FIRE ALARM EQUIPMENT
System Design Criteria
Initiating Devices
When 2-wire ionization and/or photoelectric smoke detectors are incorporated into an alarm system, you must ensure that the detector standby current (of any combination
of detectors), does not exceed the allowable total standby
detector current per zone of 1500 microamps. Normallyopen devices, such as manual fire stations, automatic
heat detectors and waterflow switches require no standby
current, and therefore can be installed in any quantity
required.
Current Alarm
Cat. No.* Detector Type Standby Req. Current
SC10U Ionization 50 microamps 100mA
SC30U Photoelectric 62 microamps 100mA
*2-wire application
Operation of a manual station, automatic heat detector or
waterflow switch on the same zone as smoke detectors
will prevent the operation of smoke detectors on that
zone.
To determine the maximum n umber of Edwards smoke
detectors that can be connected to each alarm initiating
circuit, total the smoke detector standby current requirements of all detectors . The following table and example
may be utilized as a reference:
Example:
Qty. Detector Type Microamps
20 SC10U Ion Detectors 20 x 50 = 1000
18 SC30U Photo Detectors 18 x 62 = 1116
Total microamps = 2116
Signaling Appliances
When any combination of Edwards signaling appliances
(horns, strobes, horn/strobes, bells) is used, the total signaling current requirements for the panel must not exceed as follows:
NAC/Pwr Aux Pwr
Cat. No. Description Outputs Output
E-FS101* FireShield 1 zone 1.0A 0.5A
E-FS302* FireShield 3 zone 1.5A 0.5A
E-FS502* FireShield 5 zone 2.5A 0.5A
E-FS1004* FireShield 10 zone 2.5A** 0.5A
EBPS6 6.5A Booster Panel 6.5A Tot. 2; 3 A
EBPS10 10A Booster Panel 10.0A Tot. 2; 3 A
*Add "G" for gray cabinet or "R" for red cabinet
**Expandable to 5.0A with Cat. No. XTR3A-120 Transformer
To determine the maximum number of signaling appliances that can be connected to the signaling circuit, total
the signaling appliance alarm current requirements of all
signaling appliances. See the below examples and applicable catalog pages as a reference:
Qty Cat. No. Type mA Total Current
3 2447TH Horn 20 3 x 20 = 60 mA
4 2452THS-15/75-R Horn/Strobe 225 4 x 225 = 900 mA
Total Signaling Current 960 mA
© Copyright 2004 Edwards
D-04
12-51