Edwards Signaling Genesis High Candela Ceiling Horn-Strobe User Manual

Page 1

Description

Horn 95 to 177 multi white
Horn 95 to 177 multi white, with FIRE marking
Model name
Auto
Genesis Signal Master Remote Mount
1.
1
7
7
1
5
0
9
5
11
5
1
2
Genesis High Candela Ceiling Horn-Strobe Installation Sheet
Description
The Genesis High Candela Ceiling Horn-Strobe is a fire alarm notification appliance designed for indoor ceilings and walls. See Table 1 for a list of model numbers.
Number
-strobe,
-cd,
-strobe,
-cd,
Field configurable jumper options are available for selecting the desired dB output, temporal or steady horn output, and strobe signal output.
The horn-strobe includes a field configurable switch for selecting the desired candela output. The candela output setting is locked in place and remains visible after final installation.
This strobe features an enhanced synchronization circuit to comply with the latest requirements of UL 1971 Signaling Devices for the Hearing Impaired and the latest Canadian standard CAN/ULC-S526. Synchronized operation requires a separately installed synchronization control module. See Table 2 for a list of compatible synchronization modules.
Install this device in accordance with applicable requirements in the latest editions of the NFPA codes and standards and Canadian Electrical Code, Part 1, Section 32 and CAN/ULC­S524, Standard for the Installation of Fire Alarm Systems, and in accordance with the local authorities having jurisdiction.
ADTGC-HDVMH MGC-HDVMH EGC-HDVMH XLSGC-HDVMH GC-HDVMH ZGC-HDVMH
ADTGCF-HDVMH MGCF-HDVMH EGCF-HDVMH XLSGCF-HDVMH GCF-HDVMH ZGCF-HDVMH

Installation

WARNING: To reduce the risk of shock, disconnect all power
and allow 10 minutes for stored energy to dissipate before handling.
Caution: Electrical supervision requires the wire run to be
broken at each terminal. Do not loop the signaling circuit field wires around the terminals.
To install the horn-strobe:
1. Remove the cover by depressing the tab on the side of the unit with a small screwdriver. Turn the cover counterclockwise to release.
2. Set the horn signal, sound output level, and strobe signal to the desired settings. See Figure 2.
3. Connect the strobe terminals to the signal circuit field wiring. You must observe polarity for the unit to function properly. See Figure 4.
4. Slide the candela switch to the desired candela output (95, 115, 150, or 177 cd) by aligning it with the indicator below the switch. See Figure 1.
5. Mount the unit onto a compatible electrical box. See Figure 5.
6. Replace the cover by positioning the alignment arrows together and rotating the cover clockwise.
7. Test the unit for proper operation.
Figure 1: Candela switch
Table 2: Compatible synchronization module models
-Sync Output Module
© 2013 UTC Fire & Security. All rights reserved. 1 / 4 P/N 3100617 • REV 04 • REB 30JAN13
Number
SIGA-CC1S SIGA-MCC1S GSA-CC1S GSA-MCC1S
-
ADTG1M-RM MG1M-RM EG1M-RM XLSG1M-RM G1M-RM ZG1M-RM
Candela switch 2. Indicator
Page 2
Figure 2: Horn and strobe settings
1.
2.
3. JP3: Horn sound output: Cut to change from high dB to low dB
1. Angle
Note: Horizontal and vertical outputs have the same pattern
1. From NAC output 2 Note: Signal polarity is shown in the alarm condition.
VDC
VFWR
VDC = Volts direct current, regulated and filtered VFWR = Volts full wave rectified
Operating currents shown above were measured by UL at 16 VDC and 16 VFWR.
JP3
JP1 JP2
1
2
3
100
95
90
858075
706560
555045
40
353025
201510
5
0
5
101520
25
303540
455055
606570
75
808590
95
100
0
5
10
15
20
25
30
35
40
45
50
55
60
65
70
75
80
85 90
-5
-10
-15
-20
-25
-30
-35
-40
-45
-50
-55
-60
-65
-70
-75
-80
-85
-90
1
2
1 2
-
+
JP1: Horn signal jumper: Cut to change from temporal to steady JP2: Strobe signal output: Cut to change from 1 flash per second
(public mode) to temporal (private mode)
Note: If the strobe is set to temporal (private mode), this
device is no longer UL 1971 or ULC-S526 Listed or FM Approved but is UL 1638 Listed.
Figure 5: Mounting diagram
Figure 3: UL 1971 minimum light output (% of rating vs. angle)
2. Percentage of rated output

