Edwards Signaling FSRSI User Manual

FSRSI Remote System Indicator Installation Sheet
Installation
Install the FSRSI according to the instructions provided below.
Caution: Make sure all power is disconnected from the panel
before installing. Observe static-sensitive handling practices.
For more information, see the technical reference manual listed inside the control panel door.
To install the FSRSI:
1. Configure the jumpers as described in Table 1.
Description
The FSRSI is a remote system indicator for F-series fire alarm control panels. The FSRSI provides five LEDs and a buzzer to indicate AC power status, alarm events, supervisory events, trouble events, and ground fault events. The FSRSI also provides a local silence button to turn the buzzer off without affecting the LED indicators.
FSRSI remote system indicators include a cover plate for installation in a standard, single-gang electrical box. You can also install the FSRSI with one or two remote zone indicators in an approved 2-, 3-, or 4-gang electrical box. Cover plates for 2-, 3-, or 4-gang electrical boxes (model numbers FSAT2, FSAT3, or FSAT4) are ordered separately.
FSRSI remote system indicators are configured using the jumper described in the table below.
Table 1: Group selection jumper
J2 Description
ON Selects peripheral group 1
OFF Selects peripheral group 2
Note: Only one FSRSI is allowed per peripheral group.
2. Verify that all field wiring is free of opens, shorts, and ground faults.
3. Wire the FSRSI as shown Figure 1.
4. Mount the FSRSI in the electrical box using the two plain machine screws. Figure 2.
Note: If you are surface mounting the FSRSI, you must install
washers (provided) between it and the surface mount box.
5. Attach the faceplate to the FSRSI. Use the two white machine screws provided with the faceplate.
Note: FSRSI remote system indicators will not operate
properly until detected by the control panel. For more information, see the technical reference manual listed inside the control panel door.
Figure 1: FSRSI wiring diagram
From
control panel
Regulated 24 VDC from control panel or external power supply [2] [3]
C
C
C C
J2
ON: Group 1 OFF: Group 2
next remote
To
module
© 2013 UTC Fire & Security. All rights reserved. 1 / 2 P/N 3101034 • REV 02 • REB 25JAN13
Notes
1. All wiring is supervised and power-limited
[2] AUX power supplied by the control panel can’t exceed 0.5
A. If more than 0.5 A is required, you must use a power­limited and regulated 24 VDC auxiliary/booster power supply that is UL/ULC Listed for fire protective signaling systems.
[3] If powered from an external supply, the supply must be
installed in the same room as the control panel and their 24 VDC commons () wired together
Figure 2: Installing the FSRSI in a single-gang electrical box
Compatible 1-gang electrical box
FSRSI
Specifications
Voltage 18.8 to 27.3 VDC
Current Standby Alarm
Circuit capacitance 0.03 µF, max.
Circuit resistance 13 ohms, max.
Ground fault impedance 0
Wire size 12 to 18 AWG (0.75 to 2.5 sq mm)
Compatible electrical box ANSI/NEMA OS1-1996, 1- to 4-gang
LED indicators AC power (green), alarm (red),
Buzzer operation Steady (trouble event), temporal (alarm
Operating environment Temperature Relative Humidity
17 mA at 24 VDC 56 mA at 24 VDC
electrical box
supervisory (yellow), trouble (yellow), ground fault (yellow)
event), slow pulse (supervisory event), intermittent (AC fail event)
32 to 120°F (0 to 49°C) 0 to 93% RH, noncondensing
FSAT1
2 / 2 P/N 3101034 • REV 02 • REB 25JAN13
Loading...