Edwards Signaling FIRE ALARM EQUIPMENT Design Guide

FIRE ALARM EQUIPMENT
System Design Criteria
Initiating Devices
When 2-wire ionization and/or photoelectric smoke detec­tors are incorporated into an alarm system, you must en­sure that the detector standby current (of any combination of detectors), does not exceed the allowable total standby detector current per zone of 1500 microamps. Normally­open devices, such as manual fire stations, automatic heat detectors and waterflow switches require no standby current, and therefore can be installed in any quantity required.
Current Alarm
Cat. No.* Detector Type Standby Req. Current
SC10U Ionization 50 microamps 100mA SC30U Photoelectric 62 microamps 100mA
*2-wire application
Operation of a manual station, automatic heat detector or waterflow switch on the same zone as smoke detectors will prevent the operation of smoke detectors on that zone.
To determine the maximum n umber of Edwards smoke detectors that can be connected to each alarm initiating circuit, total the smoke detector standby current require­ments of all detectors . The following table and example may be utilized as a reference:
Example:
Qty. Detector Type Microamps
20 SC10U Ion Detectors 20 x 50 = 1000 18 SC30U Photo Detectors 18 x 62 = 1116
Total microamps = 2116
Signaling Appliances
When any combination of Edwards signaling appliances (horns, strobes, horn/strobes, bells) is used, the total sig­naling current requirements for the panel must not ex­ceed as follows:
NAC/Pwr Aux Pwr
Cat. No. Description Outputs Output
E-FS101* FireShield 1 zone 1.0A 0.5A
E-FS302* FireShield 3 zone 1.5A 0.5A
E-FS502* FireShield 5 zone 2.5A 0.5A
E-FS1004* FireShield 10 zone 2.5A** 0.5A
EBPS6 6.5A Booster Panel 6.5A Tot. 2; 3 A
EBPS10 10A Booster Panel 10.0A Tot. 2; 3 A
*Add "G" for gray cabinet or "R" for red cabinet
**Expandable to 5.0A with Cat. No. XTR3A-120 Transformer
To determine the maximum number of signaling appli­ances that can be connected to the signaling circuit, total the signaling appliance alarm current requirements of all signaling appliances. See the below examples and appli­cable catalog pages as a reference:
Qty Cat. No. Type mA Total Current
3 2447TH Horn 20 3 x 20 = 60 mA 4 2452THS-15/75-R Horn/Strobe 225 4 x 225 = 900 mA
Total Signaling Current 960 mA
© Copyright 2004 Edwards
D-04
12-51
Loading...