
Description
Genesis Low Frequency (520 Hz) Horn
Installation Sheet
Installation
Install and wire this device in accordance with applicable
national and local codes, ordinances, and regulations.
Note: Electrical supervision requires that you break the wire
run at each terminal. Do not loop wires around the terminals.
To install the horn:
1. Remove the cover by using a screwdriver to depress and
slightly twist both tabs on top of the unit.
2. Set the horn signal and sound output level to desired
settings. See Figure 1.
To change the horn output level from high dB to low dB,
cut jumper JP3.
To change the horn signal from temporal to steady, cut
jumper JP2.
3. Mount the horn as follows.
Description
The Genesis Low Frequency (520 Hz) horn can be used for
applications where a low frequency alarm notification appliance
is required. The device is designed for indoor use only and can
be mounted on the wall or ceiling. See Table 1 for a list of
model numbers.
The horn includes field-configurable jumper options for
selecting:
• Temporal or steady horn output
• High dB or low dB output
Table 1: Models
Number
frequency (520 Hz) horn, white housing,
frequency (520 Hz) horn, white housing,
frequency (520 Hz) horn, red housing, no
frequency (520 Hz) horn, red housing,
box, white housing G4B
box, red housing G4RB
G4LFWN-H
G4LFWF-H
G4LFRN-H
G4LFRF-H
Note: Route the signal circuit field wiring through the
cutout in the center of the horn.
Flush mount: Mount the horn and flush mount spacer
onto a compatible electrical box (Figure 2), making sure
not to overtighten the mounting screws. See
“Specifications” for compatible electrical boxes.
Surface mount: Mount the G4B or G4RB surface mount
box on the wall or ceiling (Figure 3), and then secure the
appliance to the box using the screws provided with the
box.
4. Connect the signal circuit field wiring to the horn terminals
(Figure 4). Observe polarity for the unit to function
properly.
5. Replace the cover by aligning it at the bottom, and then
snapping it in at the top (Figure 2 and Figure 3).
6. Test the unit for proper operation.
© 2014 UTC Fire & Security Americas Corporation, Inc. 1 / 4 P/N 3102148-EN • REV 02 • ISS 25MAR14

Figure 1: Horn settings
(1) Compatible electrical box
(2)
(3) Horn
(4) 8-32 x 1 in. screw 2X
(1) Surface mount box (G4B or
(3) Screw 4X (provided with
(1) From NAC output
(2)
Note: Polarity is shown in the active condition.
Figure 3: Surface mount
Figure 2: Flush mount
G4RB)
Figure 4: Wiring diagram
G4B or G4RB box)
Flush mount spacer
2 / 4 P/N 3102148-EN • REV 02 • ISS 25MAR14
(provided)
To next device or EOL

Maintenance
Audible directional
characteristics
Compatible electrical
boxes
[1] This
voltage limits of 16 V and 33 V. Do not apply 80% and 110% of these
values for system operation.
[2] Peak output at 16 VDC, set for steady tone.
Manufacturer
Year of
manufacture
Caution: To maintain the required agency listings, do not
change factory-applied finishes.
This unit is not serviceable or repairable. Should the unit fail to
operate, contact the supplier for a replacement.
Perform a visual inspection and an operational test twice a
year or as directed by the local authority having jurisdiction.
Specifications
oltage 24 VDC or 24 VFWR [1]
Alarm
Operating
12 to 18 AWG (1.0 to 4.0 mm²)
Temperature
Relative humidity
device was tested to the Regulated 24 DC/FWR operating
166 mA at 16 VDC, 215 mA at 16 VFWR
See Table 4
See Table 2 and Table 3
See Table 5 and Table 6
Standard 4 in. square box 1-1/2 in. (38 mm),
2-1/8 in. (54 mm) deep box, or G4B/G4RB
surface mount box
32 to 120°F (0 to 49°C)
0 to 93% noncondensing
Table 4: Nominal operating current in RMS (mA)
oltage Low High
16 VDC 86 166
24 VDC 43 112
33 VDC 36 87
16 VFWR 97 215
24 VFWR 78 159
33 VFWR 76 140
16 VDC 36 160
24 VDC 45 109
33 VDC 36 86
16 VFWR 92 212
24 VFWR 80 168
33 VFWR 77 141
VDC = Volts direct current, regulated and filtered
VFWR = Volts full wave rectified
Table 5: Audible directional characteristics (horizontal pattern)
Output (dB) [2]
85
82
90 82
Angles are measured from a perpendicular axis; positive angles to
Table 2: UL sound level output (dBA) [1]
Low High
16 VDC 72.4 76.0
24 VDC 72.3 75.7
33 VDC 73.3 75.4
16 VDC 75.7 79.8
24 VDC 76.1 78.6
33 VDC 75.4 78.8
[1] UL 464: Sound level output at 10 ft. (3.05 m) measured in a
reverberant room
Table 3: Nominal sound level output (dBA, temporal tone) [1]
Low High
84.0 85.5
83.9 85.4
83.7 85.5
83.7 86.1
83.9 85.9
84.0 85.9
[1] Measured in an anechoic chamber at 10 ft. (3.05 m)
Table 6: Audible directional characteristics (vertical pattern)
Output (dB) [2]
85
82
90 82
[1] Angles are measured from a perpendicular axis; positive angles are
up.
[2] Peak output at 16 VDC, set for steady tone.
Regulatory information
Edwards, A Division of UTC Fire & Security
Americas Corporation, Inc.
8985 Town Center Parkway, Bradenton, FL
34202, USA
The first two digits of the date code (located on
Regulated 24 DC and 24 FWR
the product identification label) are the year of
manufacture.
UL 464
Contact information
P/N 3102148-EN • REV 02 • ISS 25MAR14 3 / 4
For contact information, see www.edwardsutcfs.com.

4 / 4 P/N 3102148-EN • REV 02 • ISS 25MAR14