FIRE ALARM EQUIPMENT
Genesis® Horns, Strobes & Horn/Strobes
Field Configurable Horn & Strobe Output
EG1* Series
FEATURES
> Unique low-profile design
> Attractive appearance
> Ultra-slim - protrudes les than
one inch from wall
> No visible mounting screws
®
> Exclusive FullLight
Strobe
Technology
> Low current draw
> 15/30/75/110 and 95-177 candela
output models
> High (default) or low dB horn
> Temporal (default) or steady horn
> Public mode flash rate (default) or
private mode temporal flash
AGENCY APPROVALS
> UL 1971 Listed for the hearing
impaired
> UL 1638 Listed as protective
visual signaling appliances
> UL 464
> ULC S525 & S526
> CE Marked
The Genesis line of signals are the smallest, most compact audible
and visible emergency signaling devices in the world. About the
size of a deck of playing cards, these devices are designed to
blend with any building environment. Edwards Genesis horn/strobes
mask-and-cavity design, channels and conditions light to produce a
highly controllable distribution pattern. Intensive development
employing this new technology have given rise to a new benchmark
in strobe performance – FullLight
The EG1-HDVM series horn/strobes offer 15 to 110 candela output,
which is selectable with a conveniently-located switch on the side
of the device. The EG1-HDVMH series offers 95 to 177 candela
output. The candela output setting remains clearly visible even after
final installation, yet it stays locked in place to prevent unautho-
rized tampering. Its horn output reaches as high as 99 dB and
features a unique multiple frequency tone that results in excellent
wall penetration and an unmistakable warning of danger. Horns may
be configured for either coded or non-coded signal circuits. They
can also be set for low dB output with a jumper cut that reduces
horn output by 5 dB.
When installed with the Cat. No. EG1M Signal Master, strobe
flashes from devices on the same circuit are synchronized to within
10 milliseconds of each other indefinitely. The Signal Master also
permits independent horn control over a single pair of wires. Only
one Signal Master is required per circuit. No separate backbox —
simply snap it onto the back of the first signal on the circuit.
®
technology.
> FCC
> MEA, FM, CSFM pending
D-04
12-24
*Insert "R" for red, "W" for white "RF" for red with fire marking, "F" for white with fire marking.
© Copyright 2004 Edwards
TECHNICAL INFORMATION
FIRE ALARM EQUIPMENT
2 3/4”
(70mm)
4 1/2”
(114mm)
Feature Description
Housing Red or white textured UV stabilized, color impregnated engineered plastic. Exceeds 94V-0 UL flammability rating.
Lens Optical grade polycarbonate (clear)
Mounting Flush mount: 2 1/2" inch (64mm) deep one-gang box
(indoor wall mount only) Surface mount: Edwards model 27193 surface mount box, wiremold box, or equivalent surface-mount box
With optional trim plate: one-gang, two-gang, four-inch square, octagonal, or European single-gang box
Wire Connections Screw terminals: single input for both horn and strobe, #18 to #12 AWG (0.75 mm2 to 2.5 mm2) wire size
Operating Environment Indoor only: 32-120° F (0-49° C) ambient temperature; 0-93% relative humidity.
Agency UL 1971, UL 1638, UL 464, ULC S525, ULC S526, CE, FCC, (MEA, FM, CSFM pending). Listings/Approvals (All models comply with ADA Code of Federal Regulation Chapter 28 Part 36 Final Rule.)
Strobe Output Selectable 15 cd, 30 cd, 75 cd, or 110 cd output or Selectable 95 - 177 cd output
Operating Voltage EG1-VM series strobes: Non-coded, filtered 16-33V DC or unfiltered 16-33V DC FWR
EG1-HD temporal horns: Non-coded, filtered 16-33V DC or unfiltered 16-33V DC FWR (or coded when set to steady) EG1-P steady horns: Coded or non-coded, filtered 20-31V DC or unfiltered 20-27V FWR EG1-HDVM series temporal tone horn/strobes: Non-coded, filtered 16-33V DC or unfiltered 16-33V DC FWR (or coded (audible NAC only) when used with optional EG1M Genesis Signal Master)
Strobe Output Rating UL 1971, UL 1638, ULC S526: selectable 15 cd, 30 cd, 75 cd, or 110 cd output
Strobe Flash Rate EG1-VM series strobes and EG1-HDVM series temporal horn/strobes: one flash per second synchronized with
optional EG1M Genesis Signal Master indefinitely within 10 milliseconds (or self-synchronized within 200 milliseconds over thirty minutes on a common circuit without EG1M Genesis Signal Master) Temporal setting (private mode only): synchronized to temporal output of horns on same circuit
Compatible EG1M, EG1M-RM Synchronization Module
Horn Pulse Rate EG1-HD temporal-tone horns and EG1-HDVM series temporal-tone horn-strobes: temporal rate synchronized
with optional EG1M Genesis Signal Master indefinitely within 10 milliseconds (or self-synchronized within 200 milliseconds over thirty minutes on a common circuit without EG1M Genesis Signal Master) EG1-P steady-tone horns: continuous, steady tone only
Temporal Audible Pattern 1/2 sec ON, 1/2 sec OFF, 1/2 sec ON, 1/2 sec OFF, 1/2 sec ON, 1 1/2 sec OFF, then repeat cycle
27/32”
(21mm)
D-04
© Copyright 2004 Edwards
12-25