Edwards Signaling ESL 700 User Manual

Page 1
ESL 700 SERIES
Commercial Self-Diagnostic Smoke Detectors
The ESL 700 Series self-diagnostic detectors provide field-replaceable optical chambers, and rate-of-rise heat detectors with fast response algorithms in some models (711UT, 721UT, and 741UT).
Electrical Compatibility
The two-wire units are compatible with a wide range of UL Listed control panels. For information on detector/control unit compatibility, refer to ESL’s Compatibility Index. For a copy of the Compatibility Index, call 800-648-7424 or visit the Publication Library at www.ge-security.com.
WARNING !
System may not operate if the detector is not connected to the control unit initiating device circuit as specified in the detector or control unit literature.
For optional four-wire operation, compatibility listings with individual panels are not available from UL, therefore you only need to verify that the voltage range of the detector equals or exceeds the voltage range of the control panel power supply, and sufficient current is available to insure the operation of all detectors.
California State Fire Marshal Approved MEA (New York City) Approved
Installation
Placement and Spacing
Use the following location guidelines to optimize performance and reduce the chance of false alarms:
• Locate ceiling-mounted smoke detectors in the center of a room or hallway at least 4 inches (10cm) from any walls or partitions.
• Locate wall-mounted smoke detectors so the top of the unit is 4 to 12 inches (10 to 30cm) below the ceiling. See Figure 1.
• Locate in a suitable environment as follows:
- Temperature between 32°F (0°C) and 100°F (38°C)
- Humidity between 0 and 95% non-condensing
• Locate away from air conditioners, heating registers, and any other ventilation source that may interfere with smoke entering the unit.
• Mount units on a firm permanent surface.
• When more than one detector is required, spacing of 30 feet (9.1m) may be used as a guide on smooth ceilings. Other spacing may be used depending on ceiling height, high air movement, and other conditions or response requirements.
• Locate away from kitchens, wood stoves, garages, furnaces, and bathrooms.
Screw terminal
enlargement detail
NOTE:
Alarm contacts shown
in non-alarm mode.
Screw terminal
enlargement detail
NOTE: Alarm contacts shown in non-alarm mode.
ESL 700 Series
Fire Alarm
Initiating Circuit
Compatible Listed
Control Unit
Continuity
Switch
First Detector
+
DC
Power
Circuit
Fire
Alarm
Initiating
Circuit
2
13
Base 701U
for Head Model 711U
Continuity
Switch
First Detector
700 Series 2-Wire Wiring Diagram
13
Base 702U or 702E for all Head Models
64
Remote Test Switch, N.O.
2
Base 702RU, 702RE, 702U, or
702E; for Heads Model 731U
5
Normally Open
Remote LED Blinks every 9 seconds during normal condition Blinks once every second during trouble condition Latches on in alarm No indication during loss of power
2
13
64
5
Common
700 Series 4-Wire Wiring Diagram 741UT Head
2
13
Base 702U or 702E
(Relay in Head)
64
5
Remote LED Blinks every 9 seconds during normal condition Blinks once every second during trouble condition Latches on in alarm No indication during loss of power
2
13
Base 702U or 702E
(Relay in Head)
64
5
Last Detector
Figure 1. Wiring diagrams
End-of-Line
Device
Last Detector
Normally Closed
End-of-Line
Device
Power Supervision
Unit (204-12/24V)
Red
Black
Brown Brown
1
Page 2
ceiling
4 in. (100mm)
minimum
To lock, break out tab with pliars
acceptable here
top of detector
acceptable here
never here
4 in. (100mm)
minimum
side wall
12 in. (300mm) maximum
Figure 2. Fire sensor placement
Consider the Locking Mechanism BEFORE Installation
Each detector head is equipped with a breakaway locking tab slot to prevent unauthorized removal of the detector head (see Figure 3). For installations where unauthorized removal of the detector head is not a concern, the head can be removed by simply turning counterclockwise.
