Genesis Speaker Strobe User Manual

Genesis Speaker-Strobe Installa tion Sheet
Description
The Genesis Speaker-Strobe is a fire alarm notification appliance designed for indoor walls. See Table 1 for a list of model numbers.
Table 1: Models
Number
-Strobe,
-cd, white
-Strobe,
-cd, white, with FIRE
-Strobe,
-cd, white
-Strobe,
-cd, white, with FIRE
The speaker-strobe includes field configurable switches for selecting the desired candela output and wattage tap. These settings lock in place and remain visible after final installation.
This strobe features an enhanced synchronization circuit to comply with the latest requirements of UL 1971 Signaling Devices for the Hearing Impaired and the latest Canadian standard CAN/ULC-S526. Synchronized operation requires a separately installed synchronization control module. See Table 2 for a list of compatible synchronization modules.
Install this device in accordance with applicable requirements in the latest editions of the NFPA codes and standards and Canadian Electrical Code, Part 1, Section 32 and CAN/ULC­S524, Standard for the Installation of Fire Alarm Systems, and in accordance with the local authorities having jurisdiction.
ADTG4-S2VM MG4-S2VM EG4-S2VM XLSG4-S2VM G4-S2VM ZG4-S2VM
ADTG4F-S2VM MG4F-S2VM EG4F-S2VM XLSG4F-S2VM G4F-S2VM ZG4F-S2VM
ADTG4-S7VM MG4-S7VM EG4-S7VM XLSG4-S7VM G4-S7VM G4-S7VM
ADTG4F-S7VM MG4F-S7VM EG4F-S7VM XLSG4F-S7VM G4F-S7VM ZG4F-S7VM
ADTG4B MG4B EG4B XLSG4B G4B ZG4B
Table 2: Compatible synchronization module models
Number
-sync output module
SIGA-CC1S SIGA-MCC1S GSA-CC1S GSA-MCC1S
-
ADTG1M-RM MG1M-RM EG1M-RM XLSG1M-RM G1M-RM ZG1M-RM

Installation

WARNING: To reduce the risk of shock, disconnect all power
and allow 10 minutes for stored energy to dissipate before handling.
Caution: Electrical supervision requires the wire run to be
broken at each terminal. Do not loop the signaling circuit field wires around the terminals.
To install the speaker-strobe:
1. Remove the cover by depressing the tabs on top of the unit by inserting a small screwdriver from the top and twisting slightly.
2. If temporal strobe (private mode) operation is desired, cut jumper JP1. See Figure 2.
3. Connect the speaker and strobe terminals to the signal circuit field wiring. For the unit to function properly, observe polarity. See Figure 5.
4. Slide the candela switch to the desired candela output (15, 30, 75, or 95 cd) by aligning it with the indicator below the switch. See Figure 1.
5. Slide the wattage switch to the desired wattage tap (2 W, 1 W, 1/2 W, or 1/4 W) by aligning it with the indicator below the switch. See Figure 1.
6. Mount the unit onto a compatible electrical box. See Figure 4.
7. Replace the cover by aligning it at the bottom and snapping it in at the top.
© 2013 UTC Fire & Security. All rights reserved. 1 / 4 P/N 3100273 • REV 07 • REB 30JAN13
8. Test the unit for proper operation.
Figure 1: Field-configurable switches
1. Candela switch
2. Indicator
3. Wattage switch
4. Bottom
1. JP1: Strobe signal output: Cut to change from 1 flash per second (public mode) to temporal (private mode)
1. Percentage of candela horizontal spec.
2. Percentage of candela vertical spec.
Figure 2: Strobe settings
Figure 4: Mounting diagram
Note: If the strobe is set to temporal (private mode), this
device is no longer UL 1971 or ULC-S526 Listed or FM Approved but is UL 1638 Listed.
Figure 3: UL 1971 minimum light output (% of rating vs. angle)
2 / 4 P/N 3100273 • REV 07 • REB 30JAN13
Loading...
+ 2 hidden pages