Installation Instructions for Electronic
Horn/Strobe Signal Appliances
Description
The horn/strobes are high quality signals intended for use
in general signaling applications. The strobes flash at 1
fps across their full operating voltage range.
It is recommended that these products be installed in accordance with the requirements in the latest edition of
national and local electrical codes.
See T able 2 and Figures 1, 5 and 6 for specifications.
T able 1. Electronic Horn/Strobes
Horn/Strobe, Gray, Surface Mount Indoor 867STR(*)-**
Horn/Strobe, Gray, Surface Mount Outdoor 868STR(*)-**
Horn/Strobe, Gray, Flush or Panel Mount
Indoor
*Insert lens color. C = Clear, R = Red, G = Green, B = Blue or
= Amber.
**Insert voltage. N5 = 120V AC, AQ = 24V AC/DC
869STR(*)-**
Installation
WARNING
To reduce the risk of shock, always disconnect all
power before handling the unit.
WARNING
To reduce the risk of shock, do not tamper with this
device when the signal circuit is energized. Disconnect all power and wait 5 minutes for stored
energy to dissipate before handling.
1. Select a mounting method as detailed in Figure 1 and
install the electrical box using suitable hardware.
a. For outdoor applications, install the weatherproof
box using four #10 x 1 1/4" (32 mm) screws and
caplugs provided in the enclosed parts bag.
Carefully adhere the gasket, part number P-0075490082 (provided in the enclosed parts bag) to the
box as shown in Figure 1.
NOTE: Be sure hook flange is facing outward as shown
in Figure 1.
NOTE: The designation "TOP" on boxes denotes
orientation of box after installation.
2. Attach mounting plate using two #8-32 screws
provided with the surface box or four #8-32 screws
provided with weatherproof box. The flush box uses
two #8-32 screws (not provided).
3. Bring signaling circuit field wiring into electrical box.
4. Connect signaling circuit field wires to terminals on
horn/strobe assembly (Figures 2-4).
Figure 1. Detailed View
P-047550-1786 ISSUE 3 © 2002
5. Ground in accordance with national and local electrical
codes. A green ground screw is provided with both
the indoor and outdoor surface boxes.
7. Apply power and activate the horn/strobe unit to verify
that it is operating properly .
6. Mount the horn/strobe assembly on the mounting
plate (Figure 1).
a. The inside of the top of the grille has hinges that
pass through cutouts and engage with tabs on the
mounting plate. With the bottom of the grille
lifted out slightly, place the grille over the
mounting plate so that the hinges of the grille
are in the mounting cutouts.
b. Properly seat the grille by pressing the bottom in.
c. Fasten the bottom of the grille to the mounting
plate by installing the captive combination drive
screw.
- horn
- strobe
Applicable
Voltage Source
+ + + +
- - - -
NOTE: Polarity must be observed for units operating on 24 VDC.
Figure 2. Wiring the Horn and Strobe on Same Circuit
- horn
- strobe
Applicable
Voltage Source
+
+
+
+ + +
Maintenance
CAUTION
Should the unit fail to operate properly, do not
attempt repair. Contact the supplier for replacement.
Perform a visual inspection and an operational test twice
a year .
-
-
-
NOTE: Polarity must be observed for units operating on 24 VDC.
- - -
Figure 3. Wiring the Horn and Strobe on Different Circuits
Figure 4. T erminal Block
P-047550-1786 ISSUE 3