However, when the head must lock to the base, break away the locking tab slot with a pair of pliers. Then, to remove the detector head, insert a small screwdriver into the slot on the side of the base and press in while simultaneously turning the detector head counterclockwise (see Figure 7).
Installing the Universal Base
The 701U and 702U 6-inch diameter universal mounting bases mount directly to standard single-gang electrical boxes, 4-inch square, round, or octagonal boxes, 3.5-inch octagonal boxes, and to WIREMOLD Nos. 5738A or 5739 fixture boxes. The 702E 4-inch diameter universal mounting bases mount only to 3-inch round electrical boxes. Bases may also be mounted without electrical boxes if approved by the AHJ or if codes allow.
The 6-inch diameter bases have two parts; the base itself that mounts to the electrical box or ceiling, and the base cover that conceals the mounting screws (see Figure 4). The 6-inch diameter bases are shipped loosely coupled to the base cover.
1. Mount the base. Align the molded line on the base with the base cover, and twist clockwise to snap in place. To remove the base cover, simply twist counter-clockwise to unsnap (see Figure 4).
2. Pull wire through the electrical box, then through the center opening of the 700 Series universal base. Connect the wire to the appropriate terminals according to the wiring diagrams (see Figure 1). Each base is equipped with either three or six clamping type wire terminals and bifurcated contact springs for contact with detector head circuit pins. Each wire clamping terminal will accommodate two conductors up to
2.0 mm in diameter (#12 AWG).
3. Dress the wiring neatly and verify that the continuity switch (jumper wire) is touching both terminal 1 and terminal 2. Securely fasten base with appropriate hardware (see Figure 5).
CHECK ALL WIRING AND MOUNTING CONNECTIONS.
End-of-Line Supervision for Four-Wire Systems
NFPA 72 requires power wiring in four-wire systems to be supervised. This is accomplished by installing a power supervision unit for the appropriate control unit voltage at the end of the detector power circuit. ESL model 204–12/24 V power supervision relay—is recommended for both 12 VDC or 24 VDC operation. See 204–12/24 V installation instructions for more information.
Figure 3. Removing the locking tab slot
Base cover
Screwdriver slot to unlock head
Align the molded lines on
Base
the base and cover, then twist to snap into place.
Figure 4. The 6" diameter mounting base
Testing the Wiring for Continuity
After all universal mounting bases are installed, including the end-of-line device, check the system wiring for continuity. Verify that the manually operated continuity switch in each base is in the shorting position — making contact with terminals 1 and 2 (for use at initial installation only). Use a screwdriver to reset any unshorted continuity switches (reset by prying the jumper wire out of the plastic stopper). This establishes continuity across the alarm initiating circuit at initial installation. The wiring can now be tested for continuity using an ohmmeter or “megger.”
Installing the Detector Head
Base models 702RE and 702RU have a special plastic protrusion built in to prevent insertion of the wrong heads. They are designed specifically for use with only 731U heads, which include auxiliary relay contacts, and are only required when high voltage (i.e. 120 VAC) is connected to the auxiliary relay. This prevents the installer from inserting a low voltage detector head into a base containing damaging high voltages. Standard base models 702E and 702U can be used with the 731U heads when 120 VAC is not present.
Every 700 Series base includes a continuity switch which shorts terminals 1 and 2 together for easy continuity testing. When a 700 Series head is inserted, the continuity switch will be snapped back, out of the way, and will no longer short terminals 1 and 2. The continuity switch can be snapped back into its original position with a screwdriver, if necessary.
To install a detector head, insert the head and rotate it clockwise until it is properly aligned and “sets” into the base (see Figure 6). Then rotate it an additional 15 degrees to lock it in place. This action will automatically “open” the continuity switch in the base and allow continuity in the system to be established by the detector heads.
