E-IDC2B Analog Dual Input Module
Installation Sheet
Operation
The module is an analog addressable device used to connect
two normally open, alarm, supervisory, or monitor type dry
contact initiating device circuits (IDCs) to a control panel. This
module is designed for Class B circuit operation.
The device address is set using the two rotary switches located
on the front of the module. Two consecutive device addresses
are required. The second device address is automat ica lly
assigned one number higher that the value set on the rotary
switches.
The device can be preset for alarm or supervisory operation
using the slide switch located on the front of the module. The
module can also be configured for other device types through
front panel programming or the configuration utility.
Slide switch operation
The following slide switch settings determine the operation of
the module. Setting the initial slide switch position is generally
performed during module installation. This setting can be
changed while the system is operating, but the change must be
confirmed through front panel programming.
Slide switch P1 is used for IDC 1 and slide switch P2 is used
for IDC 2. The waterflow device type available through front
panel programming or the configuration utility can only be used
with slide switch P1.
Table 1: Slide switch setti n g s
Operation Device type description
Alarm
Not used
Supervisory Supervisory nonlatching US marketplace:
© 2013 UTC Fire & Security. All rights reserved. 1 / 4 P/N 3101193 • REV 02 • REB 28JAN13
Alarm latching: Configures the module for
normally open dry c
When the NO input contact of an initiating
device is closed, an alarm signal is sent to
the control panel and the alarm condition is
latched at the module. (Factory default)
Supervisory latching Canadian marketplace:
Nonlatching: Configures the module for
When the NO input contact of an initiating
to the control panel and the supervisory
condition is not latched at the module.
Latching: Configures the module for
to the control panel and the supervisory
condition is latched at the module.
Additional device types are available through front panel
Figure 1: Slide switches
LED operation
The module provides a bicolor LED that shows its status.
Normal: Green LED flashes
Alarm/active: Red LED flashes
Installation
WARNINGS
• This module will not operate without electrical power. As
fires frequently cause power interruption, you should
discuss further safeguards with your local fire protection
specialist.
• This module does not support conventional smoke
detectors.
Note: The module is shipped from the factory as an assembled
unit; it contains no user-serviceable parts and should not be
disassembled.
To install the module:
1. Verify that all field wiring is free of opens, shorts, and
ground faults.
2. Make all wiring connections shown in “Wiring.”
3. Set the module address as follows:
Use a screwdriver to adjust the two rotary switches on the
front of the module. Set the TENS rotary switch (0 through
12) for the 10s and 100s digit and the ONES rotary switch
for the 0 through 9 digit. For example: device address 21,
set TENS rotary switch to 2 and set the ONES rotary
Screw
4-24
screws
Module
Wall plate
Compatible
electrical box
47
EOLR
kΩ
47
EOLR
kΩ
IDC2
Style B (Class B)
[1] [2] [4]
IDC1
Typical NO
initiating device
[3]
TB2 TB1
(+)
(+)
SLC
(+)
( )
( )
( )
From
previous
device
To next
device
SLC out (+)
SLC out
SLC in
SLC in (+)
( )
( )
switch to 1.
Refer to “Specification s” for availa ble addr e ss number s.
4. Set slide switches P1 and P2 to appropriate setting. Refer
to “Operation.”
5. Mount the module on the electrical box using screws
provided with the electrical box.
6. Mount the wall plate on the module using #4-24 x 1/2 in.
(13 mm) self-tapping screws.
Figure 2: Module address
Figure 3: Module ins t a lla tion
Wiring
Wire in accordance with NFPA 72 and CAN/ULC-S524. Be
sure to observe the polarity of the wires as shown in the
diagram.
Figure 4: Module wiring
[1] Maximum 25 Ω resistance per wire
[2] Maximum 12 AWG (2.5 mm2) wire; minimum 18 AWG (0.75 mm2) wire
[3] Refer to the control panel technical reference manual for wiring specifications
[4] Maximum 10 VDC at 350 μA
5. All wiring is power-limited and supervised
6. This module will not support two-wire smoke detectors
2 / 4 P/N 3101193 • REV 02 • REB 28JAN13