with FIRE marking, standard output clear
strobe light
Genesis Low Frequency (520 Hz) Horn-Strobe
Installation Sheet
Table 1: Models
on Number
frequency (520 Hz) horn, white housing,
frequency (520 Hz) horn, white housing,
frequency (520 Hz) horn, red housing, no
frequency (520 Hz) horn, red housing,
standard output clear strobe
, standard output clear
standard output clear strobe
box, white housing G4B
box, red housing G4RB
This strobe features an enhanced synchronization circuit to
comply with the latest requirements of UL 1971. Synchronized
operation requires a separately installed synchronization
device. See the control panel or power supply compatibility list
for compatible synchronization devices.
G4LFWN-HVM
G4LFWF-HVM
G4LFRN-HVM
G4LFRF-HVM
Description
The Genesis Low Frequency (520 Hz) Horn-Strobe can be
used for applications where a low frequency alarm notification
appliance with strobe light output is required. The device is
designed for wall mounting and indoor use only. See Table 1
for a list of model numbers.
When this device is used as a low frequency sounder in
sleeping quarters, the strobe's candela switch (Figure 1) must
be set to 110 cd.
The horn-strobe includes field-configurable jumper options for
selecting:
• Temporal or steady horn output
• Low dB or high dB output
• Temporal or continuous pattern strobe
The horn-strobe also includes a field-configurable switch for
setting the strobe candela level. This setting is locked in place
and is visible after final installation.
Installation
Install and wire this device in accordance with applicable
national and local codes, ordinances, and regulations.
The horn-strobe should be mounted so that the entire lens is
not less than 80 in. (2.03 m) and not greater than 96 in.
(2.44 m) above the finished floor. The entire lens should also
be 24 in. (61 cm) or more from the finished ceiling.
WARNING: Electrocution hazard. To avoid personal injury or
death from electrocution, remove all sources of power and
allow stored energy to discharge before installing or removing
equipment.
Note: Electrical supervision requires that you break the wire
run at each terminal. Do not loop wires around the terminals.
© 2014 UTC Fire & Security Americas Corporation, Inc. 1 / 6 P/N 3102149-EN • REV 02 • ISS 25MAR14
To install the horn-strobe:
(1) Compatible electrical box
(2)
(3) Horn-strobe
(4) 8-32 x 1 in. screw, provided
1. Remove the cover by using a screwdriver to depress and
slightly twist both tabs on top of the unit.
2. Set the horn signal, sound output level, and strobe signal
to the desired settings. See Figure 1.
To change the horn output level from high dB to low dB,
cut jumper JP3.
To change the horn signal from temporal to steady, cut
jumper JP2.
To change the strobe pattern from continuous to temporal
(private mode), cut jumper JP1.
3. Set the candela output.
Slide the candela switch to the desired candela output by
aligning it with the indicator notch below the switch. See
Figure 1.
4. Mount the horn-strobe as follows.
Note: Route the signal circuit field wiring through the
cutout in the center of the horn-strobe.
Flush mount: Mount the horn-strobe and flush mount
spacer onto a compatible electrical box (Figure 2), making
sure not to overtighten the mounting screws. See
“Specifications” for compatible electrical boxes.
Surface mount: Mount the G4B or G4RB surface mount
box on the wall (Figure 3), and then secure the appliance
to the box using the fasteners provided with the box.
5. Connect the signal circuit field wiring to the horn-strobe
terminals (Figure 4). Observe polarity for the unit to
function properly.
6. Replace the cover by aligning it at the bottom, and then
snapping it in at the top.
7. Test the unit for proper operation.
Figure 1: Horn-strobe settings
Jumper JP2
Figure 2: Flush mount
Candela switch indicator
Maintenance
Caution: To maintain the required agency listings, do not
change factory-applied finishes.
This unit is not serviceable or repairable. Should the unit fail to
operate, contact the supplier for a replacement.
Perform a visual inspection and an operational test twice a
year or as directed by the local authority having jurisdiction.
2 / 6 P/N 3102149-EN • REV 02 • ISS 25MAR14
Flush mount spacer
(2X)