Installation Instructions for Edwards 117 Series
Low Profile Strobes
Description
The Edwards 117 Series Strobe is a low profile, surface mounted
UL and cUL listed signaling appliances in a NEMA 4X rated enclosure.
Specifications
Catalog Replacement
Number Voltage Current Strobe Tube
117*-EM 10-110V DC 0.35A 114-ST
117*-N5 120V AC 0.02A 91B-ST
117*-R5 240V AC 0.015A 91B-ST
*Letter in this position indicates lens color: A - amber, B - blue, C - clear,
G - green, or R - red
Installation
WARNING
To prevent electrical shock, ensure power is turned
off before installation or maintenance.
Surface Mounting (Figure 1)
1. Place the mounting gasket (supplied) over the hole in the
surface and route the signal wires through the gasket and
the hole in the panel.
2. Secure the beacon to the surface using two screws appropriate
for the mounting surface (not supplied).
3. Using wire nuts (not supplied), connect the signal's wire leads
as shown in Figure 1. Polarity must be observed on DC units.
Maintenance
WARNINGS
To prevent electrical shock, ensure power is turned
off before installation or maintenance.
To avoid risk of injury, install lens before energizing.
Cleaning
The module lens exterior surfaces should be periodically cleaned
with a soft clean cloth using water and a mild detergent to maintain optimum light visibility. Disconnect power before cleaning.
Light Source Replacement
1. Disconnect wiring.
2. Unscrew lens from base.
3. Unplug strobe tube and replace with new strobe tube as
appropriate (see specifications). Replace lens on base.
117 Series
Gasket
(supplied)
(2) Mounting
holes
White (neutral)*
Black (AC hot)
*NOTE: Both power source leads
are black on 240V AC (-R5) units
Figure 1. Mounting
P/N 3100818 ISSUE 1 © 2005