Removing the Detector Head
To remove the detector head turn it counterclockwise. However, if the locking tab slot has been removed, insert a small screwdriver into the locking tab slot on the side of the base and press in while simultaneously turning the detector head counterclockwise (see Figure 7). When a detector head is removed for cleaning or repair, continuity in the system is broken. Continuity can be re-established by manually resetting the continuity switch on the empty base with a screwdriver.
2
ESL 700 Series
Page 3
Continuity switch
Head
Base
Figure 5. Continuity switch
Detector cap
Screwdriver slot
Figure 8. Removing detector cap
Figure 6. Installing the detector head
Figure 9. Optical chamber
Testing the System
After all connections are completed and the wiring is checked per NFPA 72, apply power to the system. There should not be an alarm. If there is, power down the system and determine whether a unit is latched or if there is a problem with the wiring. If no alarm has occurred, go to the last unit and check the unit power with a volt meter for the specified voltage.
Testing Each Detector
1. Prior to testing, remove the red dust cover. The units will not work
with the dust cover in place.
2. Disconnect alarm notification appliances, releasing service devices,
and extinguishing systems prior to detector tests.
3. Be sure to reconnect all devices at the conclusion of testing.
SQUEEZE
Figure 7. Removing the detector head
with the locking tab slot removed
Detector cap
HERE
Field replaceable optical chamber
Figure 10. Sensitivity level test
FlashesFlashes
Flashes
FlashesFlashes
0- 1 Indication: Unservicable hardware fault.
Action: Reset and rerun sensitivity test. If the error
persists, replace unit.
2- 3 Indication: Unit is becoming insensitive.
Action: Clean and reset the unit. Rerun sensitivity test. If
the error persists, replace the unit.
4- 7 Indication: Unit is within normal sensitivity range.
Action: N/A
8- 9 Indication: Unit is becoming too sensitive.
Action: Verify the optical chamber is snapped down
securely. Clean the unit and replace the optical chamber.
Smoke Test
The units should be tested in place annually using one of the following methods:
1. Use Smoke! in a can® and follow the directions on the can. OR
2. Hold a smoldering punk or cotton wick close to the unit and gently
direct the smoke into the smoke entry openings for 20 seconds or until an alarm is indicated.
The unit performs a smoke test every 9 seconds while flashing its LED. If smoke is detected, the rate of sampling increases to every 4.5 seconds. Excessive smoke must be detected in three consecutive tests for the alarm to sound. BE SURE TO PROPERLY EXTINGUISH THE SMOKE SOURCE AFTER TESTING!
If it is successful, the LED will remain lit. This is a gross, go/no-go test and is not a reliable indication of unit sensitivity. For in-depth sensitivity testing, see Sensitivity Test. To reset the detector, operate the system reset switch for 2 to 3 seconds to remove power from the detectors. Control unit alarm and all ancillary functions should be verified for a complete test of each detector.
Sensitivity T est
1. Hold the magnet near the integral reed switch of the unit for more
than one second (see Figure 10). The LED will flash 1 to 9 times.
2. Count the number of LED flashes, then use the following table to
determine if any action is necessary.
After the sequence of blinks, if the sensitivity is found to be within limits and if all other tests pass, the detector will go into alarm until reset by the panel. If the sensitivity is not within limits, or an unserviceable hardware fault has been detected, the alarm LED will continue to flash once per second until the detector is reset by the panel. If sensitivity test indicates an unacceptable level, take action recommended above. If action does not result in acceptable sensitivity, replace unit.
Maintenance
If a unit drifts beyond its approved sensitivity range for more than 24 hours, or fails internal diagnostic tests, the unit automatically indicates trouble by flashing its LED every second. This meets field sensitivity testing require­ments without the need for external meters.
In accordance with NFPA 72, unit sensitivity should be checked within one year of installation and every alternate year thereafter, in commercial in­stallations, or every three years in residential sites.
The unit’s replaceable optical block chamber unsnaps for easy field cleaning and service. Whenever the LED indicates cleaning is necessary, follow these steps:
1. Remove the detector cap (see Figure 8), unsnap and throw away the optical block chamber (see Figure 9).
2. Thoroughly blow off the optical base and snap a new optical block chamber (part #211) into place.
NOTE: Be sure the new optical block chamber is seated all the way down.
