Edwards Signaling E-2WIRE User Manual

Setting
1
2
3
E-2WIRE Analog Class A/B Two-Wire Module Installation Sheet

Operation

The E-2WIRE module is designed to interface between conventional two-wire smoke detectors and a control panel. It monitors the circuit and smoke detectors and signals the control panel of any trouble or alarm conditions. The module also regulates and supervises the 24 VDC input power.
The module is configured from the factory to operate as a two­wire alarm device that does not require alarm verification. It can be configured for two-wire alarm verified operation through front panel programming or the configuration utility. When using the alarm verification feature of the control panel, do not mix normally open contact initiating devices with two-wire conventional smoke detectors.
The module recognizes the CleanMe signal from detectors that support this feature.
The module device address is set using the two rotary switches located on the front of the module. One device address is required.
The device can be set for Class B or Class A operation using the slide switch located on the front of the module.
Caution: This module cannot be used on a device loop with
isolator modules or isolator bases.
Note: Additional device types are available through front panel
programming or the configuration utility. Refer to applicable control panel technical reference manual.
Figure 1: Slide switch

LED operation

The module provides a bicolor LED that shows its status. Normal: Green LED flashes Alarm/active: Red LED flashes

Installation

WARNING: This module will not operate without electrical
power. As fires frequently cause power interruption, you should discuss further safeguards with your local fire protection specialist.

Slide switch operation

The following slide switch settings determine the operation of the module. Setting the initial slide switch position is generally performed during module installation. This setting can be changed while the system is operating, but the change must be confirmed through front panel programming.
Table 1: Slide switch operation
Operation Device t ype descripti on
Class B
Not used Class A
© 2013 UTC Fire & Security. All rights reserved. 1 / 4 P/N 3101192 • REV 03 • REB 25JAN13
Class B 2-wire smoke non-verified: Configures the module to monitor two-wire conventional smoke detectors (that do not require alarm verification) and normally open contact initiating devices on a Class B circuit.
Class A 2-wire smoke non-verified: Configures the module to monitor two-wire conventional smoke detectors (that do not require alarm verification) and normally open contact initiating devices on a Class A circuit.
Note: The module is shipped from the factory as an assembled
unit; it contains no user-serviceable parts and should not be disassembled.
To install the module:
1. Verify that all field wiring is free of opens, shorts, and ground faults.
2. Make all wiring connections as shown in “Wiring.”
3. Set the module address as follows: Use a screwdriver to adjust the two rotary switches on the
front of the module. Set the TENS rotary switch (0 through
12) for the 10s and 100s digit and the ONES rotary switch for the 0 through 9 digit. For example: device address 21, set TENS rotary switch to 2 and set the ONES rotary switch to 1.
Refer to “Specification s” for availa ble addr e ss number s.
4. Set slide switch P1 to appropriate setting. Refer to “Operation.”
5. Mount the module on the electrical box using screws
Insert
screwdriver
here
Screw
4-24
screws
Module
Wall plate
Compatible
electrical box
[3]
Style D (Class A)
[1] [2] [4 ]
Style B (Class B)
[1] [2] [4 ]
Typical
initiating
device
TB2 TB1
From
previous
device
To next device
From control
panel (not
resettable)
24 V +
4.7 k EOLR Used for
Class B only
SLC out (+) SLC out
SLC in
SLC in (+)
SLC
DET. PWR.
(+)
(+)
(+)
(+)
+ +
RETURN
DET.
( )
( )
( )
( )
( )
24 V
( )
provided with the electrical box.
6. Mount the wall plate on the module using #4-24 × 1/2 in. (13 mm) self-tapping screw s.
Figure 2: Module address
Figure 3: Module installation
Figure 4: Module wiring
Notes [1] Maximum 25 Ω resistance per wire [2] Maximum 12 AWG (2.5 sq. mm) wire; minimum 18 AWG (0.75 mm [3] Refer to the control panel technical referenc e manual for wiring specifications [4] Maximum 23.8 VDC at 35 mA
2 / 4 P/N 3101192 • REV 03 • REB 25JAN13

Wiring

Wire in accordance with NFPA 72 and CAN/ULC-S524. Be sure to observe the polarity of the wires as shown in Figure 4.
2
) wire
Loading...
+ 2 hidden pages