Edwards Signaling Electronic Strobe Signals Installation Guide

EDWARDS
Description
Installation Instructions for
Electronic Strobe Signals
The strobes are high quality signals intended for indoor use. It is recommended that these products be installed in accordance with the requirements in the latest edition of national and local electri­cal codes.
See Table 2 and Figure 1 for specifications.
Table 1. Electronic Str obes
Catalog Number Voltage Description
89STR(*)-AQ 24V AC/DC Strobe, Flush Mount
89STR(*)-N5 120V AC
89SMSTR(*)-AQ 24V AC/DC Strobe, Surface Mount
89SMSTR(*)-N5 120V AC
*Insert Lens Color: C-clear, R-red, G-Green, B-blue or A-amber.
Installation
WARNINGS
To reduce the risk of shock, do not connect po wer to the strobe until directed in these instructions.
To reduce the risk of shock, do not tamper with unit when circuit is energized. Disconnect all power and allow 5 minutes for stored energy to dissipate before handling.
3. (Figure 1) Position the mounting plate onto the electrical box. F asten the plate using two pan head slotted scre ws (supplied).
4. For indoor surf ace mounting, ensur e all conduit holes are plugged.
5. (Figure 2) Connect the strobe wiring terminals on the unit to a signal circuit that outputs a constant (not pulsed) v oltage. Polarity must be observed for units operating on 24V DC.
6. After connections are complete, mount the unit onto the mounting plate. Fasten it using two countersunk Phillip head screws (supplied).
7. Apply power and acti vate the str obe unit to v erify that it is operating proper ly.
CAUTION
This unit is not serviceable or repairable. Should the unit fail to operate, contact the supplier f or replacement.
Maintenance
Perform a visual inspection and an operational test twice a y ear.
1. Install an appr opriate electrical bo x as listed belo w using suitable hardware (provided by others).
For Flush Mount: 1 gang Handy box, Iberville 1104 style, or equivalent.
For Surface Mount: Surface Box , Part Number P-047701­0232 and (2) Conduit Plugs (all supplied).
2. Bring signaling cir cuit field wiring into the electrical box .
Table 2. Specifications
-AQ Models -N5 Models Operating Voltage 24V 50/60 Hz, 24V DC 120V 50/60 Hz Operating Current 390 mA 87 mA Flash Rate (per second) 1 fps
Operating Environment Indoor 85% relative humidity @ 86°F (30°C), 32° to 120°F (0° to 49°C) variable ambient temperature.
NOTE: Cat. No. 89STR(*)-AQ and Cat. No. 89SMSTR(*)-AQ potentially generate timing signals or pulses above 9 kHz and therefore have been tested and found to comply with the limits for a Class A digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses and can radiate frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to ra dio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense.
CAUTION: Changes or modifications to this equipment not expressly approved by the party responsible for compliance could void the user's authority to operate the equipment.
P-047550-1777 ISSUE 1 © 1998
Figure 1. Mounting Arrangements
To P ower Source
+
Note: Polarity must be observed for units operating on 24 VDC.
Figure 2. Electrical Connections
-
P-047550-1777 ISSUE 1