FIRE ALARM EQUIPMENT
®®
®
Edwards
®®
Strobe Application Data
Description
The National Fire Protection Association (NFPA) has estab lished guidelines for the installation of visual signaling appliances for rooms, corridors, and sleeping areas. These
guidelines, referenced in NFP A 72,
take into consideration the effective
intensity of the strobe light, the size of
the space, and whether the appliance
is installed on the wall or ceiling.
Edwards synchronous, fire alarm
strobes are listed to UL Standard
1971 and conform to the ADA (Americans with Disabilities Act) equivalent
facilitation when installed using these
guidelines. Consult the Authority
Having Jurisdiction.
Space Allocation for Rooms
Table 1 provides the candela r ating
required for strobes when installed
on walls in rooms of varying size.
When ceiling mounted, the number of
strobes may be reduced while continuing to provide equivalent facilitation. Table 2 lists room, ceiling height,
and appropriate light intensity for the
given space.
Space Allocation for Corridors
Strobes mounted in corridors not
greater than 20 feet (6.1m) wide shall
be located no more than 15 feet
(4.6m) from the end of the corridor
with a separation no greater than 100
feet (30.5m) between appliances.
They shall be wall mounted in accordance with Table 3.
Space Allocation for Sleeping Rooms
Wall mounted strobes with the top of
the strobe greater than 24 inches
(61cm) from the ceiling shall be rated
110 cd. Strobes closer to the ceiling
than 24 inches (61cm) shall be rated
177 cd. The distance from the strobe
to the pillow must not exceed 16 feet.
D-04
Table 1
Minimum Required Light Output, Candela (CD)
Max. Room One Light Per (On Opposite (One per Wall)
Size Room (CD) Walls) (CD) (CD)
20' x 20' 1
30' x 30' 30 15 —
40' x 40' 60 30 15
50' x 50' 95 60 30
60' x 60' 13 5 95 30
70' x 70' 18 5 11 0 60
80' x 80' — 14 0 60
Note: The bottom of the wall mounted appliance should be not less than 80 inches
(203cm) or more than 96 inches (244cm) from the floor.
5 — —
Effective Intensity
Two Per Room Four Per Room
Table 2
Minimum Required Light Output, Candela (CD)
Max. Room Maximum Ceiling
Size Height (ft.)
20' x 20' 1
30' x 30' 10 30
40' x 40' 10 60
50' x 50' 10 95
20' x 20' 20 30
30' x 30' 20 45
40' x 40' 20 80
50' x 50' 20 11 5
20' x 20' 30 55
30' x 30' 30 75
Note: Where ceiling heights exceed 30 ft. (91.4m), visible signaling appliances
should be suspended at or below 30 ft. (91.4m) or wall mounted.
Note: The above table is based on locating the visible signaling appliance at the
center of the room. Where it is not located at the center of the room, the
effective intensity (cd) should be determined by doubling the distance from the
appliance to the farthest wall to obtain the max. room size.
Effective Intensity
One Light (CD)
0 15
Table 3
Corridor Length (ft.) Appliances Required
0-30 1
31-130
131-230 3
231-330 4
331-430 5
431-530 6
Min. Number of 15 cd Visible
2
12-50
© Copyright 2004 Edwards