Edwards Signaling CTM User Manual

CTM City Tie Module Installation Sheet
Wiring
Wire the CTM to a dedicated notification appliance circuit (NAC) as in Figure 1 on page 2. Do not install other notification
21
1234
Description
The CTM City Tie Module provides a single municipal box connection for activating a local energy type master box connected to a public fire alarm reporting system.
Installation
Install the CTM in accordance with NFPA 70 National Electrical Code.
appliances on the same circuit.
Specifications
Voltage 24 VDC nom.
Current Standby Alarm
Ground fault impedance 0
Wire size 12 to 18 AWG (0.75 to 2.5 sq mm)
Mounting North American 2-1/2 in (64 mm) deep
Municipal box connection Wire resistance: Trip current:
Operating environment Temperature Relative humidity
20 mA 300 mA, max.
1-gang box
26 200 mA into a 14.5 coil
32 to 120°F (0 to 49°C) 0 to 93% noncondensing
WARNING: This device will not operate without electrical
power. As fires frequently cause power interruptions, we suggest you discuss further safeguards with your fire protection specialist.
The CTM is shipped from the factory as an assembled unit; it contains no user-serviceable parts and should not be disassembled.
For more information, refer to the technical reference manual listed inside the control panel door.
To install the module:
1. Verify that all field wiring is free of opens, shorts, and ground faults.
2. Make all wiring connections as shown in the wiring diagram. See Figure 1.
4. Using the 4-24 × 1/2 in (13 mm) self-tapping screw provided, mount the wall plate to the module.
5. Using the two 6-32 × 1/2 in (13 mm) machine screws provided, mount the module to the electrical box.
© 2013 UTC Fire & Security. All rights reserved. 1 / 2 P/N 3101025 • REV 02 • REB 25JAN13
Figure 1: CTM installation wiring diagram
From dedicat ed notif ication appliance circuit [ 4]
Compatible electrical box
CTM
Ac t i veNor ma l
+
+
[1]
21
Local energy t ype
1234
master box
Ac t i veNor ma l
EOLR [ 3 ]
+
+
14.5 trip coil
[2]
Publi c fi re alarm
report ing system
Wall plat e
Sc r e w s
[1] Power-limited and supervised for opens, shorts, and ground faults
[2] Nonpower-limited and supervised for opens and ground faults
only. 26 , max. 4.4 A, max.
[3] Use end-of-line resistor value required by the notification
appliance circuit
[4] NAC output signal must be compatible with the input rating of the
local energy type master box.
2 / 2 P/N 3101025 • REV 02 • REB 25JAN13