Edwards Signaling Genesis Ceiling Horn-Strobe User Manual

Table
1.
Genesis Ceiling Horn-Strobe Ins tallati on Sheet
Description
The Genesis Ceiling Horn-Strobe is a fire alarm notification appliance designed for indoor ceilings and walls. See Table 1 for a list of model numbers.
Table 1: Models
Number
-strobe,
-cd, white
-strobe,
-cd, white, with
-strobe,
-cd, red, with
Field configurable jumper options are available for selecting the desired dB output, temporal or steady horn output, and strobe signal output.
The horn-strobe includes a field configurable switch for selecting the desired candela output. The candela output setting is locked in place and remains visible after final installation.
This strobe features an enhanced synchronization cir cuit to comply with the latest requirements of UL 1971 Signaling Devices for the Hearing Impaired and the latest Canadian standard CAN/ULC-S526. Synchronized operation requires a separately installed synchronization control module. See Table 2 for a list of compatible synchr o niz ati on modu les .
Install this device in accordance with applicable requirements in the latest editions of the NFPA codes and standards and Canadian Electrical Code, Part 1, Section 32 and CAN/ULC­S524, Standard for the Installation of Fire Alarm Systems, and in accordance with the local authorities having jurisdiction.
ADTGC-HDVM MGC-HDVM EGC-HDVM XLSGC-HDVM GC-HDVM ZGC-HDVM
ADTGCF-HDVM MGCF-HDVM EGCF-HDVM XLSGCF-HDVM GCF-HDVM ZGCF-HDVM
EGCFR-HDVM GCFR-HDVM MGCFR-HDVM

Installation

WARNING: To reduce the risk of shock, disconnect all power
and allow 10 minutes for stored energy to dissipate before handling.
Caution: Electrical supervision requires the wire run to be
broken at each terminal. Do not loop the signaling circuit field wires around the terminals.
To install the horn-strobe:
1. Remove the cover by depressing the tab on the side of the unit with a small screwdriver. Turn the cover counterclockwise to release.
2. Set the horn signal, sound output level, and strobe signal to the desired settings. See Figure 2.
3. Connect the strobe terminals to the signal circuit field wiring. You must observe polarity for the unit to function properly. See Figure 4.
4. Slide the candela switch to the desired candela output (95, 115, 150, or 177 cd) by aligning it with the indicator below the switch. See Figure 1.
5. Mount the unit onto a compatible electrical box. See Figure 5.
6. Replace the cover by positioning the alignment arrows together and rotating the cover clockwise.
7. Test the unit for proper oper ati on.
Figure 1: Candela switch
-sync output module
© 2013 UTC Fire & Security. All rights reserved. 1 / 4 P/N 3100616 • REV 05 • REB 30JAN13
2: Compatible synchronization module models
Number
SIGA-CC1S SIGA-MCC1S GSA-CC1S GSA-MCC1S
-
ADTG1M-RM MG1M-RM EG1M-RM XLSG1M-RM G1M-RM ZG1M-RM
Candela switch 2. Indicator
Figure 2: Horn and strobe settings
1. JP1: Horn signal jumper: Cut to change from temporal to steady
2.
3. JP 3: Horn sound output: Cut to change from high dB to low dB
1. Angle
Note: Horizontal and vertical outputs have the same pattern
1. From NAC output 2 Note: Signal polarity is shown in the alarm condition.
VDC
VFWR
VDC = Volts direct current, regulated and filtered VFWR = Volts full wave rectified
Operating currents shown above were measured by UL at 16 VDC and 16 VFWR.
100
95
90
85
80
75
70
65
60
55
50
45
40
35
30
25
20
15
10
505
10
15
20
25
3
0
3
5
4
0
4
5
50
55
60
65
70
75
80
85
90
9
5
100
0
5
10
15
20
25
30
35
40
45
50
55
60
65
70
75
80
85 90
-5
-10
-15
-20
-25
-30
-35
-40
-45
-50
-55
-60
-65
-70
-75
-80
-85
-90
1
2
1 2
-
+

Wiring

Figure 4: Wiring Diagram
JP2: Strobe signal output: Cut to change from 1 flash per second
(public mode) to temporal (private mode)
Note: If the strobe is set to temporal (private mode), this device is no longer UL 1971 or ULC-S526 Listed or FM Approved but is UL 1638 Listed.
Figure 3: UL 1971 minimum light output (% of rating vs. angle)
. To next NAC output
Figure 5: Mounting diagram
2. Perc ent age of rated output
2 / 4 P/N 3100616 • REV 05 • REB 30JAN13
Table 3: Strobe operating current in RMS (A)
15 cd 30 cd 75 cd 95 cd
0.147 0.190 0.316 0.372
0.189 0.253 0.417 0.451