Edwards Signaling E-PDD User Manual

JP3
3 2 1
Settin
1
2
LED
Power LED
Flashes intermittently when the detector is in
Alarm/active LED
E-PDD Duct Smoke Detector Installation Sheet

Operation

The duct smoke detector's primary purpose is to provide early warning of an impending fire and shut down the HVAC unit in order to prevent smoke from circulating throughout the building. The duct smoke detector is designed for use in duct applications where temperatures can exceed standard detector capabilities.
Air is introduced to the duct smoke detector's sensing chamber through a sampling tube that extends into the HVAC duct and is directed back into the ventilation system through an exhaust tube. The difference in air pressure between the two tubes pulls the sampled air through the sensing chamber. When a sufficient amount of smoke is detected in the sensing cham ber, the duct smoke detector notifies the fire alarm control panel.
The device address is set using the two rotary switches located on the front of the unit. One device address is required.
The detector is capable of performing comprehensive self­diagnostics and storing the results.
In installations where the duct smoke detector’s controls and indicators are hidden from view, a remote test station or an LED indicator can be connected to the detector to provide these functions.

Jumper setting operation

The following jumper settings determine the operation of the detector.
Figure 1: Jumper setting

LED operation

The detector provides two LEDs, visible from the front side of the detector, that show its status.
Description
Off when the detector is in the alarm state
the normal state Indicates the detector is in the alarm/active
state as follows: Flashes at a continuous rate if the first
detector is in alarm/active Flashes intermittently if not the first detector
in alarm/active

Installation

WARNINGS
The duct smoke detector is not intended as a substitute for open area protection.
This detector will not operate without electrical power. As fires frequently cause power interruption, you should discuss further safeguards with your local fire protection specialist.
The duct smoke detector will not operate as designed outside of the listed electrical and environmental specifications.
Table 1:Jumper settings
g Operation Description
-2 Alarm
-3 Supervisory
© 2013 UTC Fire & Security. All rights reserved. 1 / 6 P/N 3101210 • REV 02 • ISS 28JAN13
Factory Default: Configures the detector for alarm latching operation
Configures the detector for supervisory operation
The duct smoke detector will not sense smoke unless the ventilation system is operating and the sensor’s cover is properly installed.
The duct smoke detector may not operate as designed unless installed in accordance with these instru ctio ns and all applicable national and local codes as determined by the local authority having jurisdiction.
Note: Read these instructions thoroughly before installing. In
addition to this document, important infor mation can be found in Technical Bulletin P/N 3101212.

Installation guidelines

Model
SD
SD
SD
SD
SD
SD
SD
SD
Detector
Sampling tube
socket
Exhaust tube
Thick
gasket
Thin
gasket
Exhaust tube
socket
Coupling
Sampling tube (ordered separately)
Plug
Sampling tube
connector
Sampling tube
(fully assembled)
Detector
To ensure correct operation, install the duct detector using the following guidelines:
Install the duct smoke detector on a flat section of HVAC duct between six and ten duct widths from any bends or obstructions.
Install supply-side detectors at a point downstream from the supply fan and after the air filter.
Install return-side detectors at a point before the return air stream is diluted by outside air.

Verify the duct air velocity

In order to verify airflow direction and velocity, air must be moving through the HVAC system.
To verify the duct air velocity:
1. Drill a small hole at the point where the duct smoke detector is being installed.
2. Using the SD-VTK Air Velocity Test Kit and a suitable air velocity meter, verify that the air velocity in the HVAC duct falls within the specified operating range of the detector and note which direction the air flows.
3. If the air velocity does not fall within the specified rang e, relocate the detector and seal the hole in the HVAC duct. Refer to Technical Bulletin P/N 3101212 for additional information pertaining to installation locations.

Select the appropriate sampling tube:

3. The sampling tube is normally installed from the rear, but it can also be installed from the front of the detector as shown in Figure 3. This method requires that you remove the detector cover.
Figure 2: Duct detector assembly
Figure 3: Sampling tube installa t io n
Select a sampling tube that extends at least two-thirds
For duct widths greater than 36 inches, use a sampling
Sampling tubes are available in the following lengths:
To assemble the detector:
1. Assemble the duct smoke detector as shown in Figure 2.
2. Rotate the air sampling tube so the inlet holes face the
across the width of the duct.
tube that is longer than the width of the duct.
Description
-T8 8-inch sampling tube
-T18 18-inch sampling tube
-T24 24-inch sampling tube
-T36 36-inch sampling tube
-T42 48-inch sampling tube
-T60 60-inch sampling tube
-T78 78-inch sampling tube
-T120 120-inch sampling tube
direction of airflow.
To install the detector:
1. Attach the drill template to the HVAC duct at desired mounting location.
2. Drill (or punch) the mounting holes where indicated.
Note: Sampling tubes longer than 36 inches must be
supported at both ends of the duct.
3. If using an air sampling tube that is longer than the width of the duct, drill a 3/4-inch hole on the opposite side of the duct for tube to pass through.
4. Remove any rough edges from the holes.
2 / 6 P/N 3101210 • REV 02 • ISS 28JAN13
Loading...
+ 4 hidden pages