Edwards Signaling E-IDC2B User Manual

Setting
1
ontact initiating devices.
2
3
normally open dry contact initiating devices.
device is closed, a supervisory signal is sent
normally open dry contact initiating devices. When the NO input contact of an initiating
device is closed, a supervisory signal is sent
Note:
programming or the configuration utility. Refer to applicable control panel technical reference manual.

E-IDC2B Analog Dual Input Module Installation Sheet

Operation

The module is an analog addressable device used to connect two normally open, alarm, supervisory, or monitor type dry contact initiating device circuits (IDCs) to a control panel. This module is designed for Class B circuit operation.
The device address is set using the two rotary switches located on the front of the module. Two consecutive device addresses are required. The second device address is automat ica lly assigned one number higher that the value set on the rotary switches.
The device can be preset for alarm or supervisory operation using the slide switch located on the front of the module. The module can also be configured for other device types through front panel programming or the configuration utility.

Slide switch operation

The following slide switch settings determine the operation of the module. Setting the initial slide switch position is generally performed during module installation. This setting can be changed while the system is operating, but the change must be confirmed through front panel programming.
Slide switch P1 is used for IDC 1 and slide switch P2 is used for IDC 2. The waterflow device type available through front panel programming or the configuration utility can only be used with slide switch P1.
Table 1: Slide switch setti n g s
Operation Device type description
Alarm
Not used Supervisory Supervisory nonlatching US marketplace:
© 2013 UTC Fire & Security. All rights reserved. 1 / 4 P/N 3101193 • REV 02 • REB 28JAN13
Alarm latching: Configures the module for normally open dry c When the NO input contact of an initiating device is closed, an alarm signal is sent to the control panel and the alarm condition is latched at the module. (Factory default)
Supervisory latching Canadian marketplace: Nonlatching: Configures the module for
When the NO input contact of an initiating
to the control panel and the supervisory condition is not latched at the module.
Latching: Configures the module for
to the control panel and the supervisory condition is latched at the module.
Additional device types are available through front panel
Figure 1: Slide switches

LED operation

The module provides a bicolor LED that shows its status. Normal: Green LED flashes Alarm/active: Red LED flashes

Installation

WARNINGS
This module will not operate without electrical power. As fires frequently cause power interruption, you should discuss further safeguards with your local fire protection specialist.
This module does not support conventional smoke detectors.
Note: The module is shipped from the factory as an assembled
unit; it contains no user-serviceable parts and should not be disassembled.
To install the module:
1. Verify that all field wiring is free of opens, shorts, and ground faults.
2. Make all wiring connections shown in “Wiring.”
3. Set the module address as follows: Use a screwdriver to adjust the two rotary switches on the
front of the module. Set the TENS rotary switch (0 through
12) for the 10s and 100s digit and the ONES rotary switch for the 0 through 9 digit. For example: device address 21,
set TENS rotary switch to 2 and set the ONES rotary
Insert
screwdriver
here
Screw
4-24
screws
Module
Wall plate
Compatible
electrical box
47 EOLR
k
47 EOLR
k
IDC2
Style B (Class B)
[1] [2] [4]
IDC1
Typical NO
initiating device
[3]
TB2 TB1
(+)
(+)
SLC
(+)
( )
( )
( )
From
previous
device
To next device
SLC out (+) SLC out
SLC in
SLC in (+)
( )
( )
switch to 1. Refer to “Specification s” for availa ble addr e ss number s.
4. Set slide switches P1 and P2 to appropriate setting. Refer to “Operation.”
5. Mount the module on the electrical box using screws provided with the electrical box.
6. Mount the wall plate on the module using #4-24 x 1/2 in. (13 mm) self-tapping screws.
Figure 2: Module address
Figure 3: Module ins t a lla tion

Wiring

Wire in accordance with NFPA 72 and CAN/ULC-S524. Be sure to observe the polarity of the wires as shown in the diagram.
Figure 4: Module wiring
[1] Maximum 25 Ω resistance per wire [2] Maximum 12 AWG (2.5 mm2) wire; minimum 18 AWG (0.75 mm2) wire [3] Refer to the control panel technical reference manual for wiring specifications [4] Maximum 10 VDC at 350 μA
5. All wiring is power-limited and supervised
6. This module will not support two-wire smoke detectors
2 / 4 P/N 3101193 • REV 02 • REB 28JAN13
Loading...
+ 2 hidden pages