Edwards Signaling Genesis Signal Master Module User Manual

Description

Number
Genesis Signal Master [1]
ADTG1M, EG 1 M, G1M, MG1M, XLSG1M, ZG1M
[1] This module is compatible with Genesi models and quantities, see the compatibility list referenced on the control panel.
1. Genesis appliance
2. Genesis Signal Master Module
1. From previous appliance or control panel
2.
3.
4.
Notes
The horns cannot be silenced without turning off the strobes
H
S
2
-
+
NAC_IN + NAC_IN –
1
H
S
3
2
4
Genesis Signal Master Module Installation S heet
Description
The Genesis Signal Master Module provides precision synchronization and independent horn control for Genesis strobes and horns. It mounts on the back of the first appliance on the notification appliance circuit. Model numbers are listed below.
Table 1: Models
s devices. For specific
The Signal Master Module only synchronizes appliances that are electrically connected to, and electrically downstream from it.

Installation

Install in accordance with applicable requirements in the latest editions of the NFPA codes and standards and Canadian Electrical Code, Part 1, Section 32, and in accordance with the local authorities having jurisdiction.
When determining allowable wire resistance, refer to the voltage rating of the Genesis Signal Master Module, the signaling appliance, and the control panel spe cifications.
Figure 1: Mounting the Genesis Signal Master Module
Figure 2: Synchronization using one NAC
To install the module:
1. Slide the spade connectors of the Genesis Signal Master Module into the terminals on the back of the first Genesis appliance on the notification appliance circuit. See Figure 1.
2. Observing polarity, connect the wires for the remaining appliances under the same terminals as the spade lugs. See the wiring diagrams.
3. Connect the wires to the Genesis Signal Master. (See Figure 2 through Figure 4).

Wiring

Only one Genesis Signal Master is required for each notification appliance circuit.
The strobe input of the Genesis Signal Master requires a dedicated NAC whereas the horn input of the Genesis Signal Master can be cascaded with other Genesis Signal Master modules on one NAC.
The strobe input source must supply a continuous 24 VDC when active.
Genesis appliance with Genesis Signal Master To next appliance, EOL resistor, or Class A circuit return. EOL
resistor value is determined by the control panel requirements.
Jumpers: when using a single horn and strobe NAC circuit,
attach the NAC circuit to the bottom two terminals of the Genesis Signal Master. Install jumper H− to S− and H+ to S+, as shown.
Polarity shown in alarm condition
© 2013 UTC Fire & Security. All rights reserved. 1 / 2 P/N 3100124 • REV 08 • REB 30JAN13
Figure 3: Horn silence / synchronization using two NACs
1. NAC 1 horn in
2.
3.
4.
5. Notes
The horn circuit can be silenced without turning off strobes
1. Signature data circuit from loop controller or previous device
2.
3.
4.
5. Notes
• Genesis Signal Master
Op
Operating current
Output rating
2 A max. Actual value limited by system NAC
Synchronization
Wire
Mounting
Operating environment
Manufacturer Year of manufacture UL rating
Synchronization
Environmental class
North American standards
[1] This module was tested to the regulated 24 VDC/FWR operating voltage limits o values for system operation.
-
-
+
STROBE_IN + STROBE_IN –
2
HORN_IN + HORN_IN –
H
S
4
3
1
5
++
-
+
C NC
SLC_OUT +
CR
SLC_IN +
1
STROBE_IN + STROBE_IN –
2
H
S
4
3
5
NAC 1 strobe in Horn resistor, value determined by the control panel Genesis appliance with Genesis Signal Master To next appliance. EOL resistor or Class A circuit return
Polarity shown in alarm condition
Figure 4: Horn silence / synchronization using one NAC

Specifications

erating voltage 16 to 33 VDC or 16 to 33 VFWR
33 mA
and power outputs.
Flash
Resistance between two appliances
size 12 to 18 AWG (0.75 to 2.50 mm²)
Temperature Relative humidity
Snaps to back of Genesis appliance
1/s, within 10 ms indefinitely
20 Ω max.
32 to 120°F (0 to 49°C) 0 to 93% noncondensing

Regulatory information

Edwards, A Division of UTC Fire & Security Americas Corporation, Inc. 8985 Town Center Parkway, Bradenton, FL 34202, USA
Regulated 24 DC, Regulated 24 FWR [1]
The first two digits of the product serial number (located on the product identification label) are the year of manufacture.
UL 1971 compliant
UL: Indoor
UL 1971, UL 1638, UL 464, CAN/ULC S525, CAN/ULC S526
From previous appliance or control panel Genesis appliance with Genesis Signal Master To next appliance, EOL resistor or Class A circuit return To next device or Class A circuit return
EOL resistor is determined by the control panel requirements Polarity shown in alarm condition The horn circuit can be silenced without turning off strobes CR module must be located in the same electrical box as the
2 / 2 P/N 3100124 • REV 08 • REB 30JAN13
f 16 V and 33 V. Do not apply 80% and 110% of these

Contact information

For contact information, see www.utcfireandsecurity.com.