Edwards Signaling Electronic Horn/Strobe Signal Appliances Installation Guide

A
Installation Instructions for Electronic
Horn/Strobe Signal Appliances
Description
The horn/strobes are high quality signals intended for use in general signaling applications. The strobes flash at 1 fps across their full operating voltage range.
It is recommended that these products be installed in ac­cordance with the requirements in the latest edition of national and local electrical codes.
See T able 2 and Figures 1, 5 and 6 for specifications.
T able 1. Electronic Horn/Strobes
Horn/Strobe, Gray, Surface Mount Indoor 867STR(*)-**
Horn/Strobe, Gray, Surface Mount Outdoor 868STR(*)-**
Horn/Strobe, Gray, Flush or Panel Mount Indoor
*Insert lens color. C = Clear, R = Red, G = Green, B = Blue or
**Insert voltage. N5 = 120V AC, AQ = 24V AC/DC
869STR(*)-**
Installation
WARNING
To reduce the risk of shock, always disconnect all power before handling the unit.
WARNING
To reduce the risk of shock, do not tamper with this device when the signal circuit is energized. Dis­connect all power and wait 5 minutes for stored energy to dissipate before handling.
1. Select a mounting method as detailed in Figure 1 and install the electrical box using suitable hardware.
a. For outdoor applications, install the weatherproof
box using four #10 x 1 1/4" (32 mm) screws and caplugs provided in the enclosed parts bag. Carefully adhere the gasket, part number P-007549­0082 (provided in the enclosed parts bag) to the box as shown in Figure 1.
NOTE: Be sure hook flange is facing outward as shown
in Figure 1.
NOTE: The designation "TOP" on boxes denotes
orientation of box after installation.
2. Attach mounting plate using two #8-32 screws provided with the surface box or four #8-32 screws provided with weatherproof box. The flush box uses two #8-32 screws (not provided).
3. Bring signaling circuit field wiring into electrical box.
4. Connect signaling circuit field wires to terminals on horn/strobe assembly (Figures 2-4).
Figure 1. Detailed View
P-047550-1786 ISSUE 3 © 2002
5. Ground in accordance with national and local electrical codes. A green ground screw is provided with both the indoor and outdoor surface boxes.
7. Apply power and activate the horn/strobe unit to verify that it is operating properly .
6. Mount the horn/strobe assembly on the mounting plate (Figure 1).
a. The inside of the top of the grille has hinges that
pass through cutouts and engage with tabs on the mounting plate. With the bottom of the grille lifted out slightly, place the grille over the mounting plate so that the hinges of the grille
are in the mounting cutouts. b. Properly seat the grille by pressing the bottom in. c. Fasten the bottom of the grille to the mounting
plate by installing the captive combination drive
screw.
- horn
- strobe
Applicable
Voltage Source
+ + + +
- - - -
NOTE: Polarity must be observed for units operating on 24 VDC.
Figure 2. Wiring the Horn and Strobe on Same Circuit
- horn
- strobe
Applicable
Voltage Source
+
+
+
+ + +
Maintenance
CAUTION
Should the unit fail to operate properly, do not attempt repair. Contact the supplier for replacement.
Perform a visual inspection and an operational test twice a year .
-
-
-
NOTE: Polarity must be observed for units operating on 24 VDC.
- - -
Figure 3. Wiring the Horn and Strobe on Different Circuits
Figure 4. T erminal Block
P-047550-1786 ISSUE 3