Edwards Signaling Genesis High Candela Ceiling Speaker-Strobe User Manual

Page 1

Description

Speaker 25 VRMS, 95 to 177 multi white
Speaker 25 VRMS, 95 to 177 white, with FIRE marking
Speaker 70 VRMS, 95 to 177 multi white
Speaker 70 VRMS, 95 to white, with FIRE marking
Model name
Auto
Genesis Signal Master Remote Mount
Genesis High Candela Ceiling Speaker-Strobe Installation Sheet
Description
The Genesis High Candela Ceiling Speaker-Strobe is a fire alarm notification appliance designed for indoor ceilings and walls. See Table 1 for a list of model numbers.
Number
-Strobe,
-Strobe, multi-cd,
-Strobe,
-Strobe,
177 multi-cd,
A field configurable jumper option is available for selecting the desired strobe signal output.
The speaker-strobe includes field configurable switches for selecting the desired candela and wattage outputs. These output settings lock in place and remain visible after final installation.
This strobe features an enhanced synchronization circuit to comply with the latest requirements of UL 1971 Signaling Devices for the Hearing Impaired and the latest Canadian standard CAN/ULC-S526. Synchronized operation requires a separately installed synchronization control module. See Table 2 for a list of compatible synchronization modules.
Install this device in accordance with applicable requirements in the latest editions of the NFPA codes and standards and Canadian Electrical Code, Part 1, Section 32 and CAN/ULC-S524, Standard for the Installation of Fire Alarm Systems, and in accordance with the local authorities having jurisdiction.
ADTGC-S2VMH MGC-S2VMH
-cd,
EGC-S2VMH XLSGC-S2VMH GC-S2VMH ZGC-S2VMH
ADTGCF-S2VMH MGCF-S2VMH EGCF-S2VMH XLSGCF-S2VMH GCF-S2VMH ZGCF-S2VMH
ADTGC-S7VMH MGC-S7VMH
-cd,
EGC-S7VMH XLSGC-S7VMH GC-S7VMH ZGC-S7VMH
ADTGCF-S7VMH MGCF-S7VMH EGCF-S7VMH XLSGCF-S7VMH GCF-S7VMH ZGCF-S7VMH
Table 2: Compatible synchronization module models
Number
-Sync Output Module
SIGA-CC1S SIGA-MCC1S GSA-CC1S GSA-MCC1S
-
ADTG1M-RM MG1M-RM EG1M-RM XLSG1M-RM G1M-RM ZG1M-RM

Installation

WARNING: To reduce the risk of shock, disconnect all power
and allow 10 minutes for stored energy to dissipate before handling.
Caution: Electrical supervision requires the wire run to be
broken at each terminal. Do not loop the signaling circuit field wires around the terminals.
Note: When installed, these devices are not centered on the
electrical box. Make sure boxes are mounted to compensate for this difference. See Figure 7.
To install the speaker-strobe:
1. Open the cover by depressing the tab on the side of the unit with a small screwdriver. Hinge the cover down, to access the mounting screws and selectable candela and wattage switches. The cover is also detachable for installation convenience.
2. If temporal strobe (private mode) operation is desired, cut jumper JP1. See Figure 2.
3. Connect the speaker and strobe terminals to the signal circuit field wiring. For the unit to function properly, observe polarity. See Figure 4.
4. Slide the candela switch to the desired candela output (95, 115, 150, or 177 cd) by aligning it with the indicator below the switch. See Figure 1.
5. Slide the wattage switch to the desired wattage tap (2 W, 1 W, 1/2 W, or 1/4 W) by aligning it with the indicator below the switch. See Figure 1.
© 2013 UTC Fire & Security. All rights reserved. 1 / 4 P/N 3100615 • REV 05 • REB 30JAN13
6. Mount the unit onto a compatible electrical box. See Figure 5.
Page 2
7. Replace the cover by positioning the alignment arrows
1. Candela switch
2. Indicator
3. Wattage switch
1. JP1: Strobe signal output: Cut to change from 1 flash per second (public mode) to temporal (private mode)
1. Angle
Note: Horizontal and vertical outputs have the same pattern
1. From NAC output
2
3.
Note: Signal polarity is shown in the alarm condition.
100
959085
807570
656055
504540
3530252015
10
505
101520253035404550556065707580859095
100
0
5
10
15
20
25
30
35
40
45
50
55
60
65
70
75
80
85 90
-5
-10
-15
-20
-25
-30
-35
-40
-45
-50
-55
-60
-65
-70
-75
-80
-85
-90
1
2
together and rotating the cover clockwise.
8. Test the unit for proper operation.
Figure 1: Field-selectable switches
Figure 2: Strobe settings

