E-IDCWS Analog Dual Input Waterflow/ Supervisory Module Installation Sheet
Operation
The module is an analog addressable device used to connect normally open waterflow alarm and supervisory initiating device circuits (IDCs) to a control panel. This module is designed for Class B circuit operation.
The device address is set using the two rotary switches located on the front of the module. Two consecutive device addresses are required. The second device address is automatically assigned one number higher that the value set on the rotary switches.
The module can operate in the following modes:
Table 1: Module operation
Device type description
Alarm latching delayed: Configures the module for use with only nonretarded waterflow alarm switches. When
alarm is sent to the control panel, which after a 16 second time delay, generates an alarm signal.
Supervisory active nonlatching US marketplace
Supervisory active latching Canadian marketplace Nonlatching: Configures the module for normally open
dry contact initiating devices. When the NO input contact of an initiating device is closed, a supervisory signal is sent to the control panel and the supervisory condition is not latched at the module.
Latching: Configures the module for normally open dry
an initiating device is closed, a supervisory signal is sent to the control panel and the supervisory condition is not latched at the module.

LED operation

The module provides a bicolor LED that shows its status.

Installation

WARNINGS
This module will not operate without electrical power. As fires frequently cause power interruption, you should discuss further safeguards with your local fire protection specialist.
This module does not support conventional smoke detectors.
Note: The module is shipped from the factory as an assembled
unit; it contains no user-serviceable parts and should not be disassembled.
To install the module:
1. Verify that all field wiring is free of opens, shorts, and ground faults.
2. Make all wiring connections as shown in “Wiring.”
3. Set the module address as follows: Use a screwdriver to adjust the two rotary switches on the
front of the module. Set the TENS rotary switch (0 through
12) for the 10s and 100s digit and the ONES rotary switch for the 0 through 9 digit. For example: device address 21, set TENS rotary switch to 2 and set the ONES rotary switch to 1.
Refer to “Specification s” for availa ble addr e ss number s.
4 Mount the module on the electrical box using screws
provided with the electrical box.
5. Mount the wall plate on the module using #4-24 x 1/2 in. (13 mm) self-tapping screw s.
Figure 1: Module address
Normal: Green LED flashes Alarm/active: Red LED flashes
© 2013 UTC Fire & Security. All rights reserved. 1 / 2 P/N 3101194 • REV 02 • REB 28JAN13
Figure 2: Module installation
Screw
4-24
screws
Module
Wall plate
Compatible
electrical box
Communication line voltage
Current Ground fault impedance
Operating environment
Stor
Compatible electrical boxes Wire size
Device address
Initiating device circuit (IDC)
Typical NO
Waterflow Switch
47 EOLR
k
47 EOLR
k
SUP.
Style B (Class B)
[1] [2] [4]
W/FLOW
Typical NO
Supervisory/
Tamper Switch
[3]
TB2 TB1
(+)
(+)
SLC
(+)
( )
( )
( )
From
previous
device
To next device
SLC out (+) SLC out
SLC in
SLC in (+)
( )
( )

Specifications

Maximum 20.6 V peak-to-peak
Standby Activated
10 kΩ
Temperature Humidity
age temperature range –4 to 140° F (–20 to 60° C)
01 to 63 (64 point control panel)
EOL resistor value Max. circuit resistance Max. circuit capacitance
550 μA 725μA
32 to 120° F (0 to 49° C) 0 to 93% RH
North American 4 inch square x 2-1/2 in. (64 mm) deep 2 gang box Standard 4 in. square box 1-1/2 in. (38 mm) deep
12, 14, 16, or 18 AWG wire (2.5, 1.5,
1.0, or 0.75 mm AWG are preferred)
01 to 126 (127 point control panel)
47 kΩ, (P/N: EOL-47) 50 Ω (25 Ω per wire)
0.1 μF
2
) (Sizes 16 and 18

Wiring

Wire in accordance with NFPA 72 and CAN/ULC-S524. Be sure to observe the polarity of the wires as shown in the diagram.
Figure 3: Module wiring
[1] Maximum 25 Ω resistance per wire [2] Maximum 12 AWG (2.5 mm2) wire; minimum 18 AWG (0.75 mm2) wire [3] Refer to the control panel technical reference manual for wiring specifications [4] Maximum 10 VDC at 350 μA
5. All wiring is power-limited and supervised
6. This module will not support two-wire smoke detectors
2 / 2 P/N 3101194 • REV 02 • REB 28JAN13