3. Replace the detector cap and verify sensitivity. See Sensitivity Test.
ESL 700 Series
3
Page 4
Specifications
ty
Voltage 8.5 – 33 VDC, non polarity sensitive Maximum ripple (pk to pk) 10% (Vp - p) Typical average standby current (24V)
731U, 741UT 100µA
711U, 711UT, 721UT 70µA Typical alarm current (24V) -2 Wire up to 60 mA (max), if not limited by control panel Typical alarm current (24V) -4 Wire up to 50mA (max) but 15mA (min) Relay contacts 2 A @ 30 VDC, 1 A @ 120 VAC Sensitivity 2.85%, + 0.37, – 0.75% Operating temperature 32°F to 120°F (0° to 49°C) Operating humidity range 0 to 95% Non-condensing RFI Immunity 20 V/m minimum; 0-1000 MHz Color White head and base Field wiring size 12-24 AWG Heat detector specifications Fixed temperature - 135°F ± 3°F (57°C ± 1.7°C)
(for 711UT, 721UT, and 741UT) Rate of rise - 15°F/min and > 105°F (8.3°C/min and > 40.6°C), 50 ft. spacing for 711UT/721UT/741UT UL two-wire compatibility identifier S10A for all models except 731U/731L, S11A for 731U/731L, S00 for all bases Remote LED output current 5 mA min, 8.5 mA max Drift compensation adjustment 1.0%/ft. max for photoelectric models
0.5%/ft. max for ionization models Detector head dimensions 4" (10 cm) diameter; 1.75" (4.44 cm) height Base dimensions
702E 4" (10 cm) diameter; 0.05" (1.27 cm) height
701U, 702U 6" (15.2 cm) diameter, 0.6" (1.3 cm) height Total height, head and base together 1.98" (5 cm) height Remote test input 100 ohm max Reset voltage 2.5V max Reset time 1 second minimum
Listings UL 268, FM, MEA, CSFM
Product Ordering
Detectors Description
711U 2-wire photoelectric type smoke detector 711UT 2-wire photoelectric type smoke detector with rate-of-rise heat detector and fast response algorithms 721UT 2-wire photoelectric type, with rate-of-rise heat detector with fast response algorithms, remote test, alarm/trouble LED output 731U 2-wire photoelectric type smoke detector, with auxiliary relay (N.C./N.O.) outputs, UL Listed for releasing service 741UT 4-wire photoelectric type smoke detector, alarm relay (N.O.) output and remote alarm/trouble LED output with rate-of-rise heat
detector with fast response algorithms
731L (OEM only, not for resale) See 731U description
Bases
701U Base, for 711U heads; 6" (15 cm) base, 3 terminal connectors 702E Base, for all heads; 4" (10 cm) base, 6 terminal connectors 702U Base, for all heads; 6" (15 cm) base, 6 terminal connectors 702RE Base, for 731U relay type smoke detector heads; 4" (10 cm) base, 6 terminal connectors 702RU Base, for 731U relay type smoke detector heads; 6" (15 cm) base, 6 terminal connectors
Accessories
204-12/24V End-of-line, power supervision relay for 4-wire applications SM-200 Smoke! in a can® (canned smoke) for functional testing of smoke detectors 211 Replacement optical block cover for all models (set of 10) 706U1A Remote Indicator with red alarm LED, for use with 731U and 741UT 706U2A Remote Indicator with red alarm LED and keyed remote test, for use with 731U and 741UT 706U3A Remote Indicator with red alarm LED, keyed remote test and reset, for use with 731U and 741UT
g
GE Securi
GE Security
12345 SW Leveton Drive Tualatin, OR 97062 503-692-4052 USA & Canada: 800-547-2556
Tech Support
800-648-7424
www.GESecurity.com
13083 Rev H 06/04
Loading...