Wiring

Figure 4: Wiring diagram
. To next NAC output
Amplifier output voltage matching the voltage ratings of the
speaker (25 or 70 VRMS)
Figure 5: Mounting diagram
Note: If the strobe is set to temporal (private mode), this
device is no longer UL 1971 or ULC-S526 Listed or FM Approved but is UL 1638 Listed.
Figure 3: UL 1971 minimum light output (% of rating vs. angle)
2. Percentage of rated output
2 / 4 P/N 3100615 • REV 05 • REB 30JAN13
Page 3
Table 3: Strobe operating current in RMS (A)
VDC
VFWR
VDC = Volts direct current, regulated and filtered VFWR = Volts full wave rectified
Operating currents shown above were measured by UL at 16 VDC and 16 VFWR.
1/4 W
1/2 W
1 W
2 W (UL)
2.2 W (ULC)
UL1480: Sound level output reverberant room using 400 to 4,000 Hz band limited pink noise.
Directional characteristics: Within 6 dB of on measured 90° off-axis (horizontal).
Operating voltage
Supervisory voltage
Strobe operating current
Sound level output
Speaker response
Light output
Default settings
Wire size
Compatible electrical boxes
Operating environment
Manufacturer Year of manufacture
UL/ULC rating
Environmental class
Synchronization
Agency
[1] Nameplate marking is located on the inside surface of the device.
95 cd 115 cd 150 cd 177 cd
0.330 0.392 0.502 0.565
0.432 0.518 0.643 0.693
Table 4: Sound level output (dBA)
25V (UL) 25V (ULC) 70V (UL) 70V (ULC)
80 78 80 81 84 81 84 81
87 87 87 87
90 91
90 90
at 10 ft (3.05 m) measured in a
-axis sound level when
Figure 6: Light output profile
Perform a visual inspection and an operational test twice a year or as directed by the local authority having jurisdiction.
Do no change the factory-applied finish.

Specifications

Speaker Strobe
Selectable at 95, 115, 150, and 177 cd
1 flash per second (fps)
12 to 18 AWG (0.75 TO 2.50 mm²)
Temperature Relative humidity
25 VRMS (model S2) or 70 VRMS (model S7) 24 VDC, 24 VFWR
30 V maximum
See Table 3
See Table 4
400 to 4,000 Hz
North American 4 in. square electrical box, 2-1/8 in. min. deep
32 to 120°F (0 to 49°C) 0 to 93% noncondensing

Regulatory information

Edwards, A Division of UTC Fire & Security Americas Corporation, Inc. 8985 Town Center Parkway, Bradenton, FL 34202, USA
listings UL 1480. UL 1638 and UL 1971
The first two digits of the DATE MFG number (located on the product identification label) are the year of manufacture
Regulated 24 DC, regulated 24 FWR
This device was tested to the regulated 24 DC/FWR operating voltage limits of 16 V and 33 V. Do not apply 80% and 110% of these values for system operation.
UL: Indoor dry
Meets UL 1971 requirements. Maximum allowed resistance between any two devices is 20 Ω. Refer to specifications for the synchronization control module, this strobe, and the control panel to determine allowed wire resistance.
CAN/, ULC-S541, ULC S526 BS EN 60065:2002 [1]

Maintenance

This unit is not serviceable or repairable. Should the unit fail to operate, contact the supplier for replacement.
P/N 3100615 • REV 05 • REB 30JAN13 3 / 4

Contact information

For contact information, see www.edwardsutcfs.com.
Page 4
Figure 7: Mounting template
1. Center of ceiling tile or speaker/strobe
2.
3. Electrical box
4. Speaker
Cut line for location of electrical box

Mounting template

To center the speaker-strobe:
1. Position the template to the center of the ceiling tile.
2. Orient the strobe to the desired visual position.
9. Mark the location for the electrical box.
5. Strobe
4 / 4 P/N 3100615 • REV 05 • REB 30JAN13