Description
Genesis Signal Master [1]
ADTG1M, EG 1 M, G1M, MG1M, XLSG1M,
ZG1M
[1] This module is compatible with Genesi
models and quantities, see the compatibility list referenced on the
control panel.
2. Genesis Signal Master Module
1. From previous appliance or control panel
2.
• The horns cannot be silenced without turning off the strobes
-
+
NAC_IN +
NAC_IN –
1
H
S
3
2
4
Genesis Signal Master Module Installation S heet
Description
The Genesis Signal Master Module provides precision
synchronization and independent horn control for Genesis
strobes and horns. It mounts on the back of the first appliance
on the notification appliance circuit. Model numbers are listed
below.
Table 1: Models
s devices. For specific
The Signal Master Module only synchronizes appliances that
are electrically connected to, and electrically downstream from
it.
Installation
Install in accordance with applicable requirements in the latest
editions of the NFPA codes and standards and Canadian
Electrical Code, Part 1, Section 32, and in accordance with the
local authorities having jurisdiction.
When determining allowable wire resistance, refer to the
voltage rating of the Genesis Signal Master Module, the
signaling appliance, and the control panel spe cifications.
Figure 1: Mounting the Genesis Signal Master Module
Figure 2: Synchronization using one NAC
To install the module:
1. Slide the spade connectors of the Genesis Signal Master
Module into the terminals on the back of the first Genesis
appliance on the notification appliance circuit. See
Figure 1.
2. Observing polarity, connect the wires for the remaining
appliances under the same terminals as the spade lugs.
See the wiring diagrams.
3. Connect the wires to the Genesis Signal Master. (See
Figure 2 through Figure 4).
Wiring
Only one Genesis Signal Master is required for each
notification appliance circuit.
The strobe input of the Genesis Signal Master requires a
dedicated NAC whereas the horn input of the Genesis Signal
Master can be cascaded with other Genesis Signal Master
modules on one NAC.
The strobe input source must supply a continuous 24 VDC
when active.
Genesis appliance with Genesis Signal Master
To next appliance, EOL resistor, or Class A circuit return. EOL
resistor value is determined by the control panel requirements.
Jumpers: when using a single horn and strobe NAC circuit,
attach the NAC circuit to the bottom two terminals of the Genesis
Signal Master. Install jumper H− to S− and H+ to S+, as shown.
Polarity shown in alarm condition
© 2013 UTC Fire & Security. All rights reserved. 1 / 2 P/N 3100124 • REV 08 • REB 30JAN13
Figure 3: Horn silence / synchronization using two NACs
• The horn circuit can be silenced without turning off strobes
1. Signature data circuit from loop controller or previous device
2.
2 A max. Actual value limited by system NAC
Manufacturer
Year of
manufacture
UL rating
[1] This module was tested to the regulated 24 VDC/FWR operating
voltage limits o
values for system operation.
-
-
+
STROBE_IN +
STROBE_IN –
2
HORN_IN +
HORN_IN –
H
S
4
3
1
5
++
-
+
C NC
SLC_OUT +
CR
SLC_IN +
1
STROBE_IN +
STROBE_IN –
2
H
S
4
3
5
NAC 1 strobe in
Horn resistor, value determined by the control panel
Genesis appliance with Genesis Signal Master
To next appliance. EOL resistor or Class A circuit return
Polarity shown in alarm condition
Figure 4: Horn silence / synchronization using one NAC
Specifications
erating voltage 16 to 33 VDC or 16 to 33 VFWR
33 mA
and power outputs.
Flash
Resistance
between two
appliances
size 12 to 18 AWG (0.75 to 2.50 mm²)
Temperature
Relative humidity
Snaps to back of Genesis appliance
1/s, within 10 ms indefinitely
20 Ω max.
32 to 120°F (0 to 49°C)
0 to 93% noncondensing
Regulatory information
Edwards, A Division of UTC Fire & Security
Americas Corporation, Inc.
8985 Town Center Parkway, Bradenton, FL
34202, USA
Regulated 24 DC, Regulated 24 FWR [1]
The first two digits of the product serial number
(located on the product identification label) are
the year of manufacture.
UL 1971 compliant
UL: Indoor
UL 1971, UL 1638, UL 464, CAN/ULC S525,
CAN/ULC S526
From previous appliance or control panel
Genesis appliance with Genesis Signal Master
To next appliance, EOL resistor or Class A circuit return
To next device or Class A circuit return
EOL resistor is determined by the control panel requirements
Polarity shown in alarm condition
The horn circuit can be silenced without turning off strobes
CR module must be located in the same electrical box as the
2 / 2 P/N 3100124 • REV 08 • REB 30JAN13
f 16 V and 33 V. Do not apply 80% and 110% of these
Contact information
For contact information, see www.utcfireandsecurity.com.