Wiring

Figure 4: Wiring diagram
Table 3: Strobe operating current in RMS (A)
95 cd 115 cd 150 cd 177 cd
0.341 0.406 0.506 0.570
0.487 0.578 0.670 0.730
. To next device
2 / 4 P/N 3100617 • REV 04 • REB 30JAN13
Page 3
Table 4: Sound level output (dBA)
Signal
Temporal
Steady
UL464: Sound level output reverberant room.
Signal
Temporal
Steady
ULC
chamber at 10 ft.
(3.05 m).
Angle (°) [1]
90 (Ref)
75 and 115
70 and 120
[1] Angles are measured from a perpendicular axis; the right.
[2] Peak output at regulated 24 VDC, set for temporal tone.
Angle (°) [1]
90 (Ref)
65 and 135
55
[1] Angles are measured from a perpendicular axis; positive angles are up.
[2] Peak output at 24 regulated VDC, set for temporal tone.
0
50
100
150
200
250
0
5
10
15
20
25
30
35
40
45
50
55
60
65
70
75
80
85
90
95
100
105
110
115
120
125
130
135
140
145
150
155
160
165
170
175
180
185
190
195
200
205
210
215
220
225
230
235
240
245
250
255
260
265
270
275
280
285
290
295
300
305
310
315
320
325
330
335
340
345
350
355
VDC High db Low db
16 79.8 75.0
24 83.3 78.0 33 85.0 80.9
16 83.2 79.3
24 85.4 83.0 33 87.8 85.9
at 10 ft. (3.05 m) measured in a
Table 5: Minimum sound level output per ULC-S525 (dBA, peak)
Voltage High db Low db
Reg. 24 VDC 91 89
Reg. 24 VFWR 96 93
Reg. 24 VDC 93 89
Reg. 24 VFWR 96 93
-S525: Meets or exceeds 85 dBA in an anechoic
Table 6: Audible directional characteristics (horizontal pattern)
Sound output (dBA) [2]
0 (Ref)
3
6 positive angles to
Figure 6: Light output profile

Maintenance

Do no change the factory-applied finish.
Table 7: Audible directional characteristics (vertical pattern)
Sound output (dBA) [2]
0 (Ref)
3
and 140 6
P/N 3100617 • REV 04 • REB 30JAN13 3 / 4
Page 4

Specifications

Voltage
Strobe operating current
Light output
Sound level output
Default settings
output
Wire size
Compatible electrical boxes
Operating environment
Manufacturer Year of manufacture
UL/ULC rating
Environmental class
Synchronization
Agency listings
16 to 33 VDC and 16 to 33 VFWR
See Table 3
Selectable at 95, 115, 150, and 177 cd
See Table 4
Signal Sound level
Strobe signal output
12 to 18 AWG (0.75 TO 2.50 mm²)
Temperature Relative humidity
Temporal High dB 1 flash per second (fps)
North American 4 in. square electrical box, 2-1/8 in. deep (no extension ring)
32 to 120°F (0 to 49°C) 0 to 93% noncondensing

Regulatory information

Edwards, A Division of UTC Fire & Security Americas Corporation, Inc. 8985 Town Center Parkway, Bradenton, FL 34202, USA
The first two digits of the DATE MFG number (located on the product identification label) are the year of manufacture
Regulated 24 DC, regulated 24 FWR
This device was tested to the regulated 24 DC/FWR operating voltage limits of 16 V and 33 V. Do not apply 80% and 110% of these values for system operation.
UL: Indoor
Meets UL 1971 requirements. Maximum allowed resistance between any two devices is 20 Ω. Refer to specifications for the synchronization control module, this strobe, and the control panel to determine allowed wire resistance.
Meets ULC-S525. ULC-S526 UL 464, UL 1638, and UL 1971

Contact information

For contact information, see www.edwardsutcfs.com.
4 / 4 P/N 3100617 • REV 04 • REB 30JAN13