Genesis Ceiling Strobe
Product information
The Genesis Ceiling Strobe is a visible fire alarm notification
appliance designed for indoor ceilings and walls. See Table 1
for a list of model numbers.
The strobe includes a field configurable switch for selecting the
desired candela output. The candela output setting is locked in
place and remains visible after final installation.
This strobe features an enhanced synchronization circuit to
comply with the latest requirements of UL 1971 Signaling
Devices for the Hearing Impaired and the latest Canadian
standard CAN/ULC S526-02. Synchronized operation requires
a separately installed synchronization control module. See
Table 2 for a list of compatible synchronization modules.
Install this device in accordance with applicable requirements
in the latest editions of the NFPA codes and standards and
Canadian Electrical Code, Part 1, Section 32, CAN/ULC S52401, Standard for the Installation of Fire Alarm Systems, and in
accordance with the local authorities having jurisdiction.
Table 1: Models
Description Number
Strobe,
15 to 95 multi-cd, white
Strobe,
15 to 95 multi-cd, white,
with FIRE marking
Strobe,
15 to 95 multi-cd, red,
with FIRE marking
Table 2: Compatible synchronization modules
Description Model number
Auto-Sync Output
Module
Genesis Signal Master Remote Mount
ADTGC-VM MGC-VM
EGC-VM XLSGC-VM
GC-VM ZGC-VM
GC-VM-LG
ADTGCF-VM MGCF-VM
EGCF-VM XLSGCF-VM
GCF-VM ZGCF-VM
GCF-VM-LG
EGCFR-VM
GCFR-VM
MGCFR-VM
SIGA-CC1S SIGA-MCC1S
SIGA-CC1S-LG SIGA-MCC1S-LG
ADTG1M-RM MG1M-RM
EG1M-RM XLSG1M-RM
G1M-RM ZG1M-RM
G1M-RM-LG
Specifications
Operating voltage
Regulated 16 to 33 Vdc, 16 to 33 Vfwr
This device was tested to the Regulated 24 Vdc/fwr
operating voltage limits of 16 V and 33 V. Do not apply
80% and 110% of these values for system operation.
Strobe operating current: See Table 3
Light output: Selectable at 15, 30, 75, and 95 cd
Synchronization: Meets UL 1971 requirements. Maximum
allowed resistance between any two devices is 20 Ω.
Refer to specifications for the synchronization control
module, this strobe, and the control panel to determine
allowed wire resistance.
Wire size: 12 to 18 AWG (2.50 to 0.75 sq mm)
Compatible electrical boxes
North American 4 in square electrical box, 2-1/8 in deep
(no extension ring)
Operating environment
Temperature: 32 to 120 °F (0 to 49 °C)
Humidity: 0 to 93% RH, noncondensing at 90 °F (32 °C)
Agency listings: Meets year 2004 UL requirements for
standards UL1638 and UL1971 (see Figure 1) and
Canadian requirements for standards CAN/ULC S526-02
and CAN/ULC S524-01
Table 3: Strobe operating current in RMS (A)
15 cd 30 cd 75 cd 95 cd
Vdc 0.109 0.151 0.281 0.318
Vfwr 0.131 0.194 0.379 0.437
Vdc = Volts direct current, regulated and filtered
Vfwr = Volts full wave rectified
Operating currents shown above were measured by UL at 16
Vdc and 16 Vfwr.
Angle
0
5
-5
-10
-15
-20
-25
-30
-35
-40
-45
-50
-55
-60
-65
-70
-75
-80
-85
-90
9590858075706560555045403530252015
100
Horizontal and vertical outputs reflect the same pattern.
Percentage of rated output
Figure 1: UL 1971 minimum light output (% of rating vs. angle)
10
15
20
25
30
505
10
1015202530354045505560657075808590
35
40
45
50
55
60
65
70
75
80
85
90
95
100
Installation Sheet 29APR05 P/N: 3100612 REV: 3.0
Genesis Ceiling Strobe 1 / 2
Installation Instructions
Warning: To reduce the risk of shock, disconnect all power
and allow 10 minutes for stored energy to dissipate before
handling.
Caution: Electrical supervision requires the wire run to be
broken at each terminal. Do not loop the signaling circuit field
wires around the terminals.
To install the strobe:
To listed
fire alarm
control
panel
S+S+S-
Figure 3: Wiring diagram
S-
++
To next
device or
end of line
device
1. Remove the cover by depressing the tab on the side of the
unit with a small screwdriver. Turn the cover
counterclockwise to release.
2. If temporal strobe (private mode) operation is desired, cut
jumper JP1. See Figure 2.
3. Connect the strobe terminals to the signal circuit field
wiring. You must observe polarity for the unit to function
properly. See Figure 3.
4. Slide the candela switch to the desired candela output (15,
30, 75, or 95 cd) by aligning it with the indicator below the
switch. See Figure 4.
5. Mount the unit onto a compatible electrical box. See
Figure 5.
6. Replace the cover by positioning the alignment arrows
together and rotating the cover clockwise.
7. Test the unit for proper operation.
To change the from 1 fps (public
mode) to temporal (private mode) cut jumper JP1
strobe signal output
JP1
Figure 4: Candela switch
Candela switch
5
9
5
7
0
3
5
1
Indicator
Figure 2: Strobe setting
Note: If the strobe is set to temporal (private mode), this
device is no longer UL 1971 listed and FM Approved but is UL
Figure 5: Mounting diagram
1638 listed.
Maintenance
This unit is not serviceable or repairable. Should the unit fail to
operate, contact the supplier for replacement.
Perform a visual inspection and an operational test twice a
year or as directed by the local authority having jurisdiction.
P/N: 3100612 REV: 3.0 29APR05 Installation Sheet
2 / 2 Genesis Ceiling Strobe