F-DACT(F) Digital Alarm Communicator Transmitter Installation Sheet
Description
The F-DACT(F) is a digital alarm communicator transmitter for F-series fire alarm control panels. The F-DACT(F), also called a dialer, transmits system status changes (events) to a compatible digital alarm communicator receiver over the public switched telephone network. The dialer is capable of split reporting to two different account and telephone numbers.
In addition to dialer functions, the F-DACT(F) provides:
An LCD to display event messages and programming prompts
An event history log of panel and DACT events
A modem for uploading and downloading panel configuration, history, and current status to a PC running compatible software
Note: The F-DACT(F) modem is only rated for 2400 baud
communication. Some PC modems may not be compatible with this baud rate.
The F-DACT(F) can be programmed to operate as a single or dual line DACT/Modem/LCD display, a Modem/LCD display, or an LCD display only. For the F-DACT(F) to be NFPA 72 CS compliant, the following are required:
The factory installed warning label must be removed from the F-DACT(F)’s line two phone jack
A second phone line, independent of that used for line one must be connected to phone jack two
The F-DACT(F) must be programmed for dual line operation
The F-DACT(F) must be programmed to transmit a test signal at least once every 24 hours
Leaving the JP1 wire loop intact configures the F-DACT(F) for attended downloading. The panel will not allow changes to the panel or dialer configuration unless the program jumper is inserted. It will allow changes to receiver information (account code, telephone numbers, etc.). UL requires the red wire loop to be intact for all remote station systems.
For additional download security, the F-DACT(F) can be programmed to perform a callback function. to prevent unauthorized access to the panel’s programming.
The F-DACT(F) is listed for use with the digital alarm communicator receivers listed below.
For CAN/ULC-S559 compliant configurations for fire signal receiving centre and proprietary fire signal receiving centre
applications refer to CAN/ULC-S559 Supplement Manual, P/N 3101563.
Manufacturers Models Formats
demco 685 EST 4/2, Contact ID
FBII CP220 EST 4/2, Contact ID
Osborne-Hoffman OH 2000 EST 4/2, Contact ID
Radionics D6500 EST 4/2
Silent Knight 9000 EST 4/2
Sur-Gard MLR1, MLR2,
Note: EST 4/2 is SIA DCS-02 P3 with the ability to transmit
hexadecimal event codes.
D6600 EST 4/2. Contact ID
EST 4/2, Contact ID MCDI TLR, TLR+
FCC Information
1. The dialer complies with Part 68 of the FCC rules. The dialer’s FCC certification number and Ringer Equivalence Number (REN) are displayed on the panel’s programming label and in this manual. This information must be provided to the telephone company if requested.
2. Two FCC compliant telephone cords with 8-pin modular plugs at both ends are supplied with the FSDACT. The dialer is designed to be connected to the telephone network using the supplied cord and an RJ-31X or RJ-38X jack, which must also comply with FCC Part 68 rules.
3. The REN is used to determine the maximum number of devices that may be connected to a single telephone circuit. All telephone devices are assigned a REN. The sum of the RENs for all connected devices may not exceed five. The maximum REN may vary in some areas. Contact the local telephone provider for more information.
4. If the dialer causes harm to the telephone network, the telephone company will notify you an advance that temporary discontinuance of service may be required. If advance notice is not practical, the telephone company will notify you as soon as possible. You will also be advised of your right to file a complaint with the FCC, if you believe it is necessary.
5. The telephone company may make changes in its facilities, equipment, operations, or procedures that could affect the operation of the dialer. If this happens, the telephone company will provide advance notice in order
© 2013 UTC Fire & Security. All rights reserved. 1 / 4 P/N 3101038 • REV 03 • REB 25JAN13
for you to make necessary modifications to maintain uninterrupted service.
6. If trouble is experienced with the dialer, for repair or warranty information, contact:
UTC Fire & Security
8985 Town Center Parkway Bradenton, FL 34202 Telephone: (800) 655-4497.
If the dialer is causing harm to the telephone network, the
telephone company may request you disconnect the dialer until the problem is resolved.
7. No repairs may be performed on the dialer by the user.
8. The dialer can not be used on public coin phones or party line service provided by the telephone company.
Industry Canada Information
NOTICE: This equipment meets the applicable Industry
Canada Terminal Equipment Technical Specifications. This is confirmed by the registration number. The abbreviation, IC, before the registration number signifies that registration was performed based on a Declaration of Conformity indicating that Industry Canada technical specifications were met. It does not imply that Industry Canada approved the equipment.
Before installing this equipment, users should ensure that it is permissible to be connected to the facilities of the local telecommunications company. The equipment must also be installed using an acceptable method of connection. The customer should be aware that compliance with the above conditions may not prevent degradation of service in some situations.
Repairs to certified equipment should be coordinated by a representative designated by the supplier. Any repairs or alterations made by the user to this equipment, or equipment malfunctions, may give the telecommunications company cause to request the user to disconnect the equipment.
Users should ensure for their own protection that the electrical ground connections of the power utility, telephone lines, and internal metallic water pipe system, if present, are connected together. This precaution may be particularly important in rural areas.
Installation instructions
Install the F-DACT(F) according to the instructions provided below.
WARNING: High voltages capable of causing personal injury
including death may be present. Disconnect all sources of power then wait at least 30 seconds for capacitors to discharge to a safe energy level before proceeding.
Caution: Failure to disconnect power will damage the panel
and the F-DACT(F). Observe static-sensitive handling practices.
Note: It is not necessary to remove the main panel board from
the cabinet to install the the F-DACT(F).
To install the F-DACT(F):
1. Remove the clear plastic film protecting the LCD on the F-DACT(F).
2. Mount the F-DACT(F) to the back of the circuit board. See Figure 1.
3. If this is a new installation, remove the insert from the LCD window on the control panel.
4. Connect the power cable to J2 on the control panel.
5. Connect the supplied modular phone cables to the RJ-31X/C31X jacks. See Figure 2.
6. Energize the control panel.
For programming instructions, refer to the technical manual referenced under “Commercial Protected Premises Control Unit” on the label attached to the inside of the cabinet door.
In addition, if you are installing the F-DACT(F) in a FireShield control panel, see “Programming for FireShield control panels” later in this document.
Caution: Users should not attempt to make connections
themselves, but should contact the appropriate electric inspection authority, or electrician, as appropriate.
NOTICE: The Ringer Equivalence Number (REN) for this
terminal equipment is 0.1. The REN assigned to each terminal equipment provides an indication of the maximum number of terminals allowed to be connected to a telephone interface. The termination on an interface may consist of any combination of devices subject only to the requirement that the sum of the Ringer Equivalence Numbers of all the devices does not exceed five.
2 / 4 P/N 3101038 • REV 03 • REB 25JAN13