Description
Genesis Remote Mount
Signal M
1. Compatible electrical box
2.
Genesis Remote Mount Signal Mast er Module
Installation Sheet
Description
The Genesis Remote Mount Signal Master Module provides
precision synchronization and indep end ent horn cont rol f or
Genesis strobes and horns. Model numbers are listed below.
Table 1: Models
Numbers
aster Module [1]
[1] This module is compatible with Genesis, Enhanced Integrity
(synchronized), and Audible Detector base devices. For specific
models and quantities, see the compatibility list referenced on the
control panel.
ADTG1M-RM,
G1M-RM
XLSG1M-RM
EG1M-RM
MG1M-RM
ZG1M-RM
Installation
Install in accordance with applicable requirements in the latest
editions of the NFPA codes and standards and Canadian
Electrical Code, Part 1, Section 32, and in accordance with the
local authorities having jurisdiction.
Notes
• The Genesis Remote Mount Signal Master Module is
shipped from the factory as an assembled unit; it contains
no user-serviceable parts and should not be
disassembled.
To install the module:
1. Verify that all field wiring is free of opens, shorts, and
ground faults.
2. Make all wiring connections as shown in Figure 2 through
Figure 4.
3. Using the 4-24 x 1/2 in. screw, mount the wall plate on the
module as shown in Figure 1.
4. Using the two 6-32 x 1/2 machine screws, mount the
module in the electrical box.
Figure 1: Mounting in a single-gang box
• The Signal Master Module only synchronizes appliances
that are electrically connected to it and are electrically
downstream of it
• Only one module is required for each notification
appliance circuit.
• The strobe circuit of the module requires a dedicated NAC
whereas the horn circuit of the module can be cascaded
with other Genesis Signal Master modules on one NAC.
• The strobe circuit must be continuous in alarm mode.
• When determining allowable wire resistance, refer to the
voltage rating of the module, the signaling appliance, and
the control panel specifications.
© 2013 UTC Fire & Security. All rights reserved. 1 / 4 P/N 3100299 • REV 07 • REB 30JAN13
Remote Signal Master
Module
4. 6-32 x 1/2 in. screw
5. 4-24 x 1/2 in. screw

Figure 2: Horn silence / synchronization using two NACs
1. Strobe or horn/strobe
2.
• Horn c i rc uit can be silenced without turni ng off strobes
1. Strobe or horn/strobe
2.
Notes
• Horn c i rc uit cannot be silenced without turning off strobes
–
+
+
HORN_IN +
1
G1M-RM
STROBE_IN +
STROBE_IN –
2
3
–
+
NAC_IN +
1
G1M-RM
2
2
3. To next appliance, EOL resistor, or Class A circuit return
• G1M-RM, CR modul e, and wire nut must be locat ed in the same enclosure as the Genesis Signal Master.
4
C NC
–
+
CR
SLC_IN +
SLC_OUT +
1
G1M-RM
STROBE_IN +
STROBE_IN –
2
3
Figure 4: Synchronization using one NAC
To next appliance, EOL resistor, or Class A circuit return
To next G1M-RM or end of line resistor
Polarity shown in alarm condition
Figure 3: Horn silence / synchronization using one NAC
To next appliance, EOL resistor, or Class A circuit return
Polarity shown in alarm condition
From previous device or control panel
Polarity shown in alarm condition
Horn circuit can be silenced without turning off strobes
2 / 4 P/N 3100299 • REV 07 • REB 30JAN13
4. To next device or Class A circuit return

Table 2: G 1M-RM terminal connections
Manufacturer
Year of
manufacture
UL rating
[1] This module was tested to the regulated 24 VDC/FWR operating
voltage limits of 16 V and 33 V. Do not apply 80% and 110% of these
values for system operation.
Description Terminal Description
HORN IN + 5 STROBE IN +
HORN IN − 6 STROBE IN −
HORN OUT + 7 STROBE OUT +
HORN OUT - 8 STROBE OUT -
Specifications
16 to 33 VDC; 16-33 VFWR
Flash
Resistance between two
appliances
12 to 18 AWG (0.75 to 2.50 mm²)
Compatible
Recommended
3 A max. Actual value limited by
system NAC and power outputs
1/s within 10 mss indefinitely
20 Ω max.
2-1/2 in. (64 mm) deep single4 in. square box 1-1/2 in. (38 mm)
deep with single-gang trim ring
3-3/4 x 2 in. (95 x 51 mm) (H x W) or
Regulatory information
Edwards, A Division of UTC Fire & Security
Americas Corporation, Inc.
8985 Town Center Parkway, Bradenton, FL
34202, USA
Regulated 24 DC, Regulated 24 FWR [1]
The first two digits of the product serial number
(located on the product identification label) are
the year of manufacture.
UL: Indoor
UL 1971, UL 1638, UL 464, CAN/ULC S525,
CAN/ULC S526
Contact information
For contact information, see www.edwardsutcfs.com.
Temperature
Relative humidity
32 to 120 °F (0 to 49 °C)
0 to 93% noncondensing
P/N 3100299 • REV 07 • REB 30JAN13 3 / 4