Edwards Signaling Edwards 117 Series Installation Guide

Part of GE Infrastructure
Security
Installation Instructions for Edwards 117 Series
Low Profile Strobes
Description
The Edwards 117 Series Strobe is a low profile, surface mounted UL and cUL listed signaling appliances in a NEMA 4X rated enclo­sure.
Specifications
117*-EM 10-110V DC 0.35A 114-ST 117*-N5 120V AC 0.02A 91B-ST 117*-R5 240V AC 0.015A 91B-ST *Letter in this position indicates lens color: A - amber, B - blue, C - clear,
G - green, or R - red
Installation
WARNING
To prevent electrical shock, ensure power is turned off before installation or maintenance.
Surface Mounting (Figure 1)
1. Place the mounting gasket (supplied) over the hole in the surface and route the signal wires through the gasket and the hole in the panel.
2. Secure the beacon to the surface using two screws appropriate for the mounting surface (not supplied).
3. Using wire nuts (not supplied), connect the signal's wire leads as shown in Figure 1. Polarity must be observed on DC units.
Maintenance
WARNINGS
To prevent electrical shock, ensure power is turned off before installation or maintenance.
To avoid risk of injury, install lens before energizing.
Cleaning
The module lens exterior surfaces should be periodically cleaned with a soft clean cloth using water and a mild detergent to main­tain optimum light visibility. Disconnect power before cleaning.
Light Source Replacement
1. Disconnect wiring.
2. Unscrew lens from base.
3. Unplug strobe tube and replace with new strobe tube as appropriate (see specifications). Replace lens on base.
117 Series
Gasket (supplied)
(2) Mounting holes
White (neutral)* Black (AC hot)
*NOTE: Both power source leads are black on 240V AC (-R5) units
Figure 1. Mounting