Edwards Signaling Genesis Chime User Manual

Genesis Chime
Product information
The Genesis Chime is an audible fire alarm notification appliance designed for indoor walls. See Table 1 for a list of model numbers.
The chime includes field configurable jumper options for selecting the desired dB output, steady or temporal chime output, and constant non-coded voltage or single-stroke coded voltage operation. A Genesis Signal Master is required when chimes are configured for coded operation. See Table 2 for a list of compatible synchronization modules.
Install this device in accordance with applicable requirements in the latest editions of the NFPA codes and standards and in accordance with the local authorities having jurisdiction.
Table 1: Model numbers
Model description Model numbers
Chime, white
Chime, white, with FIRE marking
Chime, red
Chime, red, with FIRE marking
Trim plate, white
ADTG1-C MG1-C EG1-C XLSG1-C G1-C ZG1-C G1-C-LG
ADTG1F-C MG1F-C EG1F-C XLSG1F-C G1F-C ZG1F-C G1F-C-LG
ADTG1R-C MG1R-C EG1R-C XLSG1R-C G1R-C ZG1R-C G1R-C-LG
ADTG1RF-C MG1RF-C EG1RF-C XLSG1RF-C G1RF-C ZG1RF-C G1RF-C-LG
ADTG1T MG1T EG1T XLSG1T G1T ZG1T G1T-LG
Table 1: Model numbers
Model description Model numbers
Trim plate, red
Table 2: Compatible synchronization modules
Model names Model numbers
Auto-Sync Output Module
Signal Master snap-on piggyback (1-gang)
Signal Master - Remote Mount
Note: Synchronization module requirements are determined by your application
ADTG1RT MG1RT EG1RT XLSG1RT G1RT ZG1RT G1RT-LG
SIGA-CC1S SIGA-MCC1S SIGA-CC1S-LG SIGA-MCC1S-LG
ADTG1M MG1M EG1M XLSG1M G1M ZG1M G1M-LG
ADTG1M-RM MG1M-RM EG1M-RM XLSG1M-RM G1M-RM ZG1M-RM G1M-RM-LG
Specifications
Operating voltage
Regulated 16 to 33 Vdc, 16 to 33 Vfwr This device was tested to the regulated 24 Vdc/fwr operating voltage limits of 16 V and 33 V. Do not apply
80% and 110% of these values for system operation. Operating current: See Table 2 Sound level output: See Table 3 Signals
Steady: 60 strokes per minute
Temporal: 3-stroke pattern
Coded: Maximum 60 strokes per minute Operating modes
Non-coded: Continuous voltage
Coded: Single-stroke controlled by voltage Default settings
Signal: Steady
Sound level output: High db
Operation: Non-coded Wire size: 12 to 18 AWG (2.50 to 0.75 sq mm) Compatible electrical boxes
North American 2-1/2 in (64 mm) deep 1-gang box
Standard 4 in square box 1-1/2 in (38 mm), 2-gang, or 4 in
octagonal with G1T or G1RT trim accessory Operating temperature range: 32 to 120 °F (0 to 49 °C) Operating humidity range: 0 to 93% RH Agency listings: Meets or exceeds UL464 Seventh Edition for
private mode
Installation Sheet 27MAY03 P/N: 3100561 REV: 1.0 Genesis Chime 1 / 2
Table 2: Operating current in (Amp RMS)
High db Low db
16 Vdc 0.030 0.019
24 Vdc 0.043 0.026
33 Vdc 0.045 0.027
16 Vfwr 0.060 0.040
24 Vfwr 0.076 0.049
33 Vfwr 0.081 0.055
Vdc = Volts direct current, regulated and filtered Vfwr = Volts full wave rectified.
Table 3: Sound level output (dBA)
Signal and voltage High db Low db
Temporal
Steady
dBA = Decibels, A-weighted
UL464: Sound level output at 10 ft (3.05 m) measured in a reverberant room.
16 Vdc 56.9 52.5
24 Vdc
33 Vdc
16 Vdc
24 Vdc
33 Vdc
59.8
60.1
58.2
60.8
61.3
54.8
55.0
52.8
55.6
56.1
Perform a visual inspection and an operational test twice a year or as directed by the local authority having jurisdiction.
To change the chime from steady to temporal cut from circle J1 to edge of circuit board
Figure 1: Chime settings
From compatible fire alarm control panel
­+
Installation instructions
signal
To change the chime
output level
from high dB to
sound
low dB cut J3 trace between holes
J1
J2
J3
To change the chime
operation
from non-coded to coded (single­stroke)
cut from circle J2 to edge
of circuit board
To next device or end of line device
-
+
+
-
+
-
Caution: Electrical supervision requires the wire run to be broken at each terminal. Do not loop the signaling circuit field wires around the terminals.
To install the chime:
1. Remove the cover by depressing both tabs on the top of the unit with a small screwdriver and twisting slightly.
2. Set the chime signal, sound output level, and desired operation settings. See Figure 1.
3. Connect the chime terminals to the signal circuit field wiring. You must observe polarity for the unit to function properly.
For constant non-coded voltage operation, see Figure 2.
For single-stroke coded voltage operation, see Figure 3.
4. Mount the unit onto a compatible electrical box, making sure not to over tighten the mounting screws.
5. Replace the cover by aligning at the bottom, then snapping in at the top.
6. Test the unit for proper operation.
Maintenance
This unit is not serviceable or repairable. Should the unit fail to operate, contact the supplier for replacement.
Note: Polarity shown in alarm condition
Figure 2: Constant non-coded voltage operation
Genesis device with Genesis Signal Master
+
-
HS
[1]
Continuous power source
Coded power source
Figure 3: Single-stroke coded voltage operation
+
-
+
-
To next device or end of line device
+
-
-
+
2 / 2 27MAY03 P/N: 3100561 REV: 1.0