Edwards Signaling ESL 511 User Manual

ESL 511/518 Series Smoke Detector
Installation Instructions
U
L
LISTED
Description
The ESL 511/518 Series Smoke Detector is a two-wire detector designed for use with a 24VDC fire system.
Refer to ESLs Compatibility Index for a complete listing of compatible control panels. For a copy of the Compatibility Index, call 1-800-648-7424.
WARNING
!
It is important that you read, understand, and follow the instructions in this guide. If you have questions, call Sentrol at 1-800-648-7424.
This document is intended for licensed electricians/ alarm installers. Sentrol cannot provide technical support to unqualified persons.
Failure to properly install, test, and maintain a smoke detector system may cause it to fail resulting in loss of life and/or property.
Figure 1 - Detector/Base Lock Knockouts
 Locate wall-mounted smoke detectors so the top of the
detector is 4 to 12 inches below the ceiling.
DO NOT locate detectors in or near bathrooms or
kitchens.
The detector provides the following features: Detector/base lock discourages unauthorized removal of
the detector by requiring a screwdriver to remove the detector from the base.
Mounting base mounts directly to standard single-gang, 3­inch round or 4-inch octagonal electrical boxes. Can also be mounted directly to walls and ceilings if the local authority having jurisdiction allows.
Selecting a Location
Selecting a suitable location is critical to the operation of smoke detectors. This equipment should be installed in accordance with the National Fire Protection Associations (NFPA) Standard 72.
Important: Regulations pertaining to detector installation vary from state to state. For more information, contact your local fire department or local authority having juris­diction.
In addition to NFPA 72, use the following location guide­lines to optimize performance and reduce the chance of false alarms from the detector:
 Locate ceiling-mounted smoke detectors in the center of
a room or hallway at least 4 inches from any walls or partitions.
 Locate in a suitable environment as follows:
- Temperature between 32°F (0°C) and 100°F (37.8°C)
- Humidity between 0 and 95% non-condensing
 Locate away from air conditioners, heating registers and
any other ventilation source that may interfere with smoke entering the detector.
 Mount smoke detectors on a firm permanent surface.
Installing the Detector
All wiring must conform to the National Electric Code (NEC) and/or local codes having jurisdiction. Use 12 to 24 AWG wire to install the detector.
1. If you are using the detector/base lock, remove the detector knockout and break off the tab on the mounting base. See Figure 1.
2. Remove the red plastic dust cover from the detector. The detector is shipped with a dust cover for protection on construction sites with dusty environments.
3. Run system wiring to the detector location and mount electrical boxes if necessary.
4. Line up and attach the gasket and mounting base to the electrical box, wall, or ceiling using the screws pro­vided. Use the wall anchors if necessary. See Figure 2.
5. Strip the system wires and connect them to the appropri­ate terminals on the detector. See Figure 3.
1
Detector
UL Listed control panel
Mounting base
Figure 2 - Mounting the Detector
Gasket
2-wire initiating circuit
+ _
Figure 3 - Wiring Diagram
6. Attach the detector to the mounting base as follows:
- Line up the raised tab on the side of the detector with the arrow on the mounting base. See Figure 4.
- Insert the smoke detector into the base and turn clockwise approximately 15 degrees. It should snap firmly into place.
7. Apply power.
8. Test the detector. See Smoke Testing the
Detector.
Important: The control panel alarm and all auxiliary functions should be verified for a complete test of the system.
EOL device
_
+
First detector
_
+
Last detector
Smoke Testing the Detector
Smoke detectors should be tested in place annually using smoke or canned aerosol simulated smoke. Follow the instructions on the canned smoke or use the following steps to test the detector with smoke:
1. Hold a smoldering punk or cotton wick close to the smoke entry openings.
2. Gently direct the smoke into the detector for 20 seconds or until an alarm is indicated.
BE SURE TO PROPERLY EXTINGUISH THE SMOKE SOURCE AFTER TESTING! The detector LED should stay on and an alarm should be indicated at the control panel. Use the system reset switch to reset the detector.
Figure 4- Attaching Detector to Base
Understanding the LED
The LED on the detector indicates the status of the detector as follows:
Flashing every 9 seconds = Normal operation. On = Detects smoke, sending an alarm. Off or flashing once every 1.5 seconds = Trouble or
maintenance is required. Test the detector. See Testing the Detector Sensitivity.
2
Loading...
+ 4 